Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Ecosine Max, 480 VAC 60 HZ Full Performance Passive Harmonic Filters

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

DATASHEET Ecosine max (5% THDi) FN 3482

Ecosine max, 480 VAC 60 Hz Full Performance Passive Harmonic Filters

Demonstrate best cost-performance ratio Approvals & Compliances


Achieve 5% THDi for diode rectifier without
DC-link choke and thyristor rectifier
Best-in-class partial load performance
Most compact open panel design for cabinet
integration
Reliable and robust
Plug and play, ready to use Features and benefits
Schaffner ecosine harmonic filters represent an
economical solution to the challenge of load-applied
harmonics mitigation in three-phase power systems.
With a plug-and-play approach and more compact
dimensions than comparable products, they can be
quickly installed and easily commissioned. They
increase the reliability and service life of electric
installations, help utilize electric sytem capacity
better, and are the key to meet Power Quality
standards such as IEEE 519. Ecosine filters reshape
Technical specifications your distorted current back to the desired sinusoidal
waveform. Schaffner ecosine filters can be applied to
Nominal operating voltage 3 x 440 VAC to 480 VAC ±10% virtually any kind of power electronics with front-end
60 Hz ±1 Hz
six-pulse rectifiers, 3-phase diode or thyristor bridges,
Operating frequency
where harmonic current distortion needs to be
Nominal motor drive input power rating 350 to 600 HP
reduced to defined limits.
Total harmonic current distortion THDi* <5% @ rated power for drives without Ldc
~3.5% @ rated power for drives equipped with 4% Ldc
Efficiency >99% for rated voltage and power Typical applications
Overload capability 1.6x rated current for 1 minute, once per hour
Equipment with front-end six-pulse rectifier
SCCR** 100 kA (UL approved)
Motor drives
High potential test voltage P -> E 2520 VAC (1s)
OV III (IEC 60664-1)
Factory automation equipment
Overvoltage category
Earthing System TN, TT, IT Water/wastewater treatment facilities
Protection category IP 00 Fan and pump applications
Cooling External cooling*** HVAC installations
Ambient temperature range –25°C to +40°C fully operational Mission-critical processes
+40°C to +70°C derated operation****
–25°C to +85°C transport and storage
DC fast chargers

Design corresponding to Filter: UL 61800-5-1, EN 61800-5-1


Chokes: EN 60076-6 Typical electrical schematic
Flammability corresponding to UL 94 V-0
MTBF @ 40°C/480 V (Mil-HB-217F) >200,000 hours
*****System requirements: THDv <2%, line voltage unbalance <1%
*****Note: performance specifications in this brochure refer to six-pulse diode rectifiers.
*****SCR rectifier front-ends will produce different results, dependent upon the firing angle of the thyristors.
*****External UL-rated fuses required. Please consult the user manual.
*****Please check the inlet air flow required for cooling table further in this document and the user manual.
*****Iderated = Inominal*√((Tmax-Tamb)/(Tmax-Tnominal)) = Inom*√((70°C-Tamb)/30°C)
2 Ecosine passive Schaffner Group Datasheets 04 Jan 2021

Filter selection table with circuit breaker module

Rated load power @ Motor drive input Rated filter input Typical losses Circuit breaker Frame
Filter 480 V/60 Hz current* current @ 40°C rated current Weight Terminal size
[kW] [HP] [Arms] [Arms] [W] [A] [kg] [lbs]
FN 3482-350-99-E0XXSXX 260 350 472 327 2832 200 245 540 Busbar S10
FN 3482-400-99-E0XXSXX 300 400 537 375 3200 200 270 595 Busbar S10
FN 3482-450-99-E0XXSXX 335 450 595 420 3451 250 295 650 Busbar S10
FN 3482-500-99-E0XXSXX 370 500 656 469 3404 250 320 705 Busbar S12
FN 3482-600-99-E0XXSXX 450 600 773 563 4173 300 385 849 Busbar L10

* Motor drive input current without harmonic filter.

Filter selection table with trap disconnect jumper

Rated load power@ 480 V/ Motor drive input Rated filter input Typical power losses @ Frame
Filter 60 Hz current* current 40°C Weight Terminal size
[kW] [HP] [Arms] [Arms] [W] [kg] [lbs]
FN 3482-350-99-E0XXJXX 260 350 472 327 2832 245 540 Busbar S10
FN 3482-400-99-E0XXJXX 300 400 537 375 3200 270 595 Busbar S10
FN 3482-450-99-E0XXJXX 335 450 595 420 3451 295 650 Busbar S10
FN 3482-500-99-E0XXJXX 370 500 656 467 3404 320 705 Busbar S12
FN 3482-600-99-E0XXJXX 450 600 773 563 4173 385 849 Busbar L10

* Motor drive input current without harmonic filter.

Earth terminals

Earth (PE) Screw thread Screw torque value


[Nm] [lbs.in]
S08-L12 M12 20-25 177-221

Frame size designation


3 Ecosine passive Schaffner Group Datasheets 04 Jan 2021

Product selector

Filter configurations

E0XXSXX E0XXJXX
- For rectifiers without DC-link - For rectifiers without DC-link
choke choke

- Filters contain trap disconnect - Filters contain trap disconnect


switch jumper
4 Ecosine passive Schaffner Group Datasheets 04 Jan 2021

Mechanical data of IP 00 enclosure

Dimensions in mm

Recommended
cabinet size
Frame size* W D H R S1 S2 S3 T LINE LOAD WxDxH
S08 max. 650 max. 505 1120 380 330 230 490 13.5 255 ± 10 470 ± 30 800x600x2000
S10 890 max. 505 1120 370 514 n/a 280 13.5 255 ± 10 240 ± 30 1000x600x2000
S12 1060 max. 505 1120 370 684 n/a 280 13.5 255 ± 10 230 ± 10 1200x600x2000
L08 max. 680 557 1320 458 320 225 485 13.5 290 ± 10 540 ± 30 800x600x2000
L10 890 max. 557 1320 455 504 n/a 285 13.5 290 ± 10 230 ± 10 1000x600x2000
L12 1060 max. 557 1320 455 674 n/a 285 13.5 290 ± 10 220 ± 10 1200x600x2000

* General tolerance: ISO 2768-v

Dimensions in inches

Recommended
cabinet size
Frame size* W D H R S1 S2 S3 T LINE LOAD WxDxH
S08 max. 25.6 max. 19.88 44.09 14.96 12.99 9.06 19.29 0.53 10.04 ± 0.039 18.5 ± 1.18 31.5x23.6x78.7
S10 35.04 max. 19.88 44.09 14.57 20.24 n/a 11.02 0.53 10.04 ± 0.039 9.45 ± 1.18 39.4x23.6x78.7
S12 41.73 max. 19.88 44.09 14.57 26.93 n/a 11.02 0.53 10.04 ± 0.039 9.06 ± 0.39 47.2x23.6x78.7
L08 max. 26.8 21.93 51.97 18.03 12.60 8.86 19.09 0.53 11.42 ± 0.039 21.26 ± 1.18 31.5x23.6x78.7
L10 35.04 max. 21.93 51.97 17.91 19.84 n/a 11.22 0.53 11.42 ± 0.039 9.06 ± 0.39 39.4x23.6x78.7
L12 41.73 max. 21.93 51.97 17.91 26.54 n/a 11.22 0.53 11.42 ± 0.039 8.66 ± 0.39 47.2x23.6x78.8

* General tolerance: ISO 2768-v

Inlet air flow required for cooling

Frame size Min air volume*

[m3/h] CFM [ft3/min]


S08, L08 1069 629
S10, L10 1069 629
S12, L12 1069 629

* Complete cooling requirement, including air inlet placement, must be followed. Please consult the user
manual.
5 Ecosine passive Schaffner Group Datasheets 04 Jan 2021

Headquarters, global PQ sales


innovation and development

Switzerland Switzerland Singapore


Schaffner Group Schaffner Power Quality Switzerland Schaffner Power Quality APAC
Industrie Nord Nordstrasse 11e #05-09, Kg Ubi Ind. Estate
Nordstrasse 11e 4542 Luterbach Blk 3015A Ubi Road 1
4542 Luterbach T +41 32 681 66 80 408705 Singapore
T +41 32 681 66 26 pqsales@schaffner.com T +65 6460 4166
info@schaffner.com pqsales@schaffner.com
China
Schaffner Power Quality China
T20-3 C, No 565 Chuangye Road
Pudong district
201201 Shanghai
T 021-38139500-2412
pqsales@schaffner.com

www.schaffner.com

© 2021 Schaffner Group

The content of this document has been


carefully checked and understood. However,
neither Schaffner nor its subsidiaries assume
any liability whatsoever for any errors or
inaccuracies of this document and the
consequences thereof. Published
specifications are subject to change without
notice. Product suitability for any area of
application must ultimately be determined by
the customer. In all cases, products must
never be operated outside their published
specifications. Schaffner does not guarantee
the availability of all published products. This
disclaimer shall be governed by substantive
Swiss law and resulting disputes shall be
settled by the courts at the place of business
of Schaffner Holding AG. Latest publications
and a complete disclaimer can be
downloaded from the Schaffner website. All
trademarks recognized.

You might also like