Iflow Manual A2: Iflow Hydronic Air Handler
Iflow Manual A2: Iflow Hydronic Air Handler
Iflow Manual A2: Iflow Hydronic Air Handler
iFLOW MANUAL A2
iNTELLIGENT SMART IoT TECHNOLOGIES
iFLOW HYDRONIC AIR HANDLER
NEW GENERATION OF HEATING & COOLING
www.iflowhvac.com
Table of Contents
Introduction
Safety ………………………………………………………………………………………………………….… 2
Summary of air handler ………………………..………………………………………………………………. 2
Technician checklist ……………………………………………………………………………………………. 2
Product Description
Components ………………………………………………………………...…………………………………3
Standard features and benefits ………………………………………………………………………….…..4
Equipment selection and sizing ………………………………………………………………………….….. 5
Suitable Applications (Choosing the correct heat source) ………………………………………………… 5
Installation
Location requirements and clearances ………………………………………………………….…….. 8
Dimensions …………………………………………………………………………………………….……. 8
Installation examples ………………………………………………………………………………………… 9
Boiler Piping …………………………………………………………………………………………………… 9
Domestic Piping ………………………………………………………………………………………….…. 9
Electrical requirements and making connections ………………………………………………………. 10
Temperature sensors ………………………………………………………………………………………… 10
A/C Evaporator Coil Freeze Protection and the Importance of Wiring the A/C Compressor to
the Proper and Dedicated A/C Connector on the iFLOW PCB.…………………………......................... 11
Start-Up
Procedure ……………………………………………………………………………………………………. 13
Flushing the heat exchanger ……………………………………………………………………………….. 13
Sequence of operation………………………………………………………………………………………… 13
Troubleshooting
Fault Codes and Explanations ……………………………………………………………………………… 23
Problems and Solutions ……………………………………………………………..………………………. 24
Component Assembly Diagram and Parts Lists……………………………………………………… 25
Commonwealth Of Massachusetts Board Policy ......................................................... 34
Warranty
Warranty Information………………………………………………………………………………………… 35
Contact Information …………………………………………………………………………………………… 35
Ensure the instructions and requirements provided in this manual are • Be sure to bleed all air from all system components and piping prior
read and understood before installation. Failure to comply with these to start-up.
instructions can cause product and property damage, serious injury • It is recommended to install purge valves between the air handler
or death. and water heater’s isolation valves.
Pay attention to the following safety symbols and words: • If connected to domestic piping creating an open system, make
sure all piping, components, and solder are lead-free and approved
for potable-use.
CAUTION
DANGER
Return air openning shall not be installed
on the back side of unit.
WARNING
• Ensure fan assembly is clear of any obstruction
• Check that air filter is installed upstream of air conditioning coil.
• If the appliance is installed with air conditioning,the A/C refrigerant
charge and system operation must be verified by a certified/ licensed
This product can expose you to chemicals including lead, mechanic prior to commissioning.
lead compounds, and carbon bisulfide which are known to the
State of California to cause cancer and birth defects or other
reproductive harm. For more information, go to
WARNING
www.P65Warnings.ca.gov.
CAUTION CAUTION
Indicated a potentially hazardous situation, which if not
avoided, may result in minor or moderate injury. It is also used The air handler must be installed such that electrical components
to alert against unsafe practices and hazards involving property are away from water (spraying, splashing, etc.) during operation and
damage. service.
All cabinets are made of high quality, and durable heavy gauge All air handlers require a field supplied single speed or 3-speed pump,
galvanized steel. The inside of the cabinet is fully insulated with ½” to be controlled by the iFLOW circulator control. This the speed of the
polyethylene sheets. This prevents moisture and mold growth, as well pump increases or decreases depending on the information provided
as unwanted heat loss due to an R-Value. The smaller cabinet size by the temperature sensors. The pump also provides maximum
and shape is designed to maximize installation flexibility. performance when used in conjunction with an instantaneous water
heater or a storage-type water heater.
Heating Coils:
Check Valve:
All iFLOW heating coils are constructed of potable, water-grade
copper for use in plumbing systems. Lead-Free solder has been used A spring-loaded check valve must be installed either with the field-
for assembly on all components. All coils and internal piping conform supplied pump or externally to prevent the by passing of water to the
to ASTM B-68, ASTM B-88 and/or B-743 standards. Carefully appliance.
engineered, high-density aluminium fins allow for maximum heat
transfer across smaller coils. This provides warmer, more comfortable Multi-Function Control Board:
heating with lower air flow for minimal operating noise.
This intelligent control board comes factory installed. No dip
Fan Motor: switches are required or included with the iFLOW control board.
Easy programming allows for user-friendly startup and service/
All iFLOW air handlers are equipped with variable speed ECM maintenance. Some of the parameters the user is able to configure
motors. This allows for separate heating, cooling, and continuous run are: heating output, CFM for heating, cooling and continuous low-
speeds. They reduce electrical-use and are dynamically balanced speed fan, outdoor design temperature and circulating pump speed.
for extra quiet operation. Blowers are mounted with four screws on
rails for easy removal and service. Multi-directional motors allow for
mounting in any direction.
Test Mode:
Model No. Description
Entering ‘test mode’ on the controller will allow the technician to test
the iFLOW air handler heating and cooling mode parameters. Once i F L H - 1 4 0 0 0 0
completed, push the test button again to return to normal operation.
Function / B: basic, W: WiFi,
▶
Heating: D: 2 zone, Q: 4 zone
The iFLOW air handler will automatically change the fan and pump
speeds to control the temperature output of the unit and cycle-time
length. This will allow the heat output of the air handler to match the
Cabinet Size / 14 : 14", 16 : 16", 18 : 18" Width
current heat loss of the home. Maximum ‘matching’ performance is
▶
achieved when used in conjunction with the outdoor sensor. This Static Pressure / L : Low Static Pressure,
▶
leads to a longer runtime, providing superior warmth and comfort. H: High Static Pressure, LH : Universal
▶ Company Initial
Cooling/Dehumidifying:
kg 28.6 32 42
Weight
lb 63 71 92.5
in 13 x 14 14 x 16 16 x 20
Supply Air Opening
(W x D)
mm 330 x 356 356 x 406 406 x 508
in 12 x 16 13 x 18 14 x 23
Return Air Opening
(H x D)
mm 406 x 304 457 x 330 584 x 355
Electrical ACV/Hz/Ph AC 120V 60Hz 1Ph AC 120V 60Hz 1Ph AC 120V 60Hz 1Ph
iFLH-140000
3 GPM 4 GPM
Entering
H.Ex.
Water CFM CFM
Rows
Temp. W.P.D W.P.D
400 600 700 800 950 400 600 700 800 950
120℉ 17,365 21,756 23,654 25,347 27,834 2.9 18,425 23,097 25,653 27,246 29,906 4.3
130℉ 20,756 26,235 28,105 30,632 33,478 2.9 21,365 27,743 30,014 32,954 36,183 4.3
140℉ 24,142 30,754 33,521 36,065 37,729 2.8 24,845 32,469 35,478 38,549 42,376 4.2
4 150℉ 27,587 35,329 38,013 41,365 44,998 2.8 28,326 37,254 40,024 44,287 48,598 4.2
160℉ 30,965 39,865 43,247 46,759 50,869 2.8 31,824 41,987 45,726 49,976 54,843 4.1
170℉ 34,329 44,432 48,628 52,125 56,941 2.7 35,327 46,743 51,214 55,643 61,176 4.1
180℉ 37,734 49,032 54,573 57,683 62,786 2.7 39,836 51,458 56,429 61,398 67,497 4.0
iFLH-160000
3 GPM 4 GPM
Entering
H.Ex.
Water CFM CFM
Rows
Temp. W.P.D W.P.D
600 800 900 1000 1250 600 800 900 1000 1250
120℉ 24,625 27,865 29,865 31,087 34,211 3.7 28,268 30,042 31,986 34,109 38,287 5.7
130℉ 28,218 33,572 35,724 37,429 41,357 3.7 33,625 36,256 38,524 41,162 46,456 5.7
140℉ 32,865 39,218 41,625 43,843 48,379 3.7 38,245 42,367 45,412 48,235 53,971 5.5
4 150℉ 37,536 45,075 47,536 50,327 55,485 3.6 42,765 48,559 52,369 55,149 61,864 5.5
160℉ 42,125 50,732 53,425 56,798 62,632 3.6 47,325 54,632 58,489 62,268 69,832 5.4
170℉ 46,852 56,579 59,425 63,266 69,769 3.5 51,869 60,861 64,542 69,345 77,846 5.4
180℉ 51,425 62,329 65,325 69,747 76,982 3.5 56,465 67,054 72,369 76,486 85,742 5.3
iFLH-180000
3 GPM 4 GPM
Entering
H.Ex.
Water CFM CFM
Rows
Temp. W.P.D W.P.D
600 800 1000 1200 1450 600 800 1000 1200 1450
120℉ 28,963 34,245 35,648 38,946 42,376 5.6 30,125 36,203 38,224 42,376 46,638 6.9
130℉ 33,412 39,632 42,820 46,981 50,966 5.5 34,845 41,952 45,996 50,996 56,173 6.8
140℉ 37,954 45,126 50,157 54,844 59,632 5.5 39,652 47,623 53,756 59,465 65,789 6.7
4 150℉ 42,503 50,520 57,489 62,529 68,334 5.4 44,321 53,304 61,533 68,255 75,223 6.7
160℉ 47,127 55,963 64,732 70,931 77,065 5.3 49,032 59,123 69,325 76,905 84,896 6.6
170℉ 51,608 61,412 72,078 78,842 85,648 5.3 53,741 64,745 77,199 85,627 94,441 6.5
180℉ 56,129 66,846 79,354 87,055 94,633 5.2 58,429 70,487 84,923 94,336 104,056 6.4
• The installer shall comply with all local, state/provincial and national
code requirements that apply to the installation of this equipment.
• The air handler must be installed in such a way that electrical PLENUM
components are protected from water during operation and service. 0 inch
• If installed in an unconditioned space, sealant should be applied
around where the electrical wires, refrigerant tubing, and condensate
lines enter the cabinet. This appliance shall not be installed in a non-
conditioned space where the potential may exist for the appliance, BACK
LEFT SIDE 0 inch
water lines and/or drain lines to freeze. 0 inch
• If installed with air conditioning in a suspended application, ensure a
drain pan with a proper slope is installed.
Recommended Clearances:
BOTTOM
0 inch
in 14 18 3/4 27 1/8 13 14 16 12
14" Cabinet
mm 355.6 476.3 689 330.2 355.6 406.4 304.8
in 16 20 3/4 27 1/8 14 16 18 13
16" Cabinet
mm 406.4 527.1 689 355.6 406.4 457.2 330.2
in 18 25 3/4 29 1/8 16 20 23 14
18" Cabinet
mm 457.2 654.1 739.8 406.4 508 584.2 355.6
Vertical Installation
AHU with Support
Case Coil or A Coil Anti-Vibration Pad
When installing the iFLOW air handler with a heating boiler or combi-
boiler in a closed loop system, refer to the boiler manufacturer’s
instructions for proper installation with an air handler. Depending on
the boiler selected and system design, it may be required to use a
primary/secondary piping arrangement to de-couple the flow through
Evaporator the boiler from the flow through the air handler.
Temperature
Sensor position
Air-removal device:
Provisions shall be made for the removal of air in the heat-distribution
piping system. The air-removal device shall be located in the area
of the heat-distribution piping system where the air is likely to
Filter Rack Filter Rack
accumulate (often the highest point in the system).
Notes: When installing the iFLOW air handler with a water heater,
Hanging Installation refer to the manufacturer’s guidelines on coupling the water heater
with an air handler. Use components and piping that are allowable
with potable use. Lead-free solder must be used on all joints.
When both top and side connections are present on the water heater,
the side connections should be used for the space-heating loop.
The heating loop connections should be positioned horizontally in a
The Threaded Rod
vertical section of the domestic water line for both the inlet and outlet.
Refer to the piping diagram for details. Minimize the distance and
piping between the water heater and the iFLOW air handler.
Spring If the main water line has an installed check valve, a potable
Flat washer
Nut expansion tank must be installed to provide room for the expansion
of water.
Check The iFLOW air handlers come equipped with 5 wire sensors that plug
Valve into connectors on the control board for easy servicing.
Circulator Check
with Valve
Check Valve
Flow
Switch
Expansion
Tank
Tank
Water Heater Cold
Water
The iFLOW Hydronic Furnace incorporates advanced freeze Thermostat Connection to iFLOW PCB
protection for your A/C evaporator coil. When the iFLOW A/C
Evaporator temperature sensor sees an air temperature of 37°F
(3°C) or below, the iFLOW will immediately interrupt the power supply
to the A/C compressor for 5 minutes. It will however maintain the
blower ‘ON’ to move air flow across the evaporator coil to warm it and
to prevent freezing. When the iFLOW A/C Evaporator Temperature
sensor sees a temperature of 45°F (7°C) or more than 3 minutes has
expired since initial compressor interrupt, it will allow the compressor
to begin again. There is a minimum off period of 3 minutes to prevent
on/off damage to the compressor.
From Thermostat
As such, when installed properly, there should be no concern
about freezing the evaporator coil, damaging the A/C compressor
nor freezing the hydronic coil with an iFLOW Hydronic Furnace.
To ensure full protection however, you MUST follow the 2-Step FIGURE C-2:
installation explanation below:
Correct Wiring:
Step 1 A/C compressor interrupt enabled
To ensure the iFLOW will be able to interrupt the A/C compressor Location of connector may vary by model
when needed to protect the equipment, the A/C compressor must be
wired to the dedicated A/C terminal on the PCB (see figures C-1 &
C-2). The location on the PCB of this dedicated A/C connector varies Dedicated A/C Compressor Output Connector
by model; please consult the wiring diagram section of this installation
manual for details. Single Stage Condensing Unit Two Stage Condensing Unit
The 24V output signal for the A/C compressor MUST NOT BE
CONNECTED be connected to the thermostat connection on the PCB
(see figure D). If the 24V signal for the A/C compressor is connected
R W G Y1 Y2 C R W G Y1 Y2 C
to the thermostat connection on the iFLOW PCB, the 24V signal will
come from the thermostat and there is no way for the iFLOW to interrupt
the compressor, thus you will have NO A/C FREEZE PROTECTION.
In addition, there is a high likelihood of damage to the PCB and the
hydronic coil. There will be NO WARRANTY for PCB damage nor To A/C To A/C
Compressor Compressor
freezing damage to the hydronic coil resulting from improper field wiring.
FIGURE D:
Incorrect Wiring:
No A/C Evap Coil Freeze Protection;
No warranty for damaged PCB or freezing of the hydronic coil
CAUTION
CAUTION
From Thermostat DO NOT DO!
To A/C Compressor
AHU with
Case Coil or A Coil
on the Supply
Air
Flow
Evaporator
Temperature
Sensor position located
downstream of slab coil
IMPORTANT
Position the sensor in the A-coil in the supply duct as shown above
Evaporator in Figure E. To relocate the A/C evaporator temperature sensor to
Temperature a slab coil in the return duct, follow the following steps. From the
Sensor position
factory, the sensor is placed loose on top of the hydronic coil. Follow
the wire back towards the PCB and disconnect the sensor at the
black male/female connector located between the sensor and the
Air PCB. Gently push the sensor back through the rubber grommet; the
Flow sensor is now free. Relocate the sensor as shown above in Figure F.
Once the sensor is relocated, reconnect the wire. If necessary, use
any thermostat wire to extend the length of the sensor wire. When
running the wire back to the original connector, ensure the wire runs
around and not in front of the PCB and transformer.
The connection port on the iFLOW PCB for the A/C Evaporator
Temperature sensor varies by model but is generally located near
the top center of the PCB. Please consult the PCB schematic in the
installation manual for details.
If steps 1 & 2 are followed, the iFLOW delivers A/C evaporator and
hydronic coil freeze protection.
Do not start the boiler or water heater until ALL air has been purged Cooling: When the thermostat calls for cooling, the circuit between
from the water lines and air handler pump. R and G is completed. The normally open contacts close and the air
handler blower motor operates. The circuit between R and Y is also
1. Fill the boiler loop or water heater with water. Do not start it. completed; this closes the contact on the outdoor condenser unit.
2. Purge all air from the heating boiler or domestic hot water system The air handler fan turns off 45 seconds after the call for cooling is
(Hold the UP & ENTER button for 10 seconds and then the circulator completed.
will alternate power ON and OFF for about 10 minutes to purge air).
3. Purge all air from the space heating loop by closing the isolation Heating: When the thermostat calls for heat, the circuit between R
valve on the return leg of the loop and open the drain to purge the air. and W is completed, activating the hot water circulating pump. A dry
Open the return leg isolation valve and then close the drain valve. switching relay labeled “T T” can be used to activate a boiler or combi
4. If a bleed screw is not present, it is recommended to run the pump boiler. After the circuit between R and W is completed, a time delay
on speed #3 for 1 minute. If air is still present, switch from speed #1 follows before the circuit between R and G is completed, which will
to #3 every 10 seconds for a minute. then activate the air handler blower motor.
5. Start the boiler or water heater according to the manufacturer’s
instructions. Set the design water temperature and wait for the Freeze protection: If the temperature of the water in the hot water
system to satisfy and shut off. coil drops below 40°F/4°C, the circuit between R and W is completed.
6. Turn on the power to the iFLOW air handler and set the room This will activate the circulating pump until the water temperature
thermostat to ‘heat’ to energize the fan and pump. If noise is still reaches 70°F.
present after one minute, repeat step #3 to purge air.
7. Check supply and return pipes for temperature differences to Pump timer/ exercise function: The iFLOW control is equipped to
make sure there is flow. There should be a noticeable difference in turn on the circulating pump to cycle the total volume of potable water
temperature. Use caution when supply water temperature is above in the system if the pump has not been turned on within the past
120˚ F. 24 hours. This function is skipped while the A/C condensing unit is
operating.
2) Flushing the heat exchanger:
How to Access and Configure the iFLOW Intelligent
Flushing the hot water coil prior to startup is required to remove any Controller
residual material from the installation or manufacturing processes as
well as to remove any air from the system. Take precautions while The controller has 4 modes:
flushing the air handler to prevent the multi-function control board and
other electrical components from getting wet.
1. Information 3. Parameters
The iFLOW air handler requires an external circulating pump to be
installed and should be installed with an external purge valve.
2. Error Codes 4. Test Mode
Lowest Outdoor
0˚F - 32˚F 5˚F
Temperature
15 - 100
Max. HeatLoss 60/70/90
KBTU/h
0 : Hot Water Only (water heater, boiler or combi-boiler) Press enter while 04 is flashing. Display will show OFF. Use up or
1: Hot Water + heat pump (Hybrid) down to turn on. Boiler TT Relay will start immediately. Press enter
to exit.
32 ~ 46°F
H/P Cut-Off Temp. 40
(0 ~ 8°C) OPT
Set the lowest temperature at which you wish the heat pump
to operate (Balance Point Consideration: H/P COP and cost of Reserved
electricity at that temperature vs. gas efficiency and cost of gas).
Below that temperature, iFLOW will switch to the gas hot water
source. Dehumidifier Relay ON / OFF
How to access Test codes: Press enter while 08 is flashing. Jumper terminals Flow Switch
Push the mode button until the screen reads 04 tES. Press enter to on right hand side of control board. The display will flash ON if
confirm the test mode. Use the up and down buttons to choose the it is working correctly. Also you may turn the hot water tap on if
test number 01-9. Each test will be explained below. connected to a tankless water heater for the same.
Blower Motor Speed Test 0 - 100% Press enter while 09 is flashing. Display will show OFF. Use up or
down to turn on. Y1 Relay will start immediatley. Press enter to exit.
Press enter while 01 is flashing. Display will flash 0. use arrows to
change value from 0-100% blower speed. Blower will speed up and Y2 Relay ON / OFF
down simultaneously as you increase or decrease the value.
1) Maintenance:
Resistance
• Filter: This filter should be inspected and replaced as required.
• Coils: the heating and air conditioning coils should not require
regular maintenance IF a regular filter maintenance schedule is
followed. In the event, the filter is damaged or plugged and dust
has fouled the coil, replace the filter and carefully vacuum the
heating and/or A/C coil.
• Circulator: The circulating pump is water lubricated and should Evap. Temperature Sensor
not require regular maintenance. The system control has a pump
exercise function during prolonged periods of no heat to avoid
seizing.
Resistance
2. Check the sensor resistance and compare the actual values with
the curve on the chart.
Temperature
3. Replacement of a sensor is required in the case of severe
deviation. Outdoor Temp. Sensor Chart
Resistance
R17
R18
J3 F1
R10 U24 J14 V1
AC24V
D2
R
LED33
R21 R19
R62 R69
R60 R67
R63 R70
R61 R68
R15 R14 Q1 R16 LED8 LED7
C5 C4 C3
~ C From Transformer
R74
C34 C30 C29 C28 C27 R6
RLY
R31
LED2 C7 ~ T1
T4 C8
R98
BD1
C6
BoilerTT
J13
C39
T T
LN
+
~
~
Dry Contact
-
U3 U2
R88
R4 R5
R97
RY2
D1 R3
TR
LED1
OPT
U12
RY3
J2 C9 R2 R1 U1
LED22 R104
R103
R106
Humidifier
RY4
D7 R89 Q8 J8 J4
RY1
AC24V
R105
18
LED17 Q7 Q9
RY5
Dehumidifier
R W G Y1 Y2 C
R76 R92
D8
R99
C40
T5
R84 LED18
R77 R93
U8
AC24V
RY6
Thermostat R85 LED19 U9
R Y1 Y2 O
R78 R94
R101
C42
D10
RY7
U10
A/C
R86 LED20
R79 R95
TRANSFORMER
J5 J9
R102
D11
C43
or
RY8
R87 LED21 U11
T2
H/P
R30 R32 Q2
C36
C21 R38
O.D.S. F. SW
R25
R80 R81 R33 Q3
PGM
O. D. Sensor
RY9
R82 Q4
Condensing Unit
B
C38 C23 J1
C19
R24
U21
LED16 R83 R42
R90 R47
R45
iFLOW
C37 C31 C32 C33 R50 BUZ1
R41
R54 T6
C45
R71 R65 R66
C35
R91 D12 Q5 LED5
R23
R75
R64 R72 R73 R12 R9
Q6
Flow Switch
T3 R53 R55 R51
HVAC INC.
LED12
LED4 R13 SW1 R8 C12
R49
R48 LED14 LED15 LED13 AHU-A2(200131)
3) Field Installation Wiring Diagram
J18
RC
J15 J11
J17
HUM DEH RAT BLOWER CTL
AC24V
TO T1
DEHUMIDITY SENSOR
DEHUMIFIER EVA. T. SENSOR
RETURN AIR TEMP. SENSOR
BLOWER
MOTOR
* Do Not Connect A/C on Thermostat Connector *
R
BOILER T T DRY C
W
G
THERMOSTAT
Y1
Y2
HUMIDIFIER AC24V
C
To setup this functionality, the iFLOW needs to know the heating will Hot
be supplied by 2 sources, the hot water-based system, and the heat Water
pump. iFLOW calls this ‘Hybrid Mode’. To set Hybrid mode, adjust Source
Mode 3, Parameter# 11 to ‘1’ (it is default set at ‘0’).
iFLOW Hybrid
Heating Mode
Hot Water or
Item Display Range Default Heat Pump with
0=Diable, Automatic
Hybrid Mode 0 Switching
1=Enable
32 ~ 46°F
H/P Cut-Off Temp. 40
(0 ~ 8°C)
Set the lowest temperature at which you wish the heat pump
to operate (Balance Point Consideration: H/P COP and cost of
electricity at that temperature vs. gas efficiency and cost of gas).
Below that temperature, iFLOW will switch to the gas hot water
source.
R
represent the heat pump being installed.
To Condensing Unit
From Thermostat
W
iFLOW
Y1 Y2 O
ROOM AHU
G
T/H CONTROL
Y2 Y1
B
C
C
R
R
To Condensing Unit
From Thermostat
W
iFLOW
Y1 Y2 O
ROOM AHU
G
T/H CONTROL
Y2 Y1
C
C
C
H/P
O
CONDENSING
Y
UNIT
R
C
CONDENSING
● On a call for cooling, the iFLOW will energize (24VAC output) at
Y
UNIT
Y1, Y2 at the dedicated output contact (not at thermostat connection)
R
to call the compressor on. The heat pump will deliver cooling.
● On a call for cooling, the iFLOW will energize (24VAC output) Notes
Y1, Y2 and B at the dedicated output contact (not at thermostat
connection) to call the compressor ‘on’ and to activate the reversing ● The signal for the reversing valve will come directly from the
valve respectively. The heat pump will deliver cooling. iFLOW to the Heat pump; as such, do not connect anything to the O
and B contacts at the thermostat; they can be ignored
Heat
Exchanger Ensure proper CFM, GPM. Make
sure no restriction of water flow
Water temperature delta t below
021 H/ex Overheating and airflow. Check sensor. Replace
3°F
if necessary. Check filter. Check
pump operation.
Insufficient or no heat:
• Filter or coil may be dirty. Refer to maintenance section for filter replacement and coil cleaning.
• Air trapped in the heating loop. Purge system.
• Inlet and outlet connections to air handler are backward. Reverse connections.
• Supply temperature is set too low. Check the water temperature.
• There is a restriction in the heating loop. Remove restriction. The check valve may be stuck. Valves may be too restrictive or left partially
closed after purging.
Freeze Protection:
This feature is initiated by extremely low air temperatures and is detected by the ambient air sensor.
Cooling Lockout:
This feature is initiated after three freeze protection cycles occur within a single cooling cycle, or if three freeze cycles occur when a cooling
cycle is not in progress. A freeze protection cycle is when the air handler A/C coil freeze sensor is triggered by unacceptably low discharge air
temperature.
Assemble Diagram
0014RC11A iFLH-140000
7 Right Panel 0016RC11A iFLH-160000
0018RC11A iFLH-180000
0014RG00A iFLH-140000
7-1 Right Panel Heat Exchange Guide 0016RG00A iFLH-160000
0018RG00A iFLH-180000
0014RC00A iFLH-140000
8 Rear Cover 0016RC00A iFLH-160000
0018RC00A iFLH-180000
0014BC00A iFLH-140000
9 Bottom Plate 0016BC00A iFLH-160000
0018BC00A iFLH-180000
0014TC00A iFLH-140000
10 Top Plate 0016TC00A iFLH-160000
0018TC00A iFLH-180000
0014MF00A iFLH-140000
11 Middle Frame 0016MF00A iFLH-160000
0018MF00A iFLH-180000
Outdoor
Sensor An� Scald
Valve
Check
Heat Pump Circulator Valve Flow
with Switch
Check Valve Air Purge
Valve
Expansion
Tank Cold
Water
Heat Pump
Expansion
Tank
Tank
Water Heater
Cold
Water
Expansion
Tank
Check Cold
Circulator Water
with Valve
Check Valve Air Purge
Valve
Expansion
Tank
Tank
Water Heater
Air
Elliminator
Circulator
Expansion
Tank
Air
Elliminator Cold
Water
DHW
Circulator Circulator
with with
Check Valve Check Valve
Cold
Water
Circulator Circulator
with with
Check Valve Check Valve Cold
Water
DHW
34
AND RETURN
TO HEATING COIL
MIN. 2’
DEVELOPED
CHECK VALVE LENGTH TYPE L
COPPER FROM SHUT OFF VALVE HOT
WATER HEATER WATER
For the commonwealth of Massachusetts:
COIL
AUTOMATIC TEMPERING DEVICE SHUT OFF
MUST BE INSTALLED BELOW VALVE
THE TOP OF THE WATER
HEATER AS PER MANUFACTURER’S CHECK NSF-61PRODUCT
RECOMMENDATIONS VALVE APPROVED PUMP
CONNECTIONS ELECTRONICALLY CONTROLED AHU CONTROL BOARD
TANK PUMP TIMER. ACTIVATES
WATER HEATER EVERY 6 HOURS FOR 60 SECONDS.
WIRE TO PRODUCT APPROVED PUMP
SYSTEM INSTALLED WITH REVERSE ACTING
AQUASTAT TO SHUT OFF FAN. SUGGESTED
1. Terms of Standard Warranty: All iFLOW air handler parts are warranted and are to be free from defect in materials or faulty workmanship
for a 36month period from the date of original installation subject to the Conditions of Warranty set out below. When the original date of
installation cannot be determined, the warranty will be deemed to begin six months after the date of manufacture. Replacement parts will only
carry the unexpired portion of the warranty.
2. Warranty Procedure: Warranty parts shall be replaced by a qualified local contractor or dealer and will require the following information:
Model number, serial number, date of installation and an accurate description of the problem. Contractor or dealer will contact a local iFLOW
distributor for replacement parts.
3. Conditions of Warranty: iFLOW assumes no costs for warranty service or costs associated with the replacement of parts. This warranty
does not include labor, including diagnostic labor nor any freight associated with the repair service, or sales tax that might be incurred by
the purchaser under this warranty. This warranty does not cover defects caused by improper installation, modifications, alterations, abuse or
accident to, or misuse of the product or its operation in a manner contrary to the instructions included with this unit at the time of shipment,
or failure to perform maintenance as detailed in aforementioned instructions. This warranty will not cover normal maintenance, equipment
that has been moved from its original installation location, operated beyond rated capacity and at voltages other than the rate specified in the
nameplate, acts of God such as floods, winds, fires and lightning, and exposed to corrosive elements such as salt, chlorine, fluorine or other
damaging chemicals. This warranty will not cover part deficiencies due to lime or scale deposits. This warranty will not apply to damage or
defect resulting from operation with system components other than those specified in the installation instructions, which are not authorized in
writing by iFLOW manufacturing.
4. Limitations of Warranty: iFLOW manufacturing makes no express warranties other than the warranties set out above. All implied warranties
including the implied warranties of merchantability and fitness for a particular purpose are excluded to the extent legally permissible, or are
limited to a period of ONE year. Should such exclusion or limitation of warranty be unenforceable, such implied warranties are in any event
limited to the duration of the express warranty, set forth above. Liability for incidental, punitive and/or consequential damages, whether arising
out of breach warranty, breach of contract, negligence or otherwise, is excluded.
2) Contact Info
www.iflowhvac.com / 1-800-985-9227