Air System Sizing Summary For HVAC Multisplit

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Air System Sizing Summary for HVAC Multisplit

Project Name: Proyecto Refri 12/06/2021


Prepared by: RST Ingenieria 12:07AM

Air System Information


Air System Name HVAC Multisplit Number of zones 1
Equipment Class SPLT AHU Floor Area 985.3 ft²
Air System Type SZCAV Location San Jose, Costa Rica

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 3.1 Tons Load occurs at Oct 1500
Total coil load 37.5 MBH OA DB / WB 83.6 / 67.7 °F
Sensible coil load 35.9 MBH Entering DB / WB 76.2 / 65.1 °F
Coil CFM at Oct 1500 2466 CFM Leaving DB / WB 61.1 / 60.1 °F
Max block CFM 2466 CFM Coil ADP 59.4 °F
Sum of peak zone CFM 2466 CFM Bypass Factor 0.100
Sensible heat ratio 0.958 Resulting RH 57 %
CFM/Ton 788.9 Design supply temp. 58.0 °F
ft²/Ton 315.3 Zone T-stat Check 1 of 1 OK
BTU/(hr·ft²) 38.1 Max zone temperature deviation 0.0 °F
Water flow @ 10.0 °F rise N/A

Central Heating Coil Sizing Data


Max coil load 5.9 MBH Load occurs at Des Htg
Coil CFM at Des Htg 2466 CFM BTU/(hr·ft²) 6.0
Max coil CFM 2466 CFM Ent. DB / Lvg DB 69.6 / 72.1 °F
Water flow @ 20.0 °F drop N/A

Supply Fan Sizing Data


Actual max CFM 2466 CFM Fan motor BHP 0.00 BHP
Standard CFM 2205 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 2.50 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 104 CFM CFM/person 11.57 CFM/person
CFM/ft² 0.11 CFM/ft²

Hourly Analysis Program 5.11 Page 1 of 13


Zone Sizing Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

Air System Information


Air System Name HVAC Multisplit Number of zones 1
Equipment Class SPLT AHU Floor Area 985.3 ft²
Air System Type SZCAV Location San Jose, Costa Rica

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 2466 2466 2.50 0.0 - 0.0 - 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 36.4 Oct 1500 5.2 985.3

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
Room 1 1 5.0 Oct 0800 303 0.9 111.4 2.72
Room 2 1 5.3 Dec 0900 323 0.5 122.8 2.63
Room 3 1 7.0 Oct 1500 429 1.0 192.9 2.22
Living Room 1 23.2 Oct 1500 1410 2.8 558.2 2.53

Hourly Analysis Program 5.11 Page 2 of 13


Ventilation Sizing Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/20
Prepared by: RST Ingenieria 12:07A

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 104 CFM

2. Space Ventilation Analysis


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
Room 1 1 111.4 1.0 302.9 5.00 0.06 0.0 0.0 11.7
Room 2 1 122.8 2.0 323.5 5.00 0.06 0.0 0.0 17.4
Room 3 1 192.9 2.0 429.0 5.00 0.06 0.0 0.0 21.6
Living Room 1 558.2 4.0 1410.3 5.00 0.06 0.0 0.0 53.5
Totals (incl. Space Multipliers) 2465.7 104.1

Hourly Analysis Program 5.11 Page 3 of


Air System Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 162 ft² 6970 - 162 ft² - -
Wall Transmission 605 ft² 3211 - 605 ft² 2215 -
Roof Transmission 985 ft² 2615 - 985 ft² 509 -
Window Transmission 162 ft² 757 - 162 ft² 1099 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 155 ft² 15134 - 155 ft² 1341 -
Floor Transmission 985 ft² 0 - 985 ft² 0 -
Partitions 1073 ft² 552 - 1073 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 296 W 1009 - 0 0 -
Task Lighting 296 W 1009 - 0 0 -
Electric Equipment 870 W 2968 - 0 0 -
People 9 2130 1420 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 36355 1420 - 5165 0
Zone Conditioning - 35162 1420 - 5161 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2466 CFM 0 - 2466 CFM 0 -
Ventilation Load 104 CFM 775 143 104 CFM 776 0
Supply Fan Load 2466 CFM 0 - 2466 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 35937 1563 - 5937 0
Central Cooling Coil - 35937 1568 - 0 0
Central Heating Coil - 0 - - 5937 -
>> Total Conditioning - 35937 1568 - 5937 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page 4 of 13


Zone Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 162 ft² 6970 - 162 ft² - -
Wall Transmission 605 ft² 3211 - 605 ft² 2215 -
Roof Transmission 985 ft² 2615 - 985 ft² 509 -
Window Transmission 162 ft² 757 - 162 ft² 1099 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 155 ft² 15134 - 155 ft² 1341 -
Floor Transmission 985 ft² 0 - 985 ft² 0 -
Partitions 1073 ft² 552 - 1073 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 296 W 1009 - 0 0 -
Task Lighting 296 W 1009 - 0 0 -
Electric Equipment 870 W 2968 - 0 0 -
People 9 2130 1420 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 36355 1420 - 5165 0

Hourly Analysis Program 5.11 Page 5 of 13


Space Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

TABLE 1.1.A. Component Loads For Space "Room 1" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 68.5 °F / 63.1 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 3933 - 46 ft² - -
Wall Transmission 148 ft² 125 - 148 ft² 541 -
Roof Transmission 111 ft² 76 - 111 ft² 58 -
Window Transmission 46 ft² -228 - 46 ft² 318 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 111 ft² 0 - 111 ft² 0 -
Partitions 194 ft² 63 - 194 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 33 W 114 - 0 0 -
Task Lighting 33 W 114 - 0 0 -
Electric Equipment 160 W 546 - 0 0 -
People 1 230 120 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 4973 120 - 917 0

TABLE 1.1.B. Envelope Loads For Space "Room 1" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NE EXPOSURE
WALL 82 0.470 - -7 - 299
WINDOW 1 9 1.110 0.991 -54 288 76
SE EXPOSURE
WALL 66 0.470 - 132 - 242
WINDOW 1 38 0.823 0.607 -174 3645 242
H EXPOSURE
ROOF 111 0.066 - 76 - 58

Hourly Analysis Program 5.11 Page 6 of 13


Space Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

TABLE 1.2.A. Component Loads For Space "Room 2" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 65.8 °F / 60.6 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 38 ft² 4058 - 38 ft² - -
Wall Transmission 48 ft² 110 - 48 ft² 176 -
Roof Transmission 123 ft² 85 - 123 ft² 63 -
Window Transmission 38 ft² -281 - 38 ft² 242 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 123 ft² 0 - 123 ft² 0 -
Partitions 206 ft² 51 - 206 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 37 W 126 - 0 0 -
Task Lighting 37 W 126 - 0 0 -
Electric Equipment 160 W 546 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5310 410 - 482 0

TABLE 1.2.B. Envelope Loads For Space "Room 2" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SE EXPOSURE
WALL 48 0.470 - 110 - 176
WINDOW 1 38 0.823 0.607 -281 4058 242
H EXPOSURE
ROOF 123 0.066 - 85 - 63

Hourly Analysis Program 5.11 Page 7 of 13


Space Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

TABLE 1.3.A. Component Loads For Space "Room 3" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 35 ft² 3412 - 35 ft² - -
Wall Transmission 182 ft² 1030 - 182 ft² 667 -
Roof Transmission 193 ft² 512 - 193 ft² 100 -
Window Transmission 35 ft² 154 - 35 ft² 223 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 193 ft² 0 - 193 ft² 0 -
Partitions 248 ft² 128 - 248 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 58 W 197 - 0 0 -
Task Lighting 58 W 197 - 0 0 -
Electric Equipment 270 W 921 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7043 410 - 990 0

TABLE 1.3.B. Envelope Loads For Space "Room 3" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SW EXPOSURE
WALL 64 0.470 - 581 - 236
WINDOW 1 35 0.823 0.607 154 3412 223
NW EXPOSURE
WALL 118 0.470 - 450 - 430
H EXPOSURE
ROOF 193 0.066 - 512 - 100

Hourly Analysis Program 5.11 Page 8 of 13


Space Design Load Summary for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

TABLE 1.4.A.Component Loads For Space "Living Room" In Zone "Zone 1"
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Oct 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.6 °F / 67.7 °F HEATING OA DB / WB 62.2 °F / 51.6 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 43 ft² 1895 - 43 ft² - -
Wall Transmission 227 ft² 1189 - 227 ft² 831 -
Roof Transmission 558 ft² 1481 - 558 ft² 289 -
Window Transmission 43 ft² 217 - 43 ft² 315 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 155 ft² 15134 - 155 ft² 1341 -
Floor Transmission 558 ft² 0 - 558 ft² 0 -
Partitions 425 ft² 218 - 425 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 167 W 571 - 0 0 -
Task Lighting 167 W 571 - 0 0 -
Electric Equipment 280 W 955 - 0 0 -
People 4 920 480 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 23152 480 - 2776 0

TABLE 1.4.B. Envelope Loads For Space "Living Room" In Zone "Zone 1"
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr·ft²·°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SW EXPOSURE
WALL 62 0.470 - 557 - 227
DOOR GLASS 155 1.110 0.991 924 14209 1341
NW EXPOSURE
WALL 165 0.470 - 632 - 605
WINDOW 1 19 1.093 0.881 114 733 166
WINDOW 2 23 0.823 0.607 103 1162 149
H EXPOSURE
ROOF 558 0.066 - 1481 - 289

Hourly Analysis Program 5.11 Page 9 of 13


System Psychrometrics for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

October DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 83.6 0.01260 104 400 775 143
Vent - Return Mixing Outlet 76.2 0.01229 2466 1045 - -
Central Cooling Coil Outlet 61.1 0.01214 2466 1045 35937 1568
Central Heating Coil Outlet 61.1 0.01214 2466 1045 0 -
Supply Fan Outlet 61.1 0.01214 2466 1045 0 -
Cold Supply Duct Outlet 61.1 0.01214 2466 1045 - -
Zone Air - 75.9 0.01227 2466 1073 35162 1420
Return Plenum Outlet 75.9 0.01227 2466 1073 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.966 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4244.1 BTU/(hr-CFM)
Site Altitude = 3064.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 36355 Cooling 35162 75.9 2466 1073 0 0

Hourly Analysis Program 5.11 Page 10 of 13


System Psychrometrics for HVAC Multisplit
Project Name: Proyecto Refri 12/06/2021
Prepared by: RST Ingenieria 12:07AM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 62.2 0.00665 104 400 -776 0
Vent - Return Mixing Outlet 69.6 0.00665 2466 619 - -
Central Cooling Coil Outlet 69.6 0.00665 2466 619 0 0
Central Heating Coil Outlet 72.1 0.00665 2466 619 5937 -
Supply Fan Outlet 72.1 0.00665 2466 619 0 -
Cold Supply Duct Outlet 72.1 0.00665 2466 619 - -
Zone Air - 69.9 0.00665 2466 628 -5161 0
Return Plenum Outlet 69.9 0.00665 2466 628 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.966 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4244.1 BTU/(hr-CFM)
Site Altitude = 3064.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -5165 Heating -5161 69.9 2466 628 0 0

Hourly Analysis Program 5.11 Page 11 of 13


System Psychrometrics for HVAC Multisplit
Project Name: Proyecto Refri 12/06/20
Prepared by: RST Ingenieria 12:07A

Location: San Jose, Costa Rica


Altitude: 3064.0 ft.
Data for: October DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014
2 1
34
5
0.012

0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 12 of


System Psychrometrics for HVAC Multisplit
Project Name: Proyecto Refri 12/06/20
Prepared by: RST Ingenieria 12:07A

Location: San Jose, Costa Rica


Altitude: 3064.0 ft.
Data for: WINTER DESIGN HEATING
0.020
1. Outdoor Air
2. Mixed Air
3. Central Heating Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air

0.016

Specific Humidity ( lb/lb )


0.014

0.012

0.010

0.008
1 25 3 4
0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page 13 of