R-410A
REFRIGERANT
APCY-E SERIES
Screw Chillers
R-134a
REFRIGERANT
Range 78 TR to 438 TR
(274 kW to 1540 kW)
Contents
Introduction ...........................................2 Selection Procedure ...........................40
Legend.................................................. 2 Electrical Data ...................................41 Introduction
Nomenclature ...................................... 2 Typical Wiring Diagram .............................46
General Features ................................3 Power Entry Connection ..........................47
SKM APCY-E Series environment friendly
Main Component Features ...................3 Dimensional Data......................................48
(R-134a) Air Cooled Screw Chillers are
Microprocessor Control .......................4 Center Of Gravity....................................55
designed and manufactured to provide utmost
Optional Features ................................6 Loading Points..........................................56
Sound Data................................................62 performance, efficiency, reliability, to meet
General Data ....................................8
Capacity Ratings ................................12 Location And Space Requirements .......63 the requirements.
IPLV Calculation ...............................36 Water Piping Practices ..............................64
Capacity Correction &Limits ..............38 Guide Specifications ..............................68 APCY-E Series Chillers have low noise
Evaporator Water Pressure Drop.......39 and minimum vibration ideal for vast range
of applications including hotels, high-rise
buildings, stores, hospitals, and modern
cooling applications of modern manufacturing
industries.
Legend
APCY-E units are factory assembled, leak
The following legends are used throughout this manual:
tested, evacuated, internally wired and fully
cfm...........Cubic feet per minute L/S...........Liters per second charged with refrigerant R-134a. Every unit
EER.........Energy Efficiency Ratio Ph............Phase is fully tested before delivery and is ready for
Hz............Hertz PI.............Power Input of Compressor
kW...........Kilowatts tonR .........Tons of Refrigeration installation.
kg.............Kilogram V..............Volts
lbs............Pounds APCY-E Chillers are designed and
manufactured as per SKM Quality,
Environment, Occupational, Health and
Safety Management Systems that confirms
Nomenclature with ISO 9001:2015, ISO 14001:2015, and
OHSAS 18001:2007.
APC Y 5 155 D E Y
Power Supply Code APCY-E Chillers are ‘’Certified in accordance
Y: 380-400V/3Ph/50.0Hz
Y1: 415V/3Ph/50.0Hz with the AHRI Air-Cooled Water-Chilling
P: 440V/3Ph/50.0Hz Packages Certification Program, which is
R : 380-400V/3Ph/60.0Hz
E : 460V/3Ph/60.0Hz based on AHRI Standard 550/590 (I-P) and
T: 220V/3Ph/60.0Hz AHRI Standard 551/591 (SI). Certified units
(Consult SKM)
may be found in the AHRI Directory at www.
E-Version
ahridirectory.org”
No. of Refrigeration circuits
D – Double T – Triple
Unit Size SKM provides qualified service and stock
of replacement parts in all major cities of the
Power Supply 5 : 50.0 Hz
Frequency 6 : 60.0 Hz
G.C.C. countries, Egypt, Jordan, and Pakistan.
Y-version
See back cover for details or call SKM.
Screw Compressor, R-134a
Air Cooled
Packaged Chillers SKM Air Conditioning L.L.C
2
R-134a
R-410A
REFRIGERANT
The motors are factory wired to chiller unit control panel where
Compressors the motor starters are located to control the operation of these
motors. The fans are individually statically and dynamically
APCY-E Series Chillers use high performance and high efficiency balanced at the factory. Complete fan assembly is provided with
screw compressors which are with 5 to 6 ratio screw rotor profile suitable acrylic coated fan guard.
designed specifically for modern refrigerant characteristics,
double-walled rotor housing, robust in construction and have
a very few moving parts to minimize noise and ensure rigidity. Evaporator
Screw Compressors are directly flanged on a three stage oil
separator with low oil carry over and pressure drop demister to APCY-E evaporators are direct expansion, shell and tube,
ensure minimal refrigerant dilution in the oil and maintain high with removable head, and having 2 or 3 refrigerant circuits.
oil viscosity. Oil sight glass, oil drain valve, oil heater, discharge Evaporator shell is made of steel. Tubes of copper fixed to steel
check valve, discharge stop valve are available as standard. end plates. Baffles are provided in the water flow to increase
heat transfer efficiency. Evaporators are provided with drain
Continuous (Stepless) capacity control system and automatic and vent plugs. Cooler shell is insulated with 0.75” (19mm)
start unloading are provided as standard. thick flexible closed cell insulation, K factor 0.28 Btu. in/ft².h.oF
All compressors are provided with motor winding temperature (0.04W/m.oK). Maximum working pressure of waterside is 145
protection, discharge temperature protection, phase reversal psig (1000 kPa) and refrigerant side is 239.3 psig (1650 kPa).
protection, phase failure protection and oil level protection.
Microprocessor Controller
Refrigerant Piping
The refrigeration circuit piping is fabricated from ACR grade
copper piping. Each refrigeration circuit includes filter drier,
electronic expansion valve, and shut off valve. The refrigeration
circuit suction line is insulated with ½” (13mm) wall thickness
closed cell pipe insulation.
Economizer
All units are equipped with economizer circuit. Economizer
operation improves both cooling capacity and efficiency by
increasing subcooling where part of the liquid refrigerant is
flashed to an intermediate pressure which is used to cool the
remaining liquid refrigerant. This flash refrigerant is then fed into Microprocessor control system is available for APCY-E series
a compressor where it helps to cool the vapour from the main chiller as a standard feature. Our high energy efficient chiller has
circuit. The components of an economizer cycle include a full function microprocessor control unit designed to keep the
thermostatic expansion valve, plate type heat exchanger, solenoid chiller running at its most energy efficient level. It is a rugged
valve & ECO muffler kit. microprocessor based controller that is designed for the hostile
environment of the HVAC industry.
It provides flexibility with set points and control options that can
Control Panel be selected prior to commissioning a system or when the unit is
live and functioning. Displays, alarms and other interfaces are
The unit mounted chiller control panel enclosure is fabricated accomplished in a clear and simple language that informs the
out of heavy gauge sheet steel in phosphatized powder coated user as to the status of the system. It is designed to safeguard
baked finish. The enclosure conforms to IP54 as per guidelines the system that is being controlled, eliminating the need for
in IEC 529. A hinged access door and key-fastener is provided manual intervention to provide a simple but meaningful man-
for easy access and security. The panel is factory wired in machine-interface.
accordance with NEC 430 & 440, labelled, tagged and features
220V / 240V controls. This controller provides complete operational control for the
chiller and has built-in auto diagnostic capability that can signal
• Compressors are with star-delta start depending on models. normal operation or alarm conditions as well as shutting down
• Individual compressor and condenser fan motor contactors. the chiller or system, if necessary.
4
R-134a
R-410A
REFRIGERANT
The Main Features of the controller are as follows: System Control Philosophy
• A large graphical LCD Display (2.8˝ diagonal) with back-lit The unit may be enabled or disabled manually or through the
that can be seen in bright or dim lighting. use of an external signal from a building automation system.
• A nine button generic keypad that is so user friendly, it Control is based upon leaving chilled water temperature. How fast
rarely requires a reference manual. the temperature changes is calculated and capacity decisions
• Battery backed up built in real time clock to program the are based upon the rate, the current temperature, and the control
chiller for 2 starts and 2 stops daily to provide the information temperature zone.
about the running hours of the compressors.
Capacity is never added if the system is moving toward the
• Multiple authorization levels to provide tight security of the temperature target at an acceptable rate. The unit will monitor
control system. all control functions and stage the compressor to maintain the
• Two operating schedules per each day of the week and 8 required operating capacity.
holidays.
• The system provides ‘last time’ enabled & disabled, number
of cycles, and total run hours.
Easy Accessible Measurements Include:
• Automatic Lead/Lag changeover of the compressors.
• Pump-down at the beginning and end of every circuit cycle. • Status of the chiller.
• Capacity control based on leaving chilled water temperature. • Status of each circuit/compressor.
A special control zone based on leaving water temperature • Status of condenser fans.
that reduces compressor cycling, and improved unit part
• Leaving and Entering chilled water temperature.
load efficiency.
• Suction pressure and temperature for each refrigerant
• Start/stop facility from remote through Volt Free Contact
circuit.
(VFC) .
• Discharge pressure and temperature for each refrigerant
• Common Run, Fault and remote mode operation status volt
free contacts provided for remote signalling . circuit.
• Suction and discharge superheat for each refrigerant circuit.
• Winding temperature for each compressor.
Display Information • Ampere draw for each compressor.
• Expansion valve opening percentage.
SKM APCY-E chillers offer a graphics LCD display which allows • Ambient temperature.
the operator to access different parameters of the chiller. Operator • All active set points.
can view and change the set point of chiller parameters. The
• Run time for each compressor.
graphical display has lot of features, trending is one of the key
features of graphical a display, which shows last 25 samples with • Number of compressor starts.
an appropriate scale to allow it to fit on display. • Lockout and alarm status.
• Status of water flow switch, voltage monitor, compressor
The well designed keypad with three function keys, four direction internal motor protector, oil level switch, run/stop input and
keys and two selection keys allows the operator to navigate pump down switches.
through different Menus, such as:
• Log of last 100 alarms.
• Alarms.
• Graphs.
• Setpoint.
• Service tools.
• Lockout Reset.
• Lockout Alarm.
• Password.
System Protection Volt free contacts for Run, Common fault and Auto mode
indications and provision for remote start/stop are provided as
The following system protection controls will automatically act standard feature. In addition to these, below options can be
to ensure system reliability and protection of the unit. provided if specified.
• Low suction pressure protection. • Emergency Stop – A volt free contact from BMS to chiller,
• High discharge pressure protection. which is normally closed and opens on an emergency shut
down condition. It will make the chiller to shut down immed
• High discharge temperature protection.
-iately bypassing normal shut down procedure.
• Low discharge pressure protection.
• Chilled water reset – A 0-5VDC signal from BMS to chiller,
• Low oil level protection.
which allows resetting chilled water set point around an
• High compressor motor winding temperature protection. acceptable range.
• Low superheat protection.
• High compressor ampere protection.
• Compressor internal thermal protection. BMS protocols
• Freeze protection.
• Under voltage, over voltage, phase loss, phase reversal The chiller controller is capable of interface with four major building
and phase unbalance protection. management systems, which are BACnet, Modbus, Lonworks
and Johnson N2, by adding optional hardware. This interface
• Chilled water flow loss protection.
allows to monitoring the status of chiller and individual circuits,
• Sensor error protection. all inputs and outputs, chilled water set point etc. The required
• Pump down. BMS protocol and number of chillers needs to be specified during
• Anti-recycle. the the time of order as the cost of the BMS interface involves
these parameters.
• Time delay between stages.
• 4-Levels of passwords to restrict the intentional mishandling.
Factory Installed Options
BMS Communication
Pressure Relief Valve (PRV)
BMS communication with the chiller microprocessor is possible To protect the chiller from hi-pressure in the event of failure of
through hardwired signals or major BMS protocols. primary high pressure safety mechanisms.
6
R-134a
R-410A
REFRIGERANT
Pressure Gauges (Suction / Discharge) (SDG1) Voltmeter & Selector Switch (VSS)
Suction & discharge pressure indication of each refrigerant circuit. For incoming line voltage.
Gauges are mounted outside the Control Panel.
Compressor & Evaporator Guard (CEG)
Extra Shutoff Valve (XFV) Powder coated galvanized welded mesh guard to protect
Extra Shut off valve in liquid line to fully isolate the filter drier. Compressor, Evaporator & other piping accessories.
Suction Shut off Valve (SSOV) Touch Screen Interface Monitor (TSIM)
Screw compressors are with suction shut off valves to isolate the Optional touchscreen interface designed to provide user
compressor from the evaporator, this may be beneficial when with both graphics and service mode access.
servicing the chiller.
Ammeter & Phase Selector Switch (AMPC) Options for Field Installation
To indicate running AMPS of each compressor.
Anti-vibration mounts, spring type (CAVM)
Ammeter & Phase Selector switch (AMPI) Recommended for roof mounted units or other locations in
To indicate running AMPS on main incomer of a chiller. the vicinity of occupied spaces, where noise/vibration may be
objectionable. Can be supplied loose for site installation.
BMS Interface thru protocol (BMSP)
For interacting the units with major BMS protocols such as BACnet, Hi-Lo Pressure Gauges-Loose (CSDG1)
Modbus or LON. Extra hardware may be required depending on Without piping or isolating petcocks.
the protocol.
Victaulic Coupling Kit (VCK)
Condenser Fan Motors with built-in Anti- Coupling kit with flexible joints for Evaporator Water Connection.
Condensation Heaters. (CFMA)
Where application so requires. (Consult SKM) for power supply Flange Water Connection (FWC)
440/3Ph/ 50Hz. Flange connection for Evaporator with Victaulic water connection.
8
R-134a
R-410A
REFRIGERANT
10
R-134a
R-410A
REFRIGERANT
12
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 10.00ºF Evaporator Fouling
Factor: 0.000100 h ft².ºF/Btu .
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
14
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 10.00ºF Evaporator Fouling
Factor: 0.000100 h ft².ºF/Btu .
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
16
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 10.00ºF Evaporator Fouling
Factor: 0.000100 h ft².ºF/Btu .
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
18
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 10.00ºF Evaporator Fouling
Factor: 0.000100 h ft².ºF/Btu .
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
20
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 10.00ºF Evaporator Fouling
Factor: 0.000100 h ft².ºF/Btu .
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
22
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW.
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
24
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW.
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and
MFA values given in the electrical data pages (41 to 45) should be referred for the same
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
26
R-134a
R-410A
REFRIGERANT
Legend Table 21
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
28
R-134a
R-410A
REFRIGERANT
Legend Table 22
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and
MFA values given in the electrical data pages (41 to 45) should be referred for the same
Legend Table 23
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
30
R-134a
R-410A
REFRIGERANT
Legend Table 24
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and
MFA values given in the electrical data pages (41 to 45) should be referred for the same
Legend Table 25
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
32
R-134a
R-410A
REFRIGERANT
Legend Table 26
LWT Evaporator Leaving Water Temperature. WFR Evaporator Water flow rate.
COP Coefficient of Performance WPD Evaporator Water Pressure Drop.
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and
MFA values given in the electrical data pages (41 to 45) should be referred for the same
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same
34
R-134a
R-410A
REFRIGERANT
Notes:
1.Capacity ratings are based on with the following condition. Evaporator Water Temperature Change: 5.00ºC Evaporator Fouling
Factor:0.0176m2 K/kW..
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and
MFA values given in the electrical data pages (41 to 45) should be referred for the same
IPLV CALCULATION
Legend
EER Energy Efficiency Ratio. IPLV Integrated Part Load Value.
* Condenser Entering Air Dry Bulb Temperature.
Notes:
1.Above Part-load performance is based on Standard AHRI 550/590 (I-P).
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
36
R-134a
R-410A
REFRIGERANT
IPLV CALCULATION
Notes:
1.Above Part-load performance is based on Standard AHRI 550/590 (I-P).
2.Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data pages (41 to 45) should be referred for the same.
Condenser Pressure Refrigerant Capacity ratings based on 10.00°F (IP) and 5.00°C (SI) chilled
water range. For other than this range, please use correction
Condenser PressurePressure psig 350
Refrigerant
Maximum Working factor below.
kPa
psig 2413
350
Maximum Working Pressure psig 525
kPa 2413 Range
Test Pressure Capacity Multiplier Power Multiplier
kPa
psig 3620
525 °F (IP) °C (SI)
Test Pressure
kPa 3620 Table 32 8.00 3.90 0.995 0.998
10.00 5.00 1 1
12.00 6.10 1.005 1.002
14.00 7.20 1.01 1.004
16.00 8.30 1.015 1.006
Table 34
38
R-134a
R-410A
REFRIGERANT
(kPa) Ft.Wg
(300) 100.00
B
E
C G
D
Evaporator Water Pressure Drop
F
A
(30) 10.00
(3) 1.00
10 100 1000 10000 US gpm
(0.63) (6.3) (63.1) (631) (Liter / sec )
40
R-134a
R-410A
REFRIGERANT
ELECTRICAL DATA
Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition) .
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps.
MCA Minimum Circuit Amps.(for wire sizing), complies with FLA Full Load Amps.
NEC article 440-33.
ICF Maximum Instantaneous Current Flow.
Note :
ELECTRICAL DATA
Power Supply: 415V/3PH/50Hz
Model Unit Characteristic Compressor Condenser Fan Motor
APCY
MFA MCA ICF QTY RLA LRA QTY FLA LRA
APCY5080DE 315 223 280 2 90 167 6 3.4 13
APCY5085DE 400 238 305 1+1 102 + 90 192 + 167 6 3.4 13
APCY5090DE 400 250 317 2 102 192 6 3.4 13
APCY5095DE 400 270 370 1+1 118 + 102 245 + 192 6 3.4 13
APCY5105DE 500 293 390 2 118 245 8 3.4 13
APCY5115DE 500 340 420 1+1 156 + 118 275 + 245 8 3.4 13
APCY5125DE 630 378 458 2 156 275 8 3.4 13
APCY5130DE 630 403 476 1+1 176 + 156 293 + 275 8 3.4 13
APCY5140DE 630 430 499 2 176 293 10 3.4 13
APCY5155DE 800 475 544 2 196 318 10 3.4 13
APCY5165DE 800 501 626 1+1 217 + 196 400 + 318 10 3.4 13
APCY5175DE 800 522 647 2 217 400 10 3.4 13
APCY5185DE 1000 559 699 1+1 246 + 217 452 + 400 10 3.4 13
APCY5195DE 1000 595 732 2 246 452 12 3.4 13
APCY5210DE 1000 652 778 1+1 292 + 246 498 + 452 12 3.4 13
APCY5230DE 1000 698 824 2 292 498 12 3.4 13
APCY5250DE 1250 756 916 1+1 333 + 292 587 + 498 14 3.4 13
APCY5265DE 1250 797 957 2 333 587 14 3.4 13
APCY5285DE 1250 858 1031 1+1 376 + 333 658 + 587 16 3.4 13
APCY5300DE 1600 901 1074 2 376 658 16 3.4 13
APCY5325DE 1600 979 1240 1+1 433 + 376 820 + 658 18 3.4 13
APCY5345DE 1600 1036 1297 2 433 820 18 3.4 13
APCY5365TE 1600 1069 1225 1+2 333 + 292 587 + 498 20 3.4 13
APCY5380TE 1600 1110 1269 2+1 333 + 292 587 + 498 20 3.4 13
APCY5395TE 1600 1157 1314 3 333 587 22 3.4 13
APCY5410TE 1600 1211 1385 1+2 376 + 333 658 + 587 22 3.4 13
APCY5425TE* 1800 1261 1435 2+1 376 + 333 658 + 587 24 3.4 13
Table 37
NOTE:
220-240V/1PH/50.0Hz control power must be supplied from a separate source, through field supplied and installed disconnect switch.
-For Models marked asterisk (*), refer for table 41 for optional power connection
Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition) .
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps.
MCA Minimum Circuit Amps.(for wire sizing), complies with FLA Full Load Amps.
NEC article 440-33.
ICF Maximum Instantaneous Current Flow.
Note :
42
R-134a
R-410A
REFRIGERANT
ELECTRICAL DATA
Power Supply: 440V/3PH/50Hz
Model Unit Characteristic Compressor Condenser Fan Motor
APCY
MFA MCA ICF QTY RLA LRA QTY FLA LRA
APCY5080DE 315 225 281 2 90 167 6 3.7 14
APCY5085DE 400 238 306 1+1 101 + 90 192 + 167 6 3.7 14
APCY5090DE 400 249 317 2 101 192 6 3.7 14
APCY5095DE 400 269 370 1+1 117 + 101 245 + 192 6 3.7 14
APCY5105DE 500 293 390 2 117 245 8 3.7 14
APCY5115DE 500 330 413 1+1 147 + 117 268 + 245 8 3.7 14
APCY5125DE 630 360 443 2 147 268 8 3.7 14
APCY5130DE 630 384 460 1+1 166 + 147 285 + 268 8 3.7 14
APCY5140DE 630 411 483 2 166 285 10 3.7 14
APCY5155DE 800 456 541 2 186 323 10 3.7 14
APCY5165DE 800 481 608 1+1 206 + 186 390 + 323 10 3.7 14
APCY5175DE 800 501 628 2 206 390 10 3.7 14
APCY5185DE 800 534 670 1+1 233 + 206 432 + 390 10 3.7 14
APCY5195DE 1000 569 700 2 233 432 12 3.7 14
APCY5210DE 1000 617 718 1+1 272 + 233 450 + 432 12 3.7 14
APCY5230DE 1000 656 757 2 272 450 12 3.7 14
APCY5250DE 1250 704 813 1+1 304 + 272 502 + 450 14 3.7 14
APCY5265DE 1250 736 845 2 304 502 14 3.7 14
APCY5285DE 1250 808 852 1+1 356 + 304 505 + 502 16 3.7 14
APCY5300DE 1250 860 904 2 356 505 16 3.7 14
APCY5325DE 1600 933 1025 1+1 408 + 356 623 + 505 18 3.7 14
APCY5345DE 1600 985 1077 2 408 623 18 3.7 14
APCY5365TE 1600 998 1103 1+2 304 + 272 502 + 450 20 3.7 14
APCY5380TE 1600 1030 1139 2+1 304 + 272 502 + 450 20 3.7 14
APCY5395TE 1600 1069 1175 3 304 502 22 3.7 14
APCY5410TE 1600 1134 1178 1+2 356 + 304 505 + 502 22 3.7 14
APCY5425TE 1600 1194 1237 2+1 356 + 304 505 + 502 24 3.7 14
Table 38
NOTE:
220-240V/1PH/50.0Hz control power must be supplied from a separate source, through field supplied and installed disconnect switch.
-For Models marked asterisk (*), refer for table 41 for optional power connection
Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition) .
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps.
MCA Minimum Circuit Amps.(for wire sizing), complies with FLA Full Load Amps.
NEC article 440-33.
ICF Maximum Instantaneous Current Flow.
Note :
ELECTRICAL DATA
Power Supply: 380-400V/3PH/60Hz
Model Unit Characteristic Compressor Condenser Fan Motor
APCY
MFA MCA ICF QTY RLA LRA QTY FLA LRA
APCY6095DE 500 288 346 2 118 208 6 3.8 9
APCY6100DE 500 306 390 1+1 132 + 118 252 + 208 6 3.8 9
APCY6110DE 500 320 404 2 132 252 6 3.8 9
APCY6115DE 630 350 460 1+1 153 + 132 308 + 252 7 3.8 9
APCY6125DE 630 374 485 2 153 308 8 3.8 9
APCY6135DE 800 436 525 1+1 202 + 153 348 + 308 8 3.8 9
APCY6145DE 800 485 574 2 202 348 8 3.8 9
APCY6160DE 800 526 608 1+1 229 + 202 378 + 348 10 3.8 9
APCY6170DE 800 553 635 2 229 378 10 3.8 9
APCY6185DE 1000 609 740 2 254 458 10 3.8 9
APCY6195DE 1000 648 780 1+1 285 + 254 498 + 458 10 3.8 9
APCY6205DE 1000 679 811 2 285 498 10 3.8 9
APCY6220DE 1250 738 869 1+1 326 + 285 552 + 498 12 3.8 9
APCY6230DE 1250 779 910 2 326 552 12 3.8 9
APCY6240DE 1250 779 910 2 326 552 12 3.8 9
APCY6260DE 1250 849 961 1+1 376 + 326 600 + 552 14 3.8 9
APCY6275DE 1600 899 1011 2 376 600 14 3.8 9
APCY6300DE 1600 961 1037 1+1 420 + 376 622 + 600 16 3.8 9
APCY6320DE 1600 1005 1081 2 420 622 16 3.8 9
APCY6340DE* 1800 1111 1138 1+1 498 + 420 675 + 622 18 3.8 9
APCY6360DE* 1800 1189 1216 2 498 675 18 3.8 9
APCY6385DE* 1800 1255 1315 1+1 545 + 498 770 + 675 20 3.8 9
APCY6405DE* 2000 1302 1362 2 545 770 20 3.8 9
APCY6425TE* 1800 1360 1436 1+2 420 + 376 622 + 600 22 3.8 9
APCY6445TE* 2000 1412 1487 2+1 420 + 376 622 + 600 24 3.8 9
APCY6465TE* 2000 1456 1531 3 420 622 24 3.8 9
Table 39
NOTE:
220-230V/1PH/60.0Hz control power must be supplied from a separate source, through field supplied and installed disconnect switch.
-For Models marked asterisk (*), refer for table 41 for optional power connection
Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition) .
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps.
MCA Minimum Circuit Amps.(for wire sizing), complies with FLA Full Load Amps.
NEC article 440-33.
ICF Maximum Instantaneous Current Flow.
Note :
44
R-134a
R-410A
REFRIGERANT
ELECTRICAL DATA
Power Supply: 460V/3PH/60Hz
Model Unit Characteristic Compressor Condenser Fan Motor
APCY
MFA MCA ICF QTY RLA LRA QTY FLA LRA
APCY6095DE 400 241 304 2 97 182 6 3.8 14
APCY6100DE 400 256 340 1+1 109 + 97 218 + 182 6 3.8 14
APCY6110DE 400 268 352 2 109 218 6 3.8 14
APCY6115DE 500 294 402 1+1 127 + 109 268 + 218 7 3.8 14
APCY6125DE 500 316 424 2 127 268 8 3.8 14
APCY6135DE 630 366 473 1+1 167 + 127 317 + 268 8 3.8 14
APCY6145DE 630 406 513 2 167 317 8 3.8 14
APCY6160DE 630 441 537 1+1 189 + 167 337 + 317 10 3.8 14
APCY6170DE 800 463 559 2 189 337 10 3.8 14
APCY6185DE 800 515 638 2 212 393 10 3.8 14
APCY6195DE 800 548 665 1+1 238 + 212 420 + 393 10 3.8 14
APCY6205DE 1000 574 691 2 238 420 10 3.8 14
APCY6220DE 1000 624 745 1+1 272 + 238 470 + 420 12 3.8 14
APCY6230DE 1000 658 779 2 272 470 12 3.8 14
APCY6240DE 1000 658 779 2 272 470 12 3.8 14
APCY6260DE 1250 716 821 1+1 313 + 272 508 + 470 14 3.8 14
APCY6275DE 1250 757 862 2 313 508 14 3.8 14
APCY6300DE 1250 825 935 1+1 361 + 313 578 + 508 16 3.8 14
APCY6320DE 1250 873 983 2 361 578 16 3.8 14
APCY6340DE 1600 944 997 1+1 412 + 361 588 + 578 18 3.8 14
APCY6360DE 1600 995 1048 2 412 588 18 3.8 14
APCY6385DE 1600 1076 1162 1+1 470 + 412 698 + 588 20 3.8 14
APCY6405DE 1800 1134 1220 2 470 698 20 3.8 14
APCY6425TE 1600 1161 1271 1+2 361 + 313 578 + 508 22 3.8 14
APCY6445TE 1600 1216 1327 2+1 361 + 313 578 + 508 24 3.8 14
APCY6465TE* 1800 1264 1375 3 361 578 24 3.8 14
Table 40
NOTE:
220-230V/1PH/60.0Hz control power must be supplied from a separate source, through field supplied and installed disconnect switch.
-For Models marked asterisk (*), refer for table 41 for optional power connection
Legend
MFA Maximum Fuse Amps (for fuse/circuit breaker sizing), RLA Rated Load Amps. (at worst operating condition) .
complies with NEC Article 440-22 & 430-52. LRA Locked Rotor Amps.
MCA Minimum Circuit Amps.(for wire sizing), complies with FLA Full Load Amps.
NEC article 440-33.
ICF Maximum Instantaneous Current Flow.
Note :
ANTIFREEZE THERMOSTAT
N L
CFM 2
CFM 3
CFM 4
CFM 5
C3 C2
L
FIELD SUPPLIED SEPERATE SOURCE OF CONTROL POWER SUPPLY 220V / 1PH / 50HZ.
MCB1
SS SS
MCB2 REMOTE LOCAL C3 C1
PUMP INTERLOCK
VMM
TDR
WFS
OLM
TDR
ESV
AFT
( BY OTHERS )
MP
CR
SV
S
APCY-E Series
COMPRESSOR
C1
F1 F2 F3
( BY OTHERS )
WFS 1 2 3
( BY OTHERS )
8 RELAY-1 RELAY-2 RELAY-3 RELAY-4 RELAY-5 RELAY-6 RELAY-7 RELAY-8 RELAY-9 RELAY-10 POWER
SV1
FUSE
DISPLAY / KEYPAD Blue
485+
CURRENT TRANSFORMER
KEYPAD
SDA
COMPRESSOR MOTOR
Yellow
SELECTOR SWITCH
Black
GND
CIRCUIT BREAKER
N Red
+12V
CONTACTOR
MICROPROCESSOR
A2 Gnd A1
ANALOGE
OTPUTS
MCB3
MAIN BOARD
LEGEND
+12 Volts
- Gnd +12 Gnd
Typical Wiring Diagram
P 1
A4 Gnd A3
ANALOGE
ELECTRONIC EXPANSION VALVE
OTPUTS
MPCB
N 2
MCB
CFM
CCH
CR1
CR2
FDS
CM
CB
CT
SS
Red
C
Red 3
CONTROLLER
RS-485
Green
Green 4
MCS UC-5011
White
DIGITAL INPUTS
White 5
+
Blue B A
DI2 +5 DI1 +5
Blue 6
- Gnd
Screw Chillers
MCS I/O
7
+
- 8
+
DIGITAL INPUTS
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6 SENSOR 7 SENSOR 8 SENSOR 9 SENSOR 10 SENSOR 11 SENSOR 12
DI4 +5 DI3 +5
ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE ANALOGUE SS C2
CR3
DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL DIGITAL
REMOTE
ETHERNET
+5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI +5 Gnd SI SPARE
FUSE
VMM
1 / 4 Watt
1.27K
VOLT FREE CONTACTS FOR VOLT FREE CONTACTS FOR VOLT FREE CONTACTS FOR
RUN INDICATION
ORANGE
FAULT INDICATION REMOTE MODE INDICATION
M1
OLM S
ENTERING LEAVING COMP. COMP. COMP. COMP. COMP.
MP
AMBIENT
WATER WATER SUCTION DISCHARGE SUCTION DISCHARGE AMPS M2 COMP. TEMP.
TEMP. TEMP. PRESSURE PRESSURE TEMP. TEMP. ( CT ) WINDING TEMP.
YELLOW
BROWN
BLUE
OL
46
R-134a
R-410A
REFRIGERANT
F IEL D P O W ER
P O W ER P O I N T- 2
S U PP LY T ER M IN A L
B O A RD .
F IEL D
P O W ER
POW ER
P O I N T- 1
S U PP LY
T ER M IN A L
B O A RD .
F IEL D
CONTROL C O N TR O L
S U PP LY S U PP LY
F IEL D
PO W ER
S U PP LY
F IEL D CONTROL
C O N TRO L
S U PP LY S U PP LY
( F O R S IN G L E P O I N T P O W E R C O N N E C T IO N .
W IT H B U ILT-IN I S O L ATO R - C O N SU L T S K M )
Dimensional Data
APCYAPCY Models
Models - 5080DE,
- 5080DE, 5085DE, 5090DE,
5085DE, 5090DE, 5095DE
5095DE
6095DE, 6100DE, 6110DE
6095DE, 6100DE, 6110DE
10 44.03 44.03 44.03 10
LEGEND MODEL C.W. [254] [1118] [1118] [1118] [254]
APCY IN/OUT
1. CONDENSER FAN A1 A3 A5 A7
6100DE 6"
6110DE [DN 150]
Table 42
A2 A4 A6 A8
88.27 152.09 12
[2242] [3863] [305]
1 2 5
FILTERED
VENTILATION
BOTH SIDE
[2484]
97.79
DETACHABLE
PLATE FOR
CABLE ENTRY
A2 A4 A6 A8 A10
88.27 188.35 12
[2242] [4784] [305]
1 2 5
FILTERED
VENTILATION
BOTH SIDE
[2484]
97.79
DETACHABLE
PLATE FOR
CABLE ENTRY
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
48
R-134a
R-410A
REFRIGERANT
Dimensional Data
APCY Models - 5105DE, 5115DE, 5125DE, 5130DE
APCY Models6125DE,
- 5105DE, 5115DE,
6135DE, 5125DE, 5130DE,
6145DE
6125DE, 6135DE, 6145DE
10 42.09 42.09 42.09 42.09 10
LEGEND [254] [1069] [1069] [1069] [1069] [254]
A1 A3 A5 A7 A9
1. CONDENSER FAN
2. CONDENSER COIL
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
A2 A4 A6 A8 A10
88.27 188.35 12
[2242] [4784] [305]
1 2 5
FILTERED
VENTILATION
BOTH SIDE
[2484]
97.79
DETACHABLE
PLATE FOR
CABLE ENTRY
Table 43
FILTERED
VENTILATION
BOTH SIDE
[2484]
97.79
DETACHABLE
PLATE FOR
CABLE ENTRY
Dimensional Data
APCY Models - 5195DE, 5210DE, 5230DE, 6220DE, 6230DE, 6240DE
APCY Models - 5195DE
LEGEND 10 52.03 52.03 52.03 52.03 52.03 10
[254] [1322] [1322] [1322] [1322] [1322] [254]
1. CONDENSER FAN A1 A3 A5 A7 A9 A11
2. CONDENSER COIL
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
A2 A4 A6 A8 A10 A12
88.27 280.16 12
[2242] [7116] [305]
1 2 5
FILTERED
VENTILATION
BOTH SIDE
[2509]
98.77
DETACHABLE
PLATE FOR
CABLE ENTRY
APCY Models
APCY Models - 5250DE, 5265DE,
- 5210DE, 6260DE,
5230DE, 6275DE 6230DE, 6240DE
6220DE,
10 51.4 51.4 51.4 51.4 51.4 51.4 10
LEGEND [254] [1306] [1306] [1306] [1306] [1306] [1306] [254]
2. CONDENSER COIL
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
FILTERED
VENTILATION
BOTH SIDE
[2509]
98.77
DETACHABLE
PLATE FOR
CABLE ENTRY
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
50
R-134a
R-410A
REFRIGERANT
Dimensional Data
APCY Models - 5285DE, 5300DE, 6300DE, 6320DE
APCY Models - 5250DE, 5265DE, 6260DE, 6275DE
10 59.05 59.05 59.05 59.05 59.05 59.05 10
LEGEND [254] [1500] [1500] [1500] [1500] [1500] [1500] [254]
1. CONDENSER FAN
2. CONDENSER COIL A1 A3 A5 A7 A9 A11 A13
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
88.27 374.33 14
[2242] [9508] [356]
1 2 5
JUNCTION
BOX
[2509]
98.77
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
88.27 420.24 14
[2242] 1 2 [10674] 5 [356]
JUNCTION
BOX
[2509]
98.77
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
Dimensional Data
APCY Models
APCY Models- 6385DE, 6405DE
- 5325DE, 5345DE, 6340DE, 6360DE
10 56.06 56.06 56.06 56.06 56.06 56.06 56.06 56.06 10
LEGEND [254] [1424] [1424] [1424] [1424] [1424] [1424] [1424] [1424] [254]
1. CONDENSER FAN
2. CONDENSER COIL A1 A3 A5 A7 A9 A11 A13 A15 A17
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
JUNCTION
BOX
100.74
[2559]
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
JUNCTION
BOX
100.74
[2559]
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
52
R-134a
R-410A
REFRIGERANT
Dimensional Data
APCY Models
APCY Models - 5395TE,- 5410TE,
5365TE, 6425TE5380TE
10 54.93 54.93 54.93 54.93 54.93 54.93 54.93 54.93 54.93 10
LEGEND [254] [1395] [1395] [1395] [1395] [1395] [1395] [1395] [1395] [1395] [254]
1. CONDENSER FAN
2. CONDENSER COIL A1 A3 A5 A7 A9 A11 A13 A15 A17 A19
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
88.27 514.41 14
[2242] [13066] [356]
1 2 5
JUNCTION
BOX
100.74
[2559]
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
10 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 10
LEGEND [254] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [254]
1. CONDENSER FAN
2. CONDENSER COIL A1 A3 A5 A7 A9 A11 A13 A15 A17 A19 A21
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
88.27 560.31 14
[2242] [14232] [356]
1 2 5
JUNCTION
BOX
100.74
[2559]
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
Dimensional Data
APCY Models
APCY - 5425TE, 6445TE,
Models 6465TE 6445TE, 6465TE
- 5425TE,
10 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 54.03 10
LEGEND [254] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [1372] [254]
1. CONDENSER FAN
A1 A3 A5 A7 A9 A11 A13 A15 A17 A19 A21
2. CONDENSER COIL
3. COMPRESSOR
4. EVAPORATOR
5. CONTROL PANEL
ALL DIMENSIONS ARE IN INCHES [mm]
88.27 560.31 14
[2242] [14232] [356]
1 2 5
JUNCTION
BOX
100.74
[2559]
DETACHABLE
PLATE FOR
CABLE ENTRY
FILTERED
VENTILATION
4-NOS.
NOTE:
Drawings are not contractually binding. Certified drawings will be provided upon request or at time of order.
54
R-134a
R-410A
REFRIGERANT
CENTER OF GRAVITY
UNIT LENGHT
UNIT WIDTH
Y
ORIGIN 0,0
X
56
R-134a
R-410A
REFRIGERANT
LOAD DISTRIBUTION ON MOUNTING POINTS WITH CU/AL COIL- 50.0Hz (CCAF OPTION)
Mounting Loads Operating
Models Units
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 Weight
lbs 746 747 1173 1001 1073 1022 992 844 - - - - - - - - - - - - - - 7598
APCY5080DE
kg 338 339 532 454 487 463 450 383 - - - - - - - - - - - - - - 3446
lbs 746 747 1173 1001 1129 1042 1039 860 - - - - - - - - - - - - - - 7737
APCY5085DE
kg 338 339 532 454 512 473 471 390 - - - - - - - - - - - - - - 3509
lbs 774 757 1248 1028 1129 1042 1039 860 - - - - - - - - - - - - - - 7877
APCY5090DE
kg 351 343 566 466 512 473 471 390 - - - - - - - - - - - - - - 3572
lbs 776 759 1250 1030 1168 1058 1072 874 - - - - - - - - - - - - - - 7987
APCY5095DE
kg 352 344 567 467 530 480 486 396 - - - - - - - - - - - - - - 3622
lbs 586 548 1286 1075 828 818 1286 1083 927 833 - - - - - - - - - - - - 9270
APCY5105DE
kg 266 249 583 488 376 371 583 491 420 378 - - - - - - - - - - - - 4205
lbs 590 552 1322 1161 823 758 1375 1106 940 840 - - - - - - - - - - - - 9467
APCY5115DE
kg 268 250 600 527 373 344 624 502 426 381 - - - - - - - - - - - - 4295
lbs 607 561 1458 1309 861 807 1414 1200 945 844 - - - - - - - - - - - - 10006
APCY5125DE
kg 275 254 661 594 390 366 641 544 429 383 - - - - - - - - - - - - 4537
lbs 607 561 1458 1309 864 808 1439 1209 950 846 - - - - - - - - - - - - 10051
APCY5130DE
kg 275 254 661 594 392 366 653 548 431 384 - - - - - - - - - - - - 4558
lbs 671 882 774 987 867 1259 1451 1570 1308 1384 - - - - - - - - - - - - 11153
APCY5140DE
kg 304 400 351 448 393 571 658 712 593 628 - - - - - - - - - - - - 5058
lbs 714 1014 806 1085 930 1456 1495 1617 1336 1415 - - - - - - - - - - - - 11868
APCY5155DE
kg 324 460 366 492 422 660 678 733 606 642 - - - - - - - - - - - - 5383
lbs 714 1014 806 1085 930 1456 1548 1637 1334 1414 - - - - - - - - - - - - 11938
APCY5165DE
kg 324 460 366 492 422 660 702 742 605 641 - - - - - - - - - - - - 5414
lbs 714 1014 806 1085 930 1456 1565 1693 1333 1411 - - - - - - - - - - - - 12007
APCY5175DE
kg 324 460 366 492 422 660 710 768 605 640 - - - - - - - - - - - - 5447
lbs 716 1016 808 1087 932 1457 1609 1712 1360 1423 - - - - - - - - - - - - 12120
APCY5185DE
kg 325 461 366 493 423 661 730 776 617 645 - - - - - - - - - - - - 5497
lbs 692 909 824 1144 904 1395 856 986 1788 1934 1258 1314 - - - - - - - - - - 14004
APCY5195DE
kg 314 412 374 519 410 633 388 447 811 877 571 596 - - - - - - - - - - 6352
lbs 694 912 826 1147 907 1397 881 998 2041 2033 1320 1339 - - - - - - - - - - 14495
APCY5210DE
kg 315 414 375 520 411 634 400 453 926 922 599 607 - - - - - - - - - - 6576
lbs 703 930 836 1168 811 1080 1004 1380 2129 2303 1345 1408 - - - - - - - - - - 15097
APCY5230DE
kg 319 422 379 530 368 490 455 626 966 1044 610 639 - - - - - - - - - - 6848
lbs 587 574 935 1502 671 725 957 1499 890 971 2145 2301 1372 1425 - - - - - - - - 16554
APCY5250DE
kg 266 260 424 681 304 329 434 680 404 440 973 1044 622 646 - - - - - - - - 7507
lbs 589 576 937 1504 673 727 959 1501 905 1014 2157 2335 1379 1443 - - - - - - - - 16699
APCY5265DE
kg 267 261 425 682 305 330 435 681 410 460 978 1059 625 654 - - - - - - - - 7572
lbs 611 599 1232 2145 1067 1854 857 1157 2012 2133 1818 1860 1066 1100 - - - - - - - - 19511
APCY5285DE
kg 277 272 559 973 484 841 389 525 912 967 824 844 483 499 - - - - - - - - 8849
lbs 613 600 1234 2147 1069 1855 858 1158 2035 2201 1871 2025 1068 1102 - - - - - - - - 19836
APCY5300DE
kg 278 272 560 974 485 841 389 525 923 998 849 918 484 500 - - - - - - - - 8996
lbs 599 586 884 1130 1057 1835 1127 2069 737 818 2307 2408 1682 1810 1106 1140 - - - - - - 21295
APCY5325DE
kg 272 266 401 512 479 832 511 938 334 371 1046 1092 763 821 502 517 - - - - - - 9657
lbs 599 586 884 1130 1057 1835 1127 2069 737 818 2349 2544 1687 1825 1106 1140 - - - - - - 21493
APCY5345DE
kg 272 266 401 512 479 832 511 938 334 371 1065 1154 765 828 502 517 - - - - - - 9747
lbs 575 609 1307 1121 1780 1273 1197 1837 2085 1930 1631 2325 1938 1297 954 915 1205 1239 - - - - 25218
APCY5365TE
kg 261 276 593 508 807 577 543 833 946 875 740 1054 879 588 433 415 546 562 - - - - 11436
lbs 577 610 1308 1123 1781 1274 1205 1841 2120 1945 1674 2343 1939 1299 955 916 1207 1241 - - - - 25358
APCY5380TE
kg 262 277 593 509 808 578 546 835 961 882 759 1063 879 589 433 415 547 563 - - - - 11499
lbs 558 591 1319 1094 1795 1272 987 1366 2172 2189 1422 2078 1131 1229 1915 1280 875 856 1240 1274 - - 26643
APCY5395TE
kg 253 268 598 496 814 577 448 620 985 993 645 942 513 557 868 580 397 388 562 578 - - 12082
lbs 559 592 1320 1096 1796 1273 988 1368 2173 2190 1423 2079 1204 1258 2048 1332 889 862 1241 1275 - - 26966
APCY5410TE
kg 254 268 599 497 815 577 448 620 985 993 645 943 546 571 929 604 403 391 563 578 - - 12229
lbs 544 577 742 795 782 898 1546 1122 1545 1368 1291 2023 2262 2168 1191 1476 1412 1064 1836 1219 1279 1312 28452
APCY5425TE
kg 247 262 337 361 355 407 701 509 701 620 585 917 1026 983 540 669 640 483 833 553 580 595 12904
Table 48
58
R-134a
R-410A
REFRIGERANT
LOAD DISTRIBUTION ON MOUNTING POINTS WITH CU/AL COIL- 60.0Hz (CCAF OPTION)
Mounting Loads Operating
Models Units
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 Weight
lbs 746 747 1173 1001 1073 1022 992 844 - - - - - - - - - - - - - - 7598
APCY6095DE
kg 338 339 532 454 487 463 450 383 - - - - - - - - - - - - - - 3446
lbs 735 716 1196 1058 1147 1088 1031 841 - - - - - - - - - - - - - - 7812
APCY6100DE
kg 333 325 542 480 520 493 468 381 - - - - - - - - - - - - - - 3542
lbs 762 726 1271 1085 1147 1088 1031 841 - - - - - - - - - - - - - - 7951
APCY6110DE
kg 346 329 576 492 520 493 468 381 - - - - - - - - - - - - - - 3605
lbs 560 528 1239 1044 773 778 1269 1071 911 817 - - - - - - - - - - - - 8990
APCY6115DE
kg 254 239 562 473 351 353 576 486 413 371 - - - - - - - - - - - - 4078
lbs 587 549 1364 1271 816 787 1318 1161 928 834 - - - - - - - - - - - - 9615
APCY6125DE
kg 266 249 619 576 370 357 598 527 421 378 - - - - - - - - - - - - 4361
lbs 590 553 1368 1274 839 797 1411 1196 941 841 - - - - - - - - - - - - 9810
APCY6135DE
kg 268 251 620 578 380 361 640 542 427 381 - - - - - - - - - - - - 4448
lbs 607 561 1458 1309 861 807 1414 1200 945 844 - - - - - - - - - - - - 10006
APCY6145DE
kg 275 254 661 594 390 366 641 544 429 383 - - - - - - - - - - - - 4537
lbs 714 1014 806 1085 930 1456 1448 1551 1306 1373 - - - - - - - - - - - - 11683
APCY6160DE
kg 324 460 366 492 422 660 657 703 592 623 - - - - - - - - - - - - 5299
lbs 677 897 861 1259 912 1398 1454 1573 1310 1386 - - - - - - - - - - - - 11727
APCY6170DE
kg 307 407 390 571 414 634 659 713 594 629 - - - - - - - - - - - - 5318
lbs 714 1014 806 1085 930 1456 1516 1625 1315 1407 - - - - - - - - - - - - 11868
APCY6185DE
kg 324 460 366 492 422 660 688 737 596 638 - - - - - - - - - - - - 5383
lbs 714 1014 806 1085 930 1456 1548 1637 1334 1414 - - - - - - - - - - - - 11938
APCY6195DE
kg 324 460 366 492 422 660 702 742 605 641 - - - - - - - - - - - - 5414
lbs 714 1014 806 1085 930 1456 1558 1670 1341 1435 - - - - - - - - - - - - 12009
APCY6205DE
kg 324 460 366 492 422 660 707 757 608 651 - - - - - - - - - - - - 5447
lbs 690 908 822 1142 903 1393 826 951 1806 1918 1243 1290 - - - - - - - - - - 13892
APCY6220DE
kg 313 412 373 518 410 632 375 431 819 870 564 585 - - - - - - - - - - 6302
lbs 692 909 824 1144 904 1395 850 965 1797 1963 1256 1306 - - - - - - - - - - 14005
APCY6230DE
kg 314 412 374 519 410 633 385 438 815 890 570 592 - - - - - - - - - - 6352
lbs 699 926 831 1163 915 1424 860 993 1790 1936 1260 1316 - - - - - - - - - - 14113
APCY6240DE
kg 317 420 377 527 415 646 390 450 812 878 571 597 - - - - - - - - - - 6400
lbs 584 571 931 1498 667 722 954 1495 833 947 2029 2022 1340 1332 - - - - - - - - 15925
APCY6260DE
kg 265 259 422 679 302 327 433 678 378 429 920 917 608 604 - - - - - - - - 7221
lbs 586 573 933 1500 669 724 956 1497 831 934 2114 2288 1375 1439 - - - - - - - - 16419
APCY6275DE
kg 266 260 423 680 303 328 434 679 377 424 959 1038 624 653 - - - - - - - - 7448
lbs 608 595 1229 2142 1064 1850 853 1153 1842 1917 1738 1897 1063 1097 - - - - - - - - 19048
APCY6300DE
kg 276 270 557 971 483 839 387 523 835 869 788 860 482 498 - - - - - - - - 8638
lbs 610 597 1230 2143 1066 1852 855 1155 1879 2032 1731 1873 1064 1099 - - - - - - - - 19186
APCY6320DE
kg 277 271 558 972 483 840 388 524 852 922 785 849 483 498 - - - - - - - - 8702
lbs 598 585 883 1129 1055 1833 1126 2067 736 817 2146 2214 1627 1718 1105 1139 - - - - - - 20778
APCY6340DE
kg 271 265 400 512 478 831 511 937 334 371 973 1004 738 779 501 517 - - - - - - 9422
lbs 599 586 884 1130 1057 1835 1127 2069 737 818 2200 2381 1648 1783 1106 1140 - - - - - - 21100
APCY6360DE
kg 272 266 401 512 479 832 511 938 334 371 998 1080 747 809 502 517 - - - - - - 9569
lbs 563 597 890 1137 1124 1961 1134 2020 794 930 2065 2168 1931 2052 786 843 1193 1227 - - - - 23415
APCY6385DE
kg 255 271 404 516 510 889 514 916 360 422 937 983 876 931 356 382 541 556 - - - - 10619
lbs 563 597 890 1137 1124 1961 1134 2020 794 930 2096 2265 1948 2105 786 843 1193 1227 - - - - 23613
APCY6405DE
kg 255 271 404 516 510 889 514 916 360 422 951 1027 883 955 356 382 541 556 - - - - 10708
lbs 555 589 1212 1051 1814 1278 993 1367 2136 2174 1362 2053 1206 1257 1912 1277 795 823 1238 1271 - - 26363
APCY6425TE
kg 252 267 550 477 823 580 450 620 969 986 618 931 547 570 867 579 361 373 561 576 - - 11957
lbs 540 573 739 792 779 895 1550 1121 1452 1330 1247 2004 2128 2114 1143 1455 1311 1023 1714 1170 1276 1309 27665
APCY6445TE
kg 245 260 335 359 353 406 703 508 659 603 566 909 965 959 518 660 595 464 777 531 579 594 12548
lbs 542 575 740 793 780 896 1576 1132 1512 1354 1242 2003 2129 2115 1150 1459 1299 1019 1728 1176 1277 1310 27807
APCY6465TE
kg 246 261 336 360 354 406 715 513 686 614 563 908 966 959 522 662 589 462 784 533 579 594 12612
Table 49
LOAD DISTRIBUTION ON MOUNTING POINTS WITH CU/CU COIL- 50.0Hz (FC OPTION)
Mounting Loads Operating
Models Units
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 Weight
lbs 834 835 1293 1122 1193 1143 1044 897 - - - - - - - - - - - - - - 8361
APCY5080DE
kg 378 379 586 509 541 518 473 407 - - - - - - - - - - - - - - 3791
lbs 834 835 1293 1122 1249 1163 1091 913 - - - - - - - - - - - - - - 8500
APCY5085DE
kg 378 379 586 509 566 527 495 414 - - - - - - - - - - - - - - 3854
lbs 861 845 1368 1149 1249 1163 1091 913 - - - - - - - - - - - - - - 8639
APCY5090DE
kg 390 383 620 521 566 527 495 414 - - - - - - - - - - - - - - 3916
lbs 863 847 1370 1151 1288 1179 1124 927 - - - - - - - - - - - - - - 8749
APCY5095DE
kg 391 384 621 522 584 535 510 420 - - - - - - - - - - - - - - 3967
lbs 671 634 1400 1189 938 928 1400 1198 1012 918 - - - - - - - - - - - - 10288
APCY5105DE
kg 304 288 635 539 425 421 635 543 459 416 - - - - - - - - - - - - 4665
lbs 674 637 1436 1276 933 868 1489 1221 1025 925 - - - - - - - - - - - - 10484
APCY5115DE
kg 306 289 651 579 423 394 675 554 465 420 - - - - - - - - - - - - 4756
lbs 692 646 1572 1423 970 917 1528 1314 1029 930 - - - - - - - - - - - - 11021
APCY5125DE
kg 314 293 713 645 440 416 693 596 467 422 - - - - - - - - - - - - 4999
lbs 692 646 1572 1423 974 918 1553 1323 1035 932 - - - - - - - - - - - - 11068
APCY5130DE
kg 314 293 713 645 442 416 704 600 469 423 - - - - - - - - - - - - 5019
lbs 760 980 915 1142 1015 1422 1590 1723 1397 1482 - - - - - - - - - - - - 12426
APCY5140DE
kg 345 444 415 518 460 645 721 781 634 672 - - - - - - - - - - - - 5635
lbs 803 1112 947 1240 1078 1618 1633 1769 1425 1513 - - - - - - - - - - - - 13138
APCY5155DE
kg 364 504 429 562 489 734 741 802 646 686 - - - - - - - - - - - - 5957
lbs 803 1112 947 1240 1078 1618 1686 1790 1423 1512 - - - - - - - - - - - - 13209
APCY5165DE
kg 364 504 429 562 489 734 765 812 645 686 - - - - - - - - - - - - 5990
lbs 803 1112 947 1240 1078 1618 1703 1846 1422 1510 - - - - - - - - - - - - 13279
APCY5175DE
kg 364 504 429 562 489 734 772 837 645 685 - - - - - - - - - - - - 6021
lbs 805 1114 949 1242 1080 1620 1747 1864 1449 1521 - - - - - - - - - - - - 13391
APCY5185DE
kg 365 505 430 563 490 735 792 845 657 690 - - - - - - - - - - - - 6072
lbs 780 1006 959 1293 1044 1549 996 1140 1924 2083 1346 1411 - - - - - - - - - - 15531
APCY5195DE
kg 354 456 435 586 473 702 452 517 873 945 610 640 - - - - - - - - - - 7043
lbs 783 1009 961 1296 1046 1551 1021 1152 2177 2182 1409 1437 - - - - - - - - - - 16024
APCY5210DE
kg 355 458 436 588 474 703 463 522 987 990 639 652 - - - - - - - - - - 7267
lbs 792 1028 971 1317 950 1234 1143 1534 2264 2452 1433 1505 - - - - - - - - - - 16623
APCY5230DE
kg 359 466 440 597 431 560 518 696 1027 1112 650 683 - - - - - - - - - - 7539
lbs 675 671 1069 1650 799 867 1104 1661 1018 1113 2279 2449 1460 1522 - - - - - - - - 18337
APCY5250DE
kg 306 304 485 748 362 393 501 753 462 505 1034 1111 662 690 - - - - - - - - 8316
lbs 677 673 1071 1651 801 869 1106 1663 1033 1155 2291 2482 1466 1539 - - - - - - - - 18477
APCY5265DE
kg 307 305 486 749 363 394 502 754 468 524 1039 1126 665 698 - - - - - - - - 8380
lbs 703 700 1405 2336 1213 2014 1004 1320 2157 2293 1991 2050 1158 1202 - - - - - - - - 21546
APCY5285DE
kg 319 317 637 1059 550 913 455 599 978 1040 903 930 525 545 - - - - - - - - 9770
lbs 705 702 1407 2337 1214 2015 1006 1321 2180 2361 2044 2215 1160 1203 - - - - - - - - 21870
APCY5300DE
kg 320 318 638 1060 551 914 456 599 989 1071 927 1005 526 546 - - - - - - - - 9920
lbs 690 687 1047 1310 1203 1996 1272 2228 882 978 2453 2569 1845 1990 1197 1240 - - - - - - 23587
APCY5325DE
kg 313 312 475 594 546 905 577 1010 400 444 1112 1165 837 902 543 562 - - - - - - 10697
lbs 690 687 1047 1310 1203 1996 1272 2228 882 978 2495 2705 1850 2004 1197 1240 - - - - - - 23784
APCY5345DE
kg 313 312 475 594 546 905 577 1010 400 444 1132 1227 839 909 543 562 - - - - - - 10788
lbs 666 709 1463 1294 1927 1434 1340 1995 2227 2088 1769 2477 2089 1464 1105 1082 1296 1339 - - - - 27764
APCY5365TE
kg 302 322 663 587 874 650 608 905 1010 947 802 1123 947 664 501 491 588 607 - - - - 12591
lbs 667 710 1464 1295 1928 1435 1348 1999 2263 2102 1812 2495 2091 1466 1106 1083 1297 1340 - - - - 27901
APCY5380TE
kg 302 322 664 587 874 651 611 907 1026 953 822 1132 948 665 502 491 588 608 - - - - 12653
lbs 648 690 1468 1259 1942 1434 1128 1522 2313 2345 1558 2228 1271 1384 2067 1447 1019 1015 1330 1373 - - 29441
APCY5395TE
kg 294 313 666 571 881 650 512 690 1049 1063 707 1010 576 628 937 656 462 460 603 623 - - 13351
lbs 649 691 1469 1260 1943 1435 1129 1523 2314 2346 1559 2229 1344 1413 2200 1500 1034 1022 1331 1374 - - 29765
APCY5410TE
kg 294 313 666 571 881 651 512 691 1049 1064 707 1011 610 641 998 680 469 463 604 623 - - 13498
lbs 633 675 886 954 929 1060 1685 1275 1685 1522 1425 2171 2401 2321 1330 1630 1560 1226 1980 1378 1368 1410 31504
APCY5425TE
kg 287 306 402 433 421 481 764 578 764 690 646 985 1089 1053 603 739 707 556 898 625 620 639 14286
Table 50
60
R-134a
R-410A
REFRIGERANT
LOAD DISTRIBUTION ON MOUNTING POINTS WITH CU/CU COIL- 60.0Hz (FC OPTION)
Mounting Loads Operating
Models Units
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 Weight
lbs 834 835 1293 1122 1193 1143 1044 897 - - - - - - - - - - - - - - 8361
APCY6095DE
kg 378 379 586 509 541 518 473 407 - - - - - - - - - - - - - - 3791
lbs 822 804 1316 1179 1267 1209 1084 894 - - - - - - - - - - - - - - 8575
APCY6100DE
kg 373 365 597 535 575 548 492 405 - - - - - - - - - - - - - - 3890
lbs 850 813 1391 1206 1267 1209 1084 894 - - - - - - - - - - - - - - 8714
APCY6110DE
kg 385 369 631 547 575 548 492 405 - - - - - - - - - - - - - - 3952
lbs 634 603 1339 1145 869 874 1369 1172 985 891 - - - - - - - - - - - - 9881
APCY6115DE
kg 288 273 607 519 394 396 621 532 447 404 - - - - - - - - - - - - 4481
lbs 672 635 1478 1386 926 897 1432 1276 1013 919 - - - - - - - - - - - - 10634
APCY6125DE
kg 305 288 670 629 420 407 649 579 459 417 - - - - - - - - - - - - 4823
lbs 675 638 1482 1389 949 907 1525 1311 1026 926 - - - - - - - - - - - - 10828
APCY6135DE
kg 306 289 672 630 430 411 692 595 465 420 - - - - - - - - - - - - 4910
lbs 692 646 1572 1423 970 917 1528 1314 1029 930 - - - - - - - - - - - - 11021
APCY6145DE
kg 314 293 713 645 440 416 693 596 467 422 - - - - - - - - - - - - 4999
lbs 803 1112 947 1240 1078 1618 1586 1704 1395 1471 - - - - - - - - - - - - 12954
APCY6160DE
kg 364 504 429 562 489 734 719 773 633 667 - - - - - - - - - - - - 5874
lbs 766 995 1002 1415 1060 1561 1593 1725 1399 1485 - - - - - - - - - - - - 13001
APCY6170DE
kg 347 451 454 642 481 708 722 782 634 673 - - - - - - - - - - - - 5894
lbs 803 1112 947 1240 1078 1618 1654 1777 1404 1505 - - - - - - - - - - - - 13138
APCY6185DE
kg 364 504 429 562 489 734 750 806 637 683 - - - - - - - - - - - - 5958
lbs 803 1112 947 1240 1078 1618 1686 1790 1423 1512 - - - - - - - - - - - - 13209
APCY6195DE
kg 364 504 429 562 489 734 765 812 645 686 - - - - - - - - - - - - 5990
lbs 803 1112 947 1240 1078 1618 1696 1823 1430 1533 - - - - - - - - - - - - 13280
APCY6205DE
kg 364 504 429 562 489 734 769 827 649 695 - - - - - - - - - - - - 6022
lbs 778 1005 957 1292 1042 1547 966 1105 1942 2067 1331 1387 - - - - - - - - - - 15419
APCY6220DE
kg 353 456 434 586 473 702 438 501 881 937 604 629 - - - - - - - - - - 6994
lbs 780 1006 959 1293 1044 1549 989 1119 1933 2112 1344 1403 - - - - - - - - - - 15531
APCY6230DE
kg 354 456 435 586 473 702 449 507 877 958 610 636 - - - - - - - - - - 7043
lbs 787 1023 966 1312 1055 1578 999 1147 1926 2085 1348 1413 - - - - - - - - - - 15639
APCY6240DE
kg 357 464 438 595 478 716 453 520 873 946 611 641 - - - - - - - - - - 7092
lbs 671 667 1065 1646 796 863 1100 1657 962 1089 2163 2169 1428 1429 - - - - - - - - 17705
APCY6260DE
kg 304 302 483 746 361 391 499 751 436 494 981 984 648 648 - - - - - - - - 8028
lbs 673 669 1067 1648 798 865 1102 1659 959 1075 2248 2436 1462 1535 - - - - - - - - 18196
APCY6275DE
kg 305 303 484 747 362 392 500 752 435 488 1020 1105 663 696 - - - - - - - - 8252
lbs 700 697 1402 2332 1209 2010 1001 1316 1987 2077 1911 2088 1155 1198 - - - - - - - - 21083
APCY6300DE
kg 317 316 636 1058 548 912 454 597 901 942 867 947 524 543 - - - - - - - - 9562
lbs 702 699 1403 2334 1211 2012 1003 1318 2024 2192 1904 2064 1157 1200 - - - - - - - - 21223
APCY6320DE
kg 318 317 636 1059 549 912 455 598 918 994 863 936 525 544 - - - - - - - - 9624
lbs 689 685 1045 1308 1201 1994 1271 2227 880 976 2292 2374 1790 1897 1196 1239 - - - - - - 23064
APCY6340DE
kg 312 311 474 593 545 904 576 1010 399 443 1039 1077 812 860 542 562 - - - - - - 10459
lbs 690 687 1047 1310 1203 1996 1272 2228 882 978 2346 2542 1811 1962 1197 1240 - - - - - - 23391
APCY6360DE
kg 313 312 475 594 546 905 577 1010 400 444 1064 1153 821 890 543 562 - - - - - - 10609
lbs 654 697 1047 1309 1270 2123 1277 2177 937 1088 2203 2320 2083 2219 938 1009 1284 1327 - - - - 25962
APCY6385DE
kg 297 316 475 594 576 963 579 987 425 493 999 1052 945 1006 425 458 582 602 - - - - 11774
lbs 654 697 1047 1309 1270 2123 1277 2177 937 1088 2234 2417 2099 2272 938 1009 1284 1327 - - - - 26159
APCY6405DE
kg 297 316 475 594 576 963 579 987 425 493 1013 1096 952 1030 425 458 582 602 - - - - 11863
lbs 645 688 1361 1216 1961 1440 1134 1522 2277 2329 1497 2203 1347 1412 2065 1445 939 983 1328 1370 - - 29162
APCY6425TE
kg 293 312 617 551 889 653 514 690 1033 1056 679 999 611 640 937 655 426 446 602 621 - - 13224
lbs 630 672 883 950 926 1057 1689 1275 1591 1483 1381 2152 2267 2268 1282 1609 1458 1185 1858 1329 1365 1407 30717
APCY6445TE
kg 286 305 400 431 420 479 766 578 722 673 626 976 1028 1029 581 730 661 537 843 603 619 638 13931
lbs 631 673 884 952 927 1058 1715 1285 1651 1507 1376 2151 2268 2269 1289 1612 1447 1181 1872 1335 1366 1408 30857
APCY6465TE
kg 286 305 401 432 420 480 778 583 749 683 624 976 1029 1029 585 731 656 536 849 605 620 639 13996
Table 51
62
R-134a
R-410A
REFRIGERANT
[2134]
84"
1. There should be no obstruction on the air discharge.
2. Unit must not be installed in a pit or near a parapet
wall that is taller than the unit height.
3. Orient the unit so that prevailing winds blow parallel to
unit length. If it is not practical to orient in this manner,
a wind deflecting shield should be considered.
4. Provide adequate clearance on all sides of the unit for
service access and avoid coil starvation. Refer to
figure below for recommended clearances. 60" 60"
[1524] [1524]
[2134]
84"
Recommended Clearances
It is a necessity that the units are installed with adequate free space around them to ensure proper circulation of air that is rejected
by the condensers and to provide adequate space for unit access for servicing and maintenance. There is a possibility of recycling
of air if the rejected air from condenser encounters any obstacles leading to an increase in the ambient air temperature surrounding
the units.
Air distribution across the entire heat exchange area will be impaired if the air outlet is obstructed. These conditions lead to a
reduction in the heat exchange capacity of the coils causing an increase in discharge pressure of the compressors. This leads to
a loss of capacity & increase in compressor power input.
Units should not be completely shrouded with higher uninterrupted windshield in order to prevent reversing of airflow. In case,
such a configuration cannot be avoided , a properly designed exhaust duct or hood that does not influence any additional pressure
on the fans and which is of the same height as surrounding shield to be installed. For installation involving more than 3 chillers,
consult SKM for acceptable clearance.
MULTIPLE UNIT INSTALLATION
HEIGHT SHOULD BE LESS
THAN UNIT HEIGHT
HEIGHT
84" 122"
[2134] [3098]
60" 60"
[1524] [1524]
Figure A
Foundation
Provide a level and rigid concrete foundation or a steel platform that is strong enough to carry the operating weight of the unit.
SKM Air Conditioning is not liable for any damages and problems in the equipment caused by erroneous design in the foundation.
SKM suggests abiding by the local authorities’ chilled water piping recommendations and practices as they can provide the
installer the building and safety codes required for the installation.
Water piping should be designed to have a minimum number of bends and horizontal piping levels. Below are the following
components it should have:
1. Temperature and pressure gauges in entering and leaving chiller water piping for unit servicing and commissioning.
Pressure gauges must be installed on at the same level.
2. Vibration eliminators in entering and leaving chilled water piping to lessen the sound and vibration transmitted to the building.
3. Pipe strainer in the evaporator entering piping to protect the evaporator from water debris and maintain chiller efficiency.
4. Water flow switch in the leaving chilled water piping, wired to the terminals provided in the control panel, to make sure
that it has sufficient flow of water in the evaporator. This will prevent the evaporator from freezing up when the water flow is
interrupted and avoid compressor slugging on start-up.
5. To isolate the unit from the piping system when servicing or during maintenance, install a shuttoff valve on the entering and
leaving chilled water piping.
6. Expansion Tank provides additional space in the chilled water piping system as temperature rises and furthermore, it
maintains a positive pressure within the working limitations of the system.
7. Air Vents at high points in the chilled water system to bleed air from the system.
8. Vapour barrier on the outside of the insulation to avoid condensation in the cold surface of the pipe that may cause damage
on the building structure. A thorough leak test should be made before insulating the pipe.
Flush all chilled water piping before making the final connection to the unit. SKM recommends hiring services of water treatment
specialist to determine the type of necessary treatment. Improper or untreated chilled water leads to scaling, erosion, corrosion or
algae that can cause inefficient operation and tube damage. SKM will not be liable for damages caused by improper or untreated
chilled water.
Run the pumps 2 to 3 minutes before starting the chiller to ensure no freezing occurs that may damage the evaporator.
O R
RAT
O
VAP
E
BE WA
TU
TE
RF
L&
LO
W
L
HE
E
AG
S SS
U RE
GU
R
E TO
PR
N+ INA
PH
O LIM
SY NE
ATIO ITC
H
R
V IBR SW INE
OW T RA
FL RS E
TE LV LV
E
WA VA VA
NG E
NCI AT
LA /G
BA VE
FL
OW
WA V AL
TE LL
RF BA
LO
W
A"
l"
e tai
ed
se
Figure B
64
R-134a
R-410A
REFRIGERANT
Vibration Isolation
It is recommended to install under the base of the unit a vibration isolation of rubber-in-shear or spring type for further reduction
of sound and vibration transmission to building structures. Vibration isolators must be correctly designed for each mounting loads
of the unit. Refer to unit certified drawing for operating weight at each mounting points.
Note :
SKM can supply CAVM Spring type Anti-vibration mounts (optional). The CAVM has a deflection of 25mm and each rated load
can be distinguished easily as it is represented by different colours.
In a chilled water system, the presence of a sufficient volume of water in the piping system is crucial to achieving proper operation,
unfortunately, some systems will run with less water volume than needed, this will result in inconsistence system operation, and
uncontrolled compressor cycling, this condition is called “short water loop”.
If our building for example didn’t provide enough water volume to achieve stable controls, a storage tank should be installed to
increase the water volume.
In a standard air conditioning application, the tank should be sized to attain at least 2-minute water loop at nominal condition
(ambient air temperature of 95.0°F and evaporator water entering/leaving temperature of 54.00°F/44.00°F) and 2.5-4-minute
water loop for process cooling system.
Having enough water loop time, hence enough water volume in the evaporator loop will prevent irregular compressor cycling,
which means smoother operation.
APCY-E Series can operate at wide evaporator temperature range, 6ºF (3.33ºC) - 16.20ºF (9.00ºC), within the water flow rate limits,
and is flexible enough to permit leaving water temperatures ranging from 40.00ºF (4.40ºC) - 50.00ºF (10.00ºC). The minimum and
maximum water flow rates of each evaporator are shown in the Evaporator Water Pressure Drop table.
Although in a lot of process cooling applications, it could be found that the flow rates or leaving temperatures are outside the
specified limits, however this can be solved by making changes in the chilled water piping arrangement.
66
R-134a
R-410A
REFRIGERANT
It is strongly recommended to size the chiller for the present If the capacity requires installing more than one chiller unit or
load. For future expansion, it is recommended to install another where standby units are desired, units should be of equal size
chiller to meet the additional load demand. (or near) to ensure balanced water flow.
Oversizing of chillers by more than 10% at design conditions SKM recommends that water flow supply & return are connected
must be avoided. Oversizing causes energy inefficiency (more either parallel in case of range < 16°F (8.9°C) or in series if
power consumption), erratic system operation and shortened range > 16°F (8.9°C).
compressor life due to excessive cycling of compressors.
WFS WFS
Figure C
GUIDE SPECIFICATIONS
GENERAL
The contractor shall supply and install factory assembled The evaporator shall be provided with water drain, air vent
air-cooled packaged water chillers, the number and capacity of plugs and fittings for temperature sensors. The shell shall be
which shall be as indicated in the capacity schedule shown on insulated with 0.75” (19mm) thick flexible closed cell insulation
the drawings. with a maximum K factor of 0.28 Btu.in/ft2.hr.°F (0.04 W/m.°K).
Each machine shall consist of at least one refrigerating circuit The evaporator shall be designed for 239.3 psig (1650 kPa)
comprising of semi hermetic compact screw compressor(s), refrigerant side working pressure and 145 psig (1000 kPa)
air-cooled condenser, evaporator, interconnecting refrigerant waterside working pressure.
piping, controls, safety devices and accessories.
The machine shall be factory assembled, leak tested, evacuated CONDENSER FANS & MOTORS
and completely charged with refrigerant R-134a. All factory wiring
and piping shall be contained within the machine enclosure. The machine shall be furnished with direct driven propeller type
All electrical components shall be protected from the weather. discharging air upward condenser fans. Fans shall be constructed
of corrosion resistant blades such as heavy gauge aluminum. The
Air cooled chillers shall be satisfied in accordance with AHRI- fan and drive shall be held in proper alignment. Fan assemblies
550/590. Each machine shall be capable of operating satisfactorily shall be provided with heavy gauge, rust resistant steel. The fan
in a wide range of ambient air temperatures ranging from 25°F assembly shall be protected with an acrylic coated steel wire
(-4oC) to 115.0oF (46.1oC) at full load and shall operate up to fan guard. All condenser fans shall be individually statically and
125.6oF (52oC) unloaded stage. dynamically balanced for vibration free operation.
Unless indicated otherwise on electrical wiring diagram, each Condenser fan motor shall be Totally Enclosed Air Over (TEAO),
unit shall be factory equipped to connect to only one electrical 3-phase type, 6 poles with Class F insulation, Class B temperature
power feeder with the necessary circuit breakers. rise and IP55 protection. Also, Motor shall be with permanently
Each unit shall be mounted on anti vibration isolators flexible lubricated bearings and inherent corrosion resistance shaft.
enough to dampen any vibrations. Condenser fan motors shall be provided with individual 3 pole
motor protector circuit breakers and contactor rated for AC3
duty operation.
COMPRESSOR
Compressor shall be high performance and high efficiency screw
REFRIGERATION CIRCUITS
type. The compressor shall be driven by an electric motor in
Refrigeration circuits piping shall be fabricated from ACR
a single housing. For stability and additional sound attenuation,
grade copper pipes and each refrigeration circuit shall include
the rotors shall be mounted in a double wall housing.
a removable core filter drier, electronic expansion valve, and
The compressor motor shall be refrigerant gas cooled. Each shut off valve.
compressor shall be mounted on anti-vibration mounts to minimise
Suction line shall be insulated with ½” (13mm) wall
vibration transmission.
thickness closed cell pipe insulation with maximum k factor
Compressor shall have discharge stop off valves, built in three- 0.26 Btu.in/ft2.hr.°F (0.038 W/m.° K).
stage oil separator, oil heater, oil sight glass, oil drain service
valves and discharge check valve.
CASING
Compressor shall have automatic start unloading and shall have
infinite capacity control. Each compressor shall be provided Machine casing shall be made of heavy gauge zinc coated
with safety devices including check valve in the discharge gas galvanized steel sheets conforming to JIS-G 3302 and ASTM-
outlet, motor winding temperature protection by integrated PTC A 635.
sensors in each winding, phase sequence protection for direction
To provide an extremely tough, scratch resistance, excellent
of rotation, discharge temperature protection, oil pressure and
anti-corrosive protection, fabricated steel shall be thoroughly
oil level protection.
de-greased and then phosphatized before application of an
All compressors shall be provided with star-delta starter and an average 60 micron backed electrostatic polyester dry powder
individual 3 pole MCCB for short circuit protection & Isolation. coating in RAL 7032 color scheme. This finish shall pass 1000
Individual 3 pole contactors for switching of the compressors hour, 5% salt spray test at 95°F (35°C) and 95% relative humidity
shall be rated for AC3 duty as per (ASTM B 117).
68
R-134a
R-410A
REFRIGERANT
GUIDE SPECIFICATIONS
CONTROL PANEL & CONTROLS
Control panel enclosure shall be fabricated out of heavy gauge • Battery backed up built-in real time clock to program two
steel in phosphatized, powder coated baked finish. The enclosure start/step daily and provide the information of running hours
shall be conformed to IP54 as per guidelines in IEC 529. A hinged of the compressors.
access door and key fastener shall be provided for easy access • A multiple level passwords for security.
and security.
• Automatic lead/lag changeover of the compressors.
The control panel shall be ventilated using louvers and filters.
The panel shall be factory wired in accordance with NEC 430 & • Pump down at the beginning and end of every circuit cycle.
440, labeled, tagged and have 1 phase, 220 / 240 V for controls. • Capacity control based on leaving chilled water temperature.
Control Panel should include the following components as • Remote Start/Stop facility through Volt Free Contact.
minimum :
• Volt Free Contacts for common Run, Fault and Remote
mode operation status.
• Individual compressor and condenser fan motor contactors.
• Thermal magnetic circuit breakers for compressors and
condenser fan motors. EASY ACCESSIBLE MEASUREMENTS SHALL
INCLUDE THE FOLLOWING :
• Voltage monitoring module for protection against under
voltage, over voltage, phase loss, phase reversal and phase • Status of the chiller.
unbalance of the incoming voltage.
• Status of each circuit/compressor.
• Circuit breaker for control circuit.
• Status of condenser fans.
• Remote/Off/Local selector switch.
• Leaving and Entering chilled water temperature.
• Microprocessor master board with graphical display.
• Suction pressure and temperature for each refrigerant
• Microprocessor expansion boards as required. circuit.
• Electronic expansion valve control boards. • Discharge pressure and temperature for each refrigerant
• Control Relays. circuit.
• Control circuit on/off switch and pump down switches. • Suction and discharge superheat for each refrigerant circuit.
• Volt free contacts for run, common fault and auto mode • Winding temperature for each compressor.
indications. • Ampere draw for each compressor.
• Provision for accepting volt free contact for remote start/ • Expansion valve opening percentage.
stop.
• Ambient temperature.
• Control terminal blocks and power terminal blocks/bus bars.
• All active set points.
A Microprocessor must be provided to control the chiller as a • Run time for each compressor.
standard. The controller shall provide the flexibility with set points
• Number of compressor starts.
and control options that can be selected prior to the commisioning.
The microprocessor shall provide a complete operational control • Lockout and alarm status.
for the chiller and shall have built-in auto diagnostic capability
• Status of water flow switch, voltage monitor, compressor
that can signal off normal operation or alarm conditions as well
internal motor protector, oil level switch, run/stop input and
as shutting down the chiller.
pump down switches.
The Master Micro Controller board shall have sensor inputs, digital • Log of last 100 alarms.
inputs, relay outputs 0-10 Vdc analog outputs, keypad, graphics
LCD with 2.8” diagonal viewing analogue, real time clock, RS- • Lead compressor identification.
232, RS-485 and ethernet communication ports. • Date and time.
• Graphs of all inputs and outputs.
The main features of the Controller shall be as
follows :
GUIDE SPECIFICATIONS
THE FOLLOWING SYSTEM PROTECTION CONTROLS
SHALL AUTOMATICALLY ACT TO ENSURE SYSTEM
RELIABILITY AND PROTECTION OF THE UNIT THROUGH
THE MICROPROCESSOR:
• Freeze protection.
• Pump down.
• Anti-recycle.
70