ICPMS-2030: Pre-Installation Requirements
ICPMS-2030: Pre-Installation Requirements
ICPMS-2030: Pre-Installation Requirements
ICPMS-2030
(ICPMS-2030 P/N S211-92000-58)
Pre-Installation Requirements
CONTENTS
1 Installation ....................................................................................................................... 2
3 Ground ............................................................................................................................. 3
4 Table................................................................................................................................. 3
11 Dust .................................................................................................................................. 8
12 Vibration........................................................................................................................... 8
FIGURE- 4 ARGON GAS PLUMBING (EXAMPLE OF GAS CYLINDER LOCATED OUTDOORS) .................... 13
1
ZESD-4029A
1 Installation
1.1 Temperature and Humidity of Installation Site
The installation site should be air conditioned and meet the following conditions.
A. Set the room temperature between 18 C and 28 C. Keep room temperature
variations within 2 C an hour.
B. Position instruments where they are not exposed to drafts or air flow from the
air conditioning system.
C. Position instruments where they are not exposed to direct sunlight.
D. Keep humidity between 20 % and 70 % throughout the year.
Note: The ICPMS-2030 generates about 2900 kcal/h of heat when in the 1.2 kW high
frequency output mode.
Approximately 600 kcal/h from the plasma stand into the exhaust duct
Approximately 700 kcal/h into the waste tap water
(If an optional cooling water circulator is used instead of tap water, then
approximately 1600 kcal/h of heat is released from the cooling water circulator.)
Approximately 1000 kcal/h is released from the vacuum pump.
Approximately 200 kcal/h is released from the back of the instrument.
2
ZESD-4029A
2 Power Switch
2.1 Main Spectrometer Unit
Provide a 6 kVA single phase 200, 220, 230 or 240 volt supply (50 or 60 Hz) to
near the back panel of the spectrometer.
Maximum allowable voltage fluctuation is 10 %. A 6 kVA capacity voltage
stabilizer with output voltage precision within 5 % is required for power supplies
that vary by more than 10 %. For more details, contact your Shimadzu
representative.
3 Ground
Provide an independent ground with a resistance of 30 ohms or less, but if
possible, provide an independent ground with a resistance of 10 ohms or less.
Measure the resistance value using a direct-reading ground resistance meter,
Kohlrausch bridge, or other appropriate means.
This spectrometer uses large amounts of power to generate high frequency
waves. Therefore, it requires an independent ground with as little ground
resistance as possible. If the distance from the instrument to ground is too far, it
will increase the chance of generating noise. Therefore, keep the ground wire
length as short as possible.
4 Table
Provide a table that is more than strong enough to support the main ICPMS-2030,
which weighs 140 kg. The exterior dimensions are shown in Figure- 1.
3
ZESD-4029A
6 Argon Gas and Associated Plumbing
Provide an argon gas supply with a minimum 99.95 % purity.
450 10 kPa of pressure is required at the instrument inlet port.
4
ZESD-4029A
7 Helium Gas and Associated Plumbing
Provide helium gas with a minimum 99.999 % purity.
150 20 kPa of pressure is required at the instrument inlet port.
5
ZESD-4029A
8 Oxygen Argon Mix Gas and Associated Plumbing
The oxygen argon mix gas ratio is 70 % argon and 30 % oxygen.
450±10 kPa of pressure is required at the instrument inlet port.
8.2 Precautions for Plumbing the Oxigen Argon Mix Argon Gas
A plumbing example is shown in Figure- 7.
Be sure to secure the argon gas cylinder to prevent it from tipping over.
6
ZESD-4029A
9 Local Ventilation Equipment
Ventilate the exhaust gases from the plasma stand to the outdoors.
Figure- 3 illustrates one example of ducting work.
A. Use oxidation resistant materials for the plasma stand ventilation system
(exhaust ducting, hood, fan, etc.) that are appropriate for acids from samples.
B. An exhaust duct (122 mm I.D.) with an exhaust capacity between 1.4 m 3/min
and 2.0 m 3/min is required for the plasma stand. Include a damper in the
plasma stand exhaust ventilation system.
If the ducting connection kit (P/N: S211-93832-41 duct adapter) recommended
by Shimadzu is used, provide flexible stainless steel ducting.
C. Use the exhaust ventilation made of heat-resistant material if it is directly linked
to the plasma stand exhaust ducting. Depending on measurement conditions,
the internal temperature can exceed 100 C.
10 Cooling Water
The ICPMS-2030 requires cooling water.
Provide the following options according to operating conditions.
Operating Conditions Required Options Specifications of Option, etc.
Use tap water For cooling water Tap Water Connection Kit (1) Provide hardware separately for
Water Temp: hoses with a round- (P/N S211-90558-41) connecting the 12 mm I.D. and
trip length of 10 m 18 mm O.D. Tetron braided hose
5 to 30 C
or less to the tap water faucet (such as a
Water Volume: coupler set).
Min. 1.5 L/min.
(2) With a pressure regulator and
Water Pressure: filter
150 to 300 kPa
If cooling water Tap Water Connection Kit (1) Provide hardware separately for
hose exceeds 10 m (P/N S211-90558-41) connecting the 12 mm I.D. and
in length, 18 mm O.D. Tetron braided hose
Tetron braided hoses
(P/N S018-31509) for to the tap water faucet (such as a
coupler set).
cooling water supply and
drain (2) With a pressure regulator and
filter
(3) Order cooling water supply and
drain hoses in total length units of
one meter.
When Using a If connecting the Cooling Water Supply Set (1) Provide a 200-230 V AC (50 or
Cooling Water ICPMS-2030 (P/N S211-92962-41) 60 Hz) 2 kVA power supply for
Circulator Connection Kit for the HRS018-A-20 chiller.
HRS018 (2) Make sure the length of cooling
(P/N S211-92884-41) water supply and drain hoses are
Check Valve each 10 m or shorter. 10 m long
(P/N S211-93808-41) cooling water supply and drain
hoses are included in the
HRS018 connection kit.
7
ZESD-4029A
11 Dust
The ICPMS-2030 uses high voltages and tiny electrical currents. Therefore, dust
can cause it to malfunction.
Implement dust-prevention measures in the doors and windows of the room where
the system is installed to prevent dust.
12 Vibration
Do not install the system where there is large amounts of vibration.
Place the liquid waste tank as near the plasma stand as possible.
Tubing (2 m) from the sample injection area to the liquid waste tank is included.
After operating the instrument, close the cap of the liquid waste tank or remove
the waste liquid promptly. If waste liquid is left for long time with the cap open, off-
gassing could cause corrosion in the surrounding areas.
Also provide a liquid waste tank if an optional autosampler is used. Up to
6 mL/min of sample solution is discharged from the autosampler AS-10, in case of
ASX-520/260, 23 mL/min, when it is in operation.
8
ZESD-4029A
14 Using the High Frequency Equipment
Observe applicable regulations for the country where it is used. The 27 MHz
magnetic field leakage at 1 meter from the side of the instrument is 1 V/m or less.
9
ZESD-4029A
15 Room Lighting and Lighting Fixtures
This system is operated via a (computer) video display terminal (VDT). The same
considerations are required with respect to lighting for the health of analytical
operators as are considered for general office equipment.
(1) Avoid large differences between light and dark areas inside rooms and
prevent glare.
(2) Adjust the vertical illuminance and horizontal illuminance levels on documents
and keyboards to appropriate levels.
Guidelines:
Vertical illuminance should be 500 lux or less
Horizontal illuminance should be between 300 and 700 lux
(3) Cover bright windows with blinds, curtains or other coverings, and adjust the
brightness as necessary.
(4) The operator's field of vision should be free from bright light fixtures, windows,
wall surfaces, or flashing lights and such lights should be kept from reflecting
on the display screen.
10
ZESD-4029A
At Least 500 mm
At Least 130 mm for Normal Operation At Least 230 mm for Normal Operation
At Least 600 mm for Maintenance At Least 600 mm for Maintenance
At Least 530 mm
11
ZESD-4029A
Damper
Stainless Hood
Must allow raising hood by at
least 50 mm during installation
or maintenance
Exhaust Capacity
Plasma Stand (Inside Exhaust Duct)
Exhaust Duct
12
ZESD-4029A
Wall
6 7
5
2 To ICPMS-2030
4 Install pressure
1
regulator hose if
tubing from gas
cylinder is long.
Wall
Vaporizer
Liquid Argon
Cylinder
(1) Pressure Regulator for Argon (argon supply pressure at instrument is 450 10 kPa
(4.5 0.1 kg/cm2))
(2) Main Valve (made of BS, BC or SUS)
(3) Pressure Gauge 1000 kPa Max. Pressure
(4) Stop Valve (made of same material as 2)
(5) Tubing Copper Tubing Cut 1 - 1/2 H or annealed. 12 mm O.D. 10 mm I.D.
(6) R1/4 Joint for 1/4-inch O.D. Plastic Tubing (Shimadzu P/N 035-65503)
(7) 5 m of 1/4-inch O.D. Polypropylene Tubing (Shimadzu P/N 016-43505)
Items (1) through (5) are not included with ICPMS-2030 and must be provided by the
customer.
13
ZESD-4029A
To ICPMS-2030
1/4-inch O.D.
Argon Gas Cylinder
5 m Polypropylene Tubing
Shimadzu P/N 016-43505
14
ZESD-4029A
To ICPMS-2030
3 mm O.D.
Helium Gas Cylinder
All indicated items are not included with ICPMS-2030 and must be
provided by the customer.
Above regulator has left handed screw. Confirm the gas cylinder’s
screw before order above regulator.
15
ZESD-4029A
To ICPMS-2030
1/4-inch O.D.
5 m Polypropylene Tubing
Oxigen Argon Mix
Gas Cylinder
All indicated items are not included with ICPMS-2030 and the
organic solvent system,and must be provided by the customer.
16