MVSG MV LOAD BREAK SWITCH

METAL CLAD SWITCHGEAR FIXED MOTORIZED MV CIRCUIT BREAKER


52
3P, 3W, 13.8KV, 1250A
25 KA RATED S.C. AT 3 SEC.
52 DRAWOUT MOTORIZED CIRCUIT
WITH EXTENDIBLE BUS-BAR BREAKER

CUBICLE-01 CUBICLE-02 CUBICLE-03 CUBICLE-04 CUBICLE-05 CUBICLE-06 CUBICLE-07 CUBICLE-8 CUBICLE-09 CUBICLE-10 CUBICLE-11 CUBICLE-12 CUBICLE-13 CUBICLE-14 CUBICLE-15 CUBICLE-16 CUBICLE-17 CUBICLE-18 GX GENERATOR

GCP GENERATOR CONTROL PANEL


27 UNDERVOLTAGE RELAY
32 REVERSE POWER RELAY
40 LOSS OF EXCITATION RELAY
46 NEGATIVE SEQUENCE RELAY
49 THERMAL RELAY

50 GROUND SENSOR INSTANTANEOUS


GS OVERCURRENT RELAY
BUS 50
51
PHASE, TIME AND INSTANTANEOUS
OVERCURRENT RELAY
51N RESIDUALLY CONNECTED TIME
17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/
120V 120V 120V 120V 120V 120V OVER-CURRENT RELAY
630AF,3P 630AF,3P
3-VT CB-S1 630AF,3P 630AF,3P 630AF,3P 630AF,3P 630AF,3P 630AF,3P 630AF,3P CB-S2 51G GROUND OVERCURRENT RELAY
/120V
FU1-FU3 CB-GS CB-G1 CB-G2 CB-G3 CB-G4 CB-G5 CB-G6
15KV
Y

BACK UP OVERCURRENT RELAY,


Y

50 50 50 50 50 50 51 V
52 86 CS 52 52 52 52 52 52 52 52
51 51 51
86 CS 86 CS 86 CS 86 CS 86 CS 86 CS 86 CS MCB 51 51 51
86 CS VOLTAGE RESTRAINT
T11, T12, T13
67 AC DIRECTIONAL OVERCUREENT RELAY
52 86 CS 52 86 CS 52 86 CS 52 86 CS 52 86 CS 52 86 CS
51 51 51 51 51 51 51 51 51
51N
50 51N
50
51N
50
51N
50
51N
50
51N
50
51N
50
51N
50
51N
50
59 OVERVOLTAGE RELAY
CB-T1 CB-T2
630AF,3P 630AF,3P 630AF,3P 630AF,3P 630AF,3P 630AF,3P
(BUS TIE) (BUS TIE)
81 OVER/UNDER FREQUENCY RELAY
32 CB-SA CB-1A 32 32 32 32 32 32 32 CB-1B CB-SB 32
86 LOCKOUT RELAY
17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/ 17.5KV/
59 120V 67 120V 67 120V 67 120V 67 120V 67 120V 67 120V 67 59
87 DIFFERENTIAL RELAY
27 50 50 50 67n 67n 67n 67n 67n 67n 67n 50 50 50 27
GS GS GS GS GS GS

59 59 59 59 59 59 59
CS CONTROL SWITCH
HM
ELECTRONIC METERING DEVICE
17.5KV/
27 27 27 27 27 27 27 EMD FOR VOLTAGE, AMPERE, MAXIMUM DEMAND,
17.5KV/
Q57 120V 120V KW-HOUR POWER FACTOR, FREQUENCY, ETC.
GSR GROUND SENSING RELAY WITH INDICATING LAMP

DGPT2
DETECTION OF GAS OVER
PRESSURE & TEMPERATURE
FUSE
BUS BAR POTENTIAL TRANSFORMER
EARTHING CURRENT TRANSFORMER
GROUND CONNECTION
VOLTAGE INDICATING LAMP
F.SEC1

F.SEC2
M MOTOR
CCMS COMPUTERIZED CONTROL MONITORING SYSTEM
3X1/C 240mmSQ., CPU CENTRAL PROCESSING UNIT
CU/XLPE/LAT/MDPE MCB MINIATURE CIRCUIT BREAKER
STEP UP 15KV(17.5KV)
MCC MOTOR CONTROL CENTER
TRANSFORMER TR-G1 TR-G2 TR-G3 TR-G4 TR-G5 TR-G6 MDB MAIN DISTRIBUTION BOARD
400/13.8KV EMDB EMERGENCY MAIN DISTRIBUTION BOARD
OIL TYPE
SPARE 1500 KVA SPARE NC NORMALLY CLOSE
SEC 1 (TYPICAL) SEC 2 NO NORMALLY OPEN
LOOP-1A

LOOP-1B
PLC PROGRAMMABLE LOGIC CONTROLLER
F.G1

F.G2

F.G3

F.G4

F.G5

F.G6
RTU REMOTE TERMINAL UNIT
EMI ELECTRO-MECHANICAL INTERLOCK
6 SETS (3x1C-630mm² CU/XLPE/PVC) EI ELECTRICAL INTERLOCK
+ 2 SETS (1C-630mm² G) SEC SAUDI ELECTRIC COMPANY
(1 SET) (3X300SQ., CU/XLPE/LAT/STA/MDPE,
POWER TRANSFORMER (TYPE AS INDICATED)
15KV (17.5KV) TRANSFORMER TO BE RATED AS INDICATED
IN DRAWINGS
GCP GCP GCP GCP GCP GCP GCP
AUTO
SYNCHRONIZING AND LOAD BREAK
SWITCH
59 59 59 59 59 59 59
CONTROL PANEL (ASCP) MV - POWER SUPPLY - SEQUENCE OF OPERATION
27 27 27 27 27 27 27
ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE INCOMER & BUS TIE
(1 SET) (3X300SQ., CU/XLPE/LAT/STA/MDPE, 81 81 81 81 81 81 81
FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER FEEDER BREAKERS
40 40 40 40 40 40 40
15KV (17.5KV) SEC1 SEC2 G1 G2 G3 G4 G5 RMU-MV OUTGOING
32 32 32 32 32 32 32
DESCRIPTION CB-S1 CB-S2 CB-T1 CB-T2 CIRCUIT BREAKER
51V 51V 51V 51V 51V 51V 51V
F-SEC1 F-SEC2 F.G1 F.G2 F.G3 F.G4 F.G5
RATING AS SHOWN
46 46 46 46 46 46 46
NORMAL 1 1 0 0 0 0 0 1 1 0 0

LOSS OF ONE ACTIVE 0 1 0 0 0 0 0 0 1 0 1 13.8kV


FEEDER IN EITHER 1 0 0 0 0 0 0 1 0 0 1 EARTH SWITCH
51G 51G 51G 51G 51G 51G 51G

PRIME RATED TOTAL POWER OUTAGE


FROM UTILITY SOURCE 0 0 1 1 1 1 1 0 0 1 1
GENERATOR
G7 G1 G2 G3 G4 G5 G6S 400V, 1400KVA
(TYPICAL)

FUTURE SPACE DUTY DUTY DUTY DUTY DUTY STANDBY CURRENT SITUATION UNTIL
SEC BE AVAILABLE

PHASE 3
CENTRAL UTILITIES AREA

RMU-07 RMU-01 RMU-02 RMU-06 RMU-05 RMU-04 RMU-03 RMU-SER

3X1/C 120MMSQ., CU/XLPE/PVC, 15KV(17.5KV) 3X1/C 120MMSQ., CU/XLPE/PVC, 15KV(17.5KV) 3X1/C 120MMSQ., CU/XLPE/PVC, 15KV(17.5KV) 3X1/C 120MMSQ., 3X1/C 120MMSQ., 3X1/C 120MMSQ.,
CU/XLPE/PVC, 15KV(17.5KV) CU/XLPE/PVC, 15KV(17.5KV) CU/XLPE/PVC, 15KV(17.5KV)

TR-SER
TR-7 TR-1 TR-2 TR-6 TR-5 TR-4 TR-3 SERVICE
TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER TRANSFORMER
13.8KV/400V 13.8KV/400V 13.8KV/400V 13.8KV/400V 13.8KV/400V 13.8KV/400V 13.8KV/400V 13.8KV/400V
1000 KVA 1500 KVA 1000 KVA 1500 KVA 1000 KVA 1000 KVA 1500 KVA 1500 KVA
OIL TYPE OIL TYPE OIL TYPE OIL TYPE OIL TYPE OIL TYPE OIL TYPE OIL TYPE
(SITE) (SITE) (SITE) (SITE) (SITE) (SITE) (SITE) (SITE)

TO MDB-07 TO MDB-01 TO MDB-02 TO MDB-06 TO MDB-05 TO MDB-04 TO MDB-03 TO MDB SERVICE