PCS-9671 X Instruction Manual en Overseas General X R1.03 (En DYBH5314.0086.0004)
PCS-9671 X Instruction Manual en Overseas General X R1.03 (En DYBH5314.0086.0004)
PCS-9671 X Instruction Manual en Overseas General X R1.03 (En DYBH5314.0086.0004)
Transformer Relay
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from
manufactured goods and may not be received at the same time. Therefore this guide is provided
to ensure that printed information normally present on equipment is fully understood by the
recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual and read relevant chapters carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.
WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.
CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high
voltage generated is dangerous.
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earthing
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when the power supply to the equipment is
on, as this may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check
the supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
5 Management
Introduce the management functions (measurement, and recording etc.) of this relay.
6 Hardware
Introduce the main function carried out by each module of this relay and providing the definition of
pins of each module.
7 Settings
List of all the settings and their ranges and step sizes, together with a brief explanation of each
setting and some notes about the setting application.
9 Configurable Function
Introduce the configurable function (such as LED configuration, binary input configuration and
binary output configuration etc.) of this relay.
10 Communication
Introduce the communication port and protocol which this relay can support, the IEC60870-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
11 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
earthing recommendations. A typical wiring connection to this relay is indicated.
12 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
13 Maintenance
A general maintenance policy for this relay is outlined.
&
AND gate
≥1
OR gate
Comparator
Timer
t Timer (optional definite-time or inverse-time characteristic)
t
10ms 0ms
Timer [delay pickup (10ms), delay dropoff (0ms), non-settable]
[t1] 0ms
Timer (t1: delay pickup, settable)
0ms [t2]
Timer (t2: delay dropoff, settable)
[t1] [t2]
Timer (t1: delay pickup, t2: delay dropoff, settable)
Basic Example
A, B, C L1, L2, L3 Ia, Ib, Ic, I0 IL1, IL2, IL3, IN
AN, BN, CN L1N, L2N, L3N Ua, Ub, Uc VL1, VL2, VL3
ABC L123 Uab, Ubc, Uca VL12, VL23, VL31
U (voltage) V U0, U1, U2 VN, V1, V2
1 Introduction
Table of Contents
List of Figures
1.1 Application
This relay can sample the analog values from the traditional instrument transformers, or receive
the sampled values from the electronic current and voltage transformers (via a merging unit). The
binary inputs and outputs of this relay can be configured according to the demands of a practical
engineering through the PCS-Explorer configuration tool auxiliary software.
This relay can fully support the IEC61850 and IEC61850-9-2 protocols, and GOOSE function, and
can completely meet the demands of a modern digital substation.
side 1
*
3
PCS-9671
52
50/51P
64REF DTOC
87T 50/51P
*
64REF
1 50/87T DTOC FDR
DIFF 50/51P
64REF DTOC
*
*
1 1
52 52
3
*
3
*
side 3 side 2
1.2 Functions
The functions of this relay include protective functions, management functions and auxiliary testing
functions, and the functions of this relay are listed in the following tables.
Protective Functions
Protection functions
87T Biased differential protection
50/87UT Unrestrained instantaneous differential protection
64REF Restricted earth fault protection of side 1
64REF Restricted earth fault protection of side 2
64REF Restricted earth fault protection of side 3
50P/51P Phase overcurrent protection of side 1
50P/51P Phase overcurrent protection of side 2
50P/51P Phase overcurrent protection of side 3
CTS CT circuit supervision
CT saturation detection
nd rd
Inrush current blocking by 2 harmonic and 3 harmonic
th
Overexcitation blocking by 5 harmonic
AI Analog inputs
Current drift auto adjustment
Relay self supervision
Binary input
Output relays
Management functions
Management Functions
Measurement
Multiple setting groups
64 Protection operation reports
1024 Supervision alarm records
1024 Control operation records
1024 User operation records
FDR 64 Fault and disturbance records
1024 latest SOE records, latest records of the following elements state
SOE changing: operating abnormality alarm elements, supervision alarm
elements, protection elements and binary input elements.
Rear communication ports: Ethernet, RS-485, Printer port
Time synchronization port: RS-485
1.3 Features
This device is based on a 32-bit high performance dual-core processor, internal high
speed bus and intelligent I/O ports, and the hardware is in module design and can be
configured flexibly, featuring interchangeability and easy extension and maintenance.
The adoption of 16-bit A/D converter and the dual-channel sampling technology can
ensure the accuracy and reliability of protection sampling and the correctness of
protection operation.
This device can sample the analog values from the traditional instrument transformers, or
receive the sampled values from the electronic transformers. It can support the protocol
IEC61850-9-2 and GOOSE.
Various methods of GPS time synchronization are supported in this relay, including
IRIG-B, SNTP, IEEE1588 (V2), pulse per second (PPS) and IRIG-B synchronization.
This device can communicate with a SCADA or RTU via different communication
intermediates: Ethernet network, RS-485 serial ports. The communication protocol of this
device is optional: IEC61850, IEC60870-5-103 or DNP3.0.
The human machine interface (HMI) with a small control module (a 240×128-dot LCD, a
9-key keypad and 20 LED indicators) on the front panel is very friendly and convenient to
the user.
Y→△ transfer method is used to compensate phase angle of secondary current on each
side of the transformer, and correction coefficients are adopted to complete amplitude
compensation.
Vector group of each side transformer is settable, and 24 vector groups available for
two-winding transformer, and 288 vector groups available for 3-winding transformer.
2nd , 3rd and 5th harmonic blocking function for biased differential protection is available.
2nd harmonic and 3rd harmonic is selectable to identify inrush current, and 5th harmonic is
used to detect overexcitation condition. Besides, phase segregated blocking mode or
phase crossing blocking mode is selectable for harmonic blocking.
CT Transient detection function based on the ratio of residual current to positive current is
adopted to eliminate the influence of difference of transient characteristic and saturation
of various CT to restricted earth fault protection.
2 Technical Data
Table of Contents
Burden 300mW
380Vac
Maximal system voltage
250Vdc
Test voltage across open contact 1000V RMS for 1min
6A@3s
Short duration current 15A@0.5s
30A@0.2s
Durability 10,000 operations minimum
NOTE! Binary output for tripping are not connected to trip circuit breakers directly. They
are connected to interposing relays or lockout relays contacts which are connected to trip
circuit breakers.
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
IEC 60255-22-4:2008
Fast transient disturbance
Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
tests
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Surge immunity test
Common mode: 4kV
Differential mode: 2kV
Conducted RF IEC 60255-22-6:2001
Electromagnetic Disturbance Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150 kHz~80MHz
Power Frequency Magnetic IEC 61000-4-8:2001
Field Immunity class V, 100A/m for 1min, 1000A/m for 3s
IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic IEC 61000-4-10:2001
field immunity class V, 100kHz & 1MHz–100A/m
IEC60255-11: 2008
Auxiliary power supply
Voltage dips: Up to 500ms for dips to 40% of rated voltage without reset
performance
Voltage short interruptions: 100ms for interruption without rebooting
NOTE! There are some symbols mentioned in the following sections and the meaning of
Id – differential current
th
5 harmonic setting for inrush current
0.1~0.5, 0.001 steps
[87T.K_Hm5]
nd th
Tolerance of 2 and 5 harmonic settings ≤5% of setting or 0.01, whichever is greater
Operating time
≤35ms ( I 0 d >2×[64REF.I_Biased])
(Without time delay, without blocking criterion)
2.8 Certification
ISO9001: 2008
ISO14001:2004
OHSAS18001: 2007
ISO10012:2003
CMMI L4
3 Operation Theory
Table of Contents
List of Figures
Figure 3.4-1 Restricted earth fault protection for a wye winding......................................... 3-19
Figure 3.4-2 Two three-phase CT inputs for REF protection of side 1 ................................ 3-19
Figure 3.4-4 Logic diagram of restricted earth fault protection of HV side ..................... 3-25
Figure 3.5-1 Logic diagram of definite time overcurrent protection of side 3 .................... 3-27
List of Tables
Table 3.3-1 Matrix of phase compensation and zero-sequence current elimination ........... 3-5
Table 3.4-1 Restricted earth fault protection settings list ..................................................... 3-26
3.1 Overview
The equipment protection is composed of current differential protection, restricted earth fault
protection and overcurrent protection. Moreover, CT failure supervision function, CT saturation
detection and inrush current detection function are also included.
Protection theory is introduced from following three parts in the chapter, general fault detector and
protection element. The equipment has independent general fault detector, which picks up to
connect positive pole of power supply of output relays and make program jump to fault calculation
from normal calculation. The equipment output relays will operate to trip only if general fault
detector and protective element operates simultaneously.
General fault detector will pick up and power supply of output relay will be switched on 500 ms to
make it ready to send tripping signal, when any one of following two fault detectors is met.
Where:
Where:
NOTE! Here “Sx” means “S1” (i.e. side 1), “S2” (i.e. side 1) or “S3” (i.e. side 3), and side 1,
side 2 and side 3 represent HV side, MV side and LV side of a transformer respectively.
These symbols mentioned in the manual below have the same meanings and will not give
detailed explanation again.
Where:
Current compensation process is shown in the flowing figure in which a two-winding transformer
with two three-phase CT inputs is taken as an example, and HV and LV sides of the transformer
are connected to side 1 and side 2 inputs of the PCS-9671 respectively. In an ideal situation, the
differential current (i.e. I d =I’_S1+I’_S2)should be zero during the normal operation of the
transformer or an external fault occurring.
Ip_S1 Ip_S2
HV * * LV
I_S1 I_S2
PCS-9671
Phase shift/residual current Phase shift/residual current
eliminate (*M1) eliminate (*M2)
I'_S1 I'_S2
Calculate differential current and restraint current
Where:
M1, M2 are matrixes of phase shifting and residual current elimination of side 1 and side 2
respectively.
I 2bS 2 , I 2bS2 are rated secondary values of HV side and LV side respectively.
I da I a _ S1 I a _ S 2 I a _ S 3
I db M 1 I b _ S1 / I 2bS1 M 2 I b _ S 2 / I 2bS 2 M 3 I b _ S 3 / I 2bS3
I dc Equation 3.3-1
I c _ S1 I c _ S 2 I c _ S 3
1 2 3
I da I a1 I a 2 I a3
I db I b1 I b2 I b3 Equation 3.3-2
I dc I c1 I c 2 I c3
Where:
I a1 , I b1 , I c1 are secondary values of corrected three-phase current of side 1.
I a3 , I b3 , I c3 are secondary values of corrected three-phase current of side 3.
M1, M 2 , M 3 are matrixes of phase shifting and residual current elimination of each side
respectively, and please refer to Table 3.3-1 for details.
I 2bS1, I 2bS2 , I 2bS3 are rated secondary values of each side of transformer respectively.
I ra
1
2
I a1 I a 2 I a3
I rb
1
I b1 I b 2 I b3 Equation 3.3-3
2
I rc
1
I c1 I c 2 I c3
2
Where:
The following transforming method is based on the assumptions that the positive polarities of CT
at each side is at busbar side.
The current phase compensation for all CTs is achieved by software, and Y→Δ transforming
method is used for this purpose. The vector group of a transformer can be set by the settings
[CTConn], [WdgConn_S1], [Clk_S2_WRT_S1] and [Clk_S3_WRT_S1].
If the system logic setting [CTConn] is set as “0”, it means CT winding is star connected, and then
program will select suitable compensation matrix to complete phase compensation automatically
according to the settings [WdgConn_S1], [Clk_S2_WRT_S1] and [Clk_S3_WRT_S1]. If [CTConn]
is set as “1”, it means CT winding is delta connected, and the phase compensation is realized by
CT winding delta connection, so there is no need for the compensation calculation in program.
Delta winding side of a transformer is taken as the reference of phase compensation, and currents
of other sides are transformed through Y→Δ transforming method. When more than one side
winding are delta connected, the first delta winding side is taken as the reference in the sequence
of side 1, side 2 and side 3. If there is no winding delta connected, for example vector group
YN/y0, then a virtual 11 o’clock winding side is taken as the reference, currents of each side are
transformed to 11 o’clock.
The matrix of phase shift and residual current compensations is listed in Table 3.3-1, and relative
o’clock is the leading phase angle of one side compared to the reference side and one o’clock
represents 30°.
For example, a transformer with the vector group YN/d11/y10, side 2 is taken as the reference
side, so the relative o’clock of side 2 is 0 o’clock (i.e. 0°lag), the relative o’clock of side 1 is 1
o’clock (i.e. 30° lag), and that of side 3 is 11 o’clock (i.e. 330° lag). In Equation 3.3-1,
M1, M 2 , M 3 represent the matrixes of relative o’clock 1, 0, 11 respectively. In the following figure,
IA, IB, IC are three-phase current vector of star side of transformer, and Ia, Ib, Ic are three-phase
current vectors of delta side.
IA(Y0)
Ia(Δ11)
30°
330° Ib
IC IB
Ic
For example, a transformer with the vector group YN/yn2/y10, a virtual side of 11 o’clock delta
connection is taken as the reference side, so the relative o’clock of side 1, side 2 and side 3 are 1
o’clock (i.e. 30°lag), 3 o’clock (i.e. 90°lag) and 11 o’clock (i.e. 330°lag) respectively. In Equation
3.3-1, M1, M 2 , M 3 represent the matrix of relative o’clock 1, 3, 11 respectively.
Matrix Matrix
Relative
(with zero-sequence current (without zero-sequence current
o’clock
elimination) elimination)
2 1 1 1 0 0
1
1 2 1 0 1 0
3
0(12)
1 1 2 0 0 1
1 1 0
0 1 1
1
1
3
1 0 1
1 2 1 0 1 0
1
1 1 2 0 0 1
2
3
2 1 1 1 0 0
0 1 1
1
3 1 0 1
3
1 1 0
Matrix Matrix
Relative
(with zero-sequence current (without zero-sequence current
o’clock
elimination) elimination)
1 1 2 0 0 1
1
4 2 1 1 1 0 0
3
1 2 1 0 1 0
1 0 1
1
5 1 1 0
3
0 1 1
2 1 1 1 0 0
1
1 2 1 0 1 0
6
3
1 1 2 0 0 1
1 1 0
1
7 0 1 1
3
1 0 1
1 2 1 0 1 0
1
1 1 2 0 0 1
3
8
2 1 1 1 0 0
0 1 1
1 0 1
1
9
3
1 1 0
1 1 2 0 0 1
1
2 1 1 1 0 0
3
10
1 2 1 0 1 0
1 0 1
1 1 0
1
11
3
0 1 1
In the following two cases, zero-sequence current can not be transformed from one side to
another side of a transformer, which will result in a steady-state differential current at the
differential relay, so zero-sequence current must be eliminated before the calculation of
differential and restraint currents to avoid an unwanted operation of the current differential relay.
Case 1: When an external fault occurs at the wye winding side of the wye-delta connected
transformer (such as a transformer with the vector group YNd11), zero-sequence current exits at
the wye winding side but can not be transformed to delta winding side.
Zero-sequence current is already eliminated by Y→△ transforming at wye side in program, and
zero-sequence current at delta winding side are optional to be eliminated by configuring the logic
settings ([En_I0Elim_Sx], x=1, 2 and 3) of each side.
Power transformer ratio, mismatch between the CT ratios and different voltage levels of each side
will result in different current values of each side during transformer normal operation, so
amplitude compensation should be carried out before the calculation of differential and restraint
currents.
S n C1
I 2bS 2 Equation 3.3-4
3U1n CTR11
Where:
C1 is the connection coefficient of CT. If side 1 CT is wye connected, then the logic setting
[CTConn] is set as “0” and C1 is equal to 1. If side 1 CT is delta connected, [CTConn] is set as
NOTE! In following theory analyzing of differential protection, the currents mentioned are
all per unit values which probably are not pointed out again.
In order to ensure the calculation precision of differential protection, rated secondary current of
each side should meet the following criterion.
Where:
I 2bS1, I 2bS2 , I 2bS3 are respectively rated secondary currents of side 1, side 2 and side 3 of
transformer.
I 2nS1, I 2nS2 , I 2nS3 are rated secondary current of CT at side 1, side 2 and side 3 of differential
protection.
When viewing settings and values of conventional current differential protection in the relay, user
will find the unit “pu” (per unit). The current in differential protection calculation is not actual
secondary value but per unit value which is got by actual secondary value of each side of
transformer divided by transformer secondary rated current of each side ( I 2bS1, I 2bS2 , I 2bS3 ).
The biased differential protection with low pickup setting and restraint slope, which is also called
sensitive biased differential protection, is more sensitive to operate during slight internal fault
occurs. Besides, four blocking elements, CT saturation, inrush current (optional), overexciation
(optional) and CT circuit failure (optional), are equipped for the protection to prevent it from
unwanted operation during an external fault. Operation criterion of this sensitive biased differential
protection is:
I
1
I r i Equation 3.3-6
2
i 1
3
I d
I
i 1
i
Where:
[87T.I_Biased] is the setting of biased differential protection, which is also setting of fault detector
of biased differential protection.
Conventional biased differential protection can prevent the influence of steady state and transient
CT saturation during an external fault and can operate correctly and quickly during an internal
fault even if CT is saturated. Operation criterion of this conventional biased differential protection
is:
I d 1.2 pu I r 1.2 pu
Equation 3.3-7
I d 1.0 I r I r 1.2 pu
Where:
NOTE! Parameters of this protection have been fixed in program and do not need to be
configured by user.
If the pickup setting of sensitive biased differential protection (i.e. [87T.I_Biased]) is greater than
1.2In, then the pickup current of conventional biased differential protection will change to
[87T.I_Biased] automatically.
Unrestrained instantaneous differential element in the PCS-9671 shall operate to trip breakers at
all sides of a transformer when the differential current of any phase is higher than its setting. Its
operation criterion is:
Where:
2
k=
Operating area of
instantaneous Diff.
[87T.I_Instant]
.
iff
se of
D f
ed o
.
D
iff
ia a
as ea
d
l b are
bi ar
na g
ve ng
tio tin
iti ati
en era
ns er
1
K=
nv p
se Op
co O
1
k=
Blocking area
1.2 ]
l ope
T.S
[ 87
K=
[87T.I_Biased] restraint current
In above figure:
(1) The sensitive biased differential protection element will send tripping signal with blocking by
CT saturation, inrush current (optional), overexciation (optional) and CT circuit failure (optional). It
can ensure the sensitivity of the protection and avoid an unwanted operation when CT is
saturated during an external fault. Its operation area is the tint shadow area in the figure above.
(2) The conventional biased differential protection element will send tripping signal only with
blocking by inrush current and CT circuit failure (optional). It eliminates the influence of transient
and steady saturation of CT during an external fault and ensures the reliable operation even if CT
is saturated during an internal fault by means of its biased restraint characteristic. Its operation
area is the deeper shadow area in the figure above.
(3) The unrestrained instantaneous differential protection element will send tripping signal without
any blocking if differential current of any phase reaches its setting. Its operation area is over the
above two areas with the deepest dark shadow.
Unblocking mode
Unblocking means inrush current detection element is disabled, so differential protection will not
be blocked by inrush current.
When any phase satisfies the following equation, the biased differential protection of this phase
will be blocked. The criterion is as following.
Where:
I d _ 2nd and I d _ 3rd are the second and third harmonics of phase differential current
respectively.
I d _ 1st is the fundamental component of the differential current of the corresponding phase.
[87T.K_Hm2] and [87T.K_Hm3] are the setting values of restraint coefficient of second and third
harmonics respectively, and [87T.K_Hm3] is set fixedly to 0.2 in program.
When any phase satisfies Equation 3.3-9 and the operation criterion of the phase of biased
differential protection has been satisfied, the biased differential protection of three phases will be
blocked.
When the maximum value of fundamental component and maximum value of secondary harmonic
of three phase differential currents satisfy the following equation, three-phase differential
protection are blocked. The criterion is as following.
Where:
I d _ 1st. max is the maximum value of the fundamental component of three phase differential
currents.
I d _ 2nd. max and I d _ 3rd. max are respectively maximum values of the secondary harmonic and
Where:
If any harmonic of one phase differential current meets above formula, it will be considered that it
is CT saturation to cause this phase differential current and related sensitive biased differential
element will be blocked.
Where:
Differential CT circuit abnormality detection is realized during sampling program. If anyone of two
following criteria is met, CT circuit abnormality alarm will be issued after 10 s without blocking
differential protection.
Where:
Differential current alarm setting [87T.I_Alm] should be greater than the differential current during
transformer operation with the tap not in middle position or the maximum differential current during
other operation conditions.
NOTE! Differential current alarm setting [87T.I_Alm] should be less than the pickup
setting of differential current [87T.I_Biased] and usually be set between the value of
maximum differential current during transformer operation with the tap not in middle
position and the least value of the setting [87T.I_Biased].
Differential CT circuit failure discrimination will be enabled after pickup of fault detector of
differential protection if logic setting of biased differential protection is set as “1” and binary input of
blocking differential protection is set as “0”.
Any one of following three criteria is met after fault detector (FD) of biased differential protection
pickup, CT circuit failure discrimination will not be carried out.
(1) Maximum phase current of some side is lower than 0.2pu ( is secondary calculated rated
current of transformer) before FD pickup.
When this occurs, only CT circuit failure discrimination of this side will not be carried out.
(2) The maximum phase current is higher than 1.2pu after FD pickup.
(3) Any phase current of any side after pickup is greater than that before FD pickup.
If current of some side satisfies following two criteria simultaneously, then it will be judged as CT
circuit failure immediately.
(1) Only one phase current is lower than pickup setting of biased differential protection
[87T.I_Biased].
(2) The other two phase currents after pickup are equal to those before FD pickup.
FD_Diff
IΦmax>1.2pu
≥1
Any phase current of any side is
greater than that before FD pickup
Where:
FD_Diff is the internal flag indicating that the fault detector of differential current picks up.
[Alm_CTS] is the issued alarm signal indicating that instant CT circuit failure is distinguished.
“Before FD pickup” mentioned in the above figure represents the time 2 cycles (i.e. 40ms) before
the fault detector picks up.
When CT circuit failure is distinguished, then CT circuit failure alarm will be issued with “ALARM”
LED lit on. By configuring the logic setting [87T.En_CTS_Blk], user can get blocking functions to
differential protection. If this logic setting is set as “0”, the biased differential protection will not be
blocked by CT circuit failure. Otherwise, it will be blocked by CT circuit failure.
In order to prevent the maloperation due to CT circuit failure, if maximum phase current is greater
than 1.2pu after the alarm [87T.Alm_CTS] is issued, biased differential protection will be released.
If the alarm is issued, the alarm signal can be reset and “ALARM” can be turned off only after the
failure is removed and the binary input [BI_RstTarg] is energized or manually send command
“Reset_Target” through relay menu, or receiving reset message from SCADA or gateway.
circuit or settings. Both shall be paid attention on site. For example, differential circuits
open can not make fault detector of differential protection pick up in case of light load but
alarm will be sent. If user treats this abnormality in time, unwanted differential operation
can be avoided if the load increases or external fault occurs.
3.3.10 Logic
Differential protection operates to make the second group of tripping output contacts pick up to trip
all side circuit breakers of a transformer.
SIG [87T.En1]
&
SIG [87T.Blk]
SET [87T.En_Instant]
&
SIG Max(Ida, Idb, Idc) &
[87T.Op_Instant]
SET [87T.I_Instant]
SIG FD_Diff
&
SET [87T.En_Biased]
SIG Flg_Inrush
SIG Flg_CT_Sat
SET [87T.En_Hm5_Blk]
SET [87T.En_CTS_Blk]
SIG FD_Diff
FD_Diff is the internal flag indicating that the fault detector of differential current picks up.
[87T.En_Biased] is the logic setting used to enable biased differential protection function.
[87T.En_Instant] is the logic setting used to enable instantaneous differential protection function.
Flg_CTS is the internal flag indicating current transformer circuit failure is distinguished.
[87T.Opt_Inrush_Blk] is the logic setting used to select the blocking mode of biased differential
protection when inrush current is distinguished.
[87T.En_CTS_Blk] is the logic setting used to block biased differential protection when current
transformer circuit failure is distinguished.
[87T.En_Hm5_Blk] is the logic setting used to block biased differential protection when
overexciation state is detected.
3.3.11 Setting
Table 3.3-2 Current differential protection settings list
No. Setting Item Range Step Unit Description
0.04~1.2
6 87T.I_Alm 0.001 pu Setting of differential current abnormality alarm
Setting Explanation
1. [87T.OutMap]
The tripping logic setting is used to specify which breakers will be tripped when current differential
protection operates. This logic setting comprises 12 binary bits as follows and is expressed by a
hexadecimal number of 3 digits from 000H to FFFH. The tripping logic setting of the equipment is
specified as follows:
Bit 11 10 9 8 7 6 5 4 3 2 1 0
Trip Output
BO_Trp12
BO_Trp10
BO_Trp09
BO_Trp08
BO_Trp07
BO_Trp06
BO_Trp05
BO_Trp04
BO_Trp03
BO_Trp02
BO_Trp01
BO_Trp11
NOTE! “BO_Trp01” just means to drive the corresponding output contact to pickup and
please refer to Chapter “Hardware”. The terminals of these tripping outputs are:
The bit corresponding to the breaker to be tripped shall be set as“1” and other bits shall be “0”.
For example, if differential protection operates to make “BO_Trp01”, “BO_Trp02”, “BO_Trp03”
contacts pickup, the bit “1” and bit “2” and bit “3” positions shall be filled with “1” and other bit
positions shall be filled with “0”. Then a hexadecimal number 007H is formed as the tripping
output logic setting.
Tripping output logic settings of the equipment should be set on basis of application-specific
drawings.
Setting Path
Main Menu -> Settings -> Prot Setting-> Diff Prot Settings
Three independent restricted earth fault protections (REF) of each side are used to protect each
winding of transformer with the winding neutral point solid grounded or grounded via a low
impendence, which have more high sensitivity than current differential protection for an internal
earth fault. Restricted earth fault protection consists of sensitive and conventional biased
zero-sequence differential protection elements.
Three phase currents and neutral current are the inputs to the restricted earth fault protection of a
winding. Polarity of three-phase CT is at busbar side, and that of neutral CT is at transformer side
as shown in the Figure 3.4-1.
DANGER: Before REF protection of some side is put into operation on site, polarity of
neutral CT on neutral point of the side must have been checked right by an energizing
test of the side or a test of simulating an external fault of the side in primary system.
Otherwise a maloperation may occur during an external earth fault.
HV LV
*
3I0_Cal
Amplitude
compensation
3I0_NP
Side 1 REF relay
*
Figure 3.4-1 Restricted earth fault protection for a wye winding
Where:
When one winding is connected with more than one three-phase CT (shown in Figure 3.4-2) , or
REF protection is applied for protecting an auto-transformer, user can select the number of
three-phase CT for REF protection by configuring the logic setting [CTNum_64REF_S1(S2,S3)].
REF protections of each side support maximum two groups of three-phase CT inputs and user
needs to set the logic setting according to the applied-specific application.
*
HV
LV
*
3I01_Cal 3I02_Cal
Amplitude
compensation S1 REF
*
Where:
3I01_Cal, 3I02_Cal is calculated residual current from three-phase current of two branches of HV
side.
During the normal operation, calculated residual current and measured residual current may be
different due to the mismatch between the three-phase CT ratio and neutral CT ratio, and the
current difference side must be eliminated before do the calculation of REF protection, which is
realized by amplitude compensation in program.
The correction coefficients are scaling multiplied by the secondary value of calculated residual
current of related sides for the reference of the rated secondary current (1A or 5A)of neutral CT at
the side of REF protection. The calculation equation of correction coefficients is given below.
CTR1 CTR2 1
K CT11 K CT12 K CTN1
CTN11 CTN 11 CTN 12
CTR2 CTR3 1
CT 22
K K CT 23 K CTN 2 Equation 3.4-1
CTN21 CTN21 CTN22
CTR3 1
K CT 33 CTN K CTN 3
31 CTN32
Where:
K CT 11, K CT 12 are correction coefficients of calculated residual current of side 1 and side 2
respectively to the reference of measured residual current from neutral CT of side 1.
K CTN1 , K CTN 2 , K CTN 3 are respectively correction coefficients of residual current of neutral CT at
side 1, side 2 and side 3.
CTR1 , CTR2 , CTR3 are respectively CT ratios of side 1, side 2 and side 3 respectively.
CTN11, CTN21, CTN31 are respectively primary current of neutral CT ratios of side 1, side 2 and side 3
respectively.
CTN12 , CTN22 , CTN32 are respectively secondary current of neutral CT ratios of side 1, side 2 and
side 3 respectively.
When three-phase CT of one side is not the input of the REF protection of some side, than
correction coefficient of this CT is set to “0”. For example, if the three-phase CT of side 1 and
neutral CT of side 1 are inputs of REF protection of side 1, then K CT12 is set to “0” automatically
in program.
In order to ensure current accuracy and performance of restricted earth fault protection, corrected
coefficient of each side should not be greater than 4.
Operation criteria of REF protection of side 1, side 2 and side 3 are Equation 3.4-2, Equation 3.4-3
and Equation 3.4-4 respectively.
I 0d 2 K CT 22 3I 02 K CT 23 3I 03 K CTN 2 I N 2
I 0r 2
max K CT 22 3I 02 , K CT 23 3I 03 , K CTN 2 I N 2 Equation 3.4-3
Where:
I 0d1, I 0r1 are residual differential and restraint currents of side 1 respectively.
3I 01, 3I 02 ,3I 03 are calculated residual currents of side 1, side 2 and side 3 respectively.
I N 1 , I N 2 , I N 3 are neutral current from neutral CT of side 1, side 2 and side 3 respectively.
K CT11, K CT12 , K CT 21, K CT 22 , K CT 32 , K CTN1 , K CTN 2 , K CTN 3 have the same meanings as described
above.
After amplitude compensation, residual differential and restraint currents are per unit values to the
reference of “In” (CT secondary rated current), so when viewing settings and measured values of
REF protection in the relay, user will find “In” is the unit of residual differential and restraint
currents.
Where:
I 0d 3 , I 0r 3
[Sx.64REF.I_Biased] (x=1, 2 or 3). is the pickup setting of sensitive biased REF protection
element.
If the pickup setting of REF protection (i.e. [Sx.64REF.I_Biased]) is greater than 0.5In, its keen
point current will be set at In automatically, the operating equation is as follows:
I 0d 1.2I n I 0r 1.2 pu
Equation 3.4-7
I 0d 1.0 I 0r I 0r 1.2 pu
Where:
NOTE! Parameters of this protection have been fixed in program and do not need to be
configured by user.
If the pickup setting of sensitive biased REF protection (i.e. [Sx.64REF.I_Biased]) greater than
1.2In, then the pickup current of conventional biased REF protection will be set as
[Sx.64REF.I_Biased] automatically.
I0d(In)
Differential
current
F
RE
se f
ia a o
d
l b re
na g a
tio tin
en ra
nv pe
R f
EF
ed o
Co O
as ea
bi ar
ve ng
iti ti
a
ns er
Se Op
.0
1
k=
e]
op
.Sl Blocking area
1.2 4 RE
.6
[Sx
K=
[Sx.64REF.I_Biased] Restraint current
(1) The sensitive biased REF protection element will send tripping signal with blocking by CT
saturation. It can ensure the sensitivity of the protection and avoid an unwanted operation when
CT is saturated during an external fault. Its operation area is the tint shadow area in the figure
above.
(2) The conventional biased REF protection element will send tripping signal only without any
blocking. It eliminates the influence of transient and steady saturation of CT during an external
fault and ensures the reliable operation even if CT is saturated during an internal fault by means
of its biased restraint characteristic. Its operation area is the deeper shadow area in the figure
above.
Where:
I 0 0 I1 Equation 3.4-9
Where:
0 is a proportional constant.
Measure 2
Because neutral CT failure of some side results in unwanted operation of REF protection of this
side, current criterion is used to distinguish the neutral CT failure from an internal fault. When
following equation of any side is met, then neutral CT failure is distinguished and REF protection
of the side is blocked at same time.
Where:
3.4.8 Logic
Side 1, side 2 and side 3 have similar logics of restricted earth fault protection with independent
settings. Here take side 1 as an example.
SIG [S1.64REF.En1]
&
SIG [S1.64REF.Blk]
SET [S1.64REF.En]
&
Logic similar to [S2.64REF.t_Op] 0s
logic of side 1 &
[S2.64REF.Op]
SIG Flg_I1_Restraint ≥1
SIG FD_REF_S1
SIG FD_REF_S2
SIG FD_REF_S3
Where:
I0d_S1 and I0r_S1 are residual differential and residual restraint current of side 1 respectively.
FD_REF_S1 is the internal flags indicating that the fault detector of residual differential current of
side 1 picks up.
3.4.9 Setting
Table 3.4-1 Restricted earth fault protection settings list
Setting Explanation
These tripping logic settings have the same meaning as the setting [87T.OutMap] and please refer
Setting Path
Overcurrent protections of each side are applied as backup protection, and independent logic
settings can be configured to enable or disable the protections of each side. Overcurrent
protection is disabled generally.
3.5.1 Logic
Overcurrent protections of each side have the same logic with independent settings and here side
1 is taken as an example.
SIG [S1.50/51P.En1]
&
SIG [S1.50/51P.Blk] &
S1.50/51P.t_Op 0s
SET [S1.50/51P.En] &
[S1.50/51P.Op]
SIG Max(Ia_S1,Ib_S1,Ic_S1)
SET [S1.50/51P.I_Set]
Logic similar to S2.50/51P.t_Op 0s
logic of side 1 &
SIG FD_OC_S1
[S2.50/51P.Op]
SIG FD_OC_S2
SIG FD_OC_S2
Logic similar to S3.50/51P.t_Op 0s
logic of side 1 &
[S3.50/51P.Op]
Where:
FD_OC_S1 is the internal flag indicating that the fault detector of overcurrent protection of side 1
picks up.
3.5.2 Settings
Table 3.5-1 Overcurrent protection settings list
Setting Explanation
These tripping logic settings have the same meaning as the setting [87T.OutMap] and please refer
it in Section 3.3.11 for the details.
Setting Path
4 Supervision
Table of Contents
List of Figures
List of Tables
Table 4.4-2 Troubleshooting for equipment self-check alarm message ............................... 4-6
Table 4.4-4 Troubleshooting for equipment operation alarm message ................................ 4-8
4.1 Overview
Though the protection system is in non-operating state under normal conditions, it is waiting for a
power system fault to occur at any time and must operate for the fault without fail.
When the equipment is in energizing process before the LED “HEALTHY” is on, the equipment
needs to be checked to ensure there are no errors. Therefore, the automatic supervision function,
which checks the health of the protection system during startup and normal operation procedure,
plays an important role.
The numerical relay based on the microprocessor operations has the capability for implementing
this automatic supervision function of the protection system.
In case a fatal fault is detected during automatic supervision, the equipment will be blocked out. It
means that this relay is out of service. Therefore you must re-energize the relay or even replace a
module to make this relay back into service.
If the software version of FPGA is not proper, or FPGA is damaged, the alarm signal [Fail_FPGA]
will be issued with the message [Fail_Device] and LED indicator “HEALTHY” will be off at the
same time.
If anyone of the active settings is confirmed to be modified, this relay will be blocked, the alarm
signals [Fail_Device] and [Fail_Settings] will be issued; meanwhile, if the modified setting is out of
the appointed range, the alarm signal [Fail_Setting_OvRange] will be issued at the same time.
The LED indicator “HEALTHY” will be off at the same time.
If anyone of the items of the setting file is changed (the program of this relay is updated), the
alarm signal [Fail_SettingItem_Chgd] will be issued, The LED indicator “HEALTHY” will be off at
the same time. The items of the setting include the setting number, the setting name, the setting
If this relay is in the test of binary output contact, the alarm signals [Alm_Device] and
[Alm_BOTest] will be issued and the LED indicator “ALARM” will be on at the same time.
The CT supervision function consists of two aspects: differential CT circuit abnormality without
pickup of fault detector of differential protection and CT circuit failure with the fault detector pickup.
Differential CT circuit abnormality detection is realized during sampling program. If anyone of two
following criteria is satisfied, CT circuit abnormality alarm will be issued after 10 s without blocking
differential protection.
Where:
Differential current alarm setting [87T.I_Alm] should be greater than the differential current during
transformer operation with the tap not in middle position or the maximum differential current during
other operation conditions.
NOTE! Differential current alarm setting [87T.I_Alm] should be less than the pickup
setting of differential current [87T.I_Biased] and usually be set between the value of
maximum differential current during transformer operation with the tap not in middle
position and the least value of the setting [87T.I_Biased].
Differential CT circuit failure discrimination will be enabled after pickup of fault detector of
differential protection if logic setting of biased differential protection is set as “1” and binary input of
blocking differential protection is set as “0”.
Any one of following three criteria is satisfied after fault detector (FD) of biased differential
protection pickup, CT circuit failure discrimination will not be carried out.
(1) Maximum phase current of some side is lower than 0.2pu before FD pickup.
When this occurs, only CT circuit failure discrimination of this side will not be carried out.
(2) The maximum phase current is higher than 1.2pu after FD pickup.
(3) Any phase current of any side after pickup is greater than that before FD pickup.
If current of some side satisfies following two criteria simultaneously, then it will be judged as CT
circuit failure immediately.
(1) Only one phase current is lower than pickup setting of biased differential protection
[87T.I_Biased].
(2) The other two phase currents after pickup are equal to those before FD pickup.
FD_Diff
IΦmax>1.2pu
≥1
Any phase current of any side is
greater than that before FD pickup
Where:
FD_Diff is the internal flag indicating that the fault detector of differential current picks up.
[Alm_CTS] is the issued alarm signal indicating that instant CT circuit failure is distinguished.
“Before FD pickup” mentioned in the above figure represents the time 2 cycles (i.e. 40ms) before
the fault detector picks up.
When CT circuit failure is distinguished, then CT circuit failure alarm will be issued with “ALARM”
LED lit on. By configuring the logic setting [87T.En_CTS_Blk], user can get blocking functions to
differential protection. If this logic setting is set as “0”, the biased differential protection will not be
blocked by CT circuit failure. Otherwise, it will be blocked by CT circuit failure.
In order to prevent the maloperation due to CT circuit failure, if maximum phase current is greater
than 1.2pu after the alarm [87T.Alm_CTS] is issued, biased differential protection will be released.
If the alarm is issued, the alarm signal can be reset and “ALARM” can be turned off only after the
failure is removed and the binary input [BI_RstTarg] is energized or manually send command
“Reset_Target” through relay menu, or receiving reset message from SCADA or gateway.
circuit or settings. Both shall be paid attention on site. For example, differential circuits
open can not make fault detector of differential protection pick up of in case of light load
but alarm will be sent. If user treats this abnormality in time, unwanted differential
operation can be avoided if the load increases or external fault occurs.
If residual differential current of REF protection of some side is greater than a setting
(i.e.[Sx.64REF.I_Alm]) and the state is keeping over 10 s, the alarm of REF protection of the side
will be issued without the protection being blocked.
Some failures will result in some protective function being blocked. Some server failures of
hardware or software will result in the equipment being blocked and the contacts of equipment
failure will operate at same time. During that condition, the protection relay has to be put out of
service for maintenance.
NOTE! If an alarm signal is issued with equipment being blocked, please try to make a
fault diagnosis by referring the issued alarm messages but not to simply reboot or
re-power the relay. If user cannot find the failure reason on site, please inform
manufacturer for maintenance.
NOTE! If the equipment still cannot restore to normal operation state after suggested
When this kind of alarm messages are issued, user need to find the abnormality reason, and then
take corresponding measures to eliminate the alarm message to make the equipment return to
the normal operation state.
2 87T.Alm_Diff Please check the corresponding sampling values and CT secondary circuit to
find out the reason resulting in the abnormality. If sample values of the
3 S1.64REF.Alm
equipment are not correct, please inform the manufacturer or agent for
4 S2.64REF.Alm maintenance, and if it is caused by the failure of the CT secondary circuit or
primary system, please finish troubleshooting according to the operating
5 S3.64REF.Alm
instructions of protection relay.
5 Management
Table of Contents
5.1 Overview
The relay provides some management functions, such as protection sampling, metering, remote
control, signaling, event recording and fault & disturbance recording etc. All these functions can
ensure this relay meets the requirements of a modern power grid.
5.2 Measurement
This relay produces a variety of both directly and calculated power system quantities. There are
two kinds of measurements are supported in this relay: protection sampling and metering. All
these measurands also can be transmitted to the SCADA or gateway through communication. See
Chapter 10 for more information about the communication and protocols.
5.3 Signaling
This relay has some programmable binary inputs which are used to monitor the contact positions
of the corresponding bay, or be used in protection logics or for releasing or blocking the relevant
protective element, or be used in supervision logics calculation for supervision alarm elements
The binary inputs can be configured according to the engineering demands through the
PCS-Explorer configuration tool auxiliary software.
The binary input state change confirmation time of each binary input is configurable according to
practical application through the PCS-Explorer configuration tool auxiliary software, and the
default binary input state change confirmation time of the binary inputs is 10ms.
See Section 8.2.4 for more details about the binary inputs.
This relay supports the event recording functions which can record all the events happened in this
relay. So it is very convenient for the user to view the history records.
This relay provides the fault and disturbance recording facility for recording the sampled values of
the fault and disturbance wave when a fault is occurred in the power system. The 64 latest fault
and disturbance records can be recorded in this relay, and each wave record includes 5 cycles of
pre-fault sampled data and most 150 cycles fault sampled data.
The current and voltage sampled values, the binary input signals and the protection operation
signals are contained in the fault and disturbance wave record, and the analog value sampling rate
is 24 points per cycle. The format of the wave complies with the “COMTRADE” standard.
There are several conditions which can trigger the fault and disturbance recording of this relay.
Each waveform includes the wave recording data both before and after the fault. Each trigger
element operation will extend the wave recording time, until the appointed time delay is over after
the trigger element restores, or until the maximum number of wave recording points is reached.
6 Hardware
Table of Contents
List of Figures
Figure 6.2-1 Rack, back plane and slot allocation of this relay ............................................. 6-3
6.1 Overview
The modular design of this relay allows the relay to be easily upgraded or repaired by a qualified
service person. The faceplate is hinged to allow easy access to the configurable modules, and
back-plugging structure design makes it easy to repair or replace any modules.
There are several types of hardware modules in this relay; each module takes a different part in
this relay. The relevant modules can be selected according to the practical engineering demands.
These modules which are supported in this relay and their module codes are listed as below.
These modules can be freely equipped in the basic enclosure of this relay (see Section 6.2), and
the relationship between the module and the slot number is listed as below.
The following two figures show the front panel and the rear panel of this device.
PCS-9671
1 11 TRANSFORMER RELAY
HEALTHY
2 12
ALARM
3 13
4 14
5 15
6 16
7 17
8 18
9 19
10 20
P
GR
ENT
ESC
01
01 02
02
03
04
03 04
05 06
05
06
07 08 07
08
09 10
09
11 12
10
11
13 14
12
13
15 16
14
15
17 18
16
19 20
17
18
21 22 19
20 PWR+
23 24
21 PWR-
22 GND
25 26
NOTE! The hardware module configuration in above figure is only a demonstration for
explaining how the hardware module is configured. The hardware module configuration
can be different according to the different engineering demands, and the hardware
module configuration of a practical engineering should be taken as final and binding.
NOTE! The No.8 slot is reserved for some special demands, if the present hardware
The basic enclosure of this relay is an electronic equipment rack (see Figure 6.2-1) with an
adequate number of slots for all these modules. The basic rack is equipped with a back plane
(mother board), and the back plane provides some back plane lines for distributing signals within
the enclosure.
The rack, back plane and the slot allocation of this relay is shown as below. The hardware module
configuration is in accordance with the Figure 6.1-3.
Slot: 1 2 3 4 5 6 7 8 9
NR4126/NR4138
NR 4521
NR 4106
NR 44 12
NR 4503
NR 4304
Figure 6.2-1 Rack, back plane and slot allocation of this relay
The human machine interface (HMI) module is installed on the front panel of this device. It is used
to observe the running status and event information on the LCD, and configure the protection
settings and device operation mode. It can help the user to know the status of this relay and
detailed event information easily, and provide convenient and friendly access interface for the user.
Please see Chapter 8 for further details about how to access the human machine interface.
The power supply module is a power supply converter with electrical insulation between input and
output, and a maximum output power of 30W. The power supply module has an input voltage
range as described in Section 2.1.1.1.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device
is in cold reserve.
The power supply module also provides binary outputs which are used to send out some
necessary binary output signals according to the relevant commands from the CPU module, and
these binary outputs only can be used as tripping and closing (protection, auto-recloser or remote
control) outputs by setting the relevant settings.
NR4304
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20 PWR+
21 PWR-
22 GND
NR4304A
A 22-pin connector is fixed on the front side of this module. The terminal definition of the
connector is described as below.
Pin connections on the 22-pin connector of the power supply module NR4304:
the contact [BO_Prot] is a magnetic latched NO contact defined as protection tripping signal
fixedly
The MON module is the central part of this equipment, and contains a powerful microchip
processor and some necessary electronic elements. This powerful processor performs all of the
functions for the relay: the protection functions, the communication management functions. There
are several A/D conversion circuits on this module, which are used to convert the AC analog
signals to corresponding DC signals for fulfilling the demand of the electrical level standard. A
high-accuracy clock chip is contained in this module, it provide accurate current time for this relay.
Protection calculations
The MON module can calculate protective elements (such as overcurrent element, zero
sequence overcurrent etc.) on the basis of the analog sampled values (voltages and currents)
and binary inputs, and then decides whether the device needs to trip or close.
Communication management
The MON module can effectively manage all communication procedures, and reliably send
out some useful information through its various communication interfaces. These interfaces
are used to communicate with a SCADA or a RTU. It also can communicate with the human
machine interface module. If an event is occurred (such as SOE, protective tripping event
etc.), this module will send out the relevant event information through these interfaces, and
make it be easily observed by the user.
Auxiliary calculations
Based on the voltage and current inputs, the MON module also can calculate out the
metering values, such as active power, reactive power and power factor etc. All these values
can be sent to a SCADA or a RTU through the communication interfaces.
Time Synchronization
This module has a local clock chip and an interface to receive time synchronized signals from
external clock source. These signals include PPS (pulse per second) signal and IRIG-B
signal. Basing on the timing message (from SCADA or gateway) and the PPS signal, or
basing on the IRIG-B signal, this module can synchronize local clock with the standard clock.
There are three types of MON modules, and the view of the MON module is shown in Figure
6.5-1.
TX
RX
TX
RX
A 16-pin or 7-pin connector is fixed on the front side of the module. The terminal definition of the
connector is described as below.
Pin connections on the connector of the MON module NR4106A (NR4106AA) and NR4106C (or
NR4106AC):
Pin connections on the connector of the MON module NR4106B (or NR4106AB):
The analog input module can transform high AC input values to relevant low AC output value,
which are suited to the analog inputs of the MON module. The transformers are used both to
step-down the currents and voltages to levels appropriate to the relay’s electronic circuitry and to
provide effective isolation between the relay and the power system. A low pass filter circuit is
connected to each transformer (CT or VT) secondary circuit for reducing the noise of each analog
AC input signal.
NOTE! The rated value of the current transformer is optional: 1A or 5A. The rated value
of the CT must be definitely declared in the technical scheme and the contract.
NOTE! Because the rated value of the current transformer is optional, it is necessary to
check whether the rated value of the current transformer inputs is according to the
demand of the engineering scheme before the device is put into operation.
DANGER! Never allow the current transformer (CT) secondary circuit connected to this
relay to be opened while the primary system is energized. The opened CT secondary
circuit will produce a dangerously high voltage. If this safety precaution is disregarded,
personal death, severe personal injury or considerable equipment damage will occur.
Module NR4412 with 24 pins provides 15 analogue input channels and the view of the analog
input module is shown in Figure 6.6-1.
NR4412
01 02
03 04
05 06
07 08
09 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
A 26-pin or 24-pin connector is fixed on the front side of this module. The terminal definition of the
connector is described as below.
Pin connections on the connector of the analog input module NR4412 with 26 pins:
NOTE! In above table, Ia_S1, Ib_S1, Ic_S1, Ia_S2, Ib_S2, Ic_S2, Ia_S3, Ib_S3, Ic_S3,
NOTE! If users need to configure other analog input, please declare when place an
order.
-- Rated short-time thermal current “Ith” and rated dynamic current “Idyn”:
Performance Verification
Example
Esl = Kalf × Isn × (Rct + Rbn) = kalf × Isn × (Rct + Sbn / Isn2)
Esl’ = k × Ipcf × Isn × (Rct + Rb) / Ipn = k × Ipcf × Isn × (Rct + (Rr + 2RL + Rc)) / Ipn
The binary output module consists of some necessary contact outputs, and the binary outputs are
used as tripping outputs or signal outputs. It can receive tripping commands from the MON
module, and then act according to these commands. It also can output some alarm signals from
the MON module.
There are three types of binary output modules: NR4521A, NR4521C and NR4521D. The view of
the binary output module is shown below.
NR4521
NR4521
A 22-pin connector is fixed on the front side of this module. The terminal definition of the
connector is described as below.
Pin connections on the 22-pin connector of the binary output module NR4521A:
Pin connections on the 22-pin connector of the binary output module NR4521C:
Pin connections on the 22-pin connector of the binary output module NR4521D:
The binary input module contains some binary inputs which are used to monitor the contact
positions of the corresponding bay, and all the binary inputs except last two inputs are
configurable through PCS-Explorer configuration tool. Some of them are used as general purpose
binary inputs, and others are used as special purpose binary inputs. These binary inputs are all
optical isolated binary inputs.
The regular optical isolated binary inputs are used to monitor the position of the regular binary
signals; the special optical isolated binary inputs are used to monitor the position of the special
binary signals, which must be taken into account in the protection and interlock logic calculations
of the MON module.
There are three types of binary input modules: NR4502, NR4503 and NR4504. The view of the
binary input module is shown in Figure 6.8-1.
A 22-pin connector is fixed on the front side of this module. The terminal definition of the
connector is described as below.
Pin connections on the 22-pin connector of the binary input module NR4502:
Pin connections on the 22-pin connector of the binary input module NR4503:
Pin connections on the 22-pin connector of the binary input module NR4504:
The network DSP module is applied in a digitalized substation for leading the current and voltage
from the electronic transformer through a merging unit, and it also can receive or transmit the
GOOSE information. There are two kinds of network DSP module: NR4126 and NR4138.
The network DSP module NR4138 provides up to 6 optical Ethernet ports which can support the
protocol IEC61850-9-2, GOOSE and IEEE1588. It also provides an optical Ethernet port for the
IEC60044-8 data reception, and an optical Ethernet port for the time synchronization.
The network DSP module NR4126 provides 2 optical Ethernet ports which only can support the
GOOSE protocol.
NR4138 NR4126
1 2
3 4
TX
RX
TX
RX
RX
RX
NR4138A NR4126D
7 Settings
Table of Contents
List of Tables
7.1 Overview
Settings are classified to two kinds, protection settings and common settings. Each protection
element has its independent setting menu to configure which are given detailed description in
Chapter “Operation Theory”. Common settings consist of device settings, communication settings
and system settings,
The equipment has 10 setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, common settings are shared by all
protection setting groups, and settings of protection element are set according to secondary
values.
Setting list
50Hz
2 Opt_SysFreq Select system working frequency.
60Hz
NOTE! Symbol ”x” represents some side of transformer or VT/CT type only defined by
user through PCS-Explorer software, which may be “HVS”(HV side), “MVS”(MV side),
etc.
Setting explanation
1. [ Active_Grp]
The current protection setting group number, and total 10 group settings are provided. The device
settings, communication settings and system settings, are common for all protection groups.
[WdgConn_S1] is setting of selecting the winding connection mode of side 1. 0 is for wye winding
and 1 is for delta winding.
[Clk_S2_WRT_S1] is the setting of the relative o’clock of side 2 winding with respect to winding
connection of side 1.
[Clk_S3_WRT_S1] is the setting of the relative o’clock of side 3 winding with respect to winding
connection of side 1.
These logic settings are used to set vector group of transformer for the calculation of differential
protection inner the equipment. Please refer to Section 3.3.1.3 for details.
NOTE! For a two-winding transformer, we treat side 1 as the high voltage side and side 3
as the low voltage side. For a three-winding transformer, we treat side 1 as the high voltage
side, side 2 as the middle voltage side and side 3 as the low voltage side.
[Sx.Un] (n=1, 2, 3) is the setting of the rated primary voltage of the corresponding side of a
transformer. They should be configured as its actual value (i.e. its tap changer in normal position)
to get the high performance of differential protection.
[Sx.I1n] and [Isx.I2n] (x=1, 2, 3) are the rated primary current and the rated secondary current of
the CT of the corresponding side respectively. They should be configured as its actual value. For
example, if current ratio of CT of HV side is 600/5, the following settings should be set:
[S1.I1n]=600A, [S1.I2n] =5A.
The equipment will automatically calculate correction coefficient of each side of transformer with
rated capacity, rated voltage of each side and CT ration of each side, and then do the differential
protection calculation with the corrected currents.
three-winding transformer with three CT inputs, please set the primary current of the
unused CT and the primary rated voltage of the unused side as “0”, the secondary current
of unused CT as “1A” or “5A” and short current input terminals of the unused side of the
equipment.
5. [CTConn]
“0” is wye connection, and phase shift compensation is carried out in the program.
“1” is delta connection, and phase shit compensation is realized by external CT delta connection.
Setting path
detection.
th
Coefficient of 5 harmonics for overexcitation
5 87T.k_Hm5 0.05~0.5 0.001
detection.
0.04~1.2
6 87T.I_Alm 0.001 pu Setting of differential current abnormality alarm
“UTF-8”.
Setting explanation
1. [HDR_EncodeMode]
The setting is to select encoding format of header file .Default value of [HDR_EncodeMode] is
1((i.e. UTF-8 code) and please set it to 0(i.e. GB18030) according to the special requirement.
2. [Opt_Caption_103]
The setting is to select the caption language of IEC103 protocol. If the SCADA is supplied by a
manufacturer of China, the setting is recommended to be set to 1.
0: Current language, i.e. the caption language changes with device LCD language.
3. [Un_BinaryInput]
The setting is used to set the voltage level of binary input module. 24V and 48V can be selected
when low-voltage BI module is equipped and 110V or 220V can be selected when high voltage
BI module is equipped.
Setting path
Main menu -> Settings -> Device Setup -> Device Settings
000.000.000.000~
1 IP_LAN1 IP address of Ethernet port 1.
255.255.255.255
000.000.000.000~
2 Mask_LAN1 Subnet mask of Ethernet port1.
255.255.255.255
000.000.000.000~
3 IP_LAN2 IP address of Ethernet port 2.
255.255.255.255
000.000.000.000~
4 Mask_LAN2 Subnet mask of Ethernet port 2.
255.255.255.255
000.000.000.000~
7 Mask_LAN3 Subnet mask of Ethernet port 3.
255.255.255.255
000.000.000.000~
10 Mask_LAN4 Subnet mask of Ethernet port 4.
255.255.255.255
000.000.000.000~
12 Gateway Gateway of router
255.255.255.255
4800,9600,19200,
15 Baud_RS485A Baud rate of rear RS-485 serial port 1.
38400,57600,115200 bps
4800,9600,19200,
18 Baud_RS485B Baud rate of rear RS-485 serial port 2.
38400,57600,115200 bps
4800,9600,
23 Baud_Printer 19200,38400, 51600, Baud rate of printer port
115200 bps
Conventional
SAS Select the mode of time synchronization of
24 Opt_TimeSyn
Advanced equipment.
NoTImeSyn
Setting explanation
1. [En_LANx] (x= 2, 3, 4)
“1”: enable the IP address of Ethernet port and the corresponding IP address setting is needed to
be set.
“0”: disable the IP address of Ethernet port and the corresponding IP address setting is not needed
to be set.
2. [En_Broadcast]
This setting is only used only for IEC 103 protocol. If NR network IEC103 protocol is used, the
setting must be set as “1”.
3. [Protocol_RS485x] (x=A, B)
The setting is used to select the communication protocol of rear RS-485 serial port X.
1: Reserved
2: Modbus protocol
4. [Format_Measmt]
The setting is used to select the format of measurement data sent to SCADA through IEC103
protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard.
5. [Opt_TimeSyn]
There are four selections for clock synchronization of this device, each selection includes different
time clock synchronization signals shown in following table.
Item Description
PPS(RS-485): Pulse per second (PPS) via RS-485 differential level.
IRIG-B(RS-485): IRIG-B via RS-485 differential level.
Conventional
PPM(DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn].
PPS(DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn].
SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network.
SAS SNTP(BC): Broadcast SNTP mode via Ethernet network.
Message (IEC103): Clock messages through IEC103 protocol.
IEEE1588: Clock message via IEEE1588.
Advanced IRIG-B(Fiber): IRIG-B via optical-fibre interface.
PPS(Fiber) PPS: Pulse per second (PPS) via optical-fibre interface.
When no time synchronization signal is connected to the equipment, please select
NoTimeSyn
this option and the alarm message [Alm_TimeSyn] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by device, but “Advanced” mdoe
is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn] may be
issued to remind user loss of time synchronization signals.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional”mode is slected, if there is
no conventional clock synchronization signal, “SAS”mode will be enabled automatically with
the alarm signal [Alm_TimeSyn] being issued simultaneously.
3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without
NOTE! The clock message via IEC103 protocol is invalid when the device receives the
6. [IP_Server_SNTP]
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
7. [OffsetHour_UTC], [OffsetMinute_UTC]
When the IEC61850 protocol is adopted in substations, if the time tags of communication
messages are required according to Universal Time Coordinated (UTC), the two settings are
used to set the local time of a country or area where the relay is installed. If there is no such a
requirement, the two settings must be set as “0”.
Example 1: In China where UTC offset is UTC +8:00, [OffsetHour_UTC] and [OffsetMinute_UTC]
should be set as “8hrs” and “0min” respectively.
Example 3: In Nepal where UTC offset is UTC +5:45, [OffsetHour_UTC] and [OffsetMinute_UTC]
should be set as “+5hrs” and “45min” respectively.
st nd rd th th
Time zone GMT zone East 1 East 2 East 3 East 4 East 5
Setting 0 1 2 3 4 5
th th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11
Setting 6 7 8 9 10 11
th st nd rd th th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5
Setting -12/12 -1 -2 -3 -4 -5
th th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11
Setting -6 -7 -8 -9 -10 -11
Setting Path
Main Menu -> Settings -> Device Setup -> Comm Settings
Table of Contents
List of Figures
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-3
Figure 8.1-5 Rear view and terminal definition of NR4106 ..................................................... 8-5
Figure 8.2-4 LCD display of the protection secondary measurement values ...................... 8-9
Figure 8.2-5 LCD display of the status of the general binary inputs ................................... 8-12
Figure 8.2-10 LCD display of the selection of setting group number ................................. 8-18
Figure 8.2-11 LCD display of the selected protection settings ............................................ 8-18
Figure 8.2-12 LCD display of the change of active group .................................................... 8-19
Figure 8.4-1 Password input interface for control operation ............................................... 8-28
Figure 8.4-2 Password input interface for modifying settings ............................................. 8-28
List of Tables
8.1 Overview
Furthermore, all above functions can be realized in a remote terminal with special software
through a communication bus via a RS-485 port or an Ethernet port.
This chapter will describe human machine interface (HMI), menu tree and LCD display of the
equipment. In addition, how to input settings using keypad is described in detail.
8.1.1 Design
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user. The HMI module helps to draw your
attention to something that has occurred which may activate a LED or a report displayed on the
LCD. Operator can locate the data of interest by navigating the keypad.
PCS-9671
1 11 TRANSFORMER RELAY
HEALTHY
2 12
ALARM
3 13
4 14
5 15
6 16
7 17
8 18
9 19
10 20
P
GR
ENT
ESC
ENT
ESC
01 HEALTHY 11
01 HEALTHY
02 ALARM 12
03 13
Recommended 02 ALARM
04 14
05 15 03 TRIP
06 16
LED_03 is configured as shown in the right
07 17
side, and other LEDs (LED_04~LED_20)
08 18 are configured according to the practical
09 19 requirement through the PCS-Explorer
10 20 software.
NOTE!
The “HEALTHY” LED can only be turned on by supplying power to this device again
or rebooting this device.
“ALARM” LED is lit as long as alarm exists. When alarm signals disappear, it will be
distinguished. However, when [87T.Alm_CTS] is issued and “ALARM” LED is lit, the
alarm signal can be reset and “ALARM” LED can be extinguished only when the
failure is removed and energize the binary input [BI_RstTarg] or receiving reset message
from SAS or gateway.
The “TRIP” LED is lit once any protection element operates and remains lit even after
the trip command goes off. “TRIP” LED and corresponding latched binary outputs can
be reset by energizing binary input [BI_RstTarg] or receiving reset message from SAS
or gateway.
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explore)
after connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-Explore). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “Settings→Device Setup→Communication Settings”, it should be
ensured that the protection device and PC are in the same network segment. For example, setting
the IP address and subnet mask of network A. (using network A to connect with PC)
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled.
NR4106
NET A
NET B
NR4106A
or NR4106AA
NOTE! If using other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2]
8.2.1 Overview
In this section, the main layout of the menu which is shown on the LCD of the local human
machine interface (HMI) will be described in detail.
S 2011-06-25 11:18:25
Ida 0.000 pu
Idb 0.000 pu
Idc 0.000 pu
Ira 0.000 pu
Irb 0.000 pu
Irb 0.000 pu
Addr 188 Group 01
The first line shows the time synchronization state and the current time of this relay. The sign “S”
on left-top side means this relay receive the clock synchronization signal correctly; if there has
nothing on left-top side, it means the time synchronization is not correct. The current time format of
this relay is “yyyy-mm-dd hh:mm:ss”.
The middle part of the LCD shows the measurement for the protection.
The last line shows the last section of the IP address and the setting group number.
When the default screen is being shown, press key “▲” to enter the main menu of this relay.
Measurements
Status
Records
Settings
Print
Local Cmd
The following figure shows the menu tree structure of this device.
MAIN MENU
Measurements
Print
Measurements 1
Device Info
Secondary Values
System Settings
Records
Local Cmd
Disturb Records
Superv Events Reset Target
Control Logs
Clear Records Information
Version Info
Settings Board Info
System Settings
Test
Prot Settings
Copy Settings
Clock
Language
Press key “▲”, “▼”, “◄” or “►” to select a submenu and the press key “ENT” to show the details.
Purpose:
This menu is used to view the measured values including current, voltage, phase angle and other
calculated quantities.
Access approach:
Move cursor to the item “Measurements” and press key “ENT” to enter its submenu after entering
the main menu of this device.
Here take viewing the secondary protection measurement values as an example to introduce the
operating steps of viewing the measurements.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Measurements” and press key
“ENT” to enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Measurements1” and press key
“ENT” to enter this submenu.
4. Press key “▲” or “▼” to locate the cursor on the submenu “Secondary Values” and press
key “ENT” to enter this submenu.
Secondary Values
Ida 1.001 Ie
Idb 1.002 Ie
Idc 1.003 Ie
Ira 0.001 Ie
Irb 0.001 Ie
Irc 0.002 Ie
Id2 0.002 Ie
The following tables show all the measurement values of this relay.
Purpose:
This menu is used to view the state of the binary inputs, binary outputs and supervision alarm
elements of this relay.
Access approach:
Move cursor to the item “Status” and press key “ENT” to enter its submenu after entering the main
menu of this device.
Here take viewing the status of the general binary inputs as an example to introduce the operating
steps of viewing the status.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Status” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Inputs” and press key “ENT” to
enter this submenu.
4. Press key “▲” or “▼” to locate the cursor on the submenu “Contact Inputs” and press key
“ENT” to enter this submenu.
Contact Inputs
BI_01 0
BI_02 0
BI_03 0
BI_04 0
BI_05 0
BI_06 0
BI_07 0
Figure 8.2-5 LCD display of the status of the general binary inputs
The following tables show all the binary signal status of this relay.
The virtual signal indicating that tripping command is sent by relay, and
2 Sig_52bLock
the signal will not restore until the relay receives a reset command.
3 BO_01 The status of the binary output “BO_01”
4 BO_02 The status of the binary output “BO_02”
5 BO_03 The status of the binary output “BO_03”
6 BO_04 The status of the binary output “BO_04”
7 BO_05 The status of the binary output “BO_05”
8 BO_06 The status of the binary output “BO_06”
9 BO_07 The status of the binary output “BO_07”
10 BO_08 The status of the binary output “BO_08”
11 BO_09 The status of the binary output “BO_09”
12 BO_10 The status of the binary output “BO_10”
13 BO_11 The status of the binary output “BO_11”
14 BO_12 The status of the binary output “BO_12”
15 BO_Rev01 The status of the binary output “BO_Rev01”
16 BO_Rev02 The status of the binary output “BO_Rev02”
17 BO_Rev03 The status of the binary output “BO_Rev03”
18 BO_Rev04 The status of the binary output “BO_Rev04”
19 BO_Rev05 The status of the binary output “BO_Rev05”
Please refer to Section 4.2.1 and Section 4.2.2 for detailed alarm messages.
Purpose:
This menu is used to view all kinds of history records, such as the protection tripping reports, the
supervision alarm records and the binary state change records etc.
Access approach:
Move cursor to the item “Records” and press key “ENT” to enter its submenu after entering the
main menu of this device.
The history fault report stores the trip elements, trip time and waveform of a selected trip report.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Records” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Disturb Records” and press key
“ENT” to enter this submenu. If there is no report in the selected submenu, it will show “No
Report!” on the LCD.
4. Press key “+” or “-” to view the expected history fault report.
The first line shows the report title and the sequence number of the history trip report, and the
second line shows the operation time of the history trip report. Other lines show the protection
elements and fault information one by one according to the relative time sequence. The fault
information includes faulty phase, maximum phase current, differential current, etc. For more
information about the protection elements and fault information, see Section 8.3.1.
The history alarm report stores the alarm elements and alarm time.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Records” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Superv Events” and press key
“ENT” to enter this submenu. If there is no report in the selected submenu, it will show “No
Report!” on the LCD.
4. Press key “+” or “-” to view the expected history alarm report.
The first line shows the report title and the sequence number of the history alarm report, and
the second line shows the alarm time of the history alarm report. Other lines show the alarm
elements and state change information one by one. For more information about the alarm
elements, see Section 8.3.2.
The history binary state change report stores the binary signal name and state change time.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Records” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “IO Events” and press key “ENT”
to enter this submenu. If there is no report in the selected submenu, it will show “No Report!”
on the LCD.
4. Press key “+” or “-” to view the expected history binary state change report.
IO Events NO.98
2011-02-08 15:18:48:198ms
FD.Pkp 0->1
The first line shows the report title and the sequence number of the history binary input state
change report, and the second line shows the binary state change time of the history binary
state change report. Other lines show the binary state change information one by one. For
more information about the binary signals, see Section 8.2.4.1 .
The history user operation report stores the user operation information and user operation time.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Records” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Device Logs” and press key
“ENT” to enter this submenu.
4. Press key “+” or “-” to view the expected history user operation report.
The first line shows the report title and the sequence number of the history user operation
report, and the second line shows the user operation time of the history user operation report.
Other lines show the user operation information.
The submenu “Clear Records” is used to clear all the history reports except the user operation
report (in submenu “Device Logs”).
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Records” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Clear Records” and press key
“ENT” to clear all the history reports.
Purpose:
The menu is used to view and modify the settings and parameters of this device. Please read
Chapter 7 for the details about the all the settings.
Access approach:
Move cursor to the item “Settings” and press key “ENT” to enter its submenu after entering the
main menu of this device.
Here take viewing the overcurrent protection settings as an example to introduce the operating
steps of viewing the setting.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Settings” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Prot Settings” and press key
“ENT” to enter this submenu.
4. Press key “▲” or “▼” to locate the cursor on the submenu “OC Settings” and press key
“ENT” to enter the selecting interface of the setting group number.
5. Press key “+” or “-” to select the expected setting group number and then press key “ENT” to
show the settings of the selected group.
OC Settings
Active Group: 01
Selected Group: 01
OC Settings
S1.50/51P.I2_Set 15.000 A
S1.50/51P.t_Op 0.100 s
S1.50/51P.En 1
S1.50/51P.OutMap 00000000
S2.50/51P.I2_Set 15.000 A
S2.50/51P.t_Op 0.100 s
S2.50/51P.En 1
The settings can be modified through the local HMI to meet the demand of practical engineering.
Operating steps:
1. Refer the Section 8.2.6.1 to locate the cursor on the expected setting, and then press key
“ENT” to enter the setting modification state.
2. Press key “+” or “-” to modify a selected setting, and press key “ESC” to return to the setting
interface after the selected setting modification is finished.
3. Repeat Step “1” and “2” to modify other settings which need to be modified.
4. After finishing the setting modification, press key “ESC” to prompt the user whether to save
the settings. Select “Yes” to confirm to save the modified settings. Then the password input
interface is shown on the LCD. Input the correct password and press key “ENT” to confirm the
modification. If the modification is given up, press key “ESC” to exit the modification operation.
5. After confirming the setting modification, it will show “Saving Settings…” on the LCD. Then the
device will restart, and the new settings will be in service.
NOTE! It is necessary to certify whether the modified settings are correct absolutely
The last submenu “Copy Settings” is used to copy the active settings to another group.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Settings” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Copy Settings” and press key
“ENT” to enter the interface for copying settings.
4. Press key “+” or “-” to select the expected setting group number and then press key “ENT” to
show the password input interface.
5. Input the correct password and then press key “ENT” to copy the settings of the active group
to the selected group.
There are two methods which are used to switch one setting group to another group. One method
is to modify the setting [Active_Grp] in submenu “System Settings”. Another method is detailed
as following operating steps.
Operating steps:
1. Press key “GRP” to enter the setting group switch interface in the default displaying situation.
2. Press key “+” or “-” to select the expected setting group number and then press key “ENT” to
show the password input interface.
3. Input the correct password and then press key “ENT” to copy the settings of the active group
to the selected group.
Active Group: 01
Change to Group: 02
Purpose:
The menu is used to print the relevant information of this device. A printer is needed, and the
EPSON® LQ-300K is recommended.
Access approach:
Move cursor to the item “Print” and press key “ENT” to enter its submenu after entering the main
menu of this device.
Here take printing the overcurrent protection settings as an example to introduce the operating
steps of print a selected item.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Print” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Settings” and press key “ENT” to
enter this submenu.
4. Press key “▲” or “▼” to locate the cursor on the submenu “Prot Settings” and press key
“ENT” to enter this submenu.
5. Press key “▲” or “▼” to locate the cursor on the submenu “OC Settings” and press key
“ENT” to enter the selecting interface of the setting group number.
6. Press key “+” or “-” to select the expected setting group number and then press key “ENT” to
print the settings of the selected group.
The submenu “Cancel Print” is used to cancel the present printing content.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Print” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Cancel Print” and press key
“ENT” to cancel the present printing content. The information “Canceling Print…” is shown on
the LCD.
Purpose:
This menu is used to operate this device locally, such as signal resetting, triggering an
oscillograph, etc.
Access approach:
Move cursor to the item “Local Cmd” and press key “ENT” to enter its submenu after entering the
main menu of this device.
The submenu “Reset Target” is used to reset the signals and outputs.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Local Cmd” and press key “ENT”
to enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Reset Target” and press key
“ENT” to restore all the signals and relevant outputs of this relay.
The submenu “Trig Oscillogram” is used to trigger this relay to store a waveform.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Local Cmd” and press key “ENT”
to enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Trig Oscillograph” and press key
“ENT” to trigger an oscillogram.
Purpose:
This menu is used to view program version information and module information of this relay.
Access approach:
Move cursor to the item “Information” and press key “ENT” to enter its submenu after entering the
main menu of this device.
The program version information of this relay can be known through this menu.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Information” and press key “ENT”
to enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Version Info” and press key
“ENT” to show the program version information.
Version Info
NR
Transformer Relay
PCS - 9671
Version 1. 00
Program Time 2011 - 05 - 28
Program CRC 3 AB 58 C 98
The first line shows the title of this interface, other lines show the information of the board
information, including the manufacturer name, the device name, the device code, the program
version, the program creation time and the program CRC code.
NOTE! It is only an example for explaining the software version menu. The practical
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Information” and press key “ENT”
to enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Board Info” and press key “ENT”
to show the board information.
Board Info
NO Type Stat Conf
01 NR4106 (√) --
06 NR4521 (√) (√)
07 NR4501 (√) (√)
09 NR4304 (√) --
The first line shows the title of this interface, other lines show the information of the board
information, including the slot sequence number, the module type, the module operation state and
the module configuration state.
Purpose:
This menu is used to test particular functions of the device, such as testing binary signals and
testing binary outputs. It can provide convenience for the communication test and the operation
electrical circuit.
Access approach:
Move cursor to the item “Test” and press key “ENT” to enter its submenu after entering the main
menu of this device.
1 Device Test To test the binary signals, binary outputs and measurements etc.
2 Internal Signal This submenu is only reserved for the manufacturer
The submenu “Prot Elements”, “Superv Events” and “IO Events” have following submenus.
The binary signals include the protective element operation signals, supervision alarm signals and
binary state change signals.
Here take test the protective element operation signal as an example to introduce the operating
steps of communication test of the binary signals.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Test” and press key “ENT” to
enter this submenu.
3. Press key “▲” or “▼” to locate the cursor on the submenu “Device Test” and press key “ENT”
to enter this submenu.
4. Press key “▲” or “▼” to locate the cursor on the submenu “Prot Elements” and press key
“ENT” to enter this submenu.
5. Press key “▲” or “▼” to locate the cursor on the submenu “Select Test” and press key “ENT”
to show all the protective elements.
6. Press key “▲” or “▼” to locate the cursor on a selected protective element and then press key
“ENT” to create a binary signal.
NOTE! The submenu “All Test” is used to test all the binary signals automatically.
Purpose:
Access approach:
Move cursor to the item “Clock” and press key “ENT” to enter the clock modification interface after
entering the main menu of this device.
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Clock” and press key “ENT” to
enter the clock modification interface.
3. Press key “▲” or “▼” to locate the cursor on a selected item and press key “+” or “-” to modify
the selected item.
4. After finishing the clock modification, press key “ENT” to confirm the modification.
Clock
Year: 2011
Month: 01
Day: 23
Hour: 18
Minute: 28
Second: 58
Purpose:
Operating steps:
1. Press key “▲” to enter the main menu in the default displaying situation.
2. Press key “▲” or “▼” to locate the cursor on the submenu “Language” and press key “ENT”
to enter the language modification interface.
4. After finishing the language modification, press key “ENT” to confirm the modification.
The first line shows the report title and the sequence number of the history trip report, and the
second line shows the operation time of the history trip report. Other lines show the protection
elements and fault information one by one according to the relative time sequence. The fault
information includes fault phase, maximum fault value and minimum fault value.
NOTE! In case more than one protection element has operated, the relevant report will
be displayed alternatively one by one according to time sequence on the LCD. And the
fault information is listed after all the protection elements.
The trip report will keep being displayed on LCD until an acknowledgement is received by pressing
the key “ENT”+“ESC”, by energizing the binary input [BI_RstTarg] or by executing the submenu
“Reset Target”. The default display then appears on LCD and LED “TRIP” is turned off.
See Chapter 3 for more details about the protection operation theory.
If there is any abnormality in the operation or any firmware error is detected by the self-diagnostics
of this relay, an alarm report will be displayed instantaneously on the LCD. Therefore, default
display will be replaced by the alarm report. The format of the alarm report is shown as below.
Alarm Infor
Alm_Device
87T.Alm_CTS
The first line shows the alarm report title, and then shows the alarm elements one by one
according to the time sequence.
The alarm report will keep being displayed on LCD until the relevant alarm situation is restored to
normal state. It means that this relay does not detect any alarm situation. The default display then
appears on LCD and LED “ALARM” is off. The LED “ALARM” will not be on if either of the alarm
signals [Fail_Device] and [Fail_Setting] is issued.
Please see Section 4.4 for all alarm messages and handle suggestions for more details about the
alarm element operation theory. There are 8 alarm messages [Alm_Rev01]~[Alm_Rev08] for user
programming.
Hardware circuit and operation condition of this device are self-supervised continuously. If any
abnormal condition is detected, information or report will be displayed and a corresponding alarm
will be issued.
A common abnormality may block a certain number of protection functions while other functions
can still work.
However, if a serious hardware failure or abnormality is detected, all protection functions will be
blocked and the LED “HEALTHY” will be off.
When hardware failure is detected, all protection functions will be blocked and the corresponding
alarm signal will be issued. This relay can not work normally in such a situation and a manual
maintenance is required to fix the failure.
NOTE! If this device is blocked or alarm signal is issued during operation, do please find
out its reason by help of the history reports. If the reason can not be found on site, please
inform the manufacturer NR Electric Co., Ltd.
For the safety purpose, this device provides password security function for modifying the settings
and doing a control operation.
Only the input password is correct, the relevant operation can be done. If the input password is
correct, the relevant operation can be done; otherwise, it will show the input interface on the LCD
to prompt the user to input the password again.
The following figure shows the password input interface for control operation.
Password:
000
The password for modifying settings is fixed, and it is press key “+”, “◄”, “▲” and “-” in sequence.
The following figure shows the password input interface for modifying settings.
Password:
----
9 Configurable Function
Table of Contents
9 Configurable Function ................................................................... 9-a
9.1 Overview .......................................................................................................... 9-1
9.2 Introduction on PCS-Explorer software ........................................................ 9-1
9.3 Configurable Signals ...................................................................................... 9-2
9.3.1 Binary/GOOSE Input signals ............................................................................................... 9-2
List of Tables
Table 9.3-1 Configurable binary input signal list ..................................................................... 9-2
9.1 Overview
After function configuration is finished, disabled protection function will be hidden in the device and
in setting configuration list of PCS-Explorer Software. The user can select to show or hide some
setting by this way, and modify the setting vale.
Please refer to the instruction manual “PCS-Explorer Auxiliary Software” for details.
Overall functions:
NOTE: When users configure a binary input or GOOSE input signal, the signal is the
output.
NOTE: When users configure a binary output signal, the signal is the input.
All configurable LED indicators are list below, and the value of unconfigurable signal is the
corresponding default value.
10 Communication
Table of Contents
List of Figures
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance ....................... 10-10
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance ..................... 10-11
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances .................. 10-12
10.1 Overview
This section outlines the remote data communication interfaces of this relay. The relay can support
several protocols: IEC60870-5-103, IEC61850 and DNP3.0. Setting the relevant communication
parameter can select the expected protocol (see Section 7.3).
The EIA RS-485 standardized interfaces are isolated, as well as the Ethernet interfaces, and are
suitable for permanent connection whichever protocol is selected. The advantage of this type of
connection is that up to 32 relays can be “daisy chained” together using a simple twisted pair
electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The protocol provided by the relay is indicated in the relay’s “Comm Settings” submenu (see
Section 7.3). By using the keypad and LCD, configure the relevant communication protocol
parameters, the corresponding protocol and will be selected.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be noted that there is no agreed definition of
which terminal is which. If the master is unable to communicate with the product, and the
communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (see Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
NOTE!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will
result in an excessive bias voltage that may damage the devices connected to the bus.
As the field voltage is much higher than that required, NR can not assume responsibility for
any damage that may occur to a device connected to the network as a result of incorrect
application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic inputs)
as this may cause noise to be passed to the communication network.
A brief explanation of IP and network submask is made as below. There are four sections for an IP
address.
xxx.xxx.xxx.xxx
Section 1
Section 2
Section 3
Section 4
Where:
The network communication address for IEC60087-5-103 has above relationship described as an
equation with section 3 and section 4 of the IP address.
It is recommended to use 4-pair screened twisted category 5E cable as the communication cable.
A picture is shown below.
Each device is connected to an exchanger via communication cable and thereby to form a star
structure network. Dual-network is recommended in order to increase reliability. The SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
SCADA
Switch: Net A
Switch: Net B
……
The IEC60870-5-103 interface is a master/slave interface with this relay as the slave device.
The following IEC60870-5-103 facilities are supported by this interface: initialization (reset), time
synchronization, event record extraction, general interrogation, cyclic measurements, general
commands and disturbance records.
The unattached Ethernet ports are available for IEC60870-5-103 in this relay. The transmission
speed is 100Mbit/s.
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
Whenever the relay has been powered up, or if the communication parameters have been
changed, a reset command is required to initialize the communications. The relay will respond to
either of the two reset commands (Reset CU or Reset FCB), the difference is that the Reset CU
will clear any unsent messages in the relay’s transmit buffer.
The relay will respond to the reset command with an identification message ASDU 5, the COT
(Cause Of Transmission) of this response will be either Reset CU or Reset FCB depending on the
nature of the reset command.
In addition to the above identification message, if the relay has been powered up it will also
produce a power up event.
If the clock is synchronized using the IRIG-B input then it will not be possible to set clock by using
the IEC60870-5-103 interface. An attempt to set the time via the interface will cause this relay to
create an event with the current date and time taken from the IRIG-B synchronized internal clock.
function type (FUN) and information number (INF). This relay can support ASDU 1, ASDU 2,
ASDU 40 and ASDU 41, the cause of transmission (COT) is “1”.
ASDU 1, time-tagged message: alarm messages, special purpose binary input state change
messages.
ASDU 2, time-tagged message with relative time: tripping messages and fault detector pickup
messages.
ASDU 40, single point information: general binary input state change messages.
ASDU 41, single point information with time-tagged: sequence of event (SOE) messages.
The relay will respond to this GI command with an ASDU 44 message, the cause of transmission
(COT) of this response is 9.
Referring the IEC60870-5-103 standard can get the enough details about general interrogation.
If the relay receives one of the command messages correctly, it will respond with an ACK message,
and then send a message which has the same ASDU data with the control direction message in
the next communication turn.
Two supported type identifications are ASDU 21 and ASDU 10. For more details about generic
functions, see the IEC60870-5-103 standard.
INF Semantics
INF Semantics
240 Read headings of all defined groups
241 Read values or attributes of all entries in one group
243 Read directory of a single entry
244 Read value or attribute of a single entry
245 General interrogation of generic data
248 Write entry
249 Write entry with confirmation
250 Write entry with execution
251 Write entry abort
INF Semantics
240 Read headings of all defined groups
241 Read values or attributes of all entries of one group
243 Read directory of a single entry
244 Read value or attribute of a single entry
245 End of general interrogation of generic data
249 Write entry with confirmation
250 Write entry with execution
251 Write entry aborted
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in the standard of IEC60870-5-103.
The IEC60870-5-103 interface over Ethernet is a master/slave interface with the relay as the slave
device. It is properly developed by NR too. All the service of this relay is based on generic
functions of the IEC60870-5-103. The following table lists all the group number of this relay. And
this relay will send all the relevant information about group caption to the SAS or RTU after
establishing a successful communication link.
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment -
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment –
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment –
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
Please note that gateways can be considered as clients and servers subject to the communication
object. When retrieving data from IEDs within the substation, the gateways are considered as
servers whereas transmitting data to control centers, the gateways are considered as clients.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the individual ICD files and the SSD file. Moreover, add
communication system parameters (MMS, GOOSE, control block, SV control block) and the
connection relationship of GOOSE and SV to SCD file.
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
Note! Hereinafter, the normal operation status of net means the physical link and TCP
link are both ok. The abnormal operation status of net means physical link or TCP link is
broken.
1) Mode 1: Dual-net full duplex mode sharing the same RCB instance
Client Client
TCP Link
MMS Link
Figure 10.5-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of mode 1, IED provides the same MMS service for Net A and Net B. If
one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the working
mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In mode 1, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Client Client
TCP Link
Figure 10.5-2 Dual-net hot-standby mode sharing the same RCB instance
In mode 2, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
Note! In mode 1 and mode 2, Net A IED host address and Net B IED host address must be
the same. E.g.: if the subnet mask is 255.255.0.0, network prefix of Net A is 198.120.0.0,
network prefix of Net B is 198.121.0.0, Net A IP address of the IED is 198.120.1.2, and
then Net B IP address of the IED must be configured as 198.121.1.2, i.e.: Net A IED host
address =1x256+2=258, Net B IED host address =1x256+2=258, Net A IED host address
equals to Net B IED host address.
Client Client
TCP Link
MMS Link
Figure 10.5-3 Dual-net full duplex mode with 2 independent RCB instances
In mode 3, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of one net will not affect the other net at all.
In this mode, 2 report instances are required for each client. Therefore, the IED may be unable to
provide enough report instances if there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion:
In mode 3, the IED may be unable to provide enough report instances if too many clients are
applied on site.
For the consideration of client treatment and IED implementation, mode 1 (Dual-net full duplex
mode sharing the same report instance) is recommended for MMS communication network
deployment.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
information about the IED logical device.
The GGIO logical node is available in the PCS-9000 series relays to provide access to digital
status points (including general I/O inputs and warnings) and associated timestamps and quality
flags. The data content must be configured before the data can be used. GGIO provides digital
status points for access by clients. It is intended that clients use GGIO in order to access digital
status values from the PCS-9000 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the others in MMXN, MSQI and so on. Each MMXU logical node provides data
from an IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
The following list describes the protection elements for all PCS-9000 series relays. The specified
relay will contain a subset of protection elements from this list.
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For the
PCS-9000 series relays protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and it also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings, system settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-9000 series relays, besides the logical nodes we describe above, there are some other
logical nodes below in the IEDs:
MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as r.m.s. values for current and voltage or power flows out of the acquired voltage and
current samples. These values are normally used for operational purposes such as power flow
supervision and management, screen displays, state estimation, etc. The requested accuracy for
these functions has to be provided.
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or alternatively,
any combination of “operate” outputs of protection functions may be combined to a new “operate”
of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System” (IEC
60255-24). All enabled channels are included in the recording, independently of the trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
TrgOps: Trigger options. The following bits are supported by the PCS-9000 series
relays:
- Bit 1: Data-change
- Bit 4: Integrity
OptFlds: Option Fields. The following bits are supported by the PCS-9000 series
relays:
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-9000 device.
10.5.5.3 Timestamps
The Universal Time Coordinated (UTC for short) timestamp associated with all IEC61850 data
items represents the latest change time of either the value or quality flags of the data item
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link
settings in device.
The PCS-9000 series relays support IEC61850 Generic Object Oriented Substation Event
(GOOSE) communication. All GOOSE messages contain IEC61850 data collected into a dataset.
It is this dataset that is transferred using GOOSE message services. The GOOSE related dataset
is configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-9000 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Client-Server Roles
SCSMS Supported
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M1 Logical device C2 C2 Y
M2 Logical node C3 C3 Y
M3 Data C4 C4 Y
M4 Data set C5 C5 Y
M5 Substitution O O Y
Reporting
M7-1 sequence-number Y Y Y
M7-2 report-time-stamp Y Y Y
M7-3 reason-for-inclusion Y Y Y
M7-4 data-set-name Y Y Y
M7-5 data-reference Y Y Y
M7-6 buffer-overflow Y Y Y
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M16 Time M M Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
Server
S1 ServerDirectory M Y
Application association
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O
S14 CreateDataSet O
S15 DeleteDataSet O
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Reporting
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M Y
S24-3 data-update M Y
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M Y
S27-3 data-update M Y
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
S30 GetLCBValues O
S31 SetLCBValues O
Log
S32 QueryLogByTime O
S33 QueryLogAfter O
S34 GetLogStatusValues O
S35 SendGOOSEMessage M Y
S36 GetGoReference O
S37 GetGOOSEElementNumber O Y
S38 GetGoCBValues M Y
S39 SetGoCBValuess M Y
Control
S51 Select O
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O
File transfer
S58 SetFile O Y
S59 DeleteFile O
Time
SNTP M Y
The PCS-9000 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
10.6.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 2 of the protocol, plus some of
the features from level 3. The DNP3.0 communication uses the Ethernet ports at the rear of this
relay.
1. Supported qualifiers
The protection operation signals, alarm signals and binary input state change signals are
transported respectively according to the variation sequence in above table.
Object 2, SOE
If the master qualifier is “0x07”, the slave responsive qualifier is “0x27”; and if the master
qualifier is “0x01”, “0x06” or “0x08”, the slave responsive qualifier is “0x28”.
The measurement values are transported firstly, and then the relay measurement values are
transported.
The master adopts the “Object 60” for the Class 0 data request and the variation is “0x01”.
The slave responds with the above mentioned “Object 1”, “Object 30” and “Object 40” (see
“Supported objects and variations” in Section 10.6.4.3).
The master adopts the “Object 60” for the Class 1 data request and the variation is “0x02”.
The slave responds with the above mentioned “Object 2” (see “Supported objects and
variations” in Section 10.6.4.3).
The master adopts the “Object 60” for the multiple object request and the variation is “0x01”,
“0x02”, “0x03” and “0x04”.
The slave responds with the above mentioned “Object 1”, “Object 2”, “Object 30” and “Object 40”
see “Supported objects and variations” in Section 10.6.4.3.
11 Installation
Table of Contents
List of Figures
Figure 11.6-1 Dimensions of this relay and the cut-out in the cubicle (unit: mm) ............. 11-3
Figure 11.6-2 Demonstration of plugging a board into its corresponding slot .................. 11-4
Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7
11.1 General
The equipment must be shipped, stored and installed with the greatest care.
Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
Modules and units may only be replaced by correspondingly trained personnel. Always observe
the basic precautions to avoid damage due to electrostatic discharge when handling the
equipment.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
DANGER! Only insert or withdraw the power supply module while the power supply is
switched off. To this end, disconnect the power supply cable that connects with the power
supply module.
WARNING! Only insert or withdraw other modules while the power supply is switched off.
WARNING! The modules may only be inserted in the slots designated in Section 6.2.
WARNING! Industry packs and ribbon cables may only be replaced or the positions of
Should boards have to be removed from this relay installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
Only hold electronic boards at the edges, taking care not to touch the components.
Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Check that the consignment is complete immediately upon receipt. Notify the nearest NR
Company or agent, should departures from the delivery note, the shipping papers or the order be
found.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Section 2.1.3.
The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this relay is mounted in cubicles).
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
WARNING! Excessively high temperature can appreciably reduce the operating life of
this relay.
This relay is made of a single layer 4U height 9.5" chassis with 7 connectors on its rear panel (See
Figure 6.1-3). The following figure shows the dimensions of this relay for reference in mounting.
263.96 224.80
246.36 197.50
PCS-9671
1 11 TRANSFORMER RELAY
HEALTHY
2 12
ALARM
3 13
4 14
5 15
101.60
177.00
6 16
7 17
8 18
9 19
10 20
GR P
ENT
ESC
246.36 ± 0.10
226.00
4- Φ6.8
101.60 ±0.10
224.80
178.00
Figure 11.6-1 Dimensions of this relay and the cut-out in the cubicle (unit: mm)
NOTE! It is necessary to leave enough space top and bottom of the cut-out in the cubicle
As mentioned in Chapter 6, up to nine modules are installed in the enclosure of this relay, and
these modules must be plugged into the proper slots of this relay respectively. The safety
instructions must be abided by when installing the boards, please see Section 11.2 for the details.
Figure 11.6-2 shows the installation way of a module being plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
NOTE! All these precautions can only be effective if the station ground is of good quality.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTE! If the above conditions are not fulfilled, there is a possibility of the cubicle or parts
of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTE! For metallic connections please observe the voltage difference of both materials
The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There are some ground terminals on some connectors of this relay, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (see Figure 11.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
Power supply, binary inputs & outputs: brained copper cable, 1.5mm2 ~ 2.5mm2
The following figure shows the glancing demo about the wiring for the electrical cables.
01 02
Tighten
03 04
05 06
01
07 08
Figure 11.7-4 Glancing demo about the wiring for electrical cables
DANGER! Never allow the current transformer (CT) secondary circuit connected to this
equipment to be opened while the primary system is live. Opening the CT circuit will
produce a dangerously high voltage.
Relevant information and sections about the modules and the connectors of the relay are
described in Chapter 6. Referring the relevant sections can help to wire correctly and effectively.
The typical wiring of this relay is shown as below, all the configurable binary inputs and binary
output adopt the default definition in the factory.
Side 2
*
A
CB2 *
B
*
*
C
Side 1 Side 3
* * A
A
*
CB3
*
CB1
B B
* *
C C
*
0401 0402 0403 0404 0405 0406 0407 0408 0409 0410 0411 0412 0420 0419 0424 0423 0422 0421 0414 0413 0416 0415 0418 0417
Ia_S1 Ian_S1 Ib_S1 Ibn_S1 Ic_S1 Icn_S1 Ia_S2 Ian_S2 Ib_S2 Ibn_S2 Ic_S2 Icn_S2 I0n_S1 I0_S1 I0n_S3 I0_S3 I0n_S2 I0_S2 Ian_S3 Ia_S3 Ibn_S3 Ib_S3 Icn_S3 Ic_S3
Current Inputs
NR4412
BI_01+ 0701
Ethernet1 BI_01- 0702
BI_02+ 0703
BI_02- 0704
Ground at
remote device Ethernet2 BI_03 0705
BI_04 0706
0101 BI_05 0707
0102 A BI_06 0708
0103 B BI_07 0709
NR4503
0104 SGND BI_08 0710
NR4106
0910 0610
0911 BO_Trp02 0611
0912 BO_Trp12 0612
BO_Trp03
0913 0613
BO_1
0914 0614
BO_Trp04
0915 0615
BO_2
0916 0616
BO_Trp05
0917 0617
BO_3
0918 0618
BO_Trp06
0919 0619
BO_4
Power 0920 PWR+ 0620
Supply 0921 PWR- 0621
BO_5
0922 GND 0622
12 Commissioning
Table of Contents
12.1 General
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.
WARNING! Hazardous voltages are present in this electrical equipment during operation.
Non-observance of the safety rules can result in severe personal injury or property
damage.
WARNING! Only the qualified personnel shall work on and around this equipment after
becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
The limit values stated in the technical data (Chapter 2) must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.
DANGER! Current transformer secondary circuits must have been short-circuited before
WARNING! Primary test may only be carried out by qualified personnel, who are familiar
with the commissioning of protection system, the operation of the plant and safety rules
and regulations (switching, earthing, etc.).
Multifunctional dynamic current and voltage injection test set with interval timer.
Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440V and 0~250V
respectively.
NOTE! Modern test set may contain many of the above features in one unit.
Optional equipment:
An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
When commissioning this device for the first time, sufficient time should be allowed to become
familiar with the method by which the settings are applied. A detailed description of the menu
structure of this relay is contained in Chapter 8.
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
These product checks cover all aspects of the relay which should be checked to ensure that it has
not been physically damaged prior to commissioning, is functioning correctly and all input quantity
measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.
This relay is fully numerical and the hardware is continuously monitored. Commissioning tests can
be kept to a minimum and need only include hardware tests and conjunctive tests. The function
tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by self-monitoring when the
power supply is energized.
Function tests
These tests are performed for the following functions that are fully software-based. Tests of the
protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other
external equipment.
On load test.
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following listed items are
necessary.
Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.
Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section
meeting the requirement.
Carefully examine the wiring to see that they are no connection failure exists.
Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipment on the panel to make sure that they are well
installed into the equipment without any screw loosened.
Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
DC power supply
Test method:
To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
The relay only can be operated under the auxiliary power supply depending on the relay’s nominal
power supply rating.
The incoming voltage must be within the operating range specified in Section 2.1.1.1, before
energizing the relay, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Section 2.1.1.1. See this section
for further details about the parameters of the power supply.
WARNING! Energize this relay only when the power supply is within the specified
The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
The liquid crystal display (LCD) is designed to operate in a wide range of substation ambient
temperatures. For this purpose, this relay has an automatic “LCD contrast” adjusting feature,
which is capable to adjust LCD contrast automatically according to the ambient temperature.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a battery fitted on CPU board, the time and date will
be maintained. Therefore when the auxiliary supply is restored the time and date will be correct
and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the relay is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclose when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated power supply and check that the “HEALTHY” LED is lighting in green. We need to
emphasize that the “HEALTHY” LED is always lighting in operation course except that this device
finds serious errors in it.
Produce one of the abnormal conditions listed in Chapter 4, the “ALARM” LED will light in yellow.
When abnormal condition reset, the “ALARM” LED extinguishes.
Test the other LEDs according to the configuration of the LEDs (through the PCS-Explorer
configuration tool auxiliary software). If the conditions which can turn on the selected LED are
satisfied, the selected LED will be on.
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
Apply current equal to the current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see the following table or external connection
diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set
readout. The corresponding reading can then be checked in the relays menu.
The current measurement accuracy of the relay is ±2.5%. However an additional allowance must
be made for the accuracy of the test equipment being used.
This test checks that all the binary inputs on the relay are functioning correctly.
The binary inputs should be energized one at a time, see external connection diagrams for
terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range.
The status of each binary input can be viewed using the submenu “Contact Inputs” and “Prot
Inputs”.
NOTE! The trip circuit should remain isolated during these checks to prevent accidental
The above tests have already demonstrated that the protection is within calibration, thus the
purpose of these tests is as follows:
To conclude that the primary function of the protection can trip according to the correct
application settings.
Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
tenderization of the plant being protected.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
13 Maintenance
Table of Contents
This relay is self-supervised and so requires less maintenance than earlier designs of relay. Most
problems will result in an alarm so that remedial action can be taken. However, some periodic
tests should be done to ensure that the relay is functioning correctly and the external wiring is
intact.
The relay is almost completely self-supervised. The circuits which can not be supervised are
binary input, output circuits and human machine interfaces. Therefore regular testing can be
minimized to checking the unsupervised circuits.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the alarm record.
Failures detected by supervision are traced by checking the “Superv Events” screen on the LCD.
See Section 4.4 for the details of the alarm events.
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name and hardware type-form as the
removed module. Furthermore, the replaced module should have the same software version. And
the replaced analog input module and power supply module should have the same ratings.
WARNING! Units and modules may only be replaced while the supply is switched off and
only by appropriately trained and qualified personnel. Strictly observe the basic
precautions to guard against electrostatic discharge.
earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage. After replacing the CPU module,
check the settings.
DANGER! After replacing modules, be sure to check that the same configuration is set
as before the replacement. If this is not the case, there is a danger of the unintended
operation of switchgear taking place or of protections not functioning correctly. Persons
may also be put in danger.
Table of Contents
14.1 Decommissioning
DANGER! Before disconnecting the power supply cables that connected with the power
supply module of this relay, make sure that the external miniature circuit breaker of the
power supply is switched off.
DANGER! Before disconnecting the cables that are used to connect analog input module
with the primary CT and VT, make sure that the circuit breaker for the primary CT and VT
is switched off.
14.1.3 Dismantling
The rack of this relay may now be removed from the system cubicle, after which the cubicles may
also be removed.
DANGER! When the station is in operation, make sure that there is an adequate safety
14.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE! Strictly observe all local and national regulations when disposing of the device.