Section 14510 - Shaftless Screw Conveyors City of San Diego, CWP Guidelines Part 1 - General
Section 14510 - Shaftless Screw Conveyors City of San Diego, CWP Guidelines Part 1 - General
Section 14510 - Shaftless Screw Conveyors City of San Diego, CWP Guidelines Part 1 - General
PART 1 -- GENERAL
A. The WORK of this Section includes providing shaftless screw conveyors including electric motors,
drives, controls, instrumentation, and other appurtenances as indicated and required to provide a
complete and operable system with no spillage of sludge.
B. The WORK also requires that one manufacturer be made responsible for furnishing the WORK of this
Section, but without altering or modifying the CONTRACTOR'S responsibilities under the Contract
Documents.
C. The WORK additionally requires that the one responsible manufacturer shall manufacture the principal
elements and components including, as a minimum, the shaftless screw conveyors and troughs and shall
be responsible for the suitability of the equipment for the intended application.
D. The WORK also includes coordination of design, assembly, testing and installation.
A. The WORK of the following Sections applies to the WORK of this Section. Other Sections of the
Specifications, not referenced below, shall also apply to the extent required for proper performance of
this WORK.
1.3 CODES
A. The WORK of this Section shall comply with the current editions of the following codes as adopted by
the City of San Diego Municipal Code:
A. Except as otherwise indicated, the current editions of the following apply to the WORK of this Section:
1. Commercial Standards:
ASTM A 36 Specification for Structural Steel
2. Manufacturer's Standards:
1. Catalogue cut sheets containing descriptive information and drawings of screw conveyors and their
components.
2. Assembly and installation drawings including shaft size, seal, coupling, anchor bolt plan, parts
nomenclature, material list, outline dimensions and shipping weights.
6. Design calculations showing dead, live, and dynamic loadings for normal and seismic conditions
certified by a registered structural engineer in the State of California.
7. Calculations for stress in the auger corresponding to torsional rating as indicated under "Design
Requirements."
8. Certifications from the manufacturer stating that the equipment complies with this Specification
and the manufacturer accepts responsibility for coordination of all equipment and services required
for proper installation and operation of the installed equipment.
A. The following shall be included in the OWNER'S MANUAL in compliance with Section 01300:
2. Instructions for field procedures for erection, adjustments, inspection, and testing.
2. Inspection, checking, and adjusting the equipment for not less than [2] days.
3. Startup and field testing for proper operation for not less than [2] days.
B. Instruction of OWNER'S Personnel: The authorized service representative shall also furnish the
indicated services for instruction of the OWNER'S personnel in the operation and maintenance of the
equipment including step-by-step troubleshooting procedures with necessary test equipment for not less
than [one] day.
1.8 QUALIFICATIONS
$#
NTS: In the paragraph below, define the terms "comparable size and complexity" for the
equipment or system specified. Requiring experience of more than one successful
project requires sound justification and prior written approval from the City Project
Manager.
#$
A. Manufacturer: Company which has supplied at least one successfully performing installation of
comparable size and complexity in the United States in the recent past. Equipment of comparable size
and complexity shall have the following characteristics: [ ].
PART 2 -- PRODUCTS
A. General: The screw conveyors shall be shaftless, screw-type units designed to transfer dewatered sludge
from the [centrifuges] to the [hopper]. The shaftless screw conveyors and components shall be designed
and constructed in accordance with the Conveyor Equipment Manufacturer's Association (CEMA)
Standard No. 350 and with the schedules at the end of this Section.
B. Safety Requirements: Screw conveyors shall comply with ANSI/ASME Safety Standards B15.1 and
B20.1, as applicable.
C. Each conveyor shall be sized to convey the indicated design material handling rate at 60 percent of the
rated capacity and 30 percent trough filling. The capacity of the drive unit shall equal the rated capacity
of the conveyor.
D. Manufacturer shall demonstrate by submission of calculations that at its torsional rating, the stress in the
extreme fiber of the auger flighting does not exceed 30 percent of the Fy value of the flight material.
Manufacturer shall also demonstrate that at 250 percent of the motor nameplate horsepower, the drive
unit cannot produce more torque that the torsional rating of the flighting.
E. Materials: Materials used in the fabrication of the equipment furnished under this Section shall
conform to the following:
4. Bolts, nuts, and washers for - Type 304 stainless steel. All threads shall be
conveyor supports and in with "Never Seeze" or equal
contact with sludge
F. Conveyor Nos. [ ] shall be constructed for a design pressure of [15] psig according to ASTM Pressure
Vessel Code.
H. Conveyor Nos. [ ] shall be insulated for protection of personnel. Insulation clips shall be provided
on the conveyor shell for attaching the insulation jacket.
A. Spiral flighting for the shaftless screw conveyors shall be designed to convey material without a center
shaft. The spiral flights shall be designed with the stability to prevent distortion and jumping in the
trough.
Spiral flighting shall have full penetration welds at all splice connections. The flights shall be fabricated
and welded on a jig to assure true alignment and shall be assembled according to the manufacturer's
recommendations. The spiral flights shall be welded to the end pipe sleeve. The spiral flights shall be
coupled to the end shafts by a pipe to shaft connection of sufficient strength to transmit thrust and/or
torsion applicable to meet performance criteria.
A. Spiral flights shall be connected to the end shafts using an end flange and a pipe sleeve to effectively
transmit torque from the drive shaft to the spiral flight. The flange and pipe sleeve shall be welded to
the spiral flights, with welded gusset plates used for additional reinforcing. Bushings shall be used
between the pipe sleeve and the end shaft, if necessary.
2.4 TROUGHS
A. Troughs shall conform to the dimensional standards of CEMA 300 and enclosure classification IIIE.
Each conveyor trough shall be fabricated from a minimum 1/4-inch steel plate. Each trough shall be
equipped with filling and discharge chutes for transferring material to or from another conveyor. Each
filling chute shall be flanged. The chutes shall be fabricated from a minimum 1/4-inch steel plate.
Equal level transfers shall be permitted. A cleanout shall be provided at the low end of the conveyor
trough. Cleanouts shall be 4-inch diameter, suitable for connection to steel drain pipe. The portion of
each trough that is not covered by the filling chute shall be covered by a minimum 12 gauge steel hinged
cover. Covers shall conform to CEMA Standard No. 300-24.
A. Plastic Liners:
1. The wear liners shall be a plastimeric material that is impregnated with molybdenum disulfide and
silicone oil capable of work hardening to a friction factor of 0.08 or less. The material shall be
1. The liners shall be fabricated of 10 gauge 316 stainless steel, insertable liner conforming to the
inside diameter of the trough, capable of withstanding temperatures up to 250 degrees F. Liner
plates shall extend not less than 3 inches above the horizontal centerline of the conveyors and shall
be bolted or clamped to the conveyor troughs as required for the application.
2. Stainless steel, Type 316, rifling bars with a hardness exceeding Brinell 250 shall be stitch-
welded, to the stainless steel liner plates, parallel to the conveyor centerlines. The rifling bars
shall form the contact surface of the shaftless augers. Spacing between bars shall be 1-1/2 inch
maximum. The bar cross section shall be 2-inch by 1/4-inch minimum. The bars shall cover a
minimum of 180 degrees of the liners.
A. Rupture discs shall be provided on screw conveyors as indicated. Rupture discs shall be made of
stainless steel suitable for cyclic and pulsing duty. The maximum operating temperature and pressure
shall be [250 degrees F] and [2 inches] of water column pressure. The rupture discs' burst pressure shall
be [5] psig.
B. Rupture disc clamps shall be capable of withstanding a minimum of [5] psi more pressure than the
rupture disc rating.
C. Rupture discs mounted on Conveyor Nos. [ ] shall be equipped with rupture detectors. They shall be
monitored and alarmed at the Programmable Logic Controller at the Operator Console.
A. Each conveyor shall be furnished complete with supports suitable for mounting as indicated and
required. The supports shall be shop fabricated from structural steel shapes and plates. Structural and
support design shall be based on seismic forces for Zone 4 with completely filled conveyor. All shop
welding shall conform to the latest standards of the American Welding Society.
A. Each screw conveyor shall be driven by an electric motor connected to a gear reducer. The gear reducer
shall be mounted to the trough end. The drive system shall be designed for starting the conveyor fully
loaded. Drive size shall be as recommended by the manufacturer. All electric motors shall be [totally
enclosed fan cooled, heavy duty]. Drive system components shall be provided such that jamming of any
components do not cause damage to the equipment.
A. Provide conveyor with an emergency stop system consisting of pull-cord switches actuated by a cable
system running the full length of both sides of the conveyor. Cables shall be orange colored, plastic-
covered steel aircraft cable. Provide all cable end fittings and all intermediate cable support eyes.
Provide cable support eyes every 10 feet. Provide switches in enclosures which are NEMA rated in
accordance with the area designations of Section 16050. Switches shall limit the required actuating force
to OSHA guidelines. The switches shall be manually set after actuation and shall provide visual
indication of operation. Switches shall be single-pole, double-throw output contact, rated for inductive
load of 5 amps at 120 VAC. Switches shall be normally closed and shall open when pull-cord switches
are actuated. Actuator arms shall be 316 stainless steel.]
A. Torque overload protection shall be provided to protect the drive components and shaftless screws from
torsional loadings exceeding the torsional rating of the shaftless auger. Current transformers shall be
provided and shall sense the current draw of the motor leads. The signals shall be transmitted to the
current overload protection devices, which are set as recommended by the equipment manufacturer.]
A. All gear reducers shall be commercially built, AGMA Class I, single, double, or triple reduction,
helical gear units with high capacity roller bearings. Bearings shall be designed for the thrust loads from
the spiral flights and shall have the AFBMA L-10 life of 100,000 hours. The reducers shall be standard
air-cooled units with no auxiliary cooling allowed. Low speed output shafts shall be chrome plated.
Shaft seals shall be tripled lipseal with taconite packing design for service conditions.
Conveyor Nos.: [ ], [ ], [ ], [ ], [ ], [ ]
B. Adjustable frequency PWM (Pulse Width Modulating) AC drives shall be provided to control the speed
of the AC drive motor required by the conveyor speed range. Speed reducing gear boxes shall be
provided as required to deliver the necessary torque and acceleration required by the conveyors.
C. Enclosure: The AC drives shall be installed in a NEMA 4X enclosure which shall be purged with
nitrogen. The enclosure shall have a 1/2-inch NPT female connection for nitrogen purge. The
enclosure shall be sized to dissipate the heat generated internally,but shall not be larger than 24 inches
by 24 inches by 12 inches deep. The following items shall be mounted on the enclosure door:
D. Controls: The AC drives shall have local and remote control modes selected by local-remote switches
located in the AC drives enclosures. The normal mode of operation shall be remote by a programmable
logic controller (PLC). In the remote mode, VFDs shall interface with the PLC as follows:
E. The microprocessor-based controls shall include the following adjustable control functions entered via
the AC drive keyboard:
1. Motor/conveyor rpm
2. Minimum speed
3. Maximum speed
4. Gain adjustment
5. Acceleration
6. Deceleration
7. Current trip
8. Torque limit
9. Signal span
10. Low frequency boost
11. Volts/Hertz
12. LED/LCD status indicator programmed to display conveyor rpm
F. AC Drive Controllers: The AC drive controllers shall be all solid state inverters utilizing silicon
semiconductors and transistors which shall be standard catalog items of the device manufacturer. The
power circuits shall consist of a phase controlled rectifier, a filter choke, and an auto-sequential force
of auxiliary communicated inverter.
The inverter output voltages shall be controlled such that they vary directly proportional to the output
frequencies. The solid state AC drives shall be capable of attaining efficiencies in excess of 95 percent
at full speed and in excess in 80 percent at 50 percent speed.
The AC drives shall be designed to operate at full output power over the maximum specified input
voltages and frequency fluctuations, in ambient conditions indicated. No external venting or heat
exchangers shall be required. The AC drives shall operate from 480 volt, 3-phase, 3-wire, 60 Hertz
input power.
Normal operation shall not be affected by input power fluctuations between plus or minus 10 percent
voltage and plus or minus 2 Hertz. Voltage regulations shall be plus or minus 1 percent of setpoint
voltage. Speed regulation shall be 1 percent of full speed due to variables other than motor load.
The AC drives shall be equipped with a diagnostic system capable of troubleshooting problems down
to a component replacement level, as well as being able to monitor inverter output, process input, and
power line parameters. In addition, an indication shall be provided for each protective function to show
an "actuated" status, malfunction, or trouble.
G. Protective Devices: The AC drives shall have transient surge protection to a minimum of 10,000 volt,
50 joules, without failure. They shall meet or exceed the Institute of Electrical and Electronic Engineers
(IEEE) Surge Withstand Capability Test, IEEE Std. 472 without failure. For the purposes of this
Section, failure is defined as loss of components in the AC drive, including power semiconductors, logic
components, or fuses.
A. When recommended by the manufacturer, bearings shall be provided on both ends of each conveyor.
End bearings shall be double pillow block and shall be mounted outside the conveyor trough. Bearings
shall be completely serviceable from outside the conveyor. Intermediate bearings will not be allowed.
A plate-type lipseal shall be provided around the shaft where the shaft passes through the trough ends.
The bearing and seals shall be capable of supporting the applicable thrust loads by means of snap rings
and shall prevent angular misalignment of the shafts. Bearings shall have an L-10 life of 100,000 hours.
A. Holddown devices shall be installed on the shaftless screw conveyors if required by the manufacturer's
design or if excessive vertical movement of the spiral flights occurs during the first year of operation.
Evidence of excessive vertical movement shall include wear on the trough cover plates. Holddown
devices shall be of welded steel construction supported by the conveyor trough, and be designed to
minimize material flow interruption. The holddown devices shall be designed by the manufacturer.
2.16 STRUCTURAL
A. The ratio of the unbraced length to least radius of gyration (slenderness ratio) shall not exceed 120 for
a compression member and shall not exceed 240 for any tension member (of angles about the Z-Z axis).
In addition, all structural members and connections shall be designed so that the unit stresses will not
exceed AISC allowable stresses by more than 1/3 when subject to loading of twice the running torque
of the drive motor.
2.17 SUPPORTS
A. Supports shall be provided within 2 feet of the drive units and at locations no more than 12 feet apart
along the conveyor. Support loads shall be based on a completely filled trough plus dead weight of the
equipment designed for Zone 4 seismic forces as per UBC.
A. Spare Parts: The WORK also includes furnishing the following spare parts for each conveyor:
A. The conveyor drive system shall be assembled and given no-load running tests at the manufacturer's
plant before shipment.
B. The OWNER and the CONSTRUCTION MANAGER (at the option of either) reserve the right to
witness factory tests. The CONTRACTOR shall notify the CONSTRUCTION MANAGER 2 weeks
in advance of the testing date.
2.20 MANUFACTURERS
A. Products shall be of the following manufacture, type or model, as indicated (or equal):
2. Gear reducers:
SEW Eurodrive
Nord Gear
Falk
4. AC drives:
Allen Bradley, "Bulletin 1336"
Eaton Dynamics, "Model AF-5000+"
6. Motion detectors:
Milltronics
PART 3 -- EXECUTION
3.1 INSTALLATION
A. The equipment shall be field tested after installation to demonstrate satisfactory operation without
causing excessive noise, vibration, and overheating of the bearings. The field testing shall be performed
1. Start up, check, and operate the equipment over the entire speed range.
3. The field testing will be witnessed by the CONSTRUCTION MANAGER. In the event any of
the equipment fails to meet the above test requirements, it shall be modified and retested until it
meets the requirements of these Specifications. The manufacturer shall then certify in writing that
the equipment has been satisfactorily tested, and that all final adjustments thereto have been made.
Certification shall include the date of the final acceptance test and a listing of all persons present
during tests, and resulting test data. The costs of all work performed in this paragraph by factory-
trained representative shall be borne by the CONTRACTOR. The OWNER will pay for costs of
power and water.
SCHEDULE
No. of units - [ ]
Capacity, lbs/hr - [ ]
Pitch, inches - [ ]
Length, feet-inches - [ ][ ]
Incline, degrees - [ ]
Material conveyed - [dewatered sludge 45% solids] [dried sludge 90% solids] [
]
Density, lbs/cu ft - [ ]
Temperature, degrees F - [ ]