Bridge Engineeing Drawings 10.2 - A2 - 3

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

*JUNCTION BOX & PULL BOX (TYP.

)
FOR SIZE & LOCATION, SEE
THRIE BEAM
OR W-BEAM 2 ~ 10' STEEL JUNCTION BOX TABLE
END OF BRIDGE OR WALL CURB LINE
GUARDRAIL CONDUITS

TS LT

2 ~ STEEL CONDUIT TO PVC TRAFFIC BARRIER CONDUIT EXPANSION FITTING


CONDUIT DEFLECTION FITTING A ADAPTOR IN STATIONARY FORM ON STRUCTURE (TYP. AT EXPANSION JOINT)

2'-0"
10'-0" MIN. TO 20'-0" MAX. BARRIER WHERE PVC PIPE
WITH INTERNAL BONDING JUMPER.
SEE DETAIL THIS SHEET INSTALLED IN BARRIER
* NEMA 4X IN STATIONARY FORM BARRIER, OR
TS LT
JUNCTION BOX SIZED
PLAN NEMA 3R IN SLIP FORM BARRIER. MOUNT JUNCTION
BOX SO COVER IS FLUSH WITH BARRIER, CAN BE
PER ELECTRICAL PLANS.
LABEL JUNCTION BOX LIDS
CONDUITS & J-BOX RECESSED UP TO Â".
NOTE TO DESIGNERS A
MODIFY THE FOLLOWING TO MATCH PROJECT REQUIREMENTS:
AS SHOWN (TYP.)
IN TRAFFIC BARRIER
1. BARRIER END SECTION.
2. REMOVE GUARDRAIL IF NOT CONNECTED TO BRIDGE ITEM. ¢ J-BOX & BARRIER PANEL ¢ J-BOX & BARRIER PANEL
3. CONDUIT ALIGNMENT 180'-0" MAX. ¢ J-BOX & BARRIER PANEL
¢ J-BOX & BARRIER PANEL
180'-0" MAX.
10' STEEL CONDUIT SECTION
BUNDLE 2 R1 #5, 2 R2 #5 OR 8'-0" MIN. (L TYP.)
BETWEEN CONDUIT DEFLECTION
TOP OF BRIDGE DECK 2 R9 #5 ADJACENT TO EACH
FITTING A AND PVC CONDUIT IN SECURE CONDUIT AND BOX TO L (TYP.)
AT CURB LINE END OF JUNCTION BOX (TYP.) #4 x 3'-6" (TYP.)
STATIONARY FORM BARRIER REBAR TO PREVENT MOVEMENT

TS LT TS LT

2"ø CONDUIT PIPES OR


SIZE CONDUIT PER
BLOCKOUT FOR
CONDUITS
STEEL CONDUIT TO PVC ADAPTOR IN
STATIONARY FORM BARRIER WHERE
ELEVATION - CONDUITS & J-BOX IN TRAFFIC BARRIER WIRING SCHEDULE
¾" POLYSTYRENE
FOAM. WRAP 1½ TIMES
LABEL JUNCTION BOX COVER IN ACCORDANCE WITH STANDARD SPECIFICATION SECTION 9-29.2(4). ADJACENT JUNCTION BOXES ARE
PVC PIPE INSTALLED IN BARRIER AROUND CONDUIT AND
CONDUIT DEFLECTION SHOWN CENTERED BETWEEN ADJACENT DUMMY JOINTS. IF THE DISTANCE BETWEEN ADJACENT DUMMY JOINTS IS 16'-0"
CONDUIT FITTING
FITTING A OR GREATER, PLACE ADJACENT JUNCTION BOXES SYMMETRICALLY ON EITHER SIDE OF THE CENTER OF ONE DUMMY PANEL
WHILE MAINTAINING 8'-0" MINIMUM BETWEEN CENTER LINES OF THE JUNCTION BOXES.
6/5/2018

END
STEEL CONDUIT SECTION BETWEEN
CONDUIT DEFLECTION FITTING A ½" PREMOLDED JOINT FILLER START
AND JUNCTION BOX SEE STANDARD PLANS
WHERE CONDUIT IN A STRUCTURE IS ROUTED CONCRETE CONCRETE
WHERE CONDUIT IN A STRUCTURE IS
ROUTED ACROSS A JOINT, WRAP STEEL
SECTION B
ACROSS A JOINT, WRAP STEEL CONDUIT PIPE
FOR 1'-0" ON EACH SIDE OF JOINT. PIPE WRAP 1'-0" CONDUIT PIPE FOR 1'-0" ON EACH SIDE
3'-0" LONG EXPANDED POLYSTYRENE OF JOINT. PIPE WRAP TAPE SHALL BE 2"
TAPE SHALL BE 2" WIDE, 20 MIL THICK, AND 1" TIES @ 2½" 1"
SLEEVE AROUND CONDUIT. DUCT TAPE WIDE, 20 MIL. THICK, AND INSTALLED
INSTALLED WITH A MINIMUM OF 1" OVERLAP 2 ~ STAINLESS STEEL
SEAMS AND ENDS TO SEAL AND WITH A MINIMUM OF 1" OVERLAP
EXPANSION JOINT MOUNTING TABS (TOP & BOT.)
PREVENT CONCRETE FROM BONDING
WITH FITTING AND CONDUIT

CONCRETE
CONDUIT EXPANSION BUNDLE 2 R1 #5, 2 R2 #5 OR
FITTING *8" x 8" x 18" JUNCTION BOX

¾"
2 R9 #5 ADJACENT TO EACH
CONDUIT PIPE SIZED END OF JUNCTION BOX (TYP.)
PER WIRING SCHEDULE
¾"

CONDUIT PIPE É"ø POLYETHYLENE


OR COPPER PIPE DRAIN
3" MIN., 6" MAX. (CONDUIT AND B

1'-2"
CONDUIT DEFLECTION FITTING
SOIL
THREADS CAST OUTSIDE STRUCTURE)
WITH INTERNAL BONDING JUMPER
CONDUIT DEFLECTION FITTING
0

BONDING JUMPER
1" TIES ~ SPACE @ 2½" MAX. 1"
WITH INTERNAL BONDING JUMPER CONDUIT DEFLECTION FITTING B
CONDUIT PIPE CONDUIT FITTING - TYPE DX FOR DEFLECTION OF 30° AND ¾" MOVEMENT.
CONDUIT PIPES PLACED THROUGH RETAINING WALL TRAFFIC BARRIER SHALL
CONDUIT EXPANSION FITTING CONDUIT DEFLECTION FITTING A BE FITTED WITH DEFLECTION FITTINGS AT A MAXIMUM SPACING OF 120'.

CONDUIT FITTING - (TYPE AX FOR MOVEMENT OF ± 2")


CONDUIT FITTING - TYPE DX FOR DEFLECTION OF 30° AND
THE DEFLECTION FITTINGS SHALL BE PLACED AT THE TRAFFIC BARRIER OPEN
JOINT THAT COINCIDES WITH THE RETAINING WALL EXPANSION JOINT.
SECTION A
¾" MOVEMENT. PLACE AT CONDUIT PIPE EXIT FROM
AT BRIDGE EXPANSION JOINTS
STRUCTURE AND SHALL BE IN NEUTRAL STATE AFTER INSTALLATION.
M:\STANDARDS\Traffic Barriers\flat slab TB\FS SHAPE F BARRIER SHT 3.man
10.2-A2-3

TRAFFIC BARRIER - FLAT SLAB


FLAT SLAB - DETAILS 3 0F 3