Omnigrad M TR44, TR45: Technical Information
Omnigrad M TR44, TR45: Technical Information
Omnigrad M TR44, TR45: Technical Information
Application
• All hygienic applications for food, pharmaceutical and
fine chemicals industries
• Measuring range: -50...400 °C (-58...752 °F)
• Pressure range up to 40 bar (580 psi)
• Degree of protection: up to IP 68
Head transmitters
All Endress+Hauser transmitters are available with
enhanced accuracy and reliability compared to directly
wired sensors. Easy customizing by choosing one of the
following outputs and communication protocols:
• Analog output 4...20 mA
• HART®
• PROFIBUS® PA
• FOUNDATION Fieldbus™
Your benefits
• High flexibility due to modular assembly with standard
terminal heads and customized immersion length
• Providing most common hygienic process connections
with EHEDG certification and hygienic design due to
3-A® guidelines
• High accuracy with Pt100 sensors according
to IEC 60751 (class A or better)
• Type of protection for use in hazardous areas:
Intrinsic Safety (Ex ia)
Non-Sparking (Ex nA)
4 5 0
TI244T/02/en
71073141
TR44, TR45
Measuring system
a0008948
Example of an application
2 Endress+Hauser
TR44, TR45
Equipment architecture
TR44 TR45
10 mm
(0.4 in)
1 2
E E
E
4
4
IL IL
5 5
L L L
6 6a 6 6b 6c
a0009567
Equipment architecture of the Omnigrad M TR44 (non-replaceable insert) and TR45 (replaceable insert)
1 Insert (∅ 3 mm, 0.12 in) with mounted head 6 Various tip shapes, detailed information see chapter ’tip shape’:
transmitter, for example 6a Straight and reduced for TR44
2 Insert (∅ 6 mm, 0.24 in) with mounted 6b Tapered and reduced for TR45 inserts with ∅ 3 mm (0.12 in)
ceramic terminal block, for example 6c Straight for TR45 inserts with ∅ 6 mm (0.24 in)
3 Various terminal heads E Neck tube
4 Protection armature L Immersion length
5 Various hygienic process connections, detailed IL TR45 Insertion length = E + L + 10 mm (0.4 in)
information see chapter ’process connection’
The RTD assemblies Omnigrad M TR44 and TR45 are built up for hygienic processes and the main
requirements regarding "Cleaning-in-process" (CIP) and "Sterilization-in-process" (SIP). The architecture is
according to 3-A® standard. The hygienic process connections are easy to clean and thus they are complient
with EHEDG. The thermometers can be installed in the process (pipe or tank) using a hygienic process
connection. The most common process connections are available.
• Omnigrad M TR44 RTD assemblies consist of a terminal head and a protection armature with integrated
insert. With a diameter of 6 mm (0.24 in) resp. 8 mm (0.31 in) reduced to 5.3 mm (0.21 in) at the tip, it is
possible to realize best thermal response times. Insert and neck tube are welded together. The hygienic
process connection is also fixed connected to the neck tube.
• The Omnigrad M TR45 RTD assemblies are constructed in three modules: terminal head, protection
armature and a replaceable insert. The protection armature consists of a neck tube, process connection
welded between neck tube and integrated thermowell.
Performance characteristics
Operating conditions Ambient temperature
Without mounted head transmitter Depends on the terminal head used and the cable gland or fieldbus connec-
tor, see 'Terminal heads' section, → ä 9
With mounted head transmitter and display -20 to 70 °C (-4 to 158 °F)
Endress+Hauser 3
TR44, TR45
a0008065-en
a0008967
4 Endress+Hauser
TR44, TR45
a0008965-en
! Note!
For measurement errors in °F, calculate using equations above in °C, then multiply the outcome by 1.8.
Response time Tests of the sensor assemblies without transmitter in water at 0.4 m/s (1.3 ft/s), according to IEC 60751;
10 K temperature step change; For immersion length L > 45 mm (1.77 in):
Outer diameter Response time Reduced tip ∅ 5.3 mm (0.2 in) Straight tip ∅ 6 mm (0.24 in)
Endress+Hauser 5
TR44, TR45
Self heating RTD elements are passive resistances that are measured using an external current. This measurement current
causes a self heating in the RTD element itself which in turn creates an additional measurement error. In
addition to the measurement current the size of the measurement error is also affected by the temperature
conductivity and flow velocity of the process. This self heating error is negligible when an Endress+Hauser
iTEMP® temperature transmitter (very small measurement current) is connected.
Calibration specifications Endress+Hauser provides comparison temperature calibration from -50 to +400 °C (-58 to 752 °F) based on
the International Temperature Scale (ITS90). Calibrations are traceable to national and international standards.
The calibration report is referenced to the serial number of the thermometer.
TR44 (the complete thermometer is calibrated) Minimum standard immersion length L in mm (inch)
TR45 (only the measurement instert is calibra-
ted)
1) Can be used to a limited extent up to 800 °C (1472 °F) for low compressive loads and in non-corrosive media. Please contact your Endress+Hauser sales team
for further information.
Transmitter specifications
Measurement accuracy 0.2 °C (0.36 °F), optional 0.2 °C (0.36 °F) or 0.08% 0.1 °C (0.18 °F)
0.1 °C (0.18 °F) or 0.08%
6 Endress+Hauser
TR44, TR45
System components
Family of temperature Thermometers fitted with iTEMP® transmitters are an installation ready complete solution to improve
transmitters temperature measurement by increasing accuracy and reliability, when compared to direct wired sensors, as
well as reducing both wiring and maintenance costs.
R09-TMT182ZZ-06-06-xx-en-001
Endress+Hauser 7
TR44, TR45
Pluggable display TID10 as option • Displays the actual measured value and the measurement point identification
• Displays fault events in inverse color with channel ident and diagnostics code
• DIP-switches on the rear for hardware set-up, e. g. PROFIBUS® PA bus
address
! Note!
Display is only available with suitable terminal head with display window, e.g.
TA30
a0009955
8 Endress+Hauser
TR44, TR45
Terminal heads All terminal heads have internal geometry according to DIN 43729, form B and thermometer connection
M24x1.5.
All dimensions in mm (inch). All cable gland dimensions in the graphics are based on SKINTOP ST M20x1.5
TA20A Specification
a0008650
TA30A Specification
• Cable entry incl. glands: ½" NPT and M20x1.5, only thread: G ½",
15.5 (0.6)
a0009821
Endress+Hauser 9
TR44, TR45
TA30D Specification
a0009822
TA20B Specification
a0008663
TA21E Specification
a0008669
10 Endress+Hauser
TR44, TR45
TA20J Specification
a0008866
TA20R Specification
a0008667
Cable gland ½" NPT, M20x1.5 (non Ex) -40 to +100 °C (-40 to +212 °F)
Cable gland M20x1.5 (for dust ignition-proof area) -20 to +95 °C (-4 to +203 °F)
Fieldbus connector (M12x1 PA, 7/8" FF) -40 to +105 °C (-40 to +221 °F)
Endress+Hauser 11
TR44, TR45
a0008961
Tip shape
TR44 TR45
S R R S T
Ø9x1 Ø9x1 Ø9x1
Ø6 (0.35) Ø8 (0.31) (0.35) (0.35) (0.35)
(0.8)
20
~3.5
20 (0.8)
20 (0.8)
(0.14)
3 (0.12)
3 (0.12)
1 (0.94)
40 (1.6)
(0.12)
3.2 3.2
3
(0.13) (0.13)
12 Endress+Hauser
TR44, TR45
Process connection All dimensions are in mm. Surface finishing Ra ≤ 0.8 μm, ≤ 0.4 μm or ≤ 0.4 μm electropolished.
28 - -
- - 36
32 36 50 10 32 - 35 - 40 CE CE
34 - -
A - - 42
40 42 56 38 - 41 - CF CF
L
40 - -
- - 54
50 54 68 11 50 - 53 - 25 CG CG
D
d
52 - -
d
(**) All dimensions are in mm (***)
DN D D PN max
A B C d TR 44- TR 45-
Inches normal light (bar)
35 -
1” 30 44 22,9 CD CD
- 25,4
2 41 -
1 ¼” 36 50 10 29,3 40 CE CE
1 - 31,8
48 -
R0.4 R0.4 1 ½” 42 56 35,1 CF CF
- 38,1
a0009561 61 -
2” 54 68 11 47,8 25 CG CG
1 Centering ring - 50,8
! Note!
Only allowed with self centering gasket
B
(*) (****)
DN D D PN max
B C d TR 44- TR 45-
DIN 11864-1 Normal strong (bar)
- 30
25 42,9 9 26 CH CH
C
29 -
40
- 42
40 54,9 10 38 CJ CJ
41 -
50 66,9 11 50 53 - 25 - -
L
(**) (****)
DN PN max
D
d
B C d D TR44- TR45-
ISO BS (bar)
d 25 21,8 25,0
42,9 9 CH CH
a0009562
25,4 22,2 25,4 40
38 54,9 10 34,8 38,0 CJ CJ
(***) (****)
DN PN max
B C d D TR44- TR45-
DIN EN ISO (bar)
26,9 42,9 9 23,7 26,9 CH CH
40
42,4 54,9 10 38,4 42,4 CJ CJ
(*) Pipes according to DIN 11850.
(**) Pipes according to ISO 2037 and BS 4825 Part 1.
(***) Pipes according to DIN EN ISO 1127.
(****) With a suitable gasket, up to 140°C.
Endress+Hauser 13
TR44, TR45
Type B (DN10/DN15)
(*)
DN metric d D V PN (bar) TR44- TR45- Type
10 10 14
31 FC FC B
15 16 20
25 26 30 50 25 FB FB F
40 38 42
50 50 54
65 66 70
68 16 FA FA N
L
80 81 85
100 100 104
D 10
d
125 125 129
V
(**)
DN ISO d D V PN (bar) TR44- TR45- Type
25 29,7 33,7
32 38,4 42,4
68 25 FA FA N
40 44,3 48,3
50 56,3 60,3
a0009563
(***)
Type F (DN25, 1")
DN inches d D V PN (bar) TR44- TR45- Type
Type N (DN32...125, 1¼"...6") 1” 22,2 25,4 50 FB FB F
1 ½” 34,9 38,1 25
2” 47,6 50,8
2 ½” 60,3 63,5 68 FA FA N
16
3” 73,0 76,1
4” 97,6 101,6 10
(****)
DN IPS d D V PN (bar) TR44- TR45- Type
L
2” 57,1 60,3 25
D
d
3” 84,7 88,9 16
68 FA FA N
4” 110,1 114,4
10
6” 162,3 168,3
V
(*) Pipes according to DIN 11850.
a0009564 (**) Pipes according to DIN EN ISO 1127.
(***) Pipes according to ISO 2037 and BS 4825 Part 1.
(****) Pipes according to IPS Sch. 5.
(*) (****)
D D
DN PN max
A B C d Expanded Welded TR44- TR45-
ISO 2852 (bar)
type type
8÷18(**) 20,0 25,0 3,6 (**) (**) (**) BM -
12(***) 12 16 -
12,7(***) 12,7 16,7 -
27,5 34,0 BA BA
17,2(***) 17,2 21,2 -
21,3(***) 21,3 25,3 -
25 29 -
25
22,6 - 25,6
33,7 38,1 - 16
33,7 43,5 50,5 2,85 BB BB
31,3 - 34,3
38 42,4 -
38
35,6 - 38,6
40 44,8 -
40
37,6 - 40,6
a0009565 56,5 64,0 BC BC
51 55,8 -
51
48,6 - 51,6
(*) Pipes according to ISO 2037 and BS 4825 Part1.
(**) MicroClamp (not included in std. ISO 2852); not standard pipes.
(***) MiniClamp.
(****) Depends on clamping ring type, at 121°C with suitable gasket.
14 Endress+Hauser
TR44, TR45
B (*) (**)
D D PNmax
DN A B C d TR44- TR45-
std. strong (bar)
C
- 55,7 -
2” 56,5 64,0 47,6 BH BH
50,8 - 9÷17,2
D
(**) Depends on clamping ring type, at 121°C with suitable gasket.
d
d (***) MicroClamp.
B
C
L
d
A
MicroClamp
a0009566
1 Counterpart connection
2 Gasket
3 Groove slip-on nut
! Note!
Counterpart must fix gasket in position.
a0009568
®
Weld-in cylindrical (30x40 mm, 3-A marked) Weld-in spherical (30x40 mm, 3-A® marked) Conical connection metal-to-metal G½"
(not 3-A® marked)
30 (1.18) 30 (1.18)
3 (0.12)
(0.55) (0.31)
8
40 (1.57)
40 (1.57)
37 (1.46)
20 (0.8) 14
G½”
3 (0.12)
(0 .15
)
R
.6
L
L
a0009569 a0009570 L
18
(0.71)
a0009571
" Caution!
Maximum process pressure P = 16 bar (232 psi)
Liquiphant M G1" (3-A® marked) Ingold (not 3-A® marked) Conical connection metal-to-metal M12x1.5 (not
3-A® marked)
(0.2)
2 (0.08)
5
21 (0.83)
(0.43)
11
M12x1.5
L
7.6 (0.3)
a0009572 a0009573
L
25x50 mm 7.5
(0.3)
25x30 mm 10 (0.4)
a0009574
Endress+Hauser 15
TR44, TR45
Standard connections are available in several sizes. Others (i.e. Neumo, APV) are available on request. The
process connection is continuously welded on the probe or on the well so as to obtain a minimum welding
radius of 3.2 mm (0.13 in) between the lower surface of the connection and the sensor stem (according to
EHEDG and 3-A® standards).
Please refer to chapter ’Accessories’ for information regarding availability of welding adaptors. The Varivent®
connections must be used with dedicated Tuchenhagen® in-line components or tank adaptors. For Varivent®
flanges with small nominal diameter, maximum immersion lengths for usual applications are listed in the
following table (also refer to chapter ’Installation conditions’).
! Note!
Care should be taken by the user in the execution of the welding on the process side (suitable weld material,
welding radius > 3.2 mm, absence of pits, folds, crevices, …).
Spare parts • A thermowell for TR45 is available as spare part TW45 (see Technical Information in chapter
’Documentation’).
• The RTD insert is available as spare part TPR100 (see Technical Information in chapter ’Documentation’).
In TR45, the measuring probe is constituted by a mineral insulated insert positioned inside the thermowell. For
its replacement, the insert length (IL) must be chosen depending on the immersion length (L). If spare parts are
required, refer to the following table:
16 Endress+Hauser
TR44, TR45
Wiring
Electrical connection cables must comply with 3-A® standard, must be smooth, corrosion resistant and
cleanable.
T09-TH1112xx-04-xx-XX-ae-000
a0008848-en
a0008591-en
Endress+Hauser 17
TR44, TR45
Installation conditions
Orientation No restrictions, but self draining. If applicable leak detection hole must be at the lowest point.
Installation instructions The immersion length of the thermometer influences the accuracy. If the immersion length is too small then
errors in the measurement are caused by heat conduction via the process connection and the container wall.
If installing into a pipe then the immersion length must be half of the pipe diameter, ideally.
• Installation possibilities: Pipes, tanks or other plant components
• Minimum immersion length = 80 to 100 mm (3.15 to 3.94 in)
The immersion length should correspond to at least 8 times of the thermowell diameter. Example:
Thermowell diameter 12 mm (0.47 in) x 8 = 96 mm (3.8 in). A standard immersion length of 120 mm (4.72
in) is recommended
• ATEX certification: Always take note of the installation regulations!
! Note!
When operating in small nominal bore pipes it must be guaranteed that the thermowell tip is extending far
enough into the process to reach out past the pipe center line (see Pos. A and B). A further solution could be
an angled (tilted) installation (see Pos. C and D). When determining the immersion length all thermometer
parameters and the process to be measured must be taken into account (e.g. flow velocity, process pressure).
a0008946
18 Endress+Hauser
TR44, TR45
A B C D
Vessel wall
Sensor with
Welding boss
milk pipe
connection Sensor with Gasket
Varivent connection (O-ring)
Groove
slip-on nut
Companion
connection
O-Ring Shaped
Companion gasket
connection
Companion
connection Leak detection hole
Sealing
Centering ring
R0.4 R0.4
a0011758-en
A Milk pipe connection as per DIN 11851 only in linkage C Clamp as per ISO 2852
EHEDG certified and self centering ring
B Varivent® - process connection D Liquiphant-M G1" process connection,
horizontal installation
a0008947
The matches for the process connections as well as the gaskets are not included in the scope of delivery of this
assembly. Welding adapter for Liquiphant M G1"- and Ingold process connections with associated o-ring sets
are available as accessories → ä 25.
Care should be taken by the user in the execution of the welding on the process side (suitable weld material,
welding radius > 3.2 mm, absence of pits, folds, crevices, …). As a general rule, the assemblies should be
installed in such a way that does not adversely affect their cleanability (3-A® requirements must be adhered
to). The required flush-mounting can be achieved by the connection Varivent®, Liquiphant type M G1" (+
weld-in adapter) and Ingold (+ weld-in adapter).
Neck tube length The neck tube is the part between the process connection and the housing. It is normally made of a tube with
dimensional and physical characteristics (diameter and material) which are the same of the tube in contact with
the medium. The connection situated in the upper part of the neck allows for orientation of the terminal head.
The heating of the terminal head consequent to the process temperature is negligibly small if the process
temperature does not exceed the measuring range of TR44 and TR45.
• Standard neck tube diameter: 15 mm (0.6 in)
• Standard neck tube length:
– TR44: 82 mm (3.23 in)
– TR45: 85 mm (3.45 in)
Endress+Hauser 19
TR44, TR45
Hazardous area approvals For further details on the available Ex versions (ATEX, CSA, FM, etc.), please contact your nearest
Endress+Hauser sales organization. All relevant data for hazardous areas can be found in separate Ex
documentation. If required, please request copies.
Sanitary compatibility • EHEDG Type EL certification (TNO report n. V3912). EHEDG accepted process connections are: Varivent®
• 3-A® Authorization no. 1144 for the declaration of compliance with standard 74-03
• 3-A® accept the process connections, marked in the product structure of TR44 (→ ä 21) and TR45
(→ ä 23)
PED approval The thermometer complies with paragraph 3.3 of the Pressure Equipment Directive (97/23/CE) and is not
marked separately.
Material certification The material certificate 3.1 (according to standard EN 10204) can be directly selected from the sales structure
of the product and refers to the parts of the sensor in contact with the process fluid. Other types of certificates
related to materials can be requested separately. The "short form" certificate includes a simplified declaration
with no enclosures of documents related to the materials used in the construction of the single sensor and
guarantees the traceability of the materials through the identification number of the thermometer. The data
related to the origin of the materials can subsequently be requested by the client if necessary.
Test on thermowells Thermowell pressure tests are carried out in accordance with the specifications in the DIN 43772 standard.
With regards to thermowells with tapered or reduced tips that do not comply with this standard these are tested
using the pressure of corresponding straight thermowells. Sensors certified for use in Ex Zones, are always
tested to pressures according to the same criteria. Tests according to other specifications can be carried out on
request. Dye penetration tests verify the absence of cracks on the thermowell welding.
Test report and calibration For the tests and calibration, the "Acceptance report" comprises a declaration of conformity with the primary
points as per IEC 60751.
The "Factory calibration" is carried out according to an internal procedure in a laboratory of Endress+Hauser
accredited by the European Accreditation Organization (EA) to ISO/IEC 17025. A calibration which is
performed according to EA guidelines (SIT or DKD calibration) may be requested separately. The calibration is
performed on the replaceable insert of the thermometer. In the case of thermometers without a replaceable
insert, the entire thermometer - from the process connection to the tip of the thermometer - is calibrated.
20 Endress+Hauser
TR44, TR45
Ordering information
Product structure TR44 This information provides an overview of the order options available. The information is not exhaustive,
however, and may not be fully up to date. More detailed information is available from your local
Endress+Hauser representative.
RTD thermometer TR44 with sanitary process connection and neck. Designed for use in food and pharma industry. No replaceable insert,
in direct contact with process medium: fast response time. Wetted part built from same material.
Process connection:
BA DN12/21.3 minclamp ISO2852, 3A
BB DN25/38 ISO2852, clamp, 3A
BC DN40/51 ISO2852, clamp, 3A
BF 1+1½", ISO2852, clamp, 3A
BH 2", ISO2852, clamp, 3A
BM DN8/18 microclamp, 3A
CD DN25 DIN11851, 3A
CE DN32 DIN11851, 3A
CF DN40 DIN11851, 3A
CG DN50 DIN11851, 3A
CH DN25 Aseptic DIN11864-1-A, 3A
CJ DN40 Aseptic DIN11864-1-A, 3A
DA Cylindrical 30x40 mm, 3A
DB Spherical 30x40 mm, 3A
EA Liquiphant-M G1", 3A
FA DN32/125 Varivent D=68 mm, 3A
FB DN25 Varivent D=50 mm, 3A
FC DN10/15 Varivent D=31 mm, 3A
JD DN25 SMS, 3A
NB Ingold 25x50 (not 3A marked)
NC Ingold 25x30 (not 3A marked)
ND G½" metal-to-metal (not 3A marked)
NE M12x1.5 metal-to-metal (not 3A marked)
Immersion Length L:
A 50 mm
B 90 mm
D 160 mm
E 220 mm
F 120 mm
G 30 mm
X ..... mm
Y ..... mm, as specified
Tip Shape:
R Reduced, D=8 mm
S Straight
Terminal type:
2 Flying leads
3 Terminal block
Endress+Hauser 21
TR44, TR45
Material Certificate:
0 Not needed
C EN10204-3.1 Material, shortform
E EN10204-3.1 Material + roughness, shortform
G EN10204-3.1 Material
H EN10204-3.1 Material + roughness
J EN10204-3.1 Material + roughness + ferrit content ≤ 3 %
L EN10204-3.1 Material + + ferrit content ≤ 3 %
Test/Calibration:
A 0, 100 °C, RTD-Signal
B 0, 100 °C, RTD-Signal, 4-20 mA/loop
C 0, 100 °C, RTD-Signal, 2 Sensors
E 0, 100 °C, 150 °C, RTD-Signal
F 0, 100 °C, 150 °C, RTD-Signal, 4-20 mA/loop
G 0, 100 °C, 150 °C, RTD-Signal, 2 Sensors
0 Not needed
TR44- ← Order code (complete)
! Note!
For the option 'connection type: 2 → free wire’, in conjunction with the TA30D terminal head the transmitter
is mounted directly without an additional terminal block.
22 Endress+Hauser
TR44, TR45
Product structure TR45 This information provides an overview of the order options available. The information is not exhaustive,
however, and may not be fully up to date. More detailed information is available from your local
Endress+Hauser representative.
RTD thermometer TR45 with sanitary process connection, neck and thermowell. Designed for use in food and pharma industry. Replaceable
mineral insulated insert with Pt100.
Process connection:
BA DN12/21.3 minclamp ISO2852, 3A
BB DN25/38 ISO2852, clamp, 3A
BC DN40/51 ISO2852, clamp, 3A
BF 1+1½", ISO2852, clamp, 3A
BH 2", ISO2852, clamp, 3A
BM DN8/18 microclamp, 3A
CD DN25 DIN11851, 3A
CE DN32 DIN11851, 3A
CF DN40 DIN11851, 3A
CG DN50 DIN11851, 3A
CH DN25 Aseptic DIN11864-1-A, 3A
CJ DN40 Aseptic DIN11864-1-A, 3A
DA Cylindrical 30x40 mm, 3A
DB Spherical 30x40 mm, 3A
EA Liquiphant-M G1", 3A
FA DN32/125 Varivent D=68 mm, 3A
FB DN25 Varivent D=50 mm, 3A
FC DN10/15 Varivent D=31 mm, 3A
JD DN25 SMS, 3A
NB Ingold 25x50 (not 3A marked)
NC Ingold 25x30 (not 3A marked)
ND G1/2" metal-to-metal (not 3A marked)
Immersion Length L:
A 50 mm
B 90 mm
D 160 mm
E 220 mm
F 120 mm
G 30 mm
X ..... mm
Y ..... mm, as specified
Tip Shape:
P Straight + thermally conductive paste
Q Reduced L ≥ 30 mm + thermally conductive paste
R Reduced, L ≥ 30 mm
S Straight
T Tapered, L ≥ 65 mm
U Tapered, L ≥ 65 mm + thermally conductive paste
Terminal type:
2 Flying leads
3 Terminal block
4 HR fiber terminal block
Endress+Hauser 23
TR44, TR45
Material Certificate:
0 Not needed
C EN10204-3.1 Material, shortform
E EN10204-3.1 Material + roughness, shortform
G EN10204-3.1 Material
H EN10204-3.1 Material + roughness
J EN10204-3.1 Material + roughness + ferrit content ≤ 3 %
L EN10204-3.1 Material + + ferrit content ≤ 3 %
Test/Calibration:
A 0, 100 °C, RTD-Signal
B 0, 100 °C, RTD-Signal, 4-20 mA/loop
C 0, 100 °C, RTD-Signal, 2 Sensors
E 0, 100 °C, 150 °C, RTD-Signal
F 0, 100 °C, 150 °C, RTD-Signal, 4-20 mA/loop
G 0, 100 °C, 150 °C, RTD-Signal, 2 Sensors
0 Not needed
Additional option:
A ATEX II 1 GD EEx ia IIC
E ATEX II 1/2 GD EEx ia IIC
G ATEX II 1 G EEx ia IIC
H ATEX II 3 GD EEx nA II
K TIIS Ex ia IIC T4
L TIIS Ex ia IIC T6
0 Not needed
TR45- ← Order code (complete)
! Note!
For the option 'connection type: 2 → free wire’, in conjunction with the TA30D terminal head the transmitter
is mounted directly without an additional terminal block.
24 Endress+Hauser
TR44, TR45
Accessories
All dimensions in mm (inches).
Adapter for Liquiphant Welding boss G1", d=60 with flange for flush-mounted installation with sealing surface.
process connection
Dimensions Version Order number
a0006621
Endress+Hauser 25
TR44, TR45
a0009213-en
Documentation
Technical Information:
• RTD Insert for Temperature Sensor Omniset TPR100 (TI268T/02/en)
• Thermowell for temperature sensors omnigrad M TW 45 (TI252t/02/en)
• Temperature head transmitter iTEMP® PCP TMT181 (TI070r/09/en)
• Temperature head transmitter iTEMP® Pt TMT180 (TI088r/09/en)
• Temperature head transmitter iTEMP® HART® TMT182 (TI078r/09/en)
• Temperature head transmitter iTEMP® TMT84 PA (TI138r/09/en)
• Temperature head transmitter iTEMP® TMT85 FF (TI134r/09/en)
26 Endress+Hauser
TR44, TR45
Endress+Hauser 27
TR44, TR45
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
TI244T/02/en/07.09
71073141