Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Specification of Home UPS1.2KVA 8KVA

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Specification of Home UPS1.

2KVA~ 8KVA
Capacity VA / Watt 1.2KVA/800W 2.4KVA/1600W 3.6KVA/2400W 5KVA/4000W 6KVA/6000W 8KVA/8000W
Nominal Voltage 110/115/120 or 220/230/240Vac 220/230/240Vac
Acceptable Voltage
60~135Vac/120~270Vac 120~270Vac
Range
Frequency 45Hz ~ 70Hz Auto-sensing
Input Undervoltage
60Vac+/-2%/120Vac+/-2% 120Vac+/-2%
Voltage Range Transfer
Undervoltage Return 65Vac+/-2%/130Vac+/-2% 130Vac+/-2%
Overvoltage Transfer 135Vac+/-2%/270Vac+/-2% 270Vac+/-2%
Overvoltage Return 130Vac+/-2%/260Vac+/-2% 260Vac+/-2%
Voltage 110/115/120Vac or 220/230/240Vac re-settable via LCD panel
Voltage Regulation(Bat. Mode) <3% RMS for entire battery voltge range

Frequency Line Mode 50Hz or 60Hz


Regulation Battery Mode ±0.1Hz
Power Factor 0.67 0.8 1.0
Wave form Pure Sine wave
Effeciency >75% >80%
Overload Line Mode 110%~150% for 30 sec; >150% for 200ms, then UPS Shuts Down
Protection Battery Mode 110%~150% for 30 sec; >150% for 200ms, then UPS Shuts Down
Short Circuit Line Mode Circuit Breaker
Protection Battery Mode Electronic Circuit
DC Start Cold Start Yes
Transfer Time Typical < 8 ms.
Battery Battery Voltage 12Vdc 24Vdc 24Vdc 24Vdc 48Vdc 48Vdc
Backup Time According to the batteries connected
Recharging current >40A >50A >60A
UPS status, I/P&O/P Voltage Frequency, Load Level,
LCD
Display LCD Battery Voltage & Level, Temperature, Model
LED Normal (Green), Warning (Amber), Fault (Red)
Battery Mode Beeping every 4 seconds
Low Battery Beeping every second
Audible Alarm
UPS Fault Beeping Continuously
Overload Beeping twice per second
Optional Configuration
Operation Temperature 0-40 degree C; 32-104 degree F
Environment Relative Humidity 0-95% non-condensing
Audible Noise Less than 55dBA (at 1M)
Wall Mounted Type(W*H*D)mm 298*400*150 298*450*190 298*450*190 415*600*260 415*600*260 415*600*260
Wall Mounted Type Net Weight (Kgs) 12 24 31.5 49.2 51.4 53.6
Physical
Rack Mounted Type(W*H*D)mm 440*132*290 440*132*360 440*132*360
Rack Mounted Type Net Weight N/A
14.8 28 31
(Kgs)
Safety Standard EN62040-1-1
Safety
EMC EN62040-2
Conformance
Marks CE, cUL, UL

Specifications are subjected to change without prior notice.


1. INTRODUCTION

1.1 General Description


CONTENTS The Home UPS, a powerful all-in-one solution, delivers unsurpassed clean
true sine wave output power and combines this with a selectable multistage
battery charging current. Applicable for any kind of loads such as air
1. INTRODUCTION .............................................……......... 1
conditioner, home appliances, consumer electronic and office equipments.
2. SAFTY INSTRUCTION...................……...………….….... 2 This series features a durable&continuous 24 operation.
The built-in 5-stage intelligent charger automatically charges any type of
3. CABLE CONNECTION..........................……..……..…..... 4
batteries without the risk of overcharge. The compact&modular design
4. SYSTEM DESCRIPTION.............……........…….......…... 5 makes utility interactive installations easier and more cost effective. It is a
high quality product that offers the best price/performance ratio in the
5. UPS OPERATION .........................................……........... 10 industry.
1.2 Key features
6. TROUBLE SHOOTING GUIDE.......................….….....… 15
1. Multiple microprocessor design base.
7. OPERATION MODES OF THE UPS ..............…….......... 17 2. Compatible with both linear&non-linear load.
3. Stronger charger to support batteries of 500AH up.
8. SPECIFICATION OF HOME UPS..................…......... 19 4. 24 hours operation on the inverter.
5. DC start and automatic self-diagnostic function.
6. THD less than 3%.
7. High efficiency design to save electricity.
8. Low heat dissipation in long time operation
9. Design to operate under harsh environment
10 3U 19” Rack Mount or WALL Mounted design
1.3 Important Notices
1. Read instructions carefully before operating the UPS.
2. UPS power connect instruction should be followed.
3. Please don‘t open the case to prevent danger.
5. Retain the load within the rating of UPS to prevent faults.
6. Keep the UPS clean and dry.

1
2. SAFTY INSTRUCTION 2.4 Operation

2.1 Transporting 1. Do not disconnect the mains cable on the UPS system or the building wiring

1. Disconnect all power cables if necessary. socket outlet during operations since this would cancel the protective

2. Be careful not to damage the UPS while transporting. earthing of the UPS system and of all connected loads.

3. Don‘t move the UPS upside down. 2. The UPS has its own internal power source (batteries). The output terminals

4. Please transport the UPS system only in the original packaging (to protect may be live even when the UPS is not connected to the AC supply.

against shock and impact). 3. Ensure that no fluids or other foreign objects can enter the UPS system.

2.2 Positioning 2.5 Maintenance and Service

1. Do not put the UPS on rugged or declined surface. 1. Caution - risk of electric shock.

2. Do not install the UPS system near water or in damp environments. Even after the unit is disconnected from the mains power supply (building

3. Do not install the UPS system where it would be exposed to direct sunlight wiring socket outlet), components inside the UPS system are still connected

or near heat. to the battery and are still electrically live and dangerous. Before carrying out

4. Do not block off ventilation openings in the UPS system’s housing and don’t any kind of servicing and/or maintenance, disconnect the batteries and verify

leave objects on the top of the UPS. that no current is present.

5. Keep the UPS far away from heat emitting sources. 2. Batteries may cause electric shock and have a high short-circuit current.

6. Do not expose it to corrosive gas. Please take the precautionary measures specified below and any other
measures necessary when working with batteries:
7. Ambient temperature : 0℃ - 40℃
- remove wristwatches, rings and other metal objects
2.3 Installation - use only tools with insulated grips and handles.
1. Connect the UPS system only to an earthed shockproof socket outlet.
2. Place cables in such a way that no one can step on or trip over them.

2 3
3. CABLE CONNECTION 4. SYSTEM DESCRIPTION

3.1 Inspection 4.1 Front Panel Description for LCD Model


1. The system may be installed and wired only by qualified electricians in
accordance with applicable safety regulations.
2. When installing the electrical wiring, please note the nominal amperage of
your incoming feeder.
3. Inspect the packaging carton and its contents for damage. Please inform
the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
4. Please ensure that the incoming feeder is isolated and secured to prevent
it from being switched back on again.

3.2 Connection
1. UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket
with protection against electric current, and pay attention to the capacity of 1. LCD Display: This indicates the UPS operation information, including UPS
the socket. status, input/output voltage, input/output frequency, battery voltage,
2. UPS Output Connection battery capacity left, output load, inside temperature, and the times of
The output of this model is with socket-types only (NEMA or IEC). Simply history events.
plug the load power cord to the output sockets to complete connection. 2. Up-key: Use to select upward the UPS status on LCD Display.
3. Down-key: Use to select downward the UPS status on LCD Display.
Beside, press it simultaneously with the Up-key to switch off the UPS.
4. Enter-Key: It is pressed with the Down-key to turn on the UPS. In battery
operation mode, press it with Up-key at the same time to disable the
buzzer. Beside, it is pressed to confirm and enter the item selected.
5. Fault LED (red): To indicate the UPS is in fault condition because of
inverter shutdown or over-temperature.

4 5
6. Warning LED (yellow): To indicate the UPS is in the status of overload,
bypass and battery back-up. 2.4/3.6KVA Rack Mount Type

7. Normal LED (green): To indicate the UPS is operating normally.


8. ON/TEST/MUTE key: It should be pressed with the control key
simultaneously to switch on UPS, do UPS auto-test in normal AC mode
and turn off the buzzer in battery operation.

4.2 Outline Description

1.2KVA Rack Mount Type

6 7
1.2KVA Wall Mounted Type 2.4/3.6KVA Wall Mounted Type

8 9
4. LCD Display Menu
5. UPS OPERATION
Use Up/Down key to select menu-displays of the LCD described below. This
5.1 Check Prior to Start Up screen will refresh once the system power is enabled.
1. Ensure the UPS is in a suitable positioning.
Rated Spec Status
2. Check input cord is secured.
3. Make sure the load is disconnected or in the “OFF” position.
4. Check if input voltage meets the UPS rating required.

5.2 Storage Instruction


Disconnect input power in rear panel if you will not use it for long period. If the
UPS is stored over 3 months, please keep supplying power to the UPS for at
least 24 hours to ensure battery fully recharged.

5.3 Operation Procedure for LCD Model Voltage


Please follow the instructions below for UPS operation.
1. Once the AC source is connected, the
LCD Display shall light up immediately
to display first the main menu of
greeting context and the Normal LED is
blinking to indicate ready to switch on
the inverter.
Frequency

2. By pressing the Enter-key and the Down-key simultaneously for 3 seconds,


the UPS will start up after two beeps and Normal LED lights up to indicate
the power is from its inverter to the load.

3. When the Down-key and the Up-key are pressed simultaneously for 3
seconds, the inverter will be turned off after two beeps and the UPS is on
the standby status (LCD display illuminates and Normal LED is blinking)
until AC source is disconnected.

10 11
Battery Status

Output Voltage & Frequency Adjust

A. In this screen, press Enter-key to


enter the following steps for
output voltage and frequency
adjustment.

Output Power Temperature


B. The cursor (→) will pop up to
indicate the output voltage and
frequency newly selected.

C. Use Up or Down-key to adjust


the output voltage (if 220V
configure, 220V, 230V, and 240V
History Record is selectable; if 110V configure,
110V, 115V, and 120V is
selectable). Press Enter-key to
confirm voltage and then the
cursor will move to frequency
selection. The output frequency
(50Hz or 60Hz) can be adjusted
by the same key operation.

D. Once the correct voltage is


selected, press Enter-key again
to save the selection.

12 13
6. TROUBLE SHOOTING GUIDE
6.1 For LCD Model
Charging Current Adjust
The following guideline may be helpful for basic problem solving.
A. In this screen, press Enter-key to
No. UPS STATUS POSSIBLE CAUSE ACTION
enter the following steps for
AC utility power is 1. Charger PCB is 1. Replace the
general battery AH adjustment.
normal. UPS is running damaged. charger PCB.
1 normally, but fault LED
2. Fan is damaged. 2. Replace the fan.
lits up. Buzzer beeps
3. Unknown 3. Restart UPS
continuously.
B. The cursor (→) will pop up to
AC utility power is Overload Please reduce the
indicate the battery AH newly
normal but UPS is critical load to
selected. 100%< load< 125%
3 overloaded. Warning <100%.
LED lits up and buzzer
C. Use Up or Down-key to select
beeps per second.
the battery AH ( 100AH, 200AH,
300AH, 400AH, and 600AH AC utility power is Overload Please reduce the
selectable). Press Enter-key to normal. Warning LED critical load to
125%< load<150%
confirm your battery AH. 4 does not fade out and <100%.
buzzer beeps per 0.5
D. Once the correct battery AH is second.
selected, press Enter-key again AC utility power is Overload Please reduce the
to save the selection. normal. Warning LED critical load to
150%< load
5
lits up and buzzer <100%.
beeps continuously.

14 15
7. OPERATION MODES OF THE UPS
No. UPS STATUS POSSIBLE CAUSE ACTION 7.1 UPS System Block Diagram

AC utility power 1. AC utility power 1. Reduce the less


fails .The load is failure. critical load in
supplied by battery order to extend
2. AC input
6 power. Buzzer alarm backup time.
connection may
sounds every 4
be not correct. 2. Please check
seconds.
the rated input or
connected line.

AC utility fails. UPS is Battery power is UPS will shut


in battery backup approaching low down
7.2 Normal Operation
mode. Buzzer alarm level. automatically.
7 There are two main loops when AC utility is normal: the AC loop and the
beeps every second. Please save data
battery charging loop. The AC output power comes from AC utility input and
or turn off the
passes through static switch to support power to load. The battery charging
loads soon.
voltage comes from AC utility input and converted by AC/DC charger to
AC utility power fails. Battery runs out UPS will restart up support battery-charging power.
UPS has shut down when AC utility
8
automatically. power is restored.

16 17
8. SPECIFICATION OF HOME UPS
7.3 AC Utility Failure (Battery Mode) Home Home Home
Model
The AC output comes from battery, passing through DC/AC inverter and UPS-1.2K UPS-2.4K UPS-3.6K
1.2KVA / 2.4KVA / 3.6KVA /
static switch within the battery backup time. Capacity VA / Watt
800W 1600W 2400W

Nominal Voltage 220Vac

Acceptable Voltage
120-275Vac ; 60-135Vac
Range

Frequency 50Hz / 60Hz ( 45Hz - 70Hz)

Input
Voltage Line Low Transfer 120VAC ± 2% ; 60VAC ± 2%
Range
Line Low Return 130VAC ± 2% ; 65VAC ± 2%

Line High Transfer 275VAC ± 2% ; 135VAC ± 2%

Line High Return 260VAC ± 2% ; 130VAC ± 2%

220Vac (230V or 240VAC re-settable via LCD


panel);
Voltage
110Vac (115V or 120VAC re-settable via LCD
panel)
Voltage Regulation
< 3% RMS for entire battery voltage range
(Batt. Mode)
Output Frequency 50Hz or 60Hz

Frequency Regulation
±0.1Hz
(Batt. Mode)

Power Factor 0.8

Waveform Pure Sinewave

Transfer Time Typical < 8 ms.

Battery Voltage 12Vdc 24Vdc 24Vdc

Backup Time (at full load) long time available


Battery

Max. Charging Current


> 40A > 50A
(5 steps selectable)

18 19
Home Home Home
Model
UPS-1.2K UPS-2.4K UPS-3.6K
1.2KVA / 2.4KVA / 3.6KVA /
Capacity VA / Watt
800W 1600W 2400W
UPS status, I/P&O/P Voltage Frequency,
Load%,
LCD
Battery Voltage & %, Charge current,
Display LCD
Temperature, Model

LED Normal (Green), Warning (Yellow), Fault (Red)

Battery Mode Beeping every 4 seconds

Low Battery Beeping every second


Audible Alarm
UPS Fault Beeping Continuously

Overload Beeping twice per second

Operation Temperature 0-40 degree C; 32-104 degree F

Environment Relative Humidity 0-95% non-dondensing

Audible Noise Less than 55dBA (at 1M)

Net Weigh (Kgs) 12 24 31.50

Physical (WxHxD)mm Rack Mount 440*132*292 440*132*360 440*132*360

(WxHxD)mm Wall Mounted 298*390*149 298*450*190 298*450*190

Specifications are subjected to change without prior notice.

20 21
22 23

You might also like