Specification of Home UPS1.2KVA 8KVA
Specification of Home UPS1.2KVA 8KVA
Specification of Home UPS1.2KVA 8KVA
2KVA~ 8KVA
Capacity VA / Watt 1.2KVA/800W 2.4KVA/1600W 3.6KVA/2400W 5KVA/4000W 6KVA/6000W 8KVA/8000W
Nominal Voltage 110/115/120 or 220/230/240Vac 220/230/240Vac
Acceptable Voltage
60~135Vac/120~270Vac 120~270Vac
Range
Frequency 45Hz ~ 70Hz Auto-sensing
Input Undervoltage
60Vac+/-2%/120Vac+/-2% 120Vac+/-2%
Voltage Range Transfer
Undervoltage Return 65Vac+/-2%/130Vac+/-2% 130Vac+/-2%
Overvoltage Transfer 135Vac+/-2%/270Vac+/-2% 270Vac+/-2%
Overvoltage Return 130Vac+/-2%/260Vac+/-2% 260Vac+/-2%
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage Regulation(Bat. Mode) <3% RMS for entire battery voltge range
1
2. SAFTY INSTRUCTION 2.4 Operation
2.1 Transporting 1. Do not disconnect the mains cable on the UPS system or the building wiring
1. Disconnect all power cables if necessary. socket outlet during operations since this would cancel the protective
2. Be careful not to damage the UPS while transporting. earthing of the UPS system and of all connected loads.
3. Don‘t move the UPS upside down. 2. The UPS has its own internal power source (batteries). The output terminals
4. Please transport the UPS system only in the original packaging (to protect may be live even when the UPS is not connected to the AC supply.
against shock and impact). 3. Ensure that no fluids or other foreign objects can enter the UPS system.
1. Do not put the UPS on rugged or declined surface. 1. Caution - risk of electric shock.
2. Do not install the UPS system near water or in damp environments. Even after the unit is disconnected from the mains power supply (building
3. Do not install the UPS system where it would be exposed to direct sunlight wiring socket outlet), components inside the UPS system are still connected
or near heat. to the battery and are still electrically live and dangerous. Before carrying out
4. Do not block off ventilation openings in the UPS system’s housing and don’t any kind of servicing and/or maintenance, disconnect the batteries and verify
5. Keep the UPS far away from heat emitting sources. 2. Batteries may cause electric shock and have a high short-circuit current.
6. Do not expose it to corrosive gas. Please take the precautionary measures specified below and any other
measures necessary when working with batteries:
7. Ambient temperature : 0℃ - 40℃
- remove wristwatches, rings and other metal objects
2.3 Installation - use only tools with insulated grips and handles.
1. Connect the UPS system only to an earthed shockproof socket outlet.
2. Place cables in such a way that no one can step on or trip over them.
2 3
3. CABLE CONNECTION 4. SYSTEM DESCRIPTION
3.2 Connection
1. UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket
with protection against electric current, and pay attention to the capacity of 1. LCD Display: This indicates the UPS operation information, including UPS
the socket. status, input/output voltage, input/output frequency, battery voltage,
2. UPS Output Connection battery capacity left, output load, inside temperature, and the times of
The output of this model is with socket-types only (NEMA or IEC). Simply history events.
plug the load power cord to the output sockets to complete connection. 2. Up-key: Use to select upward the UPS status on LCD Display.
3. Down-key: Use to select downward the UPS status on LCD Display.
Beside, press it simultaneously with the Up-key to switch off the UPS.
4. Enter-Key: It is pressed with the Down-key to turn on the UPS. In battery
operation mode, press it with Up-key at the same time to disable the
buzzer. Beside, it is pressed to confirm and enter the item selected.
5. Fault LED (red): To indicate the UPS is in fault condition because of
inverter shutdown or over-temperature.
4 5
6. Warning LED (yellow): To indicate the UPS is in the status of overload,
bypass and battery back-up. 2.4/3.6KVA Rack Mount Type
6 7
1.2KVA Wall Mounted Type 2.4/3.6KVA Wall Mounted Type
8 9
4. LCD Display Menu
5. UPS OPERATION
Use Up/Down key to select menu-displays of the LCD described below. This
5.1 Check Prior to Start Up screen will refresh once the system power is enabled.
1. Ensure the UPS is in a suitable positioning.
Rated Spec Status
2. Check input cord is secured.
3. Make sure the load is disconnected or in the “OFF” position.
4. Check if input voltage meets the UPS rating required.
3. When the Down-key and the Up-key are pressed simultaneously for 3
seconds, the inverter will be turned off after two beeps and the UPS is on
the standby status (LCD display illuminates and Normal LED is blinking)
until AC source is disconnected.
10 11
Battery Status
12 13
6. TROUBLE SHOOTING GUIDE
6.1 For LCD Model
Charging Current Adjust
The following guideline may be helpful for basic problem solving.
A. In this screen, press Enter-key to
No. UPS STATUS POSSIBLE CAUSE ACTION
enter the following steps for
AC utility power is 1. Charger PCB is 1. Replace the
general battery AH adjustment.
normal. UPS is running damaged. charger PCB.
1 normally, but fault LED
2. Fan is damaged. 2. Replace the fan.
lits up. Buzzer beeps
3. Unknown 3. Restart UPS
continuously.
B. The cursor (→) will pop up to
AC utility power is Overload Please reduce the
indicate the battery AH newly
normal but UPS is critical load to
selected. 100%< load< 125%
3 overloaded. Warning <100%.
LED lits up and buzzer
C. Use Up or Down-key to select
beeps per second.
the battery AH ( 100AH, 200AH,
300AH, 400AH, and 600AH AC utility power is Overload Please reduce the
selectable). Press Enter-key to normal. Warning LED critical load to
125%< load<150%
confirm your battery AH. 4 does not fade out and <100%.
buzzer beeps per 0.5
D. Once the correct battery AH is second.
selected, press Enter-key again AC utility power is Overload Please reduce the
to save the selection. normal. Warning LED critical load to
150%< load
5
lits up and buzzer <100%.
beeps continuously.
14 15
7. OPERATION MODES OF THE UPS
No. UPS STATUS POSSIBLE CAUSE ACTION 7.1 UPS System Block Diagram
16 17
8. SPECIFICATION OF HOME UPS
7.3 AC Utility Failure (Battery Mode) Home Home Home
Model
The AC output comes from battery, passing through DC/AC inverter and UPS-1.2K UPS-2.4K UPS-3.6K
1.2KVA / 2.4KVA / 3.6KVA /
static switch within the battery backup time. Capacity VA / Watt
800W 1600W 2400W
Acceptable Voltage
120-275Vac ; 60-135Vac
Range
Input
Voltage Line Low Transfer 120VAC ± 2% ; 60VAC ± 2%
Range
Line Low Return 130VAC ± 2% ; 65VAC ± 2%
Frequency Regulation
±0.1Hz
(Batt. Mode)
18 19
Home Home Home
Model
UPS-1.2K UPS-2.4K UPS-3.6K
1.2KVA / 2.4KVA / 3.6KVA /
Capacity VA / Watt
800W 1600W 2400W
UPS status, I/P&O/P Voltage Frequency,
Load%,
LCD
Battery Voltage & %, Charge current,
Display LCD
Temperature, Model
20 21
22 23