Commissioning PSTX Manual
Commissioning PSTX Manual
Commissioning PSTX Manual
Revision: G
Author’s address:
ABB AB
Control Products
Low Voltage Products
SE-721 61 VÄSTERÅS, Sweden
www.abb.com/lowvoltage
Safety notes
This manual uses these symbols
CAUTION
Caution symbol indicates a danger that can result
in personal injury.
WARNING
Warning symbol indicates a danger that can result
in damage to equipment or property.
INFORMATION
Information sign tells the reader important facts
and conditions.
1
1 Introduction
2
2 Quick start
3
3 Description
4
4 Installation
5
5 Connection
6
6 Human machine interface (HMI)
7
7 Functions
8
8 Communication
9
9 Maintenance
10
10 Troubleshooting
11
11 Wiring diagrams
12
12 Revision
13
13 Index
1 Introduction
1.2.1 General
2.1 Connection
12
2.2 Configuration
2
14
2.2.1 Basic set-up 14
2.2.2 Application set-up 14
CAUTION
Dangerous voltage: Can cause death or serious
injury. Always set the power switch to off and lock
out all power to this device before you start to
work on the equipment.
2 1 2
WARNING!
Installation of electrical connections must be done by
authorized personnel. Obey all laws and regulations.
PSTX PSTX
WARNING!
Before you connect the softstarters PSTX30...
1SFC132081M0201
PSTX170 to the operation voltage for the first time,
apply control supply voltage to open the bypass
relays. (see 2.1 Connection). This is necessary to
avoid an accidental start of the equipment while it is
connected to operation voltage.
Figure 2.1
In Line (1) and Inside Delta (2) connection
INFORMATION
ABB personnel must obey the instructions in
ABB CISE 15.4.
5L3
3L2
1L1
1 Line side
2.1 Connection
1SFC132081M0201
2
You can connect PSTX softstarters In Line 1 and 2T1
4T2
Inside Delta 2 , see Figure 2.1.
6T3
3. Connect the line side to terminals 1L1, 3L2, 5L3. 1 Line side
INFORMATION
Use only wires of the same dimension when you
1SFC132081M0201
Figure 2.3
Terminal connection bars
INFORMATION
The ground is not a protective ground, it is a
functional ground. The maximum length of the
1SFC132081M0201
ground cable is 0.5 m. Connect the ground cable
to the installation plate were the softstarter is
attached. The installation plate must also be 2
grounded.
Figure 2.4
Functional ground, terminal 22
INFORMATION
Do not use functional ground in IT-networks, L1
L2
L3
commonly found in for instance marine N
L N
applications.
Start Stop
13 14 18 19 20 22
6. Look at the diagram, see Figure 4.5, and connect Start 24 V DC
the start/stop circuits: terminal 13, 14, 18, 19 and KM1 Stop
1SFC132081M0201
2T1 4T2 6T3 4 5 6 7 8 9 10 11 12
see chapter 5.1.2.3 Start and Stop - terminals U V W
13, 14, 18, 19, 20, 21. M
3
WARNING
Use 24V DC only when you connect terminal 13, 14, Figure 2.5
15, 16 and 17. Other voltages can cause damage Circuit diagram (Fuse and contactor version)
to the softstarter and the warranty will no longer be
valid. For more information about terminal 15, 16 and
17, see chapter 5.1.2.4 Programmable inputs - L1
L2
terminals 15, 16 and 17. L3
N
L N
Figure 2.7
Flashing “Ready” LED
You see this set-up when you start the softstarter. To WARNING!
disable this set-up, see step 6 below. Note that your saved parameter values are lost if you
select “Change to recommended values”.
1. Find the Assistants menu by pushing “Menu”.
Scroll to Assistants with the Navigation keys. Push 5. Push to enter step 3, Tune settings. In most
“Select” to enter the Assistants menu. cases the recommended values are sufficient, but
sometimes fine tuning is necessary. For fine tuning,
2. Scroll to the Basic set-up menu with the push “Edit” and then use the navigation keys
Navigation keys. Push “Select” to enter the to set:
menu. -Start ramp time: 1 - 120s
-Stop ramp time: 1 - 120s
3. The Basic set-up starts with step 1 of 5, -Start ramp initial level: 10 - 99%
Language. Push “Edit” to change language. -Stop ramp end level: 10 - 99%
Use the Navigation keys to select language and -Current limit level: 1.5 - 7.5 x Ie
then push “Save”. -Start mode: Voltage ramp, Torque ramp or Full
voltage start
4. Push to enter step 2(5), Date and time. Push -Stop mode: No ramp, Voltage ramp, Torque ramp,
“Edit” and use the Navigation keys to edit date Dynamic brake
and time, then push “Save”.
6. Push and then push “Done” to finish the
5. Push to enter step 3(5), Motor data. Application set-up. If necessary, fine tuning can
Push “Edit” to change the Motor rated current also be done in the Parameters menu.
Ie. Use the Navigation keys to change the value
and then push “Save”.
CAUTION
Dangerous voltage: Can cause death or serious
injury. Always set the power switch to off and lock
out all power to this device before you start to
work on the equipment.
WARNING!
Installation of electrical connections must be done by
authorized personnel. Obey all laws and regulations.
2
WARNING!
Before you connect the softstarters PSTX30...
PSTX170 to the operation voltage for the first time,
apply control supply voltage to open the bypass
relays. (see 2.1 Connection). This is necessary to
avoid an accidental start of the equipment while it is
connected to operation voltage.
INFORMATION
ABB personnel must obey the instructions in
ABB CISE 15.4.
3.1 Overview
18
3.1.1 Operation functions 18
3.1.2 Protection functions 18
3.1.2.1 User defined protection 19
3.1.3 Warning functions 19
3.1.4 Fault detection functions 19
3
3.1.5 Softstarter overview 20
3.1.6 Type designation 21
3.1.7 Environmental influence 21
3.1.8 Specifications 21
You can control the softstarter in 3 different ways: The PSTX softstarter has protection functions to
• Hardwire inputs control protect the softstarter, motor and other equipment. All
protections can have automatic reset or manual reset.
• Keypad control (either attached to the softstarter front You can enable or disable the protection.
or detached and connected with the cable included)
Available protections are listed below:
• Fieldbus communication interface (by built in Modbus,
Anybus module or the FieldBus Plug with adapter) • EOL protection
You can use only one type of control at the same time. • Locked rotor protection
Default selection is hardware inputs control. • Phase reversal protection
INFORMATION • Current imbalance protection
Keypad control has the highest priority and • Overvoltage protection
overrides all other control methods.
• Under voltage protection
• Too long start time protection The softstarter has a number of fault detection functions
to signal malfunction at softstarter, motor or power
• Auto restart protection network level. The softstarter identifies external and
internal faults. The user cannot disable fault detection
3.1.2.1 User defined protection functions except for Emergency mode, chapter 7.20.1.
You can use your own specified protection, with the Available faults are listed below:
programmable digital input and an external device/sensor.
• Phase loss fault
The protection operates when the input signal comes at
high level (fieldbus or physical I/O). • High current fault
• Connection fault
• Overvoltage warning
• EOL warning
Terminal marking of
control circuits
Supply voltage Us
Display
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Order code
Mini USB
Technical data
according to Country of origin
IEC 60 947-4-2
Utilization code
Technical data
according to UL 508
Approvals
Com1 Com2
Symbol for
Torque control
Terminal marking of
control circuits
1SFC132081M0201
Figure 3.1
Softstarter overview
www.abb.com/lowvoltage
WARNING!
3.2.1 General Semiconductor fuses must be used to keep the
warranty on the thyristors.
Table 3 General
General data Description INFORMATION
24 V output 24 V ± 5% Max 250 mA To achieve a type 2 coordination, semiconductor
Rated insulation voltage, 600 V / 690 V fuses must be used.
Ui
Rated operation voltage, 208-600 / 690 V, 50 / 60 Hz Table 5 Semiconductor fuses
Ue Type Ue (V) I e (A) Bussman Knife Fuses (DIN43 620)
Output relay 250 V AC, Ith = 5A, Ie = 1.5A (AC-15) PSTX300 500-690 300 3 800 170M6812
Analog output 4-20 mA, 0-20 mA, 0-10 V, 0-10 mA PSTX370 500 370 3 2000 170M6021
PTC input 2825 ohm ± 20% switch off resistance PSTX370 690 370 3 1600 170M6019
1200 ohm ± 20% switch on resistance
Cooling system Fan
Recommended fuse 6 A Delayed
3.2.4 Weights
Control supply circuit MCB use C characteristics
Communication 3 Fieldbus ports, Extension I/O
Communication DeviceNet / Profibus DP / Modbus / Table 6 Weights
protocols EtherNET/IP / Modbus TCP/ Profinet Type Weight in kg Weight in lbs
PSTX30...105 6,1 13,5
PSTX142...170 9,6 21,2
PSTX210...370 12,7 27,9
3.2.2 Technical data for external keypad PSTX470 25.5 55.1
PSTX570 27.5 59.5
Table 4 Technical data for external keypad
PSTX720 ...840 46.2 101.4
Display Display type
PSTX1050 64.5 141.1
Status indicating LEDs Ready: Green
PSTX1250 65 143.3
Run: Green
Protection: Yellow
Fault: Red
Ambient temperature Storage: -25 °C to +70 °C (-13 °F
to 158 °F)
Operation: -25 °C to +60 °C
(-13 °F to 140 °F)
Degree of protection IP66
UL approval Type 1
Type 4X
Type 12
Marine approvals Speak to your ABB sales office
PSTX250-600-70 1SFA898113R7000 75-250A 75 132 160 132 220 295 250 430
PSTX250-690-70 1SFA898213R7000 75-250A 132 160 220 220 295 400 250 430
PSTX300-600-70 1SFA898114R7000 90-300A 90 160 200 160 257 355 300 515
PSTX300-690-70 1SFA898214R7000 90-300A 160 200 257 257 355 500 300 515
PSTX370-600-70 1SFA898115R7000 111-370A 110 200 257 200 355 450 370 640
PSTX370-690-70 1SFA898215R7000 111-370A 200 257 355 355 450 600 370 640
PSTX470-600-70 1SFA898116R7000 141-470A 132 250 315 250 450 600 470 814
PSTX470...570
PSTX470-690-70 1SFA898216R7000 141-470A 250 315 450 450 600 800 470 814
PSTX570-600-70 1SFA898117R7000 171-570A 160 315 400 295 540 700 570 987
PSTX570-690-70 1SFA898217R7000 171-570A 315 400 560 540 700 960 570 987
PSTX720-600-70 1SFA898118R7000 216-720A 200 400 500 355 710 880 720 1247
PSTX720...840
PSTX720-690-70 1SFA898218R7000 216-720A 400 500 710 710 880 1200 720 1247
PSTX840-600-70 1SFA898119R7000 252-840A 250 450 600 450 800 1000 840 1455
PSTX840-690-70 1SFA898219R7000 252-840A 450 600 800 800 1000 1400 840 1455
PSTX1050-600-70 1SFA898120R7000 315-1050A 315 560 730 500 1000 1250 1050 1810
PSTX1050...1250
PSTX1050-690-70 1SFA898220R7000 315-1050A 560 730 1000 1000 1250 1700 1050 1810
PSTX1250-600-70 1SFA898121R7000 375-1250A 400 710 880 670 1200 1500 1250 2160
PSTX1250-690-70 1SFA898221R7000 375-1250A 710 880 1200 1200 1500 2000 1250 2160
PSTX250-600-70 1SFA898113R7000 75 100 200 250 150 150 350 450 248 429
PSTX250-690-70 1SFA898213R7000 200 250 350 450 248 429
PSTX300-600-70 1SFA898114R7000 100 100 250 300 150 200 450 500 302 523
PSTX300-690-70 1SFA898214R7000 250 300 450 500 302 523
PSTX370-600-70 1SFA898115R7000 125 150 300 350 200 250 500 600 361 625
PSTX370-690-70 1SFA898215R7000 300 350 500 600 361 625
PSTX470-600-70 1SFA898116R7000 150 200 400 500 250 300 600 700 480 830
PSTX470...570
PSTX720-600-70 1SFA898118R7000 250 300 600 700 400 500 1000 1200 720 1240
PSTX720...840
PSTX1050-600-70 1SFA898120R7000 400 450 900 1000 600 700 1500 1900 1062 1830
PSTX1050...1250
4 * Ie in 10 sec
Ordering data according to UL (40°C ambient)
PSTX30...105
Ø14 (2x)
13 mm (0,5 in) 6x 3
298,5 mm (11,7 in)
314 mm (12,4 in)
3 mm (0,1 in)
1SFC132081M0201
Figure 3.3
Dimensions PSTX30...105
PSTX142...170
Ø18 (2x)
35 mm (1,3 in) 4x
7,5 mm (0,3 in)
6.6 mm (0,2 in) 4x
5 mm (0,2 in)
360,5 mm (14,1 in)
377 mm (14,8 in)
Figure 3.4
Dimensions PSTX142...170
5 mm (0,2 in)
3
1SFC132081M0201
200 mm (7,9 in)
258 mm (10,2 in)
Figure 3.5
Dimensions PSTX210..370
PSTX470...570
6 mm (0.2 in) 6x
262.82 mm (10.3 in)
282.15 mm (11.1 in)
493 mm (19.4 in)
466 mm (18.3 in)
25 mm (0.9 in) 6x
Ø13 (4x)
Figure 3.6
Dimensions PSTX470..570
Ø12.5 (6x)
72 mm 40mm 7 mm (0.276 in) 4x
(2.8 in) (1.57 in)
Ø6.5 (12x)
Ø 13 (4x)
1SFC132081M0201
408.9 mm (16.1 in)
Figure 3.7
Dimensions PSTX720..840
PSTX1050...1250
133.5 mm
(5.2 in) 2x 301.5 mm (11.8 in)
Ø6.5 (12x)
515 mm (20.2 in)
565 mm (22.2 in)
485 mm (19 in)
(5.9 in) 2x
150 mm
(2.46 in) 6x
62.6 mm
Ø13 (18x)
1SFC132081M0201
Ø13 (4x)
50 mm 40 mm
(1.9 in) 6x (1.5 in) 6x = Connection bars for PSTX1050
407 mm (16 in)
Figure 3.8
Dimensions PSTX1050..1250
4.2 Installll
31
4.2.1 Lifting the softstarter 31
4.2.2 Minimum distance to wall/front 31
4.2.3 Minimum enclosure dimensions 32
4.2.4 Maximum installation angle 32
4.2.5 Dimensions and drilling plan 32
4
4.2.6 Movable keypad 32
4.2.6.1 Installation Movable HMI 33
WARNING
If you do not obey these instructions, it can cause the
softstarter to overheat or not operate correctly.
WARNING
Do not lift the softstarter by the connection bars,
as this can damage the softstarter.
WARNING
4 Risk of damage to property. Make sure that no
liquids, dust or conductive parts can go into the
softstarter.
• Make sure that the order code agrees with the delivery
documents.
• Make sure that all items are included, see the delivery
note. See Table 1 Delivery note.
1SFC132081M0201
• Examine the softstarter and the packaging. In case of
damages, speak to the transport company or the ABB
reseller/Office immediately.
Figure 4.1
• Keep the softstarter in its packaging until installation. Receiving, unpacking and checking
1SFC132081M0201
4.2.2 Minimum distance to wall/front
4
Figure 4.2
WARNING
Flow of air for cooling purpose
Risk of damage to property. Make sure that
no liquids, dust or conductive parts enter the
softstarter.
WARNING
A
If you do not obey these instructions, this can cause
the softstarter to overheat or not operate correctly.
INFORMATION
Make sure that the distances to the surrounding
1SFC132081M0201
walls are sufficient. For the minimum distance to
front and wall, see Figure 4.3 , Figure 4.4 and B A B
Table 2.
Figure 4.3
Minimum distances to wall
Table 2 Minimum distance to wall/front
Softstarter type A B C A B C
(mm) (mm) (mm) (in) (in) (in)
PSTX30...105 100 10 35 3.94 0.39 1.38
PSTX142...170 100 10 35 3.94 0.39 1.38 C
PSTX210...370 100 10 35 3.94 0.39 1.38
PSTX470...570 150 15 35 5.905 0.590 1.38
PSTX720...840 150 15 35 5.905 0.590 1.38
PSTX1050...1250 150 15 35 5.905 0.590 1.38
1SFC132081M0201
Figure 4.4
Minimum distances to front
1SFC132081M0201
Softstarter type W (mm) H (mm) D (mm)
PSTX30...105 508 508 305
D
PSTX142...170 508 508 305
W
PSTX210...370 762 914 305
PSTX470...570 914 1219 405 Figure 4.5
PSTX720...840 914 1524 405 Minimum enclosure size
PSTX1050...1250* 914 1524 405
*PSTX1250 Recommended fan capacity 230m3/h
1SFC132081M0201
PSTX720...840 36 60 16 8
PSTX1050...1250* 36 60 16 8
*PSTX1250 Recommended fan capacity 230m3/h
Figure 4.6
Airflow
4.2.4 Maximum installation angle
WARNING
Risk of damage to property. Ensure that no Figure 4.7
liquids, drilling particles, dust or conductive parts Maximum mounting angle
enter the softstarter.
WARNING
When the enclosure is too small and/or you do
not obey the instructions, the softstarter can
overheat or not operate correct.
2
4.2.6 Movable keypad
1SFC132081M0201
INFORMATION
”)
Do not use shielded RJ45 cables. Use a cable 1 (Ø 1,0
Ø25,5 1,1”)
Min. (Ø
Ø28
length of maximum 3m to reduce distortion of the Max.
communication.
2
INFORMATION
1SFC132081M0201
The softstarter HMI is IP66 approved when
installed on the enclosure door.
2 Nm (17,7 lb.in) 3
You can use the movable HMI to copy parameters Ø26 (Ø 1.02”)
from one softstarter to another during commissioning
Figure 4.9
(temporarily handheld).
Drill a hole for the detachable keypad
• Rubber gasket
4
• Plastic screw-nut 5
• RJ45 Network cable
1SFC132081M0201
see 1 and 2 in Figure 4.9.
Figure 4.12
Roll the rest of the hanging cable
WARNING
Installation of electrical connections must be
done by authorized personnel. Obey all laws and 1 2
regulations.
CAUTION
Dangerous voltage. Can cause death or serious
injury. Always set the power switch to off and lock PSTX PSTX
out all power to this device before you start to
work on the equipment.
1SFC132081M0201
WARNING!
Before you connect the softstarters PSTX30...
PSTX170 to the operation voltage for the first time,
apply control supply voltage to open the bypass
relays. (see 2.1 Connection). This is necessary to Figure 5.1
avoid an accidental start of the equipment while it is In line (1) and inside delta (2) connection
connected to operation voltage.
INFORMATION
5 5L3
ABB personnel must obey the instructions in 3L2
ABB CISE 15.4. 1L1
1
For basic connection, see chapter 2 Quick start. Line side
For connection diagrams, see chapter 11 Connection
diagrams.
Motor side
5.1 Electrical connection
1SFC132081M0201
2
2T1
4T2
WARNING
6T3
Capacitors for power factor compensation are
not permitted in between the softstarter and the Figure 5.2
motor, because this can cause current peaks In line (1) and inside delta (2) connection
which can burn the thyristors in the softstarter. If
you must use such capacitors, connect them on
the line side of the softstarter.
5L3
3L2
1L2
1 Line side
5.1.1 Main circuit
INFORMATION
The maximum voltage dip between softstarter and
motor is 5%. The cable length does not matter.
1SFC132081M0201
2 Motor side
Softstarters PSTX30...PSTX1250 can be connected 2T1
4T2
In Line, see 1 Figure 5.1, and Inside Delta, see 2 6T3
Figure 5.1.
Use wire connection for PSTX30...105 see Figure 5.2 Figure 5.3
and terminal connection for PSTX142...570 see Figure Terminal connection bars
5.3.
• Connect the line side to terminals 1L1, 3L2, 5L3, see
1 in Figure 5.2 and Figure 5.3.
1SFC132081M0201
PSTX1050...1250 Using connection bars
1L1 3L2 5L3 M12 40 mm 2x 50 mm M12
(1.57 in) (1.96in) max
max 50 mm
50 mm (1.969 in)
5 mm 6 mm (1.969 in)
2T1 4T2 6T3
45 Nm - 398 lb.in (0.19 in) (0.23 in) 45 Nm - 398 lb.in
1SFC132081M0201
5.1.2.1 Control supply voltage -
terminals 1 and 2
INFORMATION
Make sure that you have the correct supply
voltage U s. See chapter 3.2.1 General.
The control supply voltage for all PSTX
5 softstarters is Us 100-250V AC,50/60Hz.
If using the operational voltage (Phase /N) as
source for control voltage make sure to not
exceed Us 250V –AC,50/60Hz
1SFC132081M0201
M3,5 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
INFORMATION
This is not a protective ground, it is a function
ground. The grounding cable must be as short as
possible. Maximum length 0,5m. Figure 5.5
Functional ground, terminal 22
INFORMATION
Do not use functional ground in IT-networks,
commonly found in for instance marine
applications.
1SFC132081M0201
circuit with push buttons. See Figure 5.6 and Figure 5.7.
Figure 5.6
Tightening torques and cable dimensions. Start and Stop, terminals 13, 14, 18, 19, 20, 21
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
5
START
STOP
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.7
Holding circuit (pulse for start is enough)
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
SPARE
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.8
Tightening torques and cable dimensions. Conventional circuit (maintained start signal required)
1SFC132081M0201
WARNING
1SFC132081M0201
L N
100-250V
PSTX
15, 16 and 17. Other voltages can damage the
softstarter and the warranty can no longer be
valid. Figure 5.9
Holding circuit with external control voltage
(pulse for start is enough)
STOP
START +
DC
-
5
N
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.10
Conventional circuit with external control voltage
(maintained start signal is required)
Tightening torques and cable dimensions.
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
WARNING
Use only 24V DC to connect terminal 13, 14,
15, 16 and 17. Other voltages can damage the
softstarter and the warranty can no longer be
valid.
1SFC132081M0201
The softstarter has 3 programmable inputs.
INFORMATION
Connections for sequence start, see 5.1.2.5
1SFC132081M0201
Programmable inputs (Sequence start) L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.12
Programmable inputs, terminals 15, 16 and 17
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
+
DC
-
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
Figure 5.13
Tightening torques and cable dimensions. External control voltage
1SFC132081M0201
If the softstarter trips for any reason, and the trip must
1SFC132081M0201
K 25 K 27 K 29
Stop
+
5 DC
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.15
External control voltage
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
2ⁿᵈ Start seq.
3ʳᵈ Start seq.
1ˢᵗ Start seq.
Stop
1SFC132081M0201
L N
100-250V
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 DGND GND +24V
PSTX
Figure 5.16
Tightening torques and cable dimensions. Internal control voltage
1SFC132081M0201
1SFC132081M0201
Recommended to control line contactor.
Figure 5.17
Tightening torques and cable dimensions.
Programmable output relay K4, terminals 4, 5 and 6
1SFC132081M0201
M3,5 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
5
5.1.2.7 Programmable output relay - K5,
terminals 7, 8 and 9
1SFC132081M0201
Figure 5.18
Tightening torques and cable dimensions. Programmable output relay K5, terminals 7, 8 and 9
1SFC132081M0201
M3,5 3,5 x 0,6 mm AWG 12 ... 24
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
2x0,2 .. 1,5 mm2
L N
100-250V 0,5 Nm 0,2 .. 2,5 mm2
50/60 Hz K4 K5 K6 Start Stop In0 In1 In2 GND +24V
4,3 lb.in 2x0,2 .. 1,5 mm2
Figure 5.19
Programmable output relay K6, terminals 10, 11 and 12
Tightening torques and cable dimensions.
1SFC132081M0201
1SFC132081M0201
+ -
PSTX make sure that they are totally isolated grounds and Digital
GND
that the master has isolated power. The master must not
have any offset to the PSTX ground. PLC
Figure 5.20.
Figure 5.20
See chapter 8 Communication for communication
Modbus RTU
components.
5 If the motor has PTC or PT100 elements, connect the Com 3 Temp In Analog out
1SFC132081M0201
PT 100 - 3 wire
use a 3-wire connection. This creates 2 measuring
circuits. One circuit is used for reference. This way, the
tripping device can calculate the wire resistance. See
Figure 5.21.
Figure 5.21
PT100 - 3 wire
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
Com 3 Temp In Analog out
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
+(B) -(A) T1 T2 T3 +24V + GND
2x0,2 .. 1,5 mm2
Figure 5.22
PT100 - 2 wire
for the resulting systematic errors when you change the +(B) -(A) T1 T2 T3 +24V + GND
1SFC132081M0201
Figure 5.23
Tightening torques and cable dimensions. PTC100 - 2 wire
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
Com 3 Temp In Analog out
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
+(B) -(A) T1 T2 T3 +24V + GND
2x0,2 .. 1,5 mm2
5
Error caused by the line
The error caused by the line resistance is to
approximately 2.5 Kelvin/Ohm. If you don’t know the
resistance of the line and you cannot measure it, you can
make an estimation of the error caused by the line with
this table.
Temperature errors in °C / K
The table below shows temperature errors, at an ambient
temperature of 20° C, for different line lengths and
conductor cross sections for PT100 sensors.
output signal (terminals 29 and 30). The load resistance +(B) -(A) T1 T2 T3 +24V + GND
1SFC132081M0201
I (A), U (V), P (kW), P (Hp), Q (kVAr), S (kVA), A
cos Phi, Motor temp, SCR temp and Energy (kWh).
If you use the analog output, connect the cables to Figure 5.24
terminals 29 and 30. See Figure 5.24. Analog output
1SFC132081M0201
M3 3,5 x 0,6 mm AWG 12 ... 24
Com 3 Temp In Analog out
(0.138 x 0.024 in) 0,2 .. 2,5 mm2
+(B) -(A) T1 T2 T3 +24V + GND
2x0,2 .. 1,5 mm2
• 8 digital input
1SFC132081M0201
• 4 output relay
A
• 1 analog output
6
6.3 Options screen
56
6.3.1 Overview 56
6.3.2 Edit home view 43
6.3.2.1 Add information screens to home view 56
6.3.2.2 Edit information screens in home view 56
6.3.2.3 Display slot 56
6.3.2.4 Scale value range 57
6.3.3 Active faults/protections and warnings 57
PSTX
can also use the HMI to monitor, control and read status
information of the softstarter.
See Figure 6.1.
• Display
Stop Start
1SFC132081M0201
6.1.1 LED indicators
The LED status indicators work as in Table 1 LED status: Figure 6.1
HMI
Table 1 LED status
LED Color Description
Ready Green • Off: When control supply voltage Us is
1 off or unconnected.
• Flashing light: When control supply
voltage Us is On and operation voltage L N
100-250V
50/60 Hz K4 K4 K4 Start Stop Reset In1 In2 DGND DND +24V GND
Ue is Off. 1 3
PSTX
1
100-250V
50/60 Hz K4 K4 K4 Start Stop Reset In1 In2 DGND DND +24V GND
PSTX
1SFC132081M0201
The display above the key shows the current function. 5 6
See 1 Figure 6.3.
Start key
When you push this key, the motor starts and operates
with the set parameters. (Only active in local control
mode). See 6 in Figure 6.3.
With the keypad, you can change the settings for each
item or as a selection of default parameters for different Local PSTX30
applications. The default set of parameters is stored in Menu
the unit for a possible reset to default values. When the Backup handling
fieldbus communication is selected, you can change
System info
parameters from this interface.
Settings
1SFC132081M0201
Push “Menu“ to go to the menu and then use
Exit 12:00 Select
and to navigate. Push the “Select“ to make your
selection.
See Figure 6.4.
Figure 6.4
Navigation screen
30.0 A
number, the selected number is highlighted black. Then
Push or to change the value of the selected
6 number. Push “Save” to save.
See Figure 6.5. 0.0 30.0
1SFC132081M0201
Cancel 12:00 Save
Figure 6.5
Numerical setting
On/off switch
Use or o navigate or to change the value of
the selected switch, (1=on, 0=off).
Push “Save” to save.
See Figure 6.6. Local PSTX30
Shunt fault event mask
1 Event group 0
0 Event group 1
0 Event group 2
0 Event group 3
1SFC132081M0201
0 Event group 4
Cancel 12:00 Save
Figure 6.6
Switch setting
Selection list
Use the Navigation keys to navigate up and down in the
lists. The selected option is highlighted black. Push
“Save” to save.
Local PSTX30
See Figure 6.7.
Current limit type
Off
Normal
Dual
Ramp
1SFC132081M0201
Figure 6.7
Selection list
Local PSTX30
Path in menu:
Menu u Parameters u Complete list u 01 Motor rated Motor rated current Ie
current Ie
For more information about Motor Current Ie, see 30.0 A
chapter 7 Functions.
0.0 30.0
1SFC132081M0201
1. The Home view is the top level. Push “Menu”
to enter the menu. The display now appears as in Cancel 12:00 Save
Figure 6.8.
CAUTION
When you change from local control to remote
control, the setting applies immediately. If the
remote setting has direct motor start it can start
the motor automatically and can cause personal
injury.
CAUTION
After a power loss, software upgrade or cycling of
the PSTX Control supply, the PSTX automatically
is set in remote control. Remote control is the
default control of the PSTX.
INFORMATION
When you change from remote control to local
control the softstarter stays in present state.
* For information about Motor jog see chapter 6.2.4 Motor jog.
To go to the Motor Jog, follow this path in menu:
PSTX
4
4
6.2.2 Stop key 3 4
The stop key is the stop switch for the softstarter.
Push this key to stop the motor with the set parameters.
Stop Start
1SFC132081M0201
Figure 6.9
6.2.3 R\L-key Local control
R\L-key stands for Remote or local control.
Use this key to control the softstarter remote from digital
input, fieldbus or local from the HMI.
See 3 in Figure 6.9.
Event log
Jog is a slow speed drive function to drive the motor with Backups handling
low voltage output. Use this feature for example to put a
System info
conveyor belt into position.
Settings Jog
The jog has 3 default speeds:
Figure 6.10
• Fast Jog
Motor jog navigation
• Jog
• Creep
1SFC132081M0201
Exit 14:30
The motor stops immediately when you release the push
button, and .
Figure 6.11
Keypad
You can run the motor in the forward and reverse
direction with 3 different speeds.
6.3.1 Overview
Local PSTX
In Options screen, you can change the appearance of
the Home view of the softstarter and read Active faults/ 1 Motor current A
4
protections and Active warnings. 0.0
2 3
Option screen includes these menus:
Motor voltage V
• Edit home view 0.0
1SFC132081M0201
• Active faults/ protections
Options 12:00 Menu
• Active warnings
In the Display slot menu, you can set the new screen with
6.3.2 Edit home view these options:
Path in menu:
Options u Edit home view Signal
Push “Edit” to see the list of signals available for the
For navigation, see Figure 6.12.
home view. Use the Navigation keys and then push
“Select” to select the signal. Selected signal is shown by
Local PSTX HMI 1 in Figure 60.
6 Motor current A
Options Select 1 of these signals:
0.0
• Empty
Motor voltage V • Motor voltage
Edit home view
0.0 • Motor current
Active faults • Active power
Options 12:00 Menu • Active power (hp)
Active warnings • Power factor
• Reactive power
Figure 6.12 • Apparent power
Edit home view navigation • Mains voltage
• Mains frequency
Use Edit home view to change the view of the home view. • Motor connection
• Phase sequence
• Phase L1 current
6.3.2.1 Add information screens to home view • Phase L2 current
• Phase L3 current
1. Push “Options” to select Edit home view. • L1L2 phase-to-phase voltage
• L2L3 phase-to-phase voltage
2. Use the Navigation keys to select where you want • L3L1 phase-to-phase voltage
to add an information screen. • Thyristor temperature
• Motor temperature
3. Push “Add” to add the new information screen • EOL time to trip
to the home view. • EOL time to cool
• Active energy
• Active energy (resettable)
6.3.2.2 Edit information screens in home view • Reactive energy
• Reactive energy (resettable)
1. Push “Options” and then select Edit home
• Voltage imbalance
view. • Mains voltage THD
• PT100 temperature
2. Use the Navigation keys to select the display slot • PTC resistance
you want to edit. • Remaining time to start
• Number of starts (resettable)
3. Push “Edit“ and enter the Display slot menu. • Number of starts
See chapter 6.3.2.3 Display slot to set the new • Motor run time (resettable)
screen in the Display slot menu. • Motor run time
• Thyristor run time (resettable)
• Thyristor run time
• Fans run time
• Pre-start function
• Start mode
• Stop mode
1SFC132081M0201
Options 12:00 Menu
Use the Navigation keys to select display style, push
“Select” to set the parameter.
Figure 6.14
Display decimals Display slot
Select the amount of decimal numbers in the home view.
Use the Navigation keys to change the amount.
Push “Save” to save the value. Decimal numbers are
shown in 3 in FFigure 6.14.
Display name
6.3.3 Active faults/protections and
You can change the name of the selected signal. The new warnings
name can have maximum 20 characters. Path in menu:
Use the Navigation keys to change the characters. Options u Active faults / protections
Push “Save” to save the display name. Display name Options u Active warnings
is shown by 1 in Figure 6.14. 6
You can find active faults/protections/warnings in the
Signal min Options menu. The menus contain information about
Select the minimum value in the Home view. Use the
faults and warnings that occurred during operation, and
Navigation keys to change the value.
Push “Save” to save the value. Value is shown by 3 what protections are active.
in Figure 6.14. Active faults/protections and warnings menus are
highlighted black when a fault protection or warning
occurred.
Signal max
Select the maximum value in the Home view. Use the For navigation see Figure 6.15.
Navigation keys to change the value.
Push “Save” to save the value. Value is shown by 3 For more information about fault/warnings/protections,
in Figure 6.14. see chapter 10 Troubleshooting.
6
6.4.1 Parameters
Path in menu:
Menu u Parameters
System info
Settings
Figure 6.16
Complete list navigation
04 Kick start
04.01 Kick start
04.02 Kick start level
04 Kick start 04.03 Kick start time
05 Slow speed
05.01 Slow speed forward
05.02 Slow speed fwd strength
05 Slow speed 05.03 Slow speed reverse
05.04 Slow speed rev strength
09 Automatic restart
10 Internal 11 External IO 12 Communication
10.01 In0 function 11.01 1DI0 function 2.01 Com3 function
1
10.02 In1 function 11.02 1DI1 function 12.02 FB interface connector
10.03 In2 function 11.03 1DI2 function 12.03 Fieldbus control
10.04 K4 function 11.04 1DI3 function 12.04 Fieldbus address
10 Internal IO 11 External IO 10.05 K5 function 11.05 1DI4 function 12.05 Fieldbus IP address
10.06 K6 function 11.06 2DI5 function 12.06 Fieldbus IP gateway
10.07 AO reference 11.07 2DI6 function 12.07 Fieldbus IP netmask
10.08 AO type 11.08 2DI7 function 12.08 Fieldbus IP DHCP client
10.09 AO max value 11.09 1DO0 function 12.09 FB baud rate
For full parameter list see chapter 7 For full parameter list see chapter 7 12.10 FB parity
12 Communication 12.11 FB stop bits
12.12 Fieldbus DI 1
For full parameter list see chapter 7
Assistants Modified
For navigation, see Figure 6.17.
Motor jog Favorites
Motor rated current Ie
Start and stop
In the Favorites menu you can add favorite parameters Event log Limit
Kick start
for quick selection. Select parameters such as Start and Backup handling
Slow speed
Motor heating
stop, Current limit, Kick start, Torque control, etc Motor braking
Sequence start
System info Automatic restart
Internal IO
External IO
1. Push “Select” to enter the Favorites menu and Settings Communication
Protections list 1-7
then push “Select” to edit the Favorites list. Warnings list 1-5
Internal faults
Figure 6.17 External faults
Presentation
2. Use the Navigation keys to select a parameter Favorites navigation Service
1SFC132081M0201
Stop mode
Done 12:00 Select
Figure 6.18
Favorites menu
Complete list
6.4.1.3 Modified MENU
Favorites Modified
Path in menu: Modified parameters
Parameters Modified
Menu u Parameters u Modified List of parameters
that differs from their
Assistants default values.
Push “Select” and then “Edit” to edit the different System info
For more details on how to set Basic set-up and Motor jog Application set-up
Application set-up, see chapter 2 Quick start.
Event log
For more information about Assistants and Application
Backup handling
list, see chapter 7.22 Assistants.
System info
INFORMATION
After you select an application and make your
changes, do not select this application again
because this resets the application to the default
settings.
6
Enter the Assistants menu
Push “Menu” and select Assistants with the
Navigation keys.
Push “Select” to enter the Assistants menu.
Basic set-up
Local PSTX
Use the Navigation keys to select Basic set-up.
Application set-up 1(4)
Push “Select” to enter the Basic set-up.
The Basic set-up menu is divided in 5 steps: Band saw
Language, Date and time, Motor data, System Bow thruster
configuration and Setup complete. Centrifugal pump
Circular saw
1SFC132081M0201
Conveyor belt short
Application set-up
Done 12:00 Select
The Application set-up are quick settings for Applications,
Values and Tune settings.
Use the Navigation keys to select Application set-up.
Push “Select” to enter the Application set-up. Figure 6.21
Select for what type of application you use the softstarter Application set-up
by pushing “Select”.
See Figure 6.21.
Motor jog
Event logs
The Event log menu shows the event log in the Event log Faults
Protections
softstarter. The log shows the 100 latest events in Warnings
Backup handling Parameter changed
chronological order, with “type of event” and date. Run
• Warnings
• Parameter changed
• Run
Faults
Use the Navigation keys to select a Fault and push
“Details” to read details about the Fault (Name, On time Local PSTX
and Event count). Then push the i-key to see information Event logs
6
about the Fault. Push “Back” to go back to Faults log Faults
menu. Protections
Warnings
Protections
Parameter changed
Use the Navigation keys to select a Protection and
1SFC132081M0201
push “Details” to read details about the Protection Run
(Name, On time and Event count). Push the i-key to see Done 12:00 Select
information about the Protection. Push “Back” to go
back to Protections log menu.
Figure 6.23
Warnings
Event log
Use the Navigation keys to select a Warning and push
“Details” to read details about the Warning (Name,
On time and Event count). Then push the i-key to see
further information about the Warning. Push “Back”
to go back to Warning log menu.
Parameter changed
Use the Navigation keys to select a parameter and
push “Details” to read details about the changed
parameter (Name, On time and Event count). Push
“Back” to go back to Warning log menu.
Run
Use the Navigation keys to select a run event and push
“Details” to read details about the run event (Name,
On time and Event count). Push “Back” to go back to
Warning log menu.
Assistants
For navigation, see Figure 6.24.
Motor jog
You can use the movable keypad to transfer parameters
from one softstarter to another during commissioning. Event log
Settings
1SFC132081M0201
Cancel 14:30
Replace backup
Figure 6.26
Uploading parameters
Assistants
For navigation, see Figure 6.27.
Softstarter
Motor jog
The System info menu contains system info such as FW version: 1.11.0
Firmware version and Serial number. The System info Event log Serial number: 00000
menu shows system info of the Softstarter and HMI. Push Backup handling
“Select” to enter the System info menu. Softstarter
System info
Use the Navigation keys to make your selection.
HMI
Push “Back” to go back. Settings
HMI
FW version: 1.5.0
Serial number: 00000
Figure 6.27
System info navigation
6.4.6 Settings
Path in menu:
Menu u Settings
Event log
Display settings Display settings
Backup handling Contrasts 80 %
Reset to defaults Brightness 80 %
System info Powersave
Reset Home view layout [ ] White on black
Reset to defaults Reset all parameters
Settings Reset operating data
Figure 6.28
Settings navigation
1SFC132081M0201
Italian
4. Highlight the first alternative and push ”Select”
Cancel 12:00 Save
and then “Edit” to enter Language settings.
System info
Table 8 Date and time settings
Settings Reset to defaults
Option Function
Date Set date: Day, month and year. Figure 6.31
Time Set time: Hour, minutes and Date and time
seconds.
Show date as Show the date at top level in this
format:
1SFC132081M0201
Show clock
Back 12:00 Edit
When the configuration of the time setting is completed,
push “Back” 3 times to go back to the Home view,
top level. Figure 6.32
Date and time menu
Path in menu:
Menu u Settings u Display settings
Assistants
Use the Reset to defaults menu to reset home view Date and time
layout, parameters or operating data back to factory Motor jog
The reset does not change the real time clock, the hour Backup handling
Display settings
run meter, the number of starts and the presentation Reset from defaults
System info
language. Reset Home view layout
Settings Reset to defaults
• Active energy
• Reactive energy
• Number of starts
• Individual function
7.1.1 Setting parameters
• Stand by
The HMI complete list shows all parameter groups: • Stop ramp
Individual function
Top of ramp
When the motor comes at Top of ramp, (100% nominal
speed) the softstarter closes the bypass and does not
control the motor. In Top of ramp state the softstarter only
runs diagnostics.
Stop ramp
WARNING
All PSTX softstarters must be set to the rated
current of the motor.
1SFC132081M0201
Start ramp Stop ramp Time
Figure 7.1
7.2.1 Voltage start ramp Start and stop ramp
When the output voltage comes at Top of ramp, the Nominal voltage 100 %
softstarter closes the bypass, see Figure. Start ramp initial level
To come at Top of ramp these conditions are necessary:
7
• The Start ramp time passed, i.e. 100% output voltage.
Time
1SFC132081M0201
• The current is below 1.2 × nominal motor current.
Start ramp time
The Start ramp time is the time it takes to go from Start
ramp initial level to full voltage. The time to come at Top
Figure 7.2
of ramp can be longer than the set Voltage ramp time,
Voltage start ramp
because this is subject to the current.
If the motor starts with a very heavy load, the start ramp
time can be longer than usual.
02.04 Start ramp time Set the effective time it takes for the voltage to reach
1 ... 120 s 10 s
100%.
level. For best performance, set the step down level to 100%
80%. 80% Step down voltage
When step down level is reached, the softstarter controls
the output voltage during preset Stop ramp time to End 30% End voltage
voltage level and cuts the output voltage to the motor,
see Figure 7.3. Time
1SFC132081M0201
Stop ramp time
Figure 7.3
Voltage stop ramp
• Linear
• High inertia
• Progressive
1SFC132081M0201
When using the Torque start ramp, the acceleration is Start Time
constant if the set torque curve is the same as the actual
load curve. The output voltage does not increase linearly
Figure 7.4
like when using the voltage start ramp, see Figure 7.4 .
Torque start ramp
The Torque ramp makes the equipment that the motor
drives stop much softer than the Voltage start ramp.
The start ramp time can be longer if the motor starts with
a very heavy load.
03.05 Torque limit level Sets the limit for the torque during soft start with 20 ... 200% 150%
torque control
28.06 Torque profile start Sets the shape of the torque ramp during start. Constant Linear ramp
setpoint,
• Constant setpoint is for centrifuge Linear ramp,
• Linear is for compressor Progressive
curve, High
• High inertia pump is for long conveyor belts inertia curve
• Progressive curve is for centrifugal pump
28.07 Torque finish Sets the operation torque for Torque start ramp setting 30 ... 500% 100%
in percentage of base torque.
28.08 Torque tune Sets the integration time of PI controller. 0 ... 1000% 100%
28.09 Torque ctrl gain Sets the speed of the voltage regulator during torque 0.01 ... 10 0.02
start and stop. It seldom needs to be changed, but if
a dip occur in the torque curve during stop, increasing
this value might solve it.
28.10 Torque PI integration time Sets the integration time of PI controller. 0.001 ... 10 s 0.004 s
28.11 Torque slip Sets the slip difference from nominal to pull-out torque 0.1 ... 100% 1.0%
in percentage.
28.12 Torque diff Sets the maximum desired difference between 0.1 ... 100% 2.0%
reference and actual torque in percentage.
28.13 Torque filter time Sets the Torque control filter time in seconds. 0.01 ... 10 s 0.02 s
1SFC132081M0201
Stop Time
Figure 7.5
Torque stop ramp
28.08 Torque tune Sets the adjustment of resistive losses. 0...1000% 100%
28.09 Torque ctrl gain Sets the speed of the voltage regulator during torque 0.01 ... 10 0.02
start and stop. It seldom needs to be changed,
but if a dip occur in the torque curve during stop,
increasing this value might solve it.
28.10 Torque PI integration time Sets the integration time of PI controller. 0.001 ... 10 s 0.004 s
28.11 Torque slip Sets the slip difference from nominal to pull-out 0.1 ... 100% 1.0%
torque in percentage.
28.12 Torque diff Sets the maximum desired difference between 0.1 ... 100% 2.0%
reference and actual torque in percentage.
28.13 Torque filter time Sets the Torque control filter time in seconds. 0.01 ... 10 s 0.02 s
INFORMATION
Full voltage start ignores the Current limit.
WARNING
Because this function makes the motor
warm, we recommend to use a PTC or
PT100 element to monitor the temperature.
INFORMATION
Stand-still brake only works when the softstarter
is connected in-line.
07.01 Stand still brake strength Set the Braking strength 10-100%. Select a suitable 10 ... 100% 50%
value for the application.
WARNING
If the load is very heavy, current limit can prevent
the current to decrease below the set current
level and cause overheating.
1SFC132081M0201
behaves as for normal Current limit.
Time
Dual current limit can be used as a back-up function to
prevent overheating.
Figure 7.6
Dual current limit
Ramp current limit
When the current comes at the first current limit level the
output voltage restricts the current from increasing at a
maximum linearly curve up to the second current limit.
The set time determines the time it takes for the current
limit to come at the second current level.
When the current comes at the second current limit, the
softstarter behaves as for the normal current limit.
You can use Ramp current limit as a back-up function to
prevent overheating.
03.03 2nd curr lim level Sets the level of the second current limit. 1.5 ... 7.5 x Ie 7.0 x Ie
03.04 2nd curr lim time Sets the time limit from the start signal when the second 2 ... 120 s 8s
current limitation comes in operation.
INFORMATION
Current limit function does not work during kick Time
1SFC132081M0201
Kick Start time
start.
Figure 7.7
Kick start
04.02 Kick start level Sets the level of the Kick start in percentage of rated voltage. 50 ... 100% 70%
04.03 Kick start time Sets the duration of the Kick start in seconds. 0.20 ... 2.00 s 0.20 s
• Fast jog
• Jog
• Creep
The motor strength can be adjusted with separate
parameters. Select a suitable value for the application.
WARNING
The torque when using Slow speed is maximum
⅓ of the full motor torque. This is achieved when
using Fast jog and the strength parameter set to
100%.Too high value of the motor strength could
cause oscillations and if set to too low value, the
motor may not start.
WARNING
7
Because Slow speed function warms up the
motor we recommend to use a PTC or PT100
element for temperature monitoring.
In some conditions, the built-in EOL is not
accurate for this feature.
02.08 Pre-start time Sets the duration of the pre-start function. 0.0 ... 7200.0 s 10.0 s
05.01 Slow speed forward Sets the Slow speed forward. Fast jog forward Fast jog, Jog, Creep Jog
is 33%, Jog forward is 15% and Creep forward
is 8% of the nominal motor speed.
05.02 Slow speed forward strength Parameter related to the torque that is 10 ... 100% 50%
generated during Slow speed in the forward
direction.
05.03 Slow speed reverse Sets the Slow speed reverse. Fast jog reverse is Fast jog, Jog, Creep Jog
33%, Jog reverse is 20% and Creep reverse is
9% of the nominal motor speed.
05.04 Slow speed rev strength Parameter related to the torque that is 10 ... 100% 50%
generated during Slow speed in the reverse
direction.
WARNING
If the softstarter is connected inside-delta and
using the Motor heating, this can cause damage
to the equipment.
WARNING
Because Motor heating function warms up the
motor we recommend to use a PTC or PT100
element for temperature monitoring.
INFORMATION
Motor heating only works when the softstarter is
connected in-line.
7
Motor heating has these parameters:
Dynamic brake
Dynamic brake is an intelligent variant of DC brake
starting with a period of dynamic braking followed by a
switch to DC brake. During the dynamic brake the firing
angle and thyristor firing sequence are continuously
recalculated depending on operating conditions. During
DC brake these are pre-determined. The reason for
switching to DC brake is because it is effective at
low speed but ineffective at high speed. During both
dynamic- and DC-brake the kinetic energy of the motor is
converted to heat that is dissipated in the rotor.
WARNING
Braking exerts a lot of stress on the thyristors so
from a thermal perspective a brake shortly after a
start can be counted as two consecutive starts.
INFORMATION
Using a softstarter to brake the motor will cause
noise and vibrations just like any other braking
method. If a fast stop time is required the brake
strength will have to be set to a large value which
will result in increased noise and vibration.
INFORMATION
Parameter 07.03 (Dynamic brake strength) and
07.04 (DC brake strength) are the ones that
affect the motor deceleration time. Parameter
07.02 (Motor brake time) only works as a
timeout. The goal should be to choose the lowest
possible braking strength and still fulfill the user’s
deceleration time requirements.
INFORMATION
To use Dynamic brake set parameter 02.02 (Stop
mode) to Dynamic brake.
INFORMATION
An external PTC or PT100 sensor to monitor the
motor temperature is recommended.
07.03 Dynamic brake strength Sets the Dynamic braking strength. 10-100% 40%
07.05 DC brake switch speed The approximate speed when the switch from 10-100% 28%
threshold dynamic brake to DC brake occurs.
07.06 DC brake switch delay time Sets the time that the speed has be below 0.1 – 100.0 s 3.0 s
the threshold before the switch to DC brake
occurs. Configure this parameter only if the
switch occurs too soon or too late.
02.02 Stop mode Sets the desired stop mode: No ramp = No ramp/Voltage stop ramp/ No ramp
Immediately cuts power to the motor, Voltage Torque stop ramp/Dynamic
stop ramp = Decreases voltage linearly, brake
Torque stop ramp = Decreases torque in a
pre-defined pattern, Dynamic brake = Applies
brake to the motor
28.51 Firing angle sweep Enables dynamic optimization of dynamic Off, On On
brake
28.52 Auxiliary condition Enables additional thyristor trig occasions of Off, On Off
dynamic brake
28.53 Flux threshold gain 1 Flux threshold for thyristor trig of dynamic 0.0 – 1.0 0.022
brake
28.54 Flux threshold gain 2 Flux threshold for speed estimation of 0.0 – 1.0 0.147
7 dynamic brake
WARNING
EOL does not work during Sequence start.
Recommended to add separate overload
protections for each motor. Example: Start 1, (Start mode seq 1) is set to Run 1
For connections, see chapter 5.1.2.5 Programmable relay , (K4,K5 or K6) the relay closes when the start
inputs (Sequence start). signal is given, which leads to a power transfer. This
can change between softstarters and their specific
Parameters set for sequence start 1, 2 and 3 are equal. parameter settings.
If the softstarter trips, and the trip must stop the motor,
all motors stop.
08.07 Kick start seq 1 Enables a voltage peak at the beginning of Off, On Off
08.35 seq 2 the start ramp.
08.65 seq 3
Information: The function Current Limit is not
in operation during Kick start.
08.08 kick start level seq 1 Sets the level of the Kick start in percentage 50 ... 100% 70%
08.36 seq 2 of rated voltage.
08.66 seq 3
08.09 Kick start lvl seq 1 Sets the duration of the Kick start in 0.2 ... 2.0 s 0.2 s
08.37 seq 2 seconds.
08.67 seq 3
08.06 Torque lim lvl seq 1 Sets the level to which the torque is limited 20 ... 200% 150%
08.38 seq 2 during the start with torque control.
08.68 seq 3
08.10 Torque tune seq 1 Adjustment of resistive losses. 0 ... 1000% 100%
08.39 seq 2
08.69 seq 3
08.11 Torque ctrl gain seq 1 Sets the speed of the voltage regulator 0.01 ... 10.0 0.24
08.40 seq 2 during torque start and stop. It seldom
08.70 seq 3 needs to be changed, but if a dip occur in
the torque curve during stop, increasing this
value might solve it.
Chapter Function
7.12.1 Digital inputs
7.12.2 Relay outputs
7.12.3 Analog outputs
7.12.4 Temperature sensor
Internal I/O
• 5 Digital inputs
• 3 Relay output
• 1 Analog output
• 8 Digital input
• 4 Relay output
• 1 Analog output
1SFC132081M0201
terminal (NC). . See Figure 7.8 .
Normally open – Circuit is open in normal mode (circuit is
not shorted to common). Figure 7.8
Normally closed – Circuit is closed in normal mode (the A contactor may for example be connected (230 volts)
circuit is continuously shorted to common).
Temperature inputs
• PTC
• PT100
• Bi-metal switch
PTC
7
PT100
Bi-metal switch
Fieldbus type
• Modbus-TCP
• Modbus-RTU
• DeviceNet
• Profibus
• EtherNet/IP
7 • Profinet
Fieldbus control
Fieldbus address
CAUTION
The motor can start unexpectedly if there is a
start signal present during 1 of the actions below.
• Changing from 1 type of control to another (Fieldbus
control / hardwire control).
12.05 Fieldbus ip address Fieldbus IP: Sets the IP- 0.0.0.0 ... 255.255.255.255 0.0.0.0
address.
12.06 Fieldbus ip gateway Fieldbus IP: Sets the default 0.0.0.0 ... 255.255.255.255 0.0.0.0
gateway.
12.07 Fieldbus ip netmask Fieldbus IP: Sets the netmask. 0.0.0.0 ... 255.255.255.255 255.255.255.0
12.08 Fieldbus ip dhcp client Fieldbus IP: Enables dhcp. Off, On Off
12.09 FB baud rate* Sets the baud rate of internal 1200, 2400, 4800, 9600, 19200, * There are restrictions
modbus-RTU interface, 38400, 57600, 76800, 115200, on which baud rates 7
Anybus DeviceNet and Anybus 125000, 250000,500000, Auto you can use for
modbus-RTU. different protocols. See
separate Table below.
12.10 FB parity Sets parity for Anybus modbus- No parity, Odd parity, Even parity Even parity
RTU.
12.11 FB stop bits Select stop bits for Anybus 1 Stop bit, 2 Stop bits 1 Stop bit
modbus-RTU.
12.12 Fieldbus DI 1 Sets the DI 1 programmable Emergency mode feedback, Line
digital input signal. Event group 0 ... 6 status,
Fault reset feedback,
12.13 Fieldbus DI 2 Sets the DI 2 programmable Phase sequence
Line,
digital input signal.
Motor heating feedback,
12.14 Fieldbus DI 3 Sets the DI 3 programmable None, Event group 0 status
digital input signal. Phase sequence,
12.15 Fieldbus DI 4 Sets the DI 4 programmable Run reverse status, Event group 1 status
digital input signal. Run status,
Sequence 1 ... 3 Run status,
12.16 Fieldbus DI 5 Sets the DI 5 programmable Sequence 1 ... 3 TOR status, Start feedback
digital input signal. Slow speed rev feedback,
12.17 Fieldbus DI 6 Sets the DI 6 programmable Slow speed forw feedback, Stop feedback
digital input signal. Stand-still brake feedback,
Start 1 ... 3 feedback,
12.18 Fieldbus DI 7 Sets the DI 7 programmable Eventgroup 2 status
Start feedback,
digital input signal.
Start reverse feedback,
12.19 Fieldbus DI 8 Sets the DI 8 programmable Stop feedback, Eventgroup 3 status
digital input signal. TOR status,
User defined feedback
12.20 Fieldbus DI 9 Sets the DI 9 programmable Eventgroup 4 status
digital input signal.
12.21 Fieldbus DI 10 Sets the DI 9 programmable Eventgroup 5 status
digital input signal.
There are 7 event groups that you can use in any way.
Event groups 4-6 are completely unassigned by default
and are convenient to use for custom applications. The
other groups have (or may have in the future) events 7
assigned to them by default.
Example:
• Off
• Indication
13.03 EOL dual class Sets the protection class used when in top 10 A, 10, 10 A
of ramp. This parameter is only applicable 20, 30
when EOL protection mode is set to dual.
13.04 EOL out Identifies the Event groups this protection Eventgroup 0 ...6 0000010
is part of.
13.05 EOL operation Sets the operation of this protection. Off, Stop-Manual, Stop-Manual
Stop-Automatic,
Indication
14.03 Curr underload delay time Sets the time after Top of ramp that 0 ... 30 s 5s
the protection is enabled.
14.04 Curr underload out Identifies the Event groups this Eventgroup 0 ... 6 0000010
protection is part of.
14.05 Curr underload op Sets the operation of this Off, Stop manual, Off
protection. Stop auto, Indication
7
7.17.6 Current imbalance protection
17.06 PT100 out Identifies the Event groups this Eventgroup 0 ... 6 0000010
protection is part of.
17.07 PT100 op Sets the operation of this Off, Stop manual, Off
protection. Stop auto, Indication.
21.14 Current imbalance trip time User set time until warning in 0.1...100.0 s 5.0 s
seconds.
7
7.18.14 Fans fault warning
7
7.18.17 Motor runtime warning
Internal fault:
The softstarter has a fault. see chapter 10
Troubleshooting, and speak to ABB sales office if
necessary.
External fault:
There is a fault in the equipment that is connected to the
softstarter. see chapter 10 Troubleshooting, and speak
to ABB sales office if necessary.
You can add further actions for each fault, or change the
basic actions. If multiple faults occur they are all stored
in a sequence. Do a reset for each fault if manual reset is
selected.
25.02 Shunt fault op Sets the operation of this fault. Stop manual, Stop Stop manual
auto.
INFORMATION
If Automatic restart is set to on, a short circuit
fault will automatically start the motor again.
INFORMATION
If Automatic restart is set to on, an open circuit
thyristor fault will automatically start the motor
again.
25.06 Open circuit thyr op Sets the operation of this fault. Stop manual, Stop Stop manual
auto
INFORMATION
If Automatic restart is set to on, a thyristor
overload fault will automatically start the motor
again.
• Emergency mode
• Limp mode
• System mode
CAUTION
Emergency mode will disable all protections
and fault detection functions.
WARNING
The motor will not be protected from
overheating.
Normal mode 7
Normal mode is the default setting and is used in all
situations except the ones given below.
Demo mode
Demo is used mainly for training purposes to simulate a
load condition without having the softstarter connected to
main power.
CAUTION
When the softstarter is connected to a motor, do
not select demo mode, a direct start will occur.
Small motor mode
Small motor mode is used for basic testing purposes,
when using a smaller motor than the PSTX is specified
for. The softstarter is able to start the motor, but some
functions and protections are disabled.
System mode has these parameters:
Set the delay time from Top Of Ramp until the Top Of
Ramp relay is on
TOR relay delay time has these parameters:
• Language
7.22 Assistants
The Assistants menu contains default settings and
parameters. Use this menu to set only the necessary
parameters before you can start the motor. All necessary
input data shows up in an automatic loop. The Assistants
menu is divided in:
• Basic set-up
• Application set-up
INFORMATION
7
After you select an application and make your
changes, do not select this application again
because this resets the application to the default
settings.
Basic set-up
The Basic set-up menu is divided in 5 steps:
Language, Date and time, Motor data and System
configuration.
Application set-up
The Application set-up are quick settings for Applications,
Values and Tune settings. Use the Navigation keys to
select Application set-up. Push “Select” to enter the
Application set-up.
Select for what type of application you use the softstarter
by pushing “Select”.
For more details, see chapter 2 Quick start.
Start mode
Stop mode
Band saw 10 - 30 30 4 Voltage ramp No ramp
11 External IO
11.01 1DI0 function None, Reset, Enable, Slow speed forward, 0 145 None
Slow speed reverse, Motor heating, Stand-
still brake, Start reverse, User defined
protection, Emergency mode, Fieldbus
disable control, Start 1, Start 2, Start 3 ***
11.02 1DI1 function 0 ... 15 *** 0 146 None
11.03 1DI2 function 0 ... 15 *** 0 147 None
11.04 1DI3 function None, Reset, Enable, Slow speed forward, 0 148 None
Slow speed reverse, Motor heating, Stand-
still brake, Start reverse, User defined
protection, Emergency mode, Fieldbus
disable control, Start 1, Start 2, Start 3 ***
11.05 1DI4 function 0 ... 15 *** 0 149 None
11.06 2DI5 function 0 ... 15 *** 0 150 None
11.07 2DI6 function 0 ... 15 *** 0 151 None
11.08 2DI7 function 0 ... 15 *** 0 152 None
11.09 1DO0 function None, Run, Top of ramp, Event group 0, 0 153 None
7 Event group 1, Event group 2, Event group
3, Event group 4, Event group 5, Event
group 6, Sequence 1 Run, Sequence 2 Run,
Sequence 3 Run, Sequence 1 TOR,
Sequence 2 TOR, Sequence 3 TOR ****
11.10 1DO1 function 0 ... 15 *** * 0 154 None
11.11 2DO2 function 0 ... 15 *** * 0 155 None
11.12 2DO3 function 0 ... 15 *** * 0 156 None
11.13 1AO0 reference 0-10 mA, 0-20 mA, 4-20 mA, 0-10 V 0 157 4-20 mA
11.14 1AO0 type Motor current [A], Mains voltage [V], Active 0 158 Motor current
power [kW], Active power [HP], Reactive [A]
power [kVAr], Apparent power [kVA], Active
energy [kWh], Reactive energy [kVArh],
COS [θ], Motor temperature [%], Thyristor
temperature [%], Motor voltage [%]
Mains frequency [Hz], PT100 temperature
[centigrade], PTC resistance [Ω]
11.15 1AO0 max value 0 ... 1000000 0 159 500
11.16 1AO0 min value 0 ... 1000000 0 160 0
12 Communication
12.01 Com3 function None, Test, Modbus RTU slave. Extension 0 26 Test
I/O
12.02 FB interface connector FbPlug, Modbus RTU, Anybus, None 0 32 None
12.03 Fieldbus control On / Off 0 45 Off
12.04 Fieldbus address 0 ... 65535 0 51 0
12.05 Fieldbus IP address 000.000.000.000 0 58 0
12.06 Fieldbus IP gateway 000.000.000.000 0 59 0
12.07 Fieldbus IP netmask 255.255.255.000 0 83 255.255.255.0
12.08 Fieldbus IP DHCP client On / Off 0 92 Off
12.09 FB baud rate 1200, 2400, 4800, 9600, 19200, 38400, 0 185 19200
57600, 76800, 115200, 125000, 250000,
500000, auto
12 Communication
12.13 Fieldbus DI 1 None, Start feedback, Stop feedback, Fault 0 142 Run status
reset feedback, Slow speed rev feedback,
Slow speed forw feedback, Start 1 feedback,
Start 2 feedback, Start 3 feedback, Motor
heating feedback, User defined feedback,
Stand-still brake feedback, Emergency
mode feedback, Start reverse feedback, Run
status, TOR status, Line, Phase sequence,
Event group 0 status, Event group 1 status,
Event group 2 status, Event group 3 status,
Event group 4 status, Event group 5 status,
Event group 6 status, Sequence 1 Run
status, Sequence 2 Run status, Sequence
3 Run status, Sequence 1 TOR status,
Sequence 2 TOR status, Sequence 3 TOR
status, Run reverse status *** **
12.13 Fieldbus DI 2 0 ... 32 *** ** 0 143 TOR status
12.14 Fieldbus DI 3 0 ... 32 *** ** 0 144 Line
12.15 Fieldbus DI 4 0 ... 32 *** ** 0 161 Phase
sequence
12.16 Fieldbus DI 5 0 ... 32 *** ** 0 162 Start feedback
12.17 Fieldbus DI 6 0 ... 32 *** ** 0 163 Stop feedback
12.18 Fieldbus DI 7 0 ... 32 *** ** 0 164 Event group 0 7
status
12.19 Fieldbus DI 8 0 ... 32 *** ** 0 165 Event group 1
status
12.20 Fieldbus DI 9 0 ... 32 *** ** 0 166 Event group 2
status
12.21 Fieldbus DI 10 0 ... 32 *** ** 0 167 Event group 3
status
12.22 Fieldbus AI 1 None, Phase L1 current, Phase L2 current, 0 168 Phase L1
Active power (HP), Active power, Apparent current
power, Mains voltage, Power factor, Motor
voltage, Active energy (resettable), EOL time
to trip, Mains frequency, Max phase current,
Motor current, Motor run time (resettable),
Motor temperature, Motor temperature
percent, Number of starts (resettable),
Phase sequence, PT100 temperature, PTC
resistance, Reactive energy (resettable),
Reactive power, Remaining time to start,
Thyristor temperature, Thyristor temperature
percent, EOL time to cool, Top event code,
Motor current percent, Thyristor run time
(resettable), Motor connection *** ***
12.23 Fieldbus AI 2 0 ... 32 *** *** 0 169 Phase L2
current
12.24 Fieldbus AI 3 0 ... 32 *** *** 0 172 Phase L3
current
12.25 Fieldbus AI 4 0 ... 32 *** *** 0 174 Max phase
current
12.26 Fieldbus AI 5 0 ... 32 *** *** 0 177 Mains
frequency
12.27 Fieldbus AI 6 0 ... 32 *** *** 0 178 Motor voltage
12.28 Fieldbus AI 7 0 ... 32 *** *** 0 179 Motor
temperature
percent
13 Protections list 1
13.01 EOL mode Normal, Dual 0 55 Normal
13.02 EOL class 10A, 10, 20, 30 0 56 10
13.03 EOL dual class 10A, 10, 20, 30 0 57 10A
13.04 EOL out 0 ... 127 0 84 0000010
13.05 EOL operation Off, Stop-Manual, Stop-Automatic, Indication 0 227 Stop-Manual
13.06 Locked rotor level 0.5 ... 8.0 x Ie 1 54 4.0 x Ie
13.07 Locked rotor trip time 0.20 ... 10.00 s 2 53 1.00 s
13.08 Locked rotor delay time 1.00 ... 30.00 s 2 52 5.00 s
13.09 Locked rotor out 0 ... 127 0 85 0000010
13.10 Locked rotor op Off, Stop-Manual, Stop-Automatic, Indication 0 228 Off
13.11 Max no of starts per hour 1 ... 100 0 229 6
13.12 Max no of starts per hour 0 ... 127 0 230 0000010
out
13.13 Max no of starts per hour Off, Stop-Manual, Stop-Automatic, Indication 0 231 Off
op
14 Protections list 2
14.01 Curr underload level 0.3 ... 0.9 x Ie 1 232 0.5 x Ie
14.02 Curr underload trip time 0 ... 10 s 0 233 10 s
7
14.03 Curr underload delay time 0 ... 30 s 0 234 5s
14.04 Curr underload out 0 ... 127 0 87 0000010
14.05 Curr underload op Off, Stop-Manual, Stop-Automatic, Indication 0 235 Off
14.06 Pwr factor underload level 0.00 ... 1.00 2 236 0.50
14.07 Pwr factor underload trip 0 ... 10 s 0 237 10 s
time
14.08 Pwr factor underload delay 0 ... 30 s 0 238 5s
time
14.09 Pwr factor underload out 0 ... 127 0 86 0000010
14.10 Pwr factor underload op Off, Stop-Manual, Stop-Automatic, Indication 0 239 Off
14.11 Curr imb level 10 ... 80% 0 61 80%
14.12 Curr imb trip time 1 ... 30 s 0 63 10 s
14.13 Curr imb delay time 1 ... 30 s 0 62 5s
14.14 Curr imb out Eventgroup 0 ... 6 0 64 0000010
14.15 Curr imb operation Off, Stop-Manual, Stop-Automatic, Indication 0 60 Off
15 Protections list 3
15.01 Over voltage level 170 ... 850 V 0 67 850 V
15.02 Over voltage trip time 0.1 ... 100.0 s 1 65 1.0 s
15.03 Over voltage out 0 ... 127 0 68 0000010
15.04 Over voltage op Off, Stop-Manual, Stop-Automatic, Indication 0 66 Off
15.05 Under voltage level 165 ... 850 V 0 71 165 V
15.06 Under voltage trip time 0.1 ... 100.0 s 1 69 1.0 s
15.07 Under voltage op Off, Stop-Manual, Stop-Automatic, Indication 0 70 Off
15.08 Under voltage out 0 ... 127 0 72 0000010
15.09 Voltage imb level 1 ... 100% 0 77 10%
15.10 Voltage imb out 0 ... 127 0 78 0000010
15.11 Voltage imb op Off, Stop-Manual, Stop-Automatic, Indication 0 76 Off
15.12 Voltage imb trip time 1 ... 100 s 0 10 s
16 Protections list 4
16.01 Phase rev out 0 ... 127 0 89 0000010
16.02 Phase rev operation Off, Stop-Manual, Stop-Automatic, Indication 0 240 Off
16.03 Freq range lower trip lvl 40 ... 72 Hz 0 241 45 Hz
20 Warnings list 1
20.01 EOL level 40.0 ... 99.0% 1 181 90.0%
20.02 EOL out Eventgroup 0 ... 6 0 123 0000100
20.03 EOL warning On / Off 0 182 Off
20.04 Locked rotor level 0.2 ... 10.0 x Ie 1 261 1.2 x Ie
20.05 Locked rotor init time 1.0 ... 30.0 s 1 262 5.0 s
20.06 Locked rotor out Eventgroup 0 ... 6 0 125 0000100
20.07 Locked rotor On / Off 0 263 Off
20.08 Thyristor OL out Eventgroup 0 ... 6 0 124 0000100
20.09 Thyristor OL On / Off 0 122 Off
The PSTX Softstarter has a non-isolated RS485 physical These Anybus CC connection devices are available:
interface, com 3, for external devices with support for • DeviceNet
RS485 based communication. • Profibus (DPV1)
You can use this interface to control the softstarter, get • Modbus RTU
status information, and for the upload and download of • Modbus TCP
parameters. • EtherNet/IP
The softstarter uses the RS485 interface for a modbus • Profinet
RTU slave connection.
• Profibus (DPV0/DPV1)
www.abb.com/lowvoltage
9.1 Regular maintenance
For warranty for damage on the thyristors, the
coordination type 2 is necessary.
• Make sure that all installation bolts/screws are
fastened. Tighten if necessary.
CAUTION
• Make sure that the softstarter is de-energized
before tightening the bolts/screws.
• Make sure that the airways are free from dirt and dust.
WARNING
Do not use pressurized air to clean the softstarter.
• Make sure that the fan works and rotates freely. The
blades must rotate without resistance.
10.1 General
142
10.2 Troubleshooting
142
10
CAUTION
Dangerous voltage: Can cause death or serious
injury. Always set the power switch to off and lock
out all power to this device before you start to
work on the equipment.
CAUTION
Make sure that the softstarter is de-energized
before you do maintenance.
Do not open the softstarter or touch live parts
when the main and supply voltage is connected.
INFORMATION
ABB personnel must follow the ABB CISE 15.4
instructions
The softstarter indicates a fault with LED Fault, and
the display shows which type of fault occurred.
When a protection is on, the LED Protection
illuminates and the display shows which type of
protection is active.
When a warning occurs, the display shows the type
of warning.
In this chapter you can also find issues that the
softstarter does not show, such as humming
sounds.
10 10.2 Troubleshooting
Table 1 Troubleshooting
Status Possible cause Solution
Motor humming / starts without given Bypass relay closed, because of • Disconnect the operation voltage and the control
start signal. inaccurate handling. supply voltage. Remove USB cable from the computer
(PSTX30...170 only). if connected. Connect voltage in this sequence:
1. Control supply voltage on terminals
1 and 2. See chapter 5.1.2 Control supply and
control circuit.
2. Wait 4 seconds, and then connect operation
voltage on terminals L1, L2 and L3.
• If the fault stays, speak to your ABB Sales Office.
Bypass contactor/relay stuck in • Speak to your ABB Sales Office.
closed position.
Shorted thyristor. • Speak to your ABB Sales Office.
Bad motor sound during start. The motor connection is not • Examine and correct the wiring. Connect the control
correct. supply voltage. Refer to the circuit diagram. See
chapter 11 Wiring diagrams.
Incorrect ramp time for start. • Try different ramp times (some adjustments can be
necessary for best result). See chapter 7 Functions.
Incorrect ramp time for stop. • Make sure that you have the correct softstarter for
this motor size.
For test purposes you can use small motor mode.
See chapter 7 Functions.
Start and stop command given at • Make sure that start and stop command is not given
the same time. at the same time.
The operation voltage is below • Do a check of the operation voltage.
175 V.
Motor does not start when given start Control wiring is not correct. • Do a check of the connections for start and stop.
command by the hardwire inputs. Start and stop command given at • Make sure that start and stop command is not given
the same time. at the same time.
Keypad is in Local control mode. • Make sure that the keypad is not in Local Control
mode.
• Push the R\L-key to change to Remote Control mode.
• Make sure that parameter Fieldbus control is set to
No.
• Do a reset on an active event.
• Reset tripping events.
Motor does not start with Fieldbus. Softstarter has tripped on fault or • Do a reset on an active event.
protection. Reset tripping events.
Softstarter is in Local mode. • Make sure that the Stop bit of the binary output
telegram setting is set to 1.
• Make sure that parameters match between the PLC 10
and the softstarter Fieldbus documentation for the
used Fieldbus protocol.
• Make sure that the Auto mode bit of the binary output
telegram setting is set to 1.
• Do a check if the HMI is set to remote mode.
• Make sure that the Local Mode digital input on the
ABB FieldBus Plug adapter is set to Remote.
• Make sure that Fieldbus disable control in DI is not
connected.
• Make sure that the Fieldbus control parameter is set
to On.
Fieldbus operation when fault • If the parameter Fieldbus failure op is set to Change to
parameter is set to Change to I/O I/O control when fault occurs, there is a 10 seconds
control. delay before you can re-start after communication is
connected.
Loading of parameters with Fieldbus Fieldbus settings. • Make sure that parameters match between the PLC
does not work correctly. and the softstarter Fieldbus documentation for the
used Fieldbus protocol.
• Make sure that the Auto mode bit of the binary output
telegram setting is 1.
• Do a check if the HMI is set to remote control.
• Make sure that the Local Mode digital input on the
ABB FieldBus Plug adapter is set to Remote.
• Make sure that Fieldbus disable control in DI is not
connected.
• Make sure that the Fieldbus control parameter is set
to On.
Shown phase currents in screen do not Inside Delta connection. • If the softstarter is connected Inside Delta, the phase
agree with motor current. currents shown are = 58% ( 1 /(√3)) of the motor
current.
Shown current in screen is not stable. The motor is too small. • Make sure that you have the correct softstarter for
The load on the motor is too small. this motor size..
(Current is out of measuring
range.)
Dark screen and LED is active Power save mode. • Touch a key on the keypad.
Blank screen and no LED is active Supply voltage is not connected. • Connect the Supply voltage. Refer to the circuit
diagram.
• If problem stays, speak to your ABB Sales Office.
• The RJ45 plug is missing • Do a check of the RJ45 plug.
between the HMI and the • Do a check of the RJ45 Network cable
softstarter.
10
Start prerequisites
Separate func
Close bypass
Open bypass
Top of ramp
(Hexadecimal)
Start Ramp
Stop ramp
Stand by
Pre-start
Init start
Electronic overload P0Fxx X X X X X X X X X X
Locked rotor P10xx X
Phase reversal P11xx X X X X X X X X
Current imbalance P12xx X
Current underload P13xx X
User defined protection P14xx X X X X X X X X X X
Ground fault P15xx X X X X X X X X
Overvoltage P16xx X
Under voltage P17xx X
Voltage imbalance P18xx X X X X X X X X
Protections
Start prerequisites
Separate func
Close bypass
Open bypass
Top of ramp
(Hexadecimal)
Start Ramp
Stop ramp
Stand by
Pre-start
Init start
High current F02xx X X X X X X X X X X
Phase loss F03xx X X X X X X X X
Heatsink overtemperature F04xx X X X X X X X X X X
Bad network quality F05xx X X X X
Shunt fault F06xx X X X X
Low supply voltage F07xx X X X X X X X X X X
Faults
For a description of the protections, see chapter 7.17 Protections group 0-6.
Continuous run
Phase reversal The phase sequence is not • Change the phase sequence on the line side to (L1-
correct. Current imbalance L2-L3).
between the phases. • Start the motor again and do a check of the main
currents and voltage.
Current imbalance Current imbalance between the • Start the motor again and do a check of the main
phases. currents and voltage.
Current underload The motor current is below the • Examine and correct the reason for the underload.
specified value. • Make sure that the motor current parameter (Ie) is set
correctly.
User defined protection With the programmable digital • Set the programmable input signal to inactive state 10
input and an external device/ before you reset the protection event.
sensor the user can use his own
specified protection.
Ground fault Equipment protection. In a • Examine motor cables.
symmetrical 3-phase system, the • Examine the motor.
sum of the instantaneous line
currents is equal to zero. Ground
fault indicates if the sum differs
more than the specified value. This
can indicate a serious condition of
the motor.
Overvoltage The main voltage is too high • Do a check of the main voltage.
Under voltage The main voltage is too low. • Do a check of the main voltage.
Voltage imbalance Voltage imbalance between the • Do a check of the main voltage and start the motor
phases. again.
External thermal sensor The external thermal sensor • Make sure that the PTC or PT100 circuit is closed and
- PTC protection detected a temperature higher that the inputs are connected.
- PT100 protection than the trip level in the motor or • Examine and correct the reason for the high
PT100. temperature.
• Wait for the temperature of the motor to decrease
sufficiently and start again.
Power factor underload The power factor is below the • Examine and correct the reason for the underload.
normal level.
Too long current limit The time at current limit is higher • Do a check of the starting conditions and parameters.
than the set value.
The starting condition is too heavy
for the set current limit.
Bypass open fault Bypass contactor or relay does not • Do a check and speak to your ABB sales office.
close when reached TOR.
Fieldbus communication failure There is a communication error • Make sure that the FieldBus Plug is connected
between the softstarter and PLC. correctly.
• Make sure that correct type of FieldBus Plug is used.
• Make sure that the parameter Fieldbus Type is set for
the present Fieldbus type.
24V output The 24V voltage outputs is • Do a check of the connections.
overloaded or shorted.
HMI failure There is a communication error • Do a check of the connections and correct it.
between the softstarter and the
HMI.
The HMI is removed. • Put the HMI back.
Extension IO failure There is a communication error • Do a check of the connections and correct it.
between the softstarter and the
extension I/O module.
Max number of start per hour The softstarter made more starts • Wait for the next start interval.
than the pre-set limited number For parameter, see chapter 7 Functions.
of starts.
Auto-restart time-out The time between trip and auto- • Do a check of the automatic restart parameters and
restart attempt exceeds setting. correct it.
Too long start time The time to soft start the motor is • Do a check of the starting conditions and current
longer than the set value. limit..
Frequency range The frequency has been outside • Do a check of the main voltage.
the allowed range longer than the
allowed time.
10
For a description of the faults, see chapter 7.19 Faults (26) Internal faults (27) External faults
The Operation voltage is below • Make sure that you have the correct softstarter for this
175 V. motor size.
The motor is too small. • For test purposes you can use small motor mode. 10
See chapter 7 Functions.
Unspecified fault N/A • Disconnect the supply voltage (Us). Connect it again
and start again.
• If the same fault stays, speak to your ABB sales office.
Invalid ID ID parameter out of range • Speak to ABB sales office for service.
Faulty connection Motor connection unknown when • Do a check of the motor connection.
trying to start motor.
Faulty usage Inside delta motor connection • Do not use these functions with Inside delta motor
when you try to jog forward, jog connection.
11
1L1
3L2
5L3
Ct1
Ct2
22 Ct3
21
20 +24V
Internal control voltage 19
19 GND
18
18 DGND
Stop Start 20, 21 17 In2
13 16 In1
14 15 In0 Low Voltage Board
14 Stop
V1
13 Start V2
12 HMI
Internal control voltage
19
11
18 K6
3L2
1L1
5L3
10 Internal
20, 21 V3
Bypass
9 V4 K2
13 Contactor
4T2
2T1
6T3
14 8 K5
Stop Start 7
6 V5
5 V6
K4
External control voltage 24V DC 4
18
3
L Bypass*
13 2 N 100-250V
1 L 50/60 Hz
14
Stop Start 2T1
4T2
6T3
23, 24 25, 26, 27 28 29 30
Anybus Fieldbus Modbus PTC +24V Analog out GND
Extension I/O PT100
U V W
Anybus
M
* Only on PSTX470 ... PSTX1250
23 24 CXFU CCT
13 14
STOP START
21 22 13 14
STOP 13
START 14
+24V 20, 21
DGND 18
GND 19
1 2 3 13 14 15 16 17 18 19 20 21 22 L1 L2 L3
L N L
In1
In0
In2
DGND
GND
Start
Stop
+24V
Bypass*
100-250V
50/60 Hz
K4 K5 K6
Relay Relay Relay K1 K2 K3
Modbus PTC Analog
Extension I/O PT100 +24V out GND
4 5 6 7 8 9 10 11 12 Anybus Fieldbus
23 24 25, 26, 27 28 29 30
T1 T2 T3
Anybus
MTR MTR
12
Symbols D
2-wire measurement for PT100 44 Date and time 66
2-wire measurement for PTC 45 Delivery note 30
3-wire measurement for PT100 44 Description 17
Detachable keypad 32
A Digital inputs (DI) 86
ABB Fieldbus plug interface (option) 132 Dimensions and drilling plan 32
Acronyms and abbreviations 9 Direct stop 77
Active faults/protections and warnings 57 Display decimals 57
Add information screens to home view 56 Display name 57
Analog output 46, 88 Display settings 66
Anybus CompactCom 132 Display slot 56
Application Setting 14, 61, 118 Display style 57
Application set-up 14, 61 Document number 2
Assistants 61, 118 Drilling plan 32
• Application set-up 61 Dual current limit 79
• Basic set-up 61
Automatic restart 84 E
Available faults 19 Ground fault protection 101
Available protections 18. See also Protections Edit home view 56
Available warnings 19. See also Warnings Edit information screens in home view 56
Edit parameter values 52
B Electrical connection 36
Backup handling 63 Electronic overload time-to-trip warning 107
• Create backup 63 Electronic overload warning 104
• Replace backup 63 Emergency mode 115
• Uploading of parameters 63 Environmental influence 21
Bad network fault 113 EOL 9
Basic set-up 14, 61 EOL Protection 95
Bi-metal switch 89 Error caused by the line 45
Built in modbus RTU 132 Event groups 93
Bypass 18 Event log
Bypass open protection 99 • Faults 62
• Parameter changed 62
C • Protections 62
Changing the Rated motor current • Run 62
(Setting Ie). 53 • Warnings 62
Communication 131 Extension I/O failure protection 103
Communication protocols 22 Extension IO (Option) 85
Complete list 58 External control voltage 40
13
Complete parameter list 120 External fault 110
Configuration 14 External faults 113
Connection 12 External thermal sensor - PT100 protection 100
Connection fault 114 External thermal sensor - PTC protection 100
control circuit 9
Control supply and control circuit 38 F
Control supply voltage 9 Fault 22
Control supply voltage - terminals 1 and 2 38 Fault detection functions 19
cooling 31 Faults 62, 110
Cooling system 22 • External fault 110
Create backup 63 • Internal fault 110
current 9 Faults indication 146
Current imbalance protection 97 Faulty usage fault 114
Current imbalance warning 106 Favorites 60
Current Lim Fieldbus 90
• Dual current limit 79 • Fieldbus address 90
• Ramp current limit 79 • Fieldbus control 90
K P
Keypad Parameter changed 62
• i-key 51 Parameters 58
• Navigation keys 51 • Complete list 58
• R\L-key 51 Phase loss fault 113
• Start key 51 Phase reversal protection 99
• Stop key 51 PLC 9
Kick start 80 Pollution degree 21
13
Power factor underload protection 97
L Power factor underload warning 105
Language 65 Presentation settings 64
LED 9 Pre-start 70
LED indicators 50 Programmable inputs (Sequence start) 42
LED status 50 Programmable inputs - terminals 15, 16 and 17 41
Limp mode 116 Programmable output relay - K4, terminals 4, 5 and 6 43
Line contactor close time 116 Programmable output relay - K5, terminals 7, 8 and 9 43
Local control from keypad 54 Programmable output relay - K6, terminals 10, 11 and 12 43
• R\L-key 54 Protection 21
• Start key 54 Protection functions 18
• Stop key 54 Protection indication 145, 148
Locked rotor protection 95 Protection indication shown on screen 145
Locked rotor warning 104 Protections 62, 94
Low supply voltage fault 114 PT100 89
Under voltage warning 106 PTC 89
Softstarters Type PSTX, Installation and commissioning manual, 1SFC132081M0201 rev G, January 2016
Specification subject to change without notice.
Control Products
Low Voltage Products
www.abb.com/lowvoltage