Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Managed Ethernet Switch: Features

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

www.nrec.

com/en

PCS-9882
Managed Ethernet Switch

The PCS-9882 series 1U 19” managed Ethernet switches and interference factors in industrial applications to ensure a
are designed for severe environments. It supports high data reliable data transmission under harsh environments.
transmission rate to meet the increasing requirements in • This device is especially suitable for IEC 61850 application
substation automation system (SAS), networked control system and digital substation process level bus.
(NCS), distributed control systems (DCS), industrial system, etc.
• Support of IEC 61850 modeling and monitoring via IEC 61850
protocol
Features
• 6XSSRUWRI0$&EDVHGDQGSURWRFROEDVHGÀRZFRQWUROWRSUHYHQW
• The PCS-9882 series Ethernet switches adopt high- message isolation in process level bus of digital substation
performance switching chip and excellent industrial design to
keep the line speed forwarding under full duplex and full rate • Support of static multicast management to make the flow
operation of all the ports. The design and manufacturing of control more transparent and reliable

Automation System
this device has fully considered various adverse conditions

Gateway
SCADA

PCS-9
PCS-9882
PCS 9882
9

Ethernet Switch Giga-uplink Giga-uplink


Ethernet Switch

BCU Relay

Figure 1 Typical application

135
Protection Automation Control

• Support of ACL-based white list and black list along with DoS • VLAN, traffic prioritization, RSTP, port security, GMRP/
anti-attack technology to ensure the security and reliability of GVRP, IGMP snooping are supported to meet the process
digital substation process level bus level bus requirements in digital substation.

• The advanced heat emission technology (protected by • The port security strategy, which is based on static MAC
patent) is applied to ensure an excellent heat emission address and IEEE 802.1X, guarantees the access security of
performance and a stable working environment range connected IEDs.
between -40°C ~ +85°C.
• To ensure the security access control, SSL/SSH is supported.
• The advanced technologies, including total-enclosed
housing, partitioned grounding connection, anti-interference • Support of IEEE 1588V2 protocol, support of the one-step
power supply, PCB division by voltage level and cable and two-step methods.
shielding, ensure zero package loss under strong
• The device is designed as an industrial managed Ethernet
electromagnetic interference.
switch with abundant functions (e.g. port flow control,
• The compact parallel processing technology is applied to network storm limitation, port mirroring, SNMP, RMON, WEB,
ensure an excellent store and forward performance. port trunking, SNTP, RADIUS, etc.).

• The optimized RSTP protocol is adopted and the switch • In case of a power supply short interruption, this device can still
failover time has achieved an international leading level: work for up to 500ms, to ensure enough time for data forward.
max.2ms per hop.
• Several Gigabit ports are equipped for the improvement of
• The dual load-sharing hot-swappable technology is adopted uplink performance.
for AC and DC power supply.
• The GOOSE/SMV message delay compensation technology can
• The processing capacity guarantees a handling of any efficiently solve the reliance problem on clock synchronization
packet (64~1518 bytes) with zero loss of package. network in digital substation process level bus. (PCS-9882SD
only)

Functions
The following table shows all the subtypes of PCS-9882. Different Ethernet port0s arrangements and functions are provided.

Functions PCS-9882AD PCS-9882BD PCS-9882ED PCS-9882PD PCS-9882SD PCS-9882GD

Ethernet Switching
Gigabit port (SFP, 1000BASE-SX,
0~4 0~2 0 0~4[4] 0~4[5]
1.25GBd, IEEE 802.3, hot plug)
Gigabit port (Copper, 10BASE-
0~4 0~2 0 0~4[4] 0~4[5]
T/100BASE-TX/100BASE-T, MDI/MDIX)
[6]
Fast Ethernet ports (SFP, 100BASE-FX,
0~2[1] 0~16[2] 0~12[3] 0~4[4] 0~18[5]
IEEE 802.3, hot plug)
Fast Ethernet ports (Copper, 10BASE-
22~24[1] 0~16[2] 12~24[3] 24 0
T/100BASE-TX, MDI/MDIX)
Direct forward mode Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Flow Control (IEEE 802.3x)
Network storm suppression Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Port rate limitation Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Port mirror Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Link aggregation Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Quality of Service control Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Flow limitation (MAC-based) Ɣ Ɣ Ɣ
Flow limitation (protocol-based) Ɣ Ɣ Ɣ

136
www.nrec.com/en

Functions PCS-9882AD PCS-9882BD PCS-9882ED PCS-9882PD PCS-9882SD PCS-9882GD

Delay Compensation
GOOSE message-based Ɣ
SMV message-based Ɣ
Virtual Local Area Network
Port-based VLAN Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
MAC-based VLAN Ɣ Ɣ Ɣ
Protocol-based VLAN Ɣ Ɣ Ɣ
IP-based VLAN Ɣ Ɣ Ɣ
IEEE 802.1Q-based VLAN Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
2YHUODSSHG9/$1FRQ¿JXUDWLRQ Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
9/$1WDJLQVHUWLRQPRGL¿FDWLRQDQG
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
deletion
GARP VLAN registration protocol Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
QinQ VLAN Ɣ Ɣ Ɣ
Ring Network
STP (IEEE 802.1D), RSTP (IEEE 802.1w),
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
MSTP (fast switch to backup link)
NR-Ring private protocol (faster recovery
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
speed)
Dedicated protocol (minimize network
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
storm)
MRP Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Multicast
IEEE802.1Q-based VLAN multicast Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
MAC-based static multicast management Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
GMRP dynamic multicast management Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ

Automation System
IGMP snooping dynamic multicast
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
management.
Port Security
Static MAC-based port security
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
FHUWL¿FDWLRQ
IEEE 802.1X-based port security
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
FHUWL¿FDWLRQ
RADIUS Server (with IEEE 802.1X for
Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
UHPRWHDQGORFDOFHUWL¿FDWLRQ
SSL/SSH Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Quantity limitation on MAC learning Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Telnet ON/OFF Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Free of DoS attack Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
ACL function Ɣ Ɣ Ɣ
Security log and operation log Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Clock Synchronization
SNTP Server/Client Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
PTP Ɣ Ɣ Ɣ
File Management

137
Protection Automation Control

Functions PCS-9882AD PCS-9882BD PCS-9882ED PCS-9882PD PCS-9882SD PCS-9882GD

2IÀLQHPRGL¿FDWLRQRIFRQ¿J¿OH Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
8SORDGLQJDQGGRZQORDGLQJRIFRQ¿J¿OH Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
/RJDQGHYHQW¿OHXSORDGLQJWR3& Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Management Method
WEB Server, Telnet and CLI Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
IEC 61850 MMS remote monitoring Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
SNMP V1/V2C/V3. Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
RMON Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
Alarm and block output contact via relay Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
,3FRQÀLFWGHWHFWLRQ Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
LLDP Ɣ Ɣ Ɣ Ɣ Ɣ Ɣ
TACACS+, RADIUS and IEEE802.1X Ɣ Ɣ Ɣ
Data Store & Forward Delay
Fast Ethernet port ȝV ȝV ȝV ȝV ȝV ȝV
Gigabit port ȝV ȝV ȝV ȝV ȝV ȝV

>@)RU3&6$'WKH1R IDVW(WKHUQHWSRUWVDUHFRQ¿JXUDEOHWREHFRSSHURU¿EHURSWLF3OHDVHXVHGLIIHUHQW6)3VRFNHWV
for the distinction.

>@)RU3&6%'DOOWKHIDVW(WKHUQHWSRUWVDUHFRQ¿JXUDEOHWREHFRSSHURU¿EHURSWLF3OHDVHXVHGLIIHUHQW6)3VRFNHWVIRUWKH
distinction.

>@)RU3&6('WKH1RaIDVW(WKHUQHWSRUWVDUHFRQ¿JXUDEOHWREHFRSSHURU¿EHURSWLF3OHDVHXVHGLIIHUHQW6)3VRFNHWVIRU
the distinction.

>@)RU3&63'DOOWKH*LJDELWSRUWVVKDUHWKHVDPHLQWHUIDFHVZLWK¿EHURSWLFIDVW(WKHUQHWSRUWV3OHDVHXVHGLIIHUHQW6)3
sockets for the distinction.

>@)RU 3&66' DOO WKH  *LJDELW SRUWV VKDUH WKH VDPH LQWHUIDFHV ZLWK  RXW RI   ¿EHU RSWLF IDVW (WKHUQHW SRUWV 3OHDVH XVH
different SFP sockets for the distinction.

>@)RU3&6*'PRGXODUVWUXFWXUHVZLWFKDOOWKHSRUWVDUHFRQ¿JXUDEOH3OHDVHVSHFLI\\RXUUHTXLUHPHQWZLWKSRUWW\SHDQG
quantity according to the following table.

>@)RU 3&6*' DOO WKH ¿EHU RSWLF IDVW (WKHUQHW SRUWV PD[  VKDUH WKH VDPH LQWHUIDFHV ZLWK DOO WKH ¿EHU RSWLF *LJDELW SRUWV
Please use different SFP sockets for the distinction.

[8]For PCS-9882GD, all the copper fast Ethernet and Gigabit ports share the same interfaces.

Gigabit Port Fast Ethernet Port


Type
Fiber Optic Copper Fiber Optic Copper
PCS-9882GD-28F 0~28[7] / 0~28[7] /
PCS-9882GD-4F24C 0~4[7] 0~24[8] 0~4[7] 0~24[8]
PCS-9882GD-8F16C 0~8[7] 0~16[8] 0~8[7] 0~16[8]
PCS-9882GD-16F 0~16[7] / 0~16[7] /
PCS-9882GD-16F8C 0~16[7] 0~8[8] 0~16[7] 0~8[8]
PCS-9882GD-8F8C 0~8[7] 0~8[8] 0~8[7] 0~8[8]

138