Dual Modular Safety Shutoff Valves DMV-D/11 Series DMV-DLE/11 Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Dual Modular Safety

Shutoff Valves

DMV-D/11 Series
DMV-DLE/11 Series

Two normally closed safety shutoff


valves in one housing; each with
the following approvals.

CSA Certified
• ANSI Z21.21
• CSA 6.5
• Marked C/I
• File # 157406

FM Approved
• Class 7411
• File # J.I. 3007653

Commonwealth of Massachusetts
Approved Product
• Approval code G1-1107-35
• Gas Safety Shutoff Valve

EU Gas Appliance Regulation


• EN161

Codes and Standards


This product is intended for instal-
lations covered by but not limited to
NFPA 86, NFPA 37, CSA B149.1, Description Directly mounting the following DUNGS
CSA B149.3 and CSA 149.6 The DUNGS Dual Modular Valve (DMV) accessories creates a compact valve
combines two safety shutoff valves in train without additional piping:
DUNGS is an ISO 9001 one compact housing, which can be - High and low gas pressure switches
manufacturing facility. wired independently or in parallel. - Valve proving system
- 1" NPT Vent line adapter
Valve 1 (V1) of the DMV-D and DMV-
DMV ISO FLANGED Sales Brochrue • P/N 242955 • Ed. 05/19

DLE series is fast opening and fast Application


closing. Valve 2 (V2) of the DMV-D is The DUNGS DMV is recommended for
fast opening, while V2 of the DMV-DLE industrial and commercial heating apli-
is slow-opening for smoother light-off. cations that require two safety shutoff
Max. flow adjustment on V1 provides valves. The DMV Dual Modular Valve is
variable main flow on both models. suitable for dry natural gas, propane, bu-
tane, air and other inert gases. Suitable
Internal profiles and compact design for up to 0.1% by volume, dry H2S.
optimize flow and provide a low pres-
sure drop. A “dry” gas has a dew point lower than
+15 °F and its relative humidity is less
than 60 %.

1…6
DMV-D…/11 Two normally closed safety shutoff valves in one housing. V1 and V2 are fast opening, fast closing.
Adjustable max. flow with V2.

DMV-DLE…/11 Two normally closed safety shutoff valves in one housing. V1 fast opening, fast closing.
V2 is slow opening, fast closing. Adjustable max. flow and adjustable initial lift with V2.

Specifications
Flange sizes DN 40 (1 1/2") 50 (2") 65 (2 1/2") 80 (3") 100 (4") 125 (5")
Connection flange as per DIN 2501 Part 1, to fit pre-weld flanges as per DIN 2633
(PN 16) DN 40 to DN 125, ISO 7005 - 1 (PN 16), or ISO 7005 - 2 (PN 16).
Max. operating pressure 7 PSI (500 mbar) CSA, FM, CE (Class A)
Max. body pressure 15 PSI (1000 mbar)
Max. close off pressure 7 PSI (500 mbar) CSA, FM, CE (Class A)
Electrical ratings (+10 % / -15 %) 110 - 120 VAC @ 50 - 60 Hz and 24 VDC. Part numbers listed on page 3.
220 - 240 VAC @ 50 - 60 Hz
Enclosure rating NEMA Type 12
Electrical connection DIN-connector with 1/2” NPT conduit adapter (order separately)
Operating time 100 % duty cycle
Closing time <1s
Opening time (to max. flow) DMV-D…/11 V1 & V2 < 1 s
DMV-DLE…/11 V1 < 1 s; V2 Adjustable to approx. 10 to 20 s at 70 °F
Initial lift adjustment Adjustable on V2 DLE only; 0 to 70 % of total flow; 0 to 25% of stroke
Max. flow adjustment Adjustable on V1 <10 to 100 % of total flow; <10 to 100% of stroke
Materials in contact with gas Housing: Aluminium, Steel; free of non-ferrous metals
Sealings on valve seats: NBR-based rubber
Ambient temperature rating +5 °F to +140 °F (-15 °C to +60 °C)
Installation position Safety shut off valve from vertically upright to horizontal
Gas strainer (standard) Installed in the housing upstream V1 (23 mesh)
Position indication CPI 400 with indication lamps and SPDT interlock switch or
(order separately) Visual indicator (VI)
Test ports / G 1/8 ISO 228 ports available on both sides. Each side has two ports upstream
Pressure switch mounting ports V1, one between V1 and V2, one downstream V2.
G 1/4 ISO 228 on both flanges, upstream of V1, downstream of V2
Valve proving system VPS 504; mounts directly to either side of DMV

Power Ratings
Version Coil Type Approx. Power Approx. Power Approx. Approx.
Rating [VA] @ Rating [VA] @ 24 Current [A] @ 120 Current [A] @ 24
120 VAC VDC VAC VDC
DMV-D(LE) 5040/11 1212 90 70 0.74 2.6
DMV-D(LE) 5050/11 1212 90 70 0.74 2.6
DMV-D(LE) 5065/11 1411 110 90 0.92 3.8
DMV-D(LE) 5080/11 1511 110 95 0.92 4.0
DMV-D(LE) 5100/11 1611 135 95 1.12 4.0
DMV-D(LE) 5125/11 1711 200 155 1.68 6.5

2…6
Dimensions inch (mm)

Type 110 - 120 VAC 24 VDC Pmax. Connection Dimensions [inch] Weight
@ 50 - 60 Hz Order No. [PSI] DN Dimensions [mm] [lbs]
Order No. [kg]
a b c e f
DMV-D 5040/11 226061 226063 7 DN 40 9.5 2.5 7.6 3.9 5.9 17.2
240 62,5 192 100 150 7,8
DMV-D 5050/11 226064 226066 7 DN 50 9.5 2.9 7.6 3.9 6.5 18.3
240 73 192 100 165 8,3
DMV-D 5065/11 226067 226069 7 DN 65 11.4 3.4 9.9 4.0 7.3 32.2
290 87 251 102 185 14,6
DMV-D 5080/11 226070 226072 7 DN 80 12.2 4.1 11.5 5.1 7.9 52.0
310 104 293 129 200 23,6
DMV-D 5100/11 226073 226075 7 DN 100 13.8 4.7 13.0 5.6 8.7 67.5
350 119 331 143 220 30,6
DMV-D 5125/11 226076 226078 7 DN 125 15.8 5.6 16.2 6.3 10.0 111.6
400 142 412 161 255 50,6
DMV-DLE 5040/11 226115 226117 7 DN 40 9.5 2.5 8.7 3.9 5.9 17.4
240 62,5 220 100 150 7,9
DMV-DLE 5050/11 226118 226120 7 DN 50 9.5 2.9 8.7 3.9 6.5 18.5
240 73 220 100 165 8,4
DMV-DLE 5065/11 226102 226103 7 DN 65 11.4 3.4 10.6 4.0 7.3 32.6
290 87 269 102 185 14,8
DMV-DLE 5080/11 226104 226106 7 DN 80 12.2 4.1 12.3 5.1 7.9 53.1
310 104 312 129 200 24,1
DMV-DLE 5100/11 226112 226114 7 DN 100 13.8 4.7 15.1 5.6 8.7 68.6
350 119 382 143 220 31,1
DMV-DLE 5125/11 226108 226110 7 DN 125 15.8 5.6 18.2 6.3 10.0 112.7
3…6 400 142 462 161 255 51,1
Equipment variants of DMV 5040/11 - DMV 5125/11 X standard
DMV.../11 double solenoid valve, (X) on request
single-stage mode
- not possible
DMV-D X
DMV-DLE X
Sieve X
Gas pressure switch can be mounted:
on flange X
Possible using
a pipe nipple
downstream of sieve (X)
downstream of valve 2 (X)
Valve V1, double-seat X
Valve V2, double-seat X
Valves opening separately X
G 3/4 ignition gas flange can be mounted (X)

Required Flanges & Accessories


Body Size Flange # of Holes * Flange Bolt size **Bolt ***Gasket
Description per Flange Order No. Order No. Order No.
DMV-D(LE) 5040/11 1 1/2“ ISO Flanged 4 227137 M16x55 135930 267463
DMV-D(LE) 5050/11 2“ ISO Flanged 4 227138 M16x65 135930 267464
DMV-D(LE) 5065/11 2 1/2“ ISO Flanged 4 227139 M16x65 135930 267465
DMV-D(LE) 5065/11 2 1/2“ ISO to NPT 4 243690 M16x65 135930 267465
DMV-D(LE) 5080/11 3“ ISO Flanged 8 227140 M16x65 135930 267466
DMV-D(LE) 5080/11 3“ ISO to NPT 8 243219 M16x65 135930 267466
DMV-D(LE) 5100/11 4“ ISO Flanged 8 227141 M16x65 135930 267467
DMV-D(LE) 5125/11 5“ ISO Flanged 8 227142 M16x75 148830 267468
*When a control is used alone, one mating flange is needed for each end, for a total of two flanges.

When one control is bolted to another, such as an FRS to a DMV, one mating flange is needed for each end, for a total of two flanges.

**includes one bolt, one lock washer, and one nut.

***one gasket needed for each flange connection.

4…6
Dual Modular Valve (DMV) system

Port 1
Port 2

Port 3
Port 4

Port 5
V1 V2
Port 6 Port 7

DMV

Port 1 Port 5

Port 2

Port 4
Port 3
Valve Valve
switch switch
Min. gas pressure switch Max. gas pressure switch

Valve proving system

Additional Accessories GAO/GMH/GML A2 pressure switch Adapters


• 1/4” NPT adapter (225047)
VPS 504 Position indication • 1/2” NPT Pilot gas adapter;
Valve proving system (approved by some CPI 400 with indication lamps and SPDT Check flow requirements. (225043)
authorities having jurisdiction in lieu of interlock switch, or Visual indicator (VI) • G 1/8” Test nipple (219008)
vent valve and “proof of closure” e.g. FM • 1" NPT Vent line adapter (243760)
and Swiss Re). DMK butterfly control valve
Mounts directly downstream of DMV to
modulate gas flow. Requires actuator.
Use DMA actuator with DMK butterfly
valve.

Pressure drop for other gases the “corrected” flow rate in CFH through f (f = 0.66 for propane). Use this “cor-
To determine the pressure drop when the valve for the other gas used. For ex- rected” flow rate and the flow curve on
using a gas other than natural gas, ample, when using propane, divide the the next page to determine pressure
use the flow formula below and f value volume (CFH) of propane required for drop for propane.
located in the table below to determine the application by the calculated value

Determining equivalent flow through valves using another gas

° ° Type of gas Density


Vgas used = V Natural gas x f [kg/m3]
s.g. f

Natural gas 0.81 0.65 1.00


Butane 2.39 1.95 0.58
Propane 1.86 1.50 0.66
Density of Natural gas Air 1.24 1.00 0.80

f= Density of gas used

5…6
Dual Modular Safety
Shutoff Valves

DMV-D/11 Series
DMV-DLE/11 Series

Flow curve
Pressure drop (in. W.C.)

Based on 60 °F
14.65 psia, dry

40,000 60,000
Flow (CFH) of natural gas; s.g. 0.65 at 60 °F

We reserve the right to make any changes in the interest of technical progress.

Karl Dungs, Inc. Karl Dungs GmbH & Co. KG


3890 Pheasant Ridge Drive NE P.O. Box 12 29
Suite 150 D-73602 Schorndorf, Germany
Blaine, MN 55449, U.S.A. Phone +49 (0)7181-804-0
Phone 763 582-1700 Fax +49 (0)7181-804-166
Fax 763 582-1799 e-mail info@dungs.com
e-mail info@karldungsusa.com Internet http://www.dungs.com
Internet http://www.dungs.com/usa/ 6…6

You might also like