Air System Sizing Summary For HVAC Multisplit
Air System Sizing Summary For HVAC Multisplit
Air System Sizing Summary For HVAC Multisplit
Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Room 1 1 5.0 Oct 0800 303 0.9 111.4 2.72
Room 2 1 5.3 Dec 0900 323 0.5 122.8 2.63
Room 3 1 7.0 Oct 1500 429 1.0 192.9 2.22
Living Room 1 23.2 Oct 1500 1410 2.8 558.2 2.53
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 104 CFM
TABLE 1.1.A. Component Loads For Space "Room 1" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 68.5 °F / 63.1 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 3933 - 46 ft² - -
Wall Transmission 148 ft² 125 - 148 ft² 541 -
Roof Transmission 111 ft² 76 - 111 ft² 58 -
Window Transmission 46 ft² -228 - 46 ft² 318 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 111 ft² 0 - 111 ft² 0 -
Partitions 194 ft² 63 - 194 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 33 W 114 - 0 0 -
Task Lighting 33 W 114 - 0 0 -
Electric Equipment 160 W 546 - 0 0 -
People 1 230 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4973 120 - 917 0
TABLE 1.1.B. Envelope Loads For Space "Room 1" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NE EXPOSURE
WALL 82 0.470 - -7 - 299
WINDOW 1 9 1.110 0.991 -54 288 76
SE EXPOSURE
WALL 66 0.470 - 132 - 242
WINDOW 1 38 0.823 0.607 -174 3645 242
H EXPOSURE
ROOF 111 0.066 - 76 - 58
TABLE 1.2.A. Component Loads For Space "Room 2" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 65.8 °F / 60.6 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 38 ft² 4058 - 38 ft² - -
Wall Transmission 48 ft² 110 - 48 ft² 176 -
Roof Transmission 123 ft² 85 - 123 ft² 63 -
Window Transmission 38 ft² -281 - 38 ft² 242 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 123 ft² 0 - 123 ft² 0 -
Partitions 206 ft² 51 - 206 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 37 W 126 - 0 0 -
Task Lighting 37 W 126 - 0 0 -
Electric Equipment 160 W 546 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5310 410 - 482 0
TABLE 1.2.B. Envelope Loads For Space "Room 2" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SE EXPOSURE
WALL 48 0.470 - 110 - 176
WINDOW 1 38 0.823 0.607 -281 4058 242
H EXPOSURE
ROOF 123 0.066 - 85 - 63
TABLE 1.3.A. Component Loads For Space "Room 3" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 35 ft² 3412 - 35 ft² - -
Wall Transmission 182 ft² 1030 - 182 ft² 667 -
Roof Transmission 193 ft² 512 - 193 ft² 100 -
Window Transmission 35 ft² 154 - 35 ft² 223 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 193 ft² 0 - 193 ft² 0 -
Partitions 248 ft² 128 - 248 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 58 W 197 - 0 0 -
Task Lighting 58 W 197 - 0 0 -
Electric Equipment 270 W 921 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7043 410 - 990 0
TABLE 1.3.B. Envelope Loads For Space "Room 3" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SW EXPOSURE
WALL 64 0.470 - 581 - 236
WINDOW 1 35 0.823 0.607 154 3412 223
NW EXPOSURE
WALL 118 0.470 - 450 - 430
H EXPOSURE
ROOF 193 0.066 - 512 - 100
TABLE 1.4.A.Component Loads For Space "Living Room" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 43 ft² 1895 - 43 ft² - -
Wall Transmission 227 ft² 1189 - 227 ft² 831 -
Roof Transmission 558 ft² 1481 - 558 ft² 289 -
Window Transmission 43 ft² 217 - 43 ft² 315 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 155 ft² 15134 - 155 ft² 1341 -
Floor Transmission 558 ft² 0 - 558 ft² 0 -
Partitions 425 ft² 218 - 425 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 167 W 571 - 0 0 -
Task Lighting 167 W 571 - 0 0 -
Electric Equipment 280 W 955 - 0 0 -
People 4 920 480 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 23152 480 - 2776 0
TABLE 1.4.B. Envelope Loads For Space "Living Room" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SW EXPOSURE
WALL 62 0.470 - 557 - 227
DOOR GLASS 155 1.110 0.991 924 14209 1341
NW EXPOSURE
WALL 165 0.470 - 632 - 605
WINDOW 1 19 1.093 0.881 114 733 166
WINDOW 2 23 0.823 0.607 103 1162 149
H EXPOSURE
ROOF 558 0.066 - 1481 - 289
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.966 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4244.1 BTU/(hr-CFM)
Site Altitude = 3064.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.966 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4244.1 BTU/(hr-CFM)
Site Altitude = 3064.0 ft
0.016
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )
0.016
0.012
0.010
0.008
1 25 3 4
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )