GCU 100 Operators Manual 4189340800 UK - 2013.07.01
GCU 100 Operators Manual 4189340800 UK - 2013.07.01
GCU 100 Operators Manual 4189340800 UK - 2013.07.01
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com Document no.: 4189340800A
14 9614 · Fax: +45 9614 9615 · info@deif.com · www.deif.com SW version:
GCU 100 Operators manual 4189340800
UK
1. General information
1.1. Warnings, legal information and safety..................................................................................................3
1.1.1. Warnings and notes ......................................................................................................................3
1.1.2. Legal information and disclaimer ..................................................................................................3
1.1.3. Safety issues ................................................................................................................................3
1.1.4. Electrostatic discharge awareness ...............................................................................................3
1.1.5. Factory settings ............................................................................................................................3
1.2. About the operator's manual..................................................................................................................4
1.2.1. General purpose ...........................................................................................................................4
1.2.2. Intended users ..............................................................................................................................4
1.2.3. Contents and overall structure ......................................................................................................4
4. Standard text
4.1. Status line text......................................................................................................................................11
4.1.1. Status texts .................................................................................................................................11
4.1.2. Information text ...........................................................................................................................12
5. Running modes
5.1. Running mode overview.......................................................................................................................13
1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
The general purpose of this document is to give the operator important information to be used in the daily
operation of the unit.
Please make sure to read this document before starting to work with the Multi-line 2 unit and
the generator set to be controlled. Failure to do this could result in human injury or damage to
the equipment.
1 2 3 4 5
15 14 13 12 11 10 9 8
Note that push-button 10/11 and 12/13 are not present on GCU 111 and 10/11 not on GCU 112.
1 2 3
10 9 8 7 6 5 4
2: LED steady light indicates that all alarms are acknowledged, but some are still present.
LED flashing indicates that unacknowledged alarms are present.
Note that LED 6/7/8 is not present on version GCU 111, and 6/7 is not present on version GCU
112.
Log menu:
This menu contains event, alarm and battery logs.
Alarm list:
This list shows active acknowledged and unacknowledged alarms. It is also in this list that alarms
Service menu:
This menu contains input-, output-, M-Logic status and data about the unit.
DG Running
G U-L1L2 400 V
G U-L2L3 400 V
G U-L3L1 400 V
Running hours
DG Running
G U-L1N 230 V
G U-L2N 230 V
G U-L3N 230 V
Running hours
DG Running
G U-L1L2
Use arrows to toggle betweeen
G U-L2L3
menus
G U-L3L1
Running hours
1000 -P> 1
Set point: -5.0%
Timer: 0.5 sec Use the arrows to change the
setpoint
Output A: Not used
Output B: Not used
View examples
Alarm acknowledge
Parameter settings
All alarm explanations are found in the parameter list. The channel numbers are individual for
all alarms.
The available parameters depend on the GCU variant. Some parameters can only be changed
using the PC utility software (USW). The parameter list will automatically be abandoned, if no
button is pressed during a 30 sec. period.
4. Standard text
4.1 Status line text
4.1.1 Status texts
The following table explains the different status messages in the display. Status messages are automatically
displayed during and under operation without any interaction of the operator.
Condition Comment
BB VOLTAGE DETECTED Breaker cannot close due to BB V detected
BLACKOUT No voltage detected on BB
BLACKOUT IN ###S Timer for blackout detection
BB OK IN ###S Timer for voltage on BB ok
COOLING DOWN Cooling-down period is activated
DG RUNNING DG running feedback detected
ENGINE STOPPING Engine is stopping
EXT STOP TIMER Trailing timer for external equipment
FULL TEST Test mode is activated
GB TRIP EXTERNALLY Some external equipment has stripped the breaker
GENSET STOPPING Generator stopping
IDLE RUN The timer in the "Idle run" function is active
SHUTDOWN OVERRIDE The configurable input is active
SIMPLE TEST Test mode is activated
START PREPARE The start prepare relay is activated
START RELAY OFF The start relay is deactivated during the start
START RELAY ON The start relay is activated
TB TRIP EXTERNALLY Some external equipment has tripped the breaker
VOLT/FREQ OK IN ###S The voltage and frequency on the genset is OK
Condition Comment
ALREADY RUNNING DG is already running
GB IS CLOSED GB is already closed
GB IS OPENED GB is already open
GB ON BLOCKED Generator running, GB open and an active "Trip GB" alarm
NOT IN LOCAL Manual/local mode not selected
NOT IN REMOTE Auto/remote mode not selected
NOT RUNNING Generator not running
TB IS CLOSED TB already closed
TB IS OPEN TB already open
5. Running modes
5.1 Running mode overview
The unit has three different running modes. The different running modes are selected by use of push-buttons,
digital inputs on the display or the PC utility software. For detailed information, please see the designer's ref-
erence handbook.
Auto/Remote
In auto mode, the unit will operate automatically, and the operator cannot initiate any sequences manually.
Manual/Local
Manual means that the unit will not initiate any sequences automatically, as is the case with the auto mode. It
will only initiate sequences, if external signals are given.
Test
The test sequence will start when the test mode is selected.
If reading of the alarms is not desired, use the ESC push-button to exit the alarm list.
If you decide to enter the alarm list later, press the HORN push-button for 2 seconds to jump directly to the
alarm list reading.
The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active (i.e.
the alarm condition is still present). Once an alarm is acknowledged and the condition has disappeared, the
alarm will no longer be displayed in the alarm list.
This means that if there are no alarms, the alarm list will be empty.
This display example below indicates an unacknowledged alarm. The display can show only one alarm at a
time. Therefore, all other alarms are hidden.
Alarm list:
BB U> 1
Ch 1270 UNACK
1/1 alarm(s)
To see the other alarms, use the and push-buttons to scroll in the display.
1. Event log
2. Alarm log
3. Battery test log
The log list contains up to 50 events, the alarm list contains up to 30 historical alarms, and the battery test list
contains up to 52 historical battery tests.
An event is e.g. closing of breaker and starting of engine. An alarm is e.g. overcurrent or high cooling water
temperature. A battery test is e.g. test OK or test failed.
2. Select the list which is needed with the and arrows and choose with the push-button.