Ecosine Max, 480 VAC 60 HZ Full Performance Passive Harmonic Filters
Ecosine Max, 480 VAC 60 HZ Full Performance Passive Harmonic Filters
Ecosine Max, 480 VAC 60 HZ Full Performance Passive Harmonic Filters
Rated load power @ Motor drive input Rated filter input Typical losses Circuit breaker Frame
Filter 480 V/60 Hz current* current @ 40°C rated current Weight Terminal size
[kW] [HP] [Arms] [Arms] [W] [A] [kg] [lbs]
FN 3482-350-99-E0XXSXX 260 350 472 327 2832 200 245 540 Busbar S10
FN 3482-400-99-E0XXSXX 300 400 537 375 3200 200 270 595 Busbar S10
FN 3482-450-99-E0XXSXX 335 450 595 420 3451 250 295 650 Busbar S10
FN 3482-500-99-E0XXSXX 370 500 656 469 3404 250 320 705 Busbar S12
FN 3482-600-99-E0XXSXX 450 600 773 563 4173 300 385 849 Busbar L10
Rated load power@ 480 V/ Motor drive input Rated filter input Typical power losses @ Frame
Filter 60 Hz current* current 40°C Weight Terminal size
[kW] [HP] [Arms] [Arms] [W] [kg] [lbs]
FN 3482-350-99-E0XXJXX 260 350 472 327 2832 245 540 Busbar S10
FN 3482-400-99-E0XXJXX 300 400 537 375 3200 270 595 Busbar S10
FN 3482-450-99-E0XXJXX 335 450 595 420 3451 295 650 Busbar S10
FN 3482-500-99-E0XXJXX 370 500 656 467 3404 320 705 Busbar S12
FN 3482-600-99-E0XXJXX 450 600 773 563 4173 385 849 Busbar L10
Earth terminals
Product selector
Filter configurations
E0XXSXX E0XXJXX
- For rectifiers without DC-link - For rectifiers without DC-link
choke choke
Dimensions in mm
Recommended
cabinet size
Frame size* W D H R S1 S2 S3 T LINE LOAD WxDxH
S08 max. 650 max. 505 1120 380 330 230 490 13.5 255 ± 10 470 ± 30 800x600x2000
S10 890 max. 505 1120 370 514 n/a 280 13.5 255 ± 10 240 ± 30 1000x600x2000
S12 1060 max. 505 1120 370 684 n/a 280 13.5 255 ± 10 230 ± 10 1200x600x2000
L08 max. 680 557 1320 458 320 225 485 13.5 290 ± 10 540 ± 30 800x600x2000
L10 890 max. 557 1320 455 504 n/a 285 13.5 290 ± 10 230 ± 10 1000x600x2000
L12 1060 max. 557 1320 455 674 n/a 285 13.5 290 ± 10 220 ± 10 1200x600x2000
Dimensions in inches
Recommended
cabinet size
Frame size* W D H R S1 S2 S3 T LINE LOAD WxDxH
S08 max. 25.6 max. 19.88 44.09 14.96 12.99 9.06 19.29 0.53 10.04 ± 0.039 18.5 ± 1.18 31.5x23.6x78.7
S10 35.04 max. 19.88 44.09 14.57 20.24 n/a 11.02 0.53 10.04 ± 0.039 9.45 ± 1.18 39.4x23.6x78.7
S12 41.73 max. 19.88 44.09 14.57 26.93 n/a 11.02 0.53 10.04 ± 0.039 9.06 ± 0.39 47.2x23.6x78.7
L08 max. 26.8 21.93 51.97 18.03 12.60 8.86 19.09 0.53 11.42 ± 0.039 21.26 ± 1.18 31.5x23.6x78.7
L10 35.04 max. 21.93 51.97 17.91 19.84 n/a 11.22 0.53 11.42 ± 0.039 9.06 ± 0.39 39.4x23.6x78.7
L12 41.73 max. 21.93 51.97 17.91 26.54 n/a 11.22 0.53 11.42 ± 0.039 8.66 ± 0.39 47.2x23.6x78.8
* Complete cooling requirement, including air inlet placement, must be followed. Please consult the user
manual.
5 Ecosine passive Schaffner Group Datasheets 04 Jan 2021
www.schaffner.com