Z-PC Line

Z-PC LINE
DATA ACQUISITION, DISTRIBUTED AUTOMATION AND TELECONTROL SYSTEMS
Z-PC Line is a modular automation system for managing from a For example, up to 24 digital and 8 analog signals can be ac-
single signal to thousands of I/Os. Z-PC series includes the max- quired with just one module. The DIN rail modular bus support
imum variety of I/O modules: digital inputs, fast counters, digital is available in 1, 2, 4, 8 slots. The modules are hot-swappable,
relay and mosfet outputs, analog channels (mA, V, Ohm, mV), i.e. they are hot-swappable without power and communication
strain gauge, resistance thermometers, thermocouples, electrical
interruption. The system is completed by a wide range of inter-
signals, galvanically isolated and with ModBUS, CANopen, Eth-
faces and network interconnections to expand the configuration.
ernet, M-BUS communication protocols. The I/O modules sup-
Thanks to its flexibility and modularity, the Z-PC Line is a distribut-
port RS485 serial communication with ModBUS RTU protocol,
up to 64 nodes without repeater and speeds up to 115 kbps. The ed system for multi-sector applications: data acquisition, building
wiring of the power supply and the serial connection is facilitated automation, telecontrol, energy monitoring, manufacturing con-
by means of a bus housed in the IEC EN 60715 DIN rail. Maxi- trol, ship automation, laboratory tests, environmental analysis,
mum data concentration is also guaranteed. water treatment etc.

MULTIFUNCTION CONTROL UNITS I/O MODULES

Reed, PNP, NPN,


Proximity, Contact
SoftPLC OPEN TO SCADA I/O MANAGEMENT DIGITAL BUILT-IN CONTROL SUPPORTED
IEC 61131 / OPC / WEB Built-in on board INPUTS FUNCTIONS PROTOCOLS
CLIENT External up to 1.000 I/O

power

OUT

✔︎ SPST Relay
IN

or Mosfet
IEC 81850 DATA ADVANCED DIGITAL MULTIWAYS 32 BIT COUNTERS
IEC 60870-5-101/104 STORAGE ALARM OUTPUTS ISOLATION @1,5 kVac @10kHz
ENERGY PROTOCOLS MANAGEMENT

INTEGRATION WITH SPECIAL DATA EXCHANGE WIDE OPERATING 2,5 mm2 REMOVABLE FRONT
THIRD-PARTY APPLICATIONS WITH OPC UA TEMPERATURE TERMINALS COMMUNICATION
DEVICES AND LIBRARIES STANDARD RANGE PORT

2 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
GENERAL FEATURES
WIDE UNIVERSAL FLEXIBLE CONFIGURATION TOOLS AND SERVICES FOR
RANGE APPLICATIONS (EASY SETUP, Z-NET4, SYSTEM INTEGRATORS
DIP switch)

DATA ACQUISITION TOOLS AC/DC SWITCHING POWER BUS SYSTEM


(Data Recorder, OPC UA, NI LabVIEW POWER SUPPLY TRANSDUCERS (power supply/communication)
Drivers, ModBUS Visual Studio Libraries) on DIN rail

COMMUNICATION INTERFACES

HOT SWAPPING DATA RECORDER ANALOG 3G+/4G/GPS/GLONASS SERIAL / USB INDUSTRIAL


MODULES DAQ SOFTWARE INPUT GATEWAYS / ROUTERS CONVERTERS MODEMS

RESOLUTION UP CE / UL LOAD CELL FIBER OPTICS MULTI-CHANNEL IT PROTOCOLS


TO 16 BITS APPROVALS INPUT CONVERTERS RADIO MODEMS

TEMPERATURE ELECTRICAL PID TELECONTROL / VPN IoT / Cloud


SENSORS INPUT MEASUREMENT REGULATION REMOTE SUPPORT SOLUTIONS
ASSISTANCE
SOLUTIONS
SENECA I Z-PC Line - Data Acquisition and Automation Systems 3
Z-PC Line
MODBUS RTU DIGITAL I/O MODULES
Z-D-IN Z-D-OUT Z-10-D-IN Z-10-D-OUT

5-CH digital input module / RS485 5-CH digital output module / 10-CH digital input module / 10-CH digital output module /
ModBUS RTU RS485 ModBUS RTU RS485 ModBUS RTU RS485 ModBUS RTU
GENERAL DATA
Power Supply 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac / 50-60 Hz
Max Power Consumtion 2,5 W 2,5 W 3,5 W 2,5 W
Isolation 1.500 Vac (3-ways) 1.500 Vac (3-ways) 1.500 Vac (3-ways) 1.500 Vac (3-ways)
Power Transducers Yes, 17Vdc/20mA, max 5 sensors - Yes, 17Vdc/40mA, max 10 sensors -
LED status indicators Power Supply Power Supply Power Supply Power Supply
Error Error Error Error
Data transmission Data transmission Data transmission Data transmission
Data receiving Data receiving Data receiving Data receiving
Input status Output status Input status Output status
Diagnostic
Protection degree IP20 IP20 IP20 IP20
Operating temperature -10..+65°C -10..+65°C -10..+65°C -10..+65°C
Dimension 17.5 x 100 x 112 mm 17.5 x 100 x 112 mm 17.5 x 100 x 112 mm 17.5 x 100 x 112 mm
Weght 140 g approx 140 g approx 140 g approx 140 g approx
Case Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self
extinguishing class V0 extinguishing class V0 extinguishing class V0 extinguishing class V0
Connections Removable terminals with section of 2,5 Removable terminals with section of 2,5 Removable terminals with section of 2,5 Removable terminals with section of 2,5
mm2 mm2 mm2 mm2
Mounting DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail
Programming Z-NET4 (system software) Z-NET4 (system software) Z-NET4 (system software) Z-NET4 (system software)
EASY SETUP (plug&play software) EASY SETUP (plug&play software) EASY SETUP (plug&play software) EASY SETUP (plug&play software)
DIP switch DIP switch DIP switch DIP switch
Memory (data) EEPROM for setting parameters, retention EEPROM for setting parameters, retention EEPROM for setting parameters, retention EEPROM for setting parameters, retention
time 10 years, Nr.5 registers @16 bits, Nr.5 time 10 years time 10 years, FeRAM for counters saving time 10 years
overflow bits, FeRAM for counters saving
COMMUNICATION
Interfaces RS485 2 wires RS485 2 wires RS485 2 wires RS485 2 wires
Speed Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps
Protocols ModBUS RTU slave ModBUS RTU slave ModBUS RTU slave ModBUS RTU slave
Communication time < 10 ms (@ 38400 bps) < 10 ms (@ 38400 bps) < 10 ms (@ 38400 bps) < 10 ms (@ 38400 bps)
Max distance Up to 1.200 m Up to 1.200 m Up to 1.200 m Up to 1.200 m
Connectivity Max 32 nodes Max 32 nodes Max 32 nodes Max 32 nodes
INPUT / OUTPUT DATA
Nr. Channels 5 inputs 5 outputs 10 inputs 10 outputs
Tipo Nr.5 optoisolated input Reed, Proximity, PNP, Nr.5 SPST relay output (NO in common) Nr.10 optoisolated channels (reed, proximity, Nr.10 MOSFET outputs protected from short
NPN, contact etc. max relay capacity 5A 250 Vac with pnp, npn, contact) with common negative circuit with negative in common, supplied
Nr.5 counters @16 bit, max freq. 100 Hz; resistive load; 2A with inductive load self-powered 24 Vdc, protected from from 6 to 40 Vdc, flow rate 0,5 A, resistive
Nr.1 counter @32 bit, max freq. 10 kHz Max current 12 A on common terminal transients up to 600 W/ms or inductive load
Anti-rebound filter 5..250 ms Relay safety status in case of Nr.8 inputs @16 bits max freq. 100 Hz; nr.2 Adjustable safety time 33 ms..2184 s
Overflow indication of each totalizer communication failure inputs@32 bits max freq. 10 KHz Load supply voltage measurement
Adjustable safety time from 0,5 to 25 ms Inputs protected by fast transient Diagnostic signal on the front panel for each
suppressors TVS 600 W/ms channel: ON / OFF / Overload / Open circuit
Frequency measurement for 10 kHz inputs Programmable fail-safe function (output
Measurement of period, frequency, Ton, Toff status)
for 100 Hz inputs
Total count forward or backward
Overflow indication of each totalizer
STANDARD
Approvals CE CE UL-UR CSA, CE UL-UR CSA, CE
Norms EN 50081-2; EN 55011; EN 50082-2; EN EN 50081-2; EN 55011; EN 50082-2; EN EN 50081-2; EN 55011; EN 50082-2; EN EN 50081-2; EN 55011; EN 50082-2; EN
61000-2-2/4; EN 50140/141; EN 61010-1 61000-2-2/4; EN 50140/141; EN 61010-1 61000-2-2/4; EN 50140/141; EN 61010-1 61000-2-2/4; EN 50140/141; EN 61010-1

4 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
MODBUS RTU ANALOG I/O MODULES
Z-DAQ-PID Z-4AI Z-8AI Z-3AO Z-SG

I/O universal module with 4-CH current/voltage 8-CH current/voltage 3-CH current/voltage
Strain gauge input module
PID regulation / RS485 input module / RS485 input module / RS485 output module / RS485
/ RS485 ModBUS RTU
ModBUS RRTU ModBUS RTU ModBUS RTU ModBUS RTU
GENERAL DATA
Power Supply 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac
Max power consumption 2W 3,5 W 3,5 W 3,2 W 2W
Isolation 1,5 kVac (3-way) 1,5 kVac (3-way) 1,5 kVac (3-way) 1,5 kVac (3-way) 1,5 kVac (3-way)
Power transducers Yes, 17Vdc/25mA, max 1 channel Yes, 20Vdc/40mA, max 4 channels Yes, 13Vdc/90+90mA, max 8 channels Yes, 5Vdc/60mA, max 1 sensor
Protection degree IP20 IP20 IP20 IP20 IP20
Operating temperarure -10..+65°C -10..+65°C -10..+65°C -10..+65°C -10..+65°C
Dimension 17.5x100x112 mm 17.5x100x112 mm 17.5x100x112 mm 17.5x100x112 mm 17.5x100x112 mm
Weight Approx 140 g Approx 140 g Approx 140 g Approx 140 g Approx 140 g
Case Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self Nylon 6, 30% fiberglass filled, self
extinguishing class V0 extinguishing class V0 extinguishing class V0 extinguishing class V0 extinguishing class V0
Connections Removable screw terminals for Removable screw terminals for Removable screw terminals for Removable screw terminals for Removable screw terminals for
conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2
IDC10 rear connector for DIN rail DC10 rear connector for DIN rail Nr.1 Micro USB 2.0 IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail
RS232 communication front jack RS232 communication front jack RS232 communication front jack Nr.1 Micro USB 2.0
(COM) (COM) (COM)
Mounting DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail
Programming Z-NET4 (system software) Z-NET4 (system software) Z-NET4 (system software) Z-NET4 (system software) Z-NET4 (system software)
EASY SETUP (plug&play software) EASY SETUP (plug&play software) EASY SETUP (plug&play software) EASY SETUP (plug&play software) EASY SETUP (plug&play software)
DIP switch DIP switch DIP switch DIP switch DIP switch
Memory (data) EEPROM for configuration EEPROM for configuration EEPROM for configuration EEPROM for configuration EEPROM for configuration
parameters, retention time 10 parameters, retention time 10 parameters, retention time 10 parameters, retention time 10 parameters, retention time 40
years years years years years
COMMUNICATION
Interfaces RS485 2 wires RS485 2 wires RS485 2 wires RS485 2 wires RS485 2 wires
RS232 (jack stereo 3.5 mm) RS232 (jack stereo 3.5 mm) RS232 (jack stereo 3.5 mm) RS232 (jack stereo 3.5 mm)
Speed Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps
Protocols MosBUS RTU slave MosBUS RTU slave MosBUS RTU slave MosBUS RTU slave MosBUS RTU slave
Communication time < 10 ms (@38.400 bps) < 10 ms (@38.400 bps) < 10 ms (@38.400 bps) < 10 ms (@38.400 bps) < 10 ms (@38.400 bps)
Max distance Up to 1.200 m Up to 1.200 m Up to 1.200 m Up to 1.200 m Up to 1.200 m
Connectivity Max 32 nodes Max 32 nodes Max 32 nodes Max 32 nodes Max 32 nodes
INPUT / OUTPUT DATA
Nr.channels 1 input, 1 output 4 inputs 8 inputs 3 outputs (active) 1 input, 1 output
Type INPUT Bipolar voltage ±10 Vdc or Bipolar programmable voltage Voltage (±10 V, 0/2...10 V, INPUT
Millivolt: ±2 Vdc, impedance 100 KΩ (±2.5 Vdc, ±10 Vdc, impedance controllable impedance > 600 Ω) 1 analog channel for reading (and
configurable from -10 to +80 mV Bipolar direct current ±20 mA, >100 kΩ) or current (±20 mA) or current (0/4..20 mA, controllable power supply) up to 4 (350 Ω)
Voltage: impedance 100 Ω impedance < 600 Ω) or 8 (1,000 Ω) strain gauge load
configurable from 0 to 10 V cells, 4-wire or 6-wire connection,
Current: equivalent impedance 87 Ω
configurable from 0 to 20 mA 1 DI/1DO tare calibration or weight
Potentiometer: 1 kΩ... 100 kΩ threshold
Thermocouple J,K,E,T,N,B,R,S Sensitivity from 1 to 64 mV/V
RTD: Pt100, Pt500, Pt1000, Ni100 OUTPUT
OUTPUT 1 analog retransmission channel
Configurable voltage between of the net weight in current (0..20,
0-10 V 4..20 mA) or voltage (0..5/10 V)
Active / passive current
configurable between 0-20 mA
Resolution 14 bit + sign 16 bit 16 bit 13 bit 24 bit (ADC)
Accuracy class 0,1% 0,1% 0,1% 0,1% 0,01%
Stability 0,01%/°C 0,01%/°C 0,01%/°C 0,01%/°C 25 ppm/K
STANDARD
Approvals CE CE CE, UL-UR CE, UL-UR CE
Norms EN 61000-6-4, EN 61000-6-2, EN EN 50081-2, EN 55011, EN EN 50081-2, EN 55011, EN EN 50081-2, EN 55011, EN EN 61000-6-4/2002, EN 61000-
61010-1 50082-2, EN 61000-2-2/4, EN 50082-2, EN 61000-2-2/4, EN 50082-2, EN 61000-2-2/4, EN 6-2/2002, EN 61010, EN 60742,
50140/141, EN 61010-1 50140/141, EN 61010-1 50140/141, EN 61010-1 IEC 61131

SENECA I Z-PC Line - Data Acquisition and Automation Systems 5


Z-PC Line
MODBUS RTU TEMPERATURE MODULES
Z-4RTD2 Z-4TC Z-8TC-1 Z-8TC-LAB Z-8NTC

4-CH RTD input module / 4-CH Thermocouple input 8-CH Thermocouple and 8-CH Thermocouple 8-CH NTC thermistors input
RS485 ModBUS RTU module / RS485 ModBUS mV input module / RS485 and mV input module module / RS485 ModBUS
RTU ModBUS RTU / RS485 ModBUS RTU, RTU
interchangeable clamps
GENERAL DATA
Power Supply 10..40 Vdc, 19..28 Vac 50..60 Hz 10..40 Vdc, 19..28 Vac 50..60 Hz 10..40 Vdc, 19..28 Vac 50..60 Hz, 10..40 Vdc, 19..28 Vac 50..60 Hz, 10..40 Vdc, 19..28 Vac 50..60 Hz
bus powered bus powered
Max Power Consumption 0,7 W 1W 0,6 W 0,6 W TBD
Isolation 1.500 Vac 1.500 Vac 1.500 Vac 1.500 Vac 1.500 Vac
Status indicators Power supply Power supply Power supply Power supply Power supply
Error Error Error Error Error
Data transmission Data transmission RS485 RS485 Data transmission
Data reception Data reception Data reception
Protection degree IP20 IP20 IP20 IP20 IP20
Operating temperature -10..+65°C -10..+65°C -10..+65°C -10..+65°C -20..+70°C
Dimension 17,5x100x112 mm 17,5x100x112 mm 17,5x100x112 mm 17,5x100x112 mm 17,5x100x112 mm
Weight Approx 140 g Approx 140 g Approx 140 g Approx 140 g Approx 140 g
Case Nylon 6 preloaded 30% glass fibre, Nylon 6 preloaded 30% glass fibre, Nylon 6 preloaded 30% glass fibre, Nylon 6 preloaded 30% glass fibre, Nylon 6 preloaded 30% glass fibre,
self-extinguishing class V0 self-extinguishing class V0 self-extinguishing class V0 self-extinguishing class V0 self-extinguishing class V0
Connections Removable screw terminals for Removable screw terminals for Removable screw terminals for Removable screw terminals for Removable screw terminals for
conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2 conductors up to 2.5 mm2
IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail
Nr.1 Micro USB 2.0 RS232 communication front jack RS232 communication front jack Nr.1 micro USB 2.0 Nr.1 micro USB 2.0
(COM) (COM)
Mounting For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277
Programming System software (Z-NET4) System software (Z-NET4) System software (Z-NET4) System software (Z-NET4) System software (Z-NET4)
Plug & Play Configurator (EASY Plug & Play Configurator (EASY Plug & Play Configurator (EASY Plug & Play Configurator (EASY Plug & Play Configurator (EASY
SETUP) SETUP) SETUP) SETUP) SETUP)
DIP switch DIP switch DIP switch DIP switch DIP switch
Memory (data) EEPROM for configuration EEPROM for configuration EEPROM for configuration EEPROM for configuration EEPROM for configuration
parameters, retention time 10 parameters, retention time 10 parameters, retention time 10 parameters, retention time 10 parameters, retention time 10
years years years years years
COMMUNICATION
Interfaces Nr.1 RS485 2 wires Nr.1 RS485 2 wires Nr.1 RS485 2 wires Nr.1 RS485 2 wires Nr.1 RS485 2 wires;
Nr.1 Micro USB 2.0 Nr.1 Micro USB 2.0 Nr.1 Micro USB 2.0
Speed Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps Up to 115.200 bps
Protocols ModBUS RTU slave ModBUS RTU slave ModBUS RTU slave ModBUS RTU slave ModBUS RTU slave
Communication time 45..179 ms < 20 ms (@38.400 bps) 45..179 ms 45..179 ms < 10 ms (@38.400 ms)
Max distance Up to 1.200 m Up to 1.200 m Up to 1.200 m Up to 1.200 m Up to 1.200 m
Connectivity Max 32 nodes Max 32 nodes Max 32 nodes Max 32 nodes Max 32 nodes
INPUT / OUTPUT DATA
Nr.channels 4 inputs 4 inputs 8 inputs 8 inputs 8 inputs
Type 4 terminals (ohmeter at 2,3,4 Bipolar voltage ± 80 mVdc, Thermocule type J, K, R, S, T. B, E, Thermocule type J, K, R, S, T. B, E, Generic NTC, user defined curve.
wires) impedance 10 MΩ N (EN 60584-1, ITS-90) N (EN 60584-1, ITS-90) Rated values 1K, 10K, 50K
Pt100: -200..+650°C (f.s. 330 Ω) Thermocouple J, K, R, S, T. B, E, N Range.-210.. +1820 °C Range.-210.. +1820 °C @25°C; Resistance from 100
Pt500: -200..+750°C (f.s 1.800 Ω ) Span mV: -10,1..81,4 mV Span mV: -10,1..81,4 mV Ohm to 10 kOhm; 1 kOhm to 100
Pt1000: -200..+210°C (f.s. Shunt up to 70 mΩ Shunt up to 70 mΩ kOhm; 5 kOhm to 500 kOhm
1.800 Ω)
Ni100: -60..+250°C (f.s. 330 Ω)
Resolution 16 bits 13 bits + sign 16 bits 16 bits 16 bits
Accuracy class 0,1% 0,1% 0,1% 0,1% 0,5%
Thermal drift 25 ppm/K 0,01%/°C c.d.m. < 100 ppm/K < 100 ppm/K < 100 ppm/K
STANDARD
Approvals CE, UL-UR CE CE CE CE
Norms EN 61000-6-4/2002, EN 61000- EN 50081-2, EN 55011, EN EN 61000-6-4/2002, EN 61000- EN 61000-6-4/2002, EN 61000- EN 61000-6-4, EN 61000-6-2, EN
6-2/2002, EN 61010, EN 60742 50082-2, EN 61000-6-4/2002, 6-2/2002, EN 61010, EN 60742 6-2/2002, EN 61010, EN 60742 61010, EN 60742
EN 61000-6-2/2002, EN 61010,
EN 60742

6 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
MODBUS RTU MIXED I/O MODULES
Z-D-IO Z-5DI-2DO Z-4DI-2AI-2DO

8-CH, 5 digital input - 2 analog iinputs -


8-CH, 6 digital input - 2 digital outputs 7-CH, 5 digital input - 2 digital outputs
2 digital outputs - 2 module,
control module, RS485 ModBUS RTU module, RS485 ModBUS RTU
RS485 ModBUS RTU
GENERAL DATA
Power supply 10..40 Vdc / 19..28 Vac / 50-60 Hz 10..40 Vdc / 19..28 Vac 11.40 Vdc; 19..28 Vac
Max consumption 2,5 W 3,5 W 4W
Isolation 1.500 Vac vs inputs 1.500 Vac vs inputs 1.500 Vac
3.750 Vac vs outputs 3.000 Vac vs outputs
Power transducers - - Yes, 12V/(20)40mA, max 8 sensors
LED status indicators Power suppy Power suppy RX/TX RS485
Error Error Error
Data transmission Data transmission
Data reception Data reception
Input status Input status
Output status Output status
Protection degree IP20 IP20 IP20
Operating temperature -10..+65°C -20..+65°C -20..+70°C
Dimension 17,5 x 100 x 112 mm 17,5 x 100 x 112 mm 35x100x112 mm
Weight Approx 200 g Approx 140 g Approx 170 g
Case Nylon 6 reinforced 30% glass fibre class self-extinguishing Nylon 6 reinforced 30% glass fibre class self-extinguishing Black plastic PA6 glass filled
V0 V0
Connections Removable screw terminals for conductors up to 2.5 mm2 Removable screw terminals for conductors up to 2.5 mm2 Removable screw terminals for conductors up to 2.5 mm2
Micro USB (programming)
Mounting 35 mm rail DIN 46277 35 mm rail DIN 46277 35 mm rail DIN 46277
Programming Z-NET4 (system software) EASY SETUP (plug&play software) EASY SETUP (plug&play software)
EASY SETUP (plug&play software) DIP switches DIP switches
DIP switches Web Server
IEC 1131-2 type 1 logic for motors, valves and alarm
controls
Data memory EEPROM for configuration parameters, retention time 10 EEPROM for configuration parameters, retention time 10 Flash 512 kB, FeRAM 64 kB (counters)
years years, Nr.5 registers 32 bit, Nr.5 overflow bits, FeRAM for
saving counters
COMMUNICATION
RS485 Nr.1 RS485 2 wires, up to 115,200 bps, ModBUS RTU Nr.1 RS485 2 wires, up to 115,200 bps, ModBUS RTU Nr.2 RS485 2 wires, up to 115,200 bps, ModBUS RTU
slave, communication time < 10 ms (@38,400 bps), max slave, communication time < 10 ms (@38,400 bps), max slave, communication time from 1 to 300 ms, max distance
distance 1.200, max 32 nodes distance 1.200, max 32 nodes 1,200, max 32 nodes
USB Nr.1 Micro USB Nr.1 Micro USB
INPUT / OUTPUT DATA
Nr.channels 6 digital inputs, 2 digital outputs 5 digital inputs, 2 digital outputs 4 digital inputs, 2 analogue inputs, 2 digital outputs
Type Nr. 6 digital inputs, 2 digital outputs Nr. 5 optoisolated inputs Reed, Proximity, PNP, NPN, contact Nr. 4 optoisolated inputs Reed, Proximity, PNP, NPN, contact
Nr. 6 optoisolated inputs with common type Reed Proximity, etc. etc.
PNP, NPN, contact etc.; internal/external inputs power Nr. 5 counters @32 bit, freq. max 5 kHz” Nr.4 counters @32 bit, freq. max 5 kHz
supply; min pulse length 20 ms Nr. 2 SPST relay outputs with common, fail-safe, capacity Nr. 2 SPST relay outputs with common, fail-safe, capacity
Nr. 2 SPST relay outputs with common, capacity 5A 2A - 250Vac, NO/NC contact, selectable by jumper 2A - 250Vac, NO/NC contact, selectable by jumper
250Vac, NO/NC contact Freq. period measurement Ton/Toff on all inputs” Nr.2 configurable analog inputs mA/V, 0..30Vdc / 0..20mA,
accuracy 0,1%, resolution 16bit, sampling time 1-300 ms
STANDARD
Approvals CE CE CE
Norms EN61000-6-4; EN61000-6-2; EN61010-1 EN61000-6-4; EN61000-6-2; EN61010-1 EN 61000-6-4, EN 61000-6-2, EN 61010-1, EN 60950

SENECA I Z-PC Line - Data Acquisition and Automation Systems 7


Z-PC Line
MODBUS RTU / TCP-IP I/O MODULES
ZE-4DI-2AI-2DO ZE-2AI R-16DI-8DO

R-LINE
ETHERNET

8-CH Mixed 4 digital inputs, 2 analog inputs, 2-CH analog inputs ModBUS RTU / ModBUS 24-CH 16 digital inputs / 8 digital relay
2 digital outputs, ModBUS RTU / ModBUS TCP-IP module outputs Modbus TCP-IP / Modbus RTU
TCP-IP module module
GENERAL DATA
Power supply 11.40 Vdc; 19..28 Vac 10..40 Vdc / 19..28 Vac 11.40 Vdc; 19..28 Vac
Isolation 1,5 kVac 1,5 kVac 1,5 kVac
Protection degree IP20 IP20 IP20
Operating temperature -20..+70°C -20..+70°C -20..+65°C
Dimension 35x100x112 mm 17.5x100x112 mm 106x90x32 mm
Weight Approx 170 g Approx 140 g Approx 170 g
Connections Removable screw terminals for conductors up to 2.5 mm2 Removable screw terminals for conductors up to 2.5 mm2 Clamps pitch 3.5 mm
IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail Double RJ45 connector
Mini USB Mini USB Micro USB (programming)
Mounting For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 / wall-mount
Programming Plug & Play Configurator (EASY SETUP) Plug & Play Configurator (EASY SETUP) SENECA Studio
DIP switch DIP switch Web Server
Web Server Web Server Dual Ethernet Connection Daisy Chain
Special functions LAN ModBUS TCP Server LAN ModBUS TCP Server LAN fault bypass (active connection between the two
Ethernet ports of the device in case of power failure)
Max 32 Peer to Peer Rules (I/O Mirror)
No need master mode
Counters with frequency measurement, TON, TOFF, Period
Modbus Passthrough (TCP-IP to RS485)
Identification and configuration IP, MAC, firmware update
via SDD tool
Data memory Flash 512 kB, FeRAM 64 kB (counters) Flash 512 kB, FeRAM 64 kB (counters) FeRAM for counter backups
COMMUNICATION
Interfaces Nr.1 Ethernet 10/100 Mbps Nr.1 Ethernet 10/100 Mbps Nr.2 Ethernet 10/100 Mbps
Nr.2 RS485 Nr. 2 RS485 Nr. 1 RS485
Nr.1 mini USB 2.0 Nr.1 mini USB 2.0 Nr.1 Micro USB
Speed Up to 115.200 bps (RS485) / 100 Mbps (TCP-IP) Up to 115.200 bps (RS485) / 100 Mbps (TCP-IP) Up to 115.200 bps (RS485) / 100 Mbps (TCP-IP)
Protocols ModBUS RTU, ModBUS TCP-IP, http ModBUS RTU, ModBUS TCP-IP, http ModBUS RTU, ModBUS TCP-IP, http
INPUT DATA
Nr.Channels 4 digital inputs, 2 analog inputs 2 analog inputs 16 digital inputs
Type Nr.2 Analog Inputs 0-20 mA / 0-30 V 0-20 mA / 0-30 V; 16 bit resolution (1-300 ms); sampling PNP with internal/external power supply, NPN with
Nr.4 PNP / NPN Digital Inputs (also configurable as 0,1% f.s. internal power supply; Voltage Threshold OFF / ON: <8
totalizers or counters@32 bit max 7 kHz) V; > 9 V; Max frequency 5 kHz, 32 bit holding counters;
Current consumption 2.25 mA; IEC 6113-2 Type 1 & 3
compliance; Response time P2P 20ms
OUTPUT DATA
Nr.Channels 2 digital outputs 8 digital outputs
Type Relay NO / NC max 5A SPST relay Voltage/Current max 30V / 1A
STANDARD
Approvals CE CE CE
Norms EN 61000-6-4, EN 61000-6-2, EN 61010-1, EN 60950 EN 61000-6-4, EN 61000-6-2, EN 61010-1 EN61000-6-4, EN61000-6-2, EN61010-1

Z-PC Line mixed I/O modules for high-performance analog and digital signals support communication protocols Mod-
BUS TCP-IP and ModBUS RTU on bus / terminal and an extended range for voltage input up to 30 V. These modules
can benefit from a 16-bit ADC converter with configurable acquisition speed from 5 to 300 ms. They also offer com-
ETHERNET plete configurability from a web server compatible with browsers that support Html5.
The R-Series I/O modules are designed for flexible cabling, reduced installation space, applications high-density I/O
I/O and embedded Ethernet networking. They can be connected in Ethernet daisy chain mode with fault-bypass to ensure
Ethernet connection even in the event of failure of a module in the chain and ensure the function “ModBUS
Passthrough”, thanks to the which the module can divert to RS485 the requests coming from Modbus TCP-IP behav-
ing, in fact, like a gateway.

8 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
MODBUS RTU / CANOPEN DIGITAL I/O MODULES
ZC-24DI ZC-24DO ZC-16DI-8DO

24-CH digital input module ModBUS/ 24-CH digital output module ModBUS/ 16 CH digital input - 8 CH digital output
CANopen CANopen module ModBUS/CANpen
GENERAL DATA
Power supply 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac
Power cosumption 1,5 W (typical), 2,5 W (max) 2,5 W 2,5 W
Isolation 1,5 kVac (@ 3 ways) 1,5 kVac (@ 3 ways) 1,5 kVac (@ 3 ways)
Power transducers Yes, 16V/70mA, max 24 sensors - Yes, 16V/70mA, max 16+8 sensors
LED status indicators Power supply Power supply Power supply
Input status Output status Input / Output status
Communication Communication Communication
Protection degree IP20 IP20 IP20
Operating temperature -10..-65˚C -10..-65˚C -10..-65˚C
Dimension 35 x 100 x 112 mm 35 x 100 x 112 mm 35 x 100 x 112 mm
Weight Approx 200 g Approx 200 g Approx 200 g
Case Nylon 6 reinforced 30% glass fibre, self-extinguishing Nylon 6 reinforced 30% glass fibre, self-extinguishing Nylon 6 reinforced 30% glass fibre, self-extinguishing
class V0 class V0 class V0
Connections Removable 4-way screw terminals pitch 3.5 mm, section Removable 4-way screw terminals pitch 3.5 mm, section Removable 4-way screw terminals pitch 3.5 mm, section
2.5 mm2 2.5 mm2 2.5 mm2
Nr.1 Micro USB 2.0 (front panel) Nr.1 Micro USB 2.0 (front panel) Nr.1 Micro USB 2.0 (front panel)
Nr.1 IDC10 rear connector for DIN rail Nr.1 IDC10 rear connector for DIN rail Nr.1 IDC10 rear connector for DIN rail
Nr.1 IDC10 side connector Nr.1 IDC10 side connector
Nr.1 IDC20 side connector
Mounting 35 mm DIN rail IEC EN 60715 35 mm DIN rail IEC EN 60715 35 mm DIN rail IEC EN 60715
Programming DIP switch, Z-NET4, EASY SETUP, EDS, Codesys (IEC DIP switch, Z-NET4, EASY SETUP, EDS, Codesys (IEC DIP switch, Z-NET4, EASY SETUP, EDS, Codesys (IEC
61131) 61131) 61131)
Approvals / Norms CE, EN 61000-6-4, EN 64000-6-2, EN 61010-1, CAN CE, EN 61000-6-4, EN 64000-6-2, EN 61010-1, CAN CE, EN 61000-6-4, EN 64000-6-2, EN 61010-1, CAN
2.0A, 2.0B CiA 401 v.2.01 IEC EN 61131-2 2.0A, 2.0B CiA 401 v.2.01 IEC EN 61131-2 2.0A, 2.0B CiA 401 v.2.01 IEC EN 61131-2
COMMUNICATION
Interfaces RS485, RS232 RS485, RS232 RS485, RS232
Data rate 1 Mbps (CANopen); 115.200 bps (ModBUS) 1 Mbps (CANopen); 115.200 bps (ModBUS) 1 Mbps (CANopen); 115.200 bps (ModBUS)
Protocols CAN bus standard (2.0A, 2.0B); CANopen (profile CiA 401 CAN bus standard (2.0A, 2.0B); CANopen (profile CiA 401 CAN bus standard (2.0A, 2.0B); CANopen (profile CiA 401
v.2.01); ModBUS RTU (via RS485) v.2.01); ModBUS RTU (via RS485) v.2.01); ModBUS RTU (via RS485)
Communication time 2,5 ms 1,2 ms 1,2..2,5 ms
Special function CANopen/ModBUS protocol switching CANopen/ModBUS protocol switching CANopen/ModBUS protocol switching

INPUT / OUTPUT DATA


Nr. Channels 24 inputs (with common negative self-powered at 16 Vdc) 24 outputs 16 inputs, 8 outputs
Type Nr. 24 digital inputs with polarity EN 61131-2 type 2, Nr.24 Mosfet outputs (open source with common Nr.16 digital inputs with polarity EN 61131-2 type 2, synq
synq (pnp); Nr 8 @ 32 bit, freq. max 10 kHz; configuration negative); supply voltage 5..30 Vc; Imax=0,5A (from (pnp); Nr 8 @ 32 bit, freq. max 10 kHz; configuration
increment, reset, preset; Overflow indication; Vmax=30V; terminals) / 25 mA (from connectors); on/off delay < 1ms; increment, reset, preset; Overflow indication; Vmax=30V;
pulse width 250μs; on/off delay < 3ms; TPDO < 1msa RPDO < 1,25 ms pulse width 250μs; on/off delay < 3ms; TPDO < 1ms
Nr.8 Mosfet outputs (open source with common negative);
supply voltage 5..30 Vc; Imax=0,5A (from terminals) /
25 mA (from connectors); on/off delay < 1ms; RPDO <
1,25 ms

CANopen Z-PC Line is a truly distributed I/O system based on IEC 61131 programming that does not require the use of
couplers, controllers or repeaters for each communication line. All modules have an interface CAN communication with
speeds up to 1 Mbps and are therefore ideal for acquiring and controlling system signals on plants and machines where
the distance between the signals plays a fundamental role.
CANopen Z-PC Line modules can be integrated with configurators and master controllers / network managers of third
I/O parties, even on existing machines and installations. The advantage of not needing an end-of-line coupler significantly
reduces the cost factor for small to medium installations CANopen.

SENECA I Z-PC Line - Data Acquisition and Automation Systems 9


Z-PC Line
CANOPEN ANALOG I/O MODULES
ZC-8AI ZC-3AO ZC-4RTD ZC-8TC ZC-SG

8-CH analog (mA, V) input 3-CH analog (mA, V) 4-CH thermoresistance 8-CH thermocouple 1-CH load celle CANopen
module CANopen output CANopen module CANopen module CANopen module module
GENERAL DATA
Power supply 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac 10..40 Vdc / 19..28 Vac (strain
gauge powered by the instrument)
Power consumption 5W 2,5 W 1W 1W 2W
Isolation 1.5 kVac 1.5 kVac 1.5 kVac 1.5 kVac 1.5 kVac
Input protection Against ESD up to 4 kV Against ESD up to 4 kV Against ESD up to 4 kV Against ESD up to 4 kV Against ESD up to 4 kV
Power transducers Yes, 16V/22mA, max 8 sensors - - - Yes, 5Vdc, max 8 sensors
LED status indicators Power supply Power supply Power supply Power supply Power supply
Communication Communication Communication Communication Communication
Input error Input error Input error Input error Input error
Protection degree IP20 IP20 IP20 IP20 IP20
Operating temperature -10..-65˚C -10..-65˚C -10..-65˚C -10..-65˚C -10..-65˚C
Dimension 17,5 x 100 x 112 mm 17,5 x 100 x 112 mm 17,5 x 100 x 112 mm 17,5 x 100 x 112 mm 17,5 x 100 x 112 mm
Weight 170 g 170 g 170 g 170 g 170 g
Case Nylon 6 reinforced 30% glass Nylon 6 reinforced 30% glass Nylon 6 reinforced 30% glass Nylon 6 reinforced 30% glass Nylon 6 reinforced 30% glass
fibre, self-extinguishing class V0 fibre, self-extinguishing class V0 fibre, self-extinguishing class V0 fibre, self-extinguishing class V0 fibre, self-extinguishing class V0
Connections 4-way removable screw terminals, 4-way removable screw terminals, 4-way removable screw terminals, 4-way removable screw terminals, 4-way removable screw terminals,
pitch 3,5 mm pitch 3,5 mm pitch 3,5 mm pitch 3,5 mm pitch 3,5 mm
IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail IDC10 rear connector for DIN rail
3.5 mm stereo front jack for 3.5 mm stereo front jack for 3.5 mm stereo front jack for 3.5 mm stereo front jack for 3.5 mm stereo front jack for
RS232 (COM) RS232 (COM) RS232 (COM) RS232 (COM) RS232 (COM)
Mounting For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277 For 35 mm rail DIN 46277
Programming DIP switch, Z-NET4, EASY SETUP, DIP switch, Z-NET4, EASY SETUP, DIP switch, Z-NET4, EASY SETUP, DIP switch, Z-NET4, EASY SETUP, DIP switch, Z-NET4, EASY SETUP,
EDS, Codesys (IEC 61131) EDS, Codesys (IEC 61131) EDS, Codesys (IEC 61131) EDS, Codesys (IEC 61131) EDS, Codesys (IEC 61131)
Approvals / Norms CE, EN 61000-6-4, EN 64000-6- CE, EN 61000-6-4, EN 64000-6- CE, EN 61000-6-4, EN 64000-6- CE, EN 61000-6-4, EN 64000-6- CE, EN 61000-6-4, EN 64000-6-
2, EN 61010-1 CAN 2.0A, 2.0B 2, EN 61010-1 CAN 2.0A, 2.0B 2, EN 61010-1 CAN 2.0A, 2.0B 2, EN 61010-1 CAN 2.0A, 2.0B 2, EN 61010-1 CAN 2.0A, 2.0B
CiA 401 v.2.01 IEC EN 61131-2 CiA 401 v.2.01 IEC EN 61131-2 CiA 401 v.2.01 IEC EN 61131-2 CiA 401 v.2.01 IEC EN 61131-2 CiA 401 v.2.01 IEC EN 61131-2
COMMUNICATION
Interfaces RS485, RS232 RS485, RS232 RS485, RS232 RS485, RS232 RS485, RS232
Data rate 1Mbps (CANopen) 1Mbps (CANopen) 1Mbps (CANopen) 1Mbps (CANopen) 1Mbps (CANopen)
Protocols CAN bus standard (2.0A, 2.0B) CAN bus standard (2.0A, 2.0B) CAN bus standard (2.0A, 2.0B) CAN bus standard (2.0A, 2.0B) CAN bus standard (2.0A, 2.0B)
CANopen (CiA 401 v.2.01 profile) CANopen (CiA 401 v.2.01 profile) CANopen (CiA 401 v.2.01 profile) CANopen (CiA 401 v.2.01 profile) CANopen (CiA 401 v.2.01 profile)
ModBUS RTU (RS485) ModBUS RTU (RS485) ModBUS RTU (RS485) ModBUS RTU (RS485) ModBUS RTU (RS485)
Sampling time < 28 ms < 7 ms < 28 ms < 28 ms < 7 ms
INPUT / OUTPUT DATA
Nr.channels 8 inputs (isolated in pairs) 3 outputs 4 RTD-isolated inputs, 8 inputs (thermocouple or mV 1 analog input,
2,3,4-wire measurement measurement) 1 digital input/output
Type Voltage (0-10 V); Voltage (± 10 V); PT100 (EN 60751/A2-ITS90), Thermocouple: J,K,E,N,S,R,B,T; “ANALOG INPUT
Current (0-20 mA) Current (0-20, 4-20 mA) -200..+650°C EN - 60584-1 (ITS-90) load cells (strain gauge);
PT500 (EN 60751/A2-ITS90), Span mV: -10,1 mV..+81,4 mV 4 / 6-wire differential measurement
-200..+750°C Input impedance: 10 MΩ (±5 mV..±320 mV);
PT1000 (EN 60751/A2-ITS90), power supply voltage 5 Vdc;
-200..+210°C impedance min 87 equivalent;
Ni100 (EN 60751/A2-ITS90), sensitivity from ±1mV/V to ±64
-60..+250°C mV/V
DIGITAL INPUT
Tare and span calibration (max
30 V)”
1 optoisolated digital output for
stable or threshold weighing (max
current 50 mA, max voltage 30 V)
Resolution 15 bit 14 bit 14 bit 15 bit 24 bit
Accuracy class 0,05% 0,01% 0,05% 0,1% 0,01%
Thermal drift <100 ppm/°C <100 ppm/°C <50 ppm/°C <100 ppm/°C <25 ppm/°C

10 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
I/O MODULES - APPLICATION DIAGRAMS
Process measurement and data retransmission ModBUS acquisition and display
via ModBUS RTU for weighing systems
Z-8AI Z-SG
S401
1 2 3
4 5 6
1 2 3
4 5 6 s
PWR
s ERR
PWR
ERR

COM

COM RX
RX TX
TX

7 8 9
7 8 9 10 11 12
10 11 12

4..20 mA
24V ModBUS RTU ModBUS RTU

Local control via PLC and remote I/O Acquisition and transmission of temperatures to a
closed loop control system
Z-4TC
24V
Remote I/O modules

S401 PLC

t, 0C t, 0C t, 0C t, 0C

RS485 RS485
ModBUS RTU ModBUS RTU
Master Master

RS485
ModBUS RTU

Inverter Controller

Data acquisition over Ethernet Ethernet Daisy Chain and ModBUS


Pass-Through connection

HMI
ETHERNET
ZE-4DI-2AI-2DO
ModBUS TCP-IP

ZE-2AI ETHERNET

Ethernet – Daisy Chain


LAYOUT DEL MODULO LAYOUT DEL MODULO LAYOUT DEL MODULO

Pass through
32.2 mm 32.2 mm 32.2 mm

ModBUS RTU
STS FAIL RX TX STS FAIL RX TX STS FAIL RX TX
micro micro micro
DO1 DO2 DO3 DO4 DO5 USB PORT1 PORT2 DO1 DO2 DO3 DO4 DO5 USB PORT1 PORT2 DO1 DO2 DO3 DO4 DO5 USB PORT1 PORT2

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
 B A GND  B A GND  B A GND
Digital outputs Power supply RS485 ETHERNET SWITCH Digital outputs Power supply RS485 ETHERNET SWITCH Digital outputs Power supply RS485 ETHERNET SWITCH
10÷40 Vdc 10÷40 Vdc 10÷40 Vdc
19÷28 Vac 19÷28 Vac 19÷28 Vac

R-16DI-8DO
ETHERNET I/O MODULE AUTOMATION INTERFACES MADE IN
R-16DI-8DO
ETHERNET I/O MODULE AUTOMATION INTERFACES MADE IN
R-16DI-8DO
ETHERNET I/O MODULE AUTOMATION INTERFACES MADE IN
ITALY ITALY ITALY

IP ADD IP ADD IP ADD


Digital outputs Digital inputs Digital outputs Digital inputs Digital outputs Digital inputs
40 41 42 43 44 45 46 47 48 49
0 5 51 52 53 54 55 56 57 58 59 61 62 63 64 65
60 40 41 42 43 44 45 46 47 48 49
0 5 51 52 53 54 55 56 57 58 59 61 62 63 64 65
60 40 41 42 43 44 45 46 47 48 49
0 5 51 52 53 54 55 56 57 58 59 61 62 63 64 65
60
12V 0V 12V 0V 12V 0V 12V 0V 12V 0V 12V 0V
DO6 DO7 DO8 DO6 DO7 DO8 DO6 DO7 DO8

PWR I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 PWR I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16 PWR I01 I02 I03 I04 I05 I06 I07 I08 I09 I10 I11 I12 I13 I14 I15 I16

Peso 170 g. Contenitore Materiale PCPeso


/ ABS autoestinguente
170 g. Contenitore
UL94-V0, coloreMateriale
nero PC / ABS autoestinguente UL94-V0, colore nero Peso 170 g. Contenitore Materiale PC / ABS autoestinguente UL94-V0, colore nero

Z-TWS4
SEGNALAZIONI DEI LED SUL FRONTALE
LED Stato
R-16DI-8DO
SEGNALAZIONI DEI LED SUL FRONTALE
Significato dei LED LED Stato Significato dei LED
SEGNALAZIONI DEI LED SUL FRONTALE
LED Stato Significato dei LED
Acceso ON  Acceso ONausiliaria
Dispositivo acceso e presenza alimentazione  Dispositivo
ai morsetti
acceso
46-47eepresenza
64-65 alimentazione ausiliaria ai morsetti 46-47 e 64-65 Acceso ON  Dispositivo acceso e presenza alimentazione ausiliaria ai morsetti 46-47 e 64-65
PWR PWR PWR
Spento OFF  Spento OFF ausiliaria
Dispositivo spento e mancanza di alimentazione Dispositivo spento e mancanza di alimentazione ausiliaria Spento OFF  Dispositivo spento e mancanza di alimentazione ausiliaria

ModBUS RTU
Acceso ON  Stato dell’ingresso 01 Attivo Acceso ON  Stato dell’ingresso 01 Attivo Acceso ON  Stato dell’ingresso 01 Attivo
I01 I01 I01
Spento OFF Stato dell’ingresso 01 non Attivo Spento OFF  Stato dell’ingresso 01 non Attivo Spento OFF  Stato dell’ingresso 01 non Attivo
..... ..... ..... ..... ..... ..... ..... ..... .....
Acceso ON  Stato dell’ingresso 16 Attivo Acceso ON  Stato dell’ingresso 16 Attivo Acceso ON  Stato dell’ingresso 16 Attivo
I016 I016 I016
Spento OFF Stato dell’ingresso 16 non Attivo Spento OFF  Stato dell’ingresso 16 non Attivo Spento OFF  Stato dell’ingresso 16 non Attivo
Acceso ON  Uscita 01 Attivata Acceso ON  Uscita 01 Attivata Acceso ON  Uscita 01 Attivata
DO01 DO01 DO01
Spento OFF Uscita 01 Disattivata Spento OFF  Uscita 01 Disattivata Spento OFF  Uscita 01 Disattivata
..... ..... ..... ..... ..... ..... ..... ..... .....
Acceso ON  Uscita 08 Attivata Acceso ON  Uscita 08 Attivata Acceso ON  Uscita 08 Attivata
DO08 DO08 DO08
Spento OFF Uscita 08 Disattivata Spento OFF  Uscita 08 Disattivata Spento OFF  Uscita 08 Disattivata
Acceso ON  Indirizzo IP impostato Acceso ON  Indirizzo IP impostato Acceso ON  Indirizzo IP impostato
STS STS STS
Lampeggio  In attesa dell’indirizzo IP dal DHCPLampeggio  In attesa dell’indirizzo IP dal DHCP Lampeggio  In attesa dell’indirizzo IP dal DHCP

Programmable handling system Automatic bottling system


Acceso ON Verifica delle uscite digitali non superata
Acceso ON  Verifica delle uscite digitali non superata Acceso ON  Verifica delle uscite digitali non superata
FAIL FAIL FAIL
Spento OFF 
Verifica delle uscite digitali superataSpento OFF  Verifica delle uscite digitali superata Spento OFF  Verifica delle uscite digitali superata
Acceso ON Verifica della connessione RS485 Acceso ON  Verifica della connessione RS485 Acceso ON  Verifica della connessione RS485
TX TX TX
Lampeggio Trasmissione pacchetto dati avvenuta Lampeggio
su RS485  Trasmissione pacchetto dati avvenuta su RS485 Lampeggio  Trasmissione pacchetto dati avvenuta su RS485
Acceso ON Verifica della connessione RS485 Acceso ON  Verifica della connessione RS485 Acceso ON  Verifica della connessione RS485
RX RX RX
Lampeggio Ricezione pacchetto dati avvenuta su Lampeggio
RS485  Ricezione pacchetto dati avvenuta su RS485 Lampeggio  Ricezione pacchetto dati avvenuta su RS485
ETH TRF ETH TRF ETH TRF
Lampeggio  Transito pacchetti su porta ethernetLampeggio  Transito pacchetti su porta ethernet Lampeggio  Transito pacchetti su porta ethernet
(Giallo) (Giallo) (Giallo)
ETH LNK ETH LNK ETH LNK

PLC
Lampeggio  La porta ethernet è connessa Lampeggio  La porta ethernet è connessa Lampeggio  La porta ethernet è connessa
(Verde) (Verde) (Verde)
Z-TWS4  
MI005150-I ITALIANO MI005150-I
- 2/6 ITALIANO - 2/6  MI005150-I ITALIANO - 2/6

ZC-24DI ZC-24DO ZC-16DI-8DO

SENECA I Z-PC Line - Data Acquisition and Automation Systems 11


Z-PC Line
MULTIFUNCTION CONTROLLERS - OVERVIEW
SENECA high connectivity multifunction controllers and RTUs (Z-TWS11, Z-TWS4, Z-PASS2-S, S6001- RTU) combine PLC tasks based on
Straton IEC 61131-1 softLPLC platform with web server, datalogger, remote control, remote assistance and energy management features (in
compliance with IEC 60870-101/104, IEC 61850 protocols).
The controllers can be used with different architectures and configurations depending on the complexity of the system and the required
hardware requirements. SENECA also provides process controllers and flow computers for predefined scenarios such as pump control and
pressure boosting units (S6001-PC) and fluid control (Z-FLOWCOMPUTER).

Z-TWS11 Z-TWS4 Z-PASS2-S S6001-RTU S6001-PC Z-FLOWCOMPUTER

MAIN FEATURES

15DI+2DI, 8DO, 4AI, 15DI+2DI, 8DO, 4AI,


Built-in I/O 2AI 1DI, 2DO, 1DI/DO 2DI, 2DO, 2Di/DO 1DI, 3AI, 2DO, 1AO
2AO 2AO

CPU ARM 32bit@120MHz ARM9 32bit@400MHz ARM9 32bit@400MHz ARM9 32bit@400MHz ARM9 32bit@400MHz ARM 32bit@120MHz

HMI application, EASY


Programming Straton, Z-NET4 Straton, Z-NET4 Straton, Z-NET4 Straton, Z-NET4 HMI application
Setup

Flash 8 MB 1 GB 1 GB 1 GB 1 GB 8 MB

RAM 256 kB 64 MB 64 MB 64 MB 64 MB 256 kB

Programming dimension 246 kB 4 MB 4 MB 4 MB - -

PLC var. memory 38 kB 4 MB 4 MB 4 MB - -


CONNECTIVITY

Modem/Router - - 3G+ / 4G 3G+ 3G+ -

ModBUS RTU/TCP, ModBUS RTU/TCP, ModBUS RTU/TCP, ModBUS RTU/TCP


ModBUS RTU/TCP, http, ModBUS RTU/TCP (Slave),
Protocols CANopen, M-BUS, http, CANopen, M-BUS, http, CANopen, M-BUS, http, (Slave), http, ftp, smtp,
ftp, smtp http, ftp,
ftp, smtp ftp, smtp, ppp ftp, smtp, ppp ppp

Iec 60870-101/104, Iec 60870-101/104, Iec 60870-101/104,


Energy protocols (opt.) - - -
IEC 61850 IEC 61850 IEC 61850

VPN - VPN Box, OpenVPN VPN Box, OpenVPN VPN Box, OpenVPN VPN Box, OpenVPN -

APN - x x x x -

Ethernet ports 1 2 2 2 1 1

Serial ports 2 3 3 3 1 1

USB ports 1 (Micro) 1 (Host) 1 (Host) 1 (Host) 1 (Host) 1 (Micro)


APPLICATIONS

Up to 200 I/O x - - - - -

Up to 1.000 I/O - x x x - -

Advanced Automation - - x x - -

Telecontrol / Remote
- x x x - -
Assistance

Microautomation x - - - - -

Energy Management - x x x - -

Pumps control - - - - x -

Gas / Steam applications - - - - - x

12 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition and Automation Systems
MULTIFUNCTION CONTROL UNITS - APPLICATION SCHEMES
Electrical stations control Temperature regulation system

IEC 61850
HMI
Ethernet Z-TWS11

RS485 - ModBUS RS485 - ModBUS

IEC 60870-5-104
Z-TWS4
PT100 Digital
acquisition output
modules modules
IEC 60870-5-101 Z-4RTD Z-D-OUT

IED IED IED


Pump - solenoid valve

Radiators

Plant control and remote maintenance Metering and enegy consumption telecontrol
Scada / Control Room
192.168.1.33

VPN BOX

ROUTER
192.168.1.32 Power
ModBUS TCP-IP Web
Meter
3G
36 35 34 33 32 31 30 29 28 26 25 22 21 20 19 36 35 34 33 32 31 30 29 28 26 25 22 21 20 19 36 35 34 33 32 31 30 29 28 26 25 22 21 20 19

S203RC-D S203RC-D S203RC-D

OK OK OK
ESC ESC ESC
MENÙ MENÙ MENÙ

ROUTER
RS232
10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18

RS485 Printer
Z-PASS2-S Z-PASS2-S ModBUS

192.168.20.154 192.168.20.154

HMI HMI
ModBUS RTU ethernet ModBUS RTU ethernet
I/O

Seneca CPU – M-BUS sensors Distributed and multiuser connection with M-BUS
and meters connection sensors and meters
Z-TWS4
ModBUS TCP-IP

Z-KEY-MBUS
Z-TWS4 Z-MBUS

Max 8 Client Ethernet


TCP-IP
Up to 25
Up to 25 devices
devices COM2 COM1
RS232/RS485 RS485

SCADA

RS232 ModBUS RTU ModBUS RTU

Pumps control Mass and steam calculation


S6001-PC
Z-FLOWCOMPUTER
Water
DI1 AI1

Vapour
DI1 AI1

AI2 AI3

AI2 AI3

SENECA I Z-PC Line - Data Acquisition and Automation Systems 13


Z-PC Line
SOFTWARE
SOFTWARE PLATFORM
SENECA software suite includes powerful system configurators, programming environments including libraries, acquisition tools, data, events and
alarms access and management. Z-NET-4, designed for the configuration of CPUs/controllers, I/O modules and ModBUS devices also enables the
management and creation of databases of machine / plant variables (IEC 61131, OPC, trend, log). Alternatively, for quick configuration of the I/O
modules is available the EASY SETUP plug&play software, also in Android app version.
The programming strategy of the SENECA controllers is based on the industry standard for IEC 61131 PLCs, in particular the Straton softPLC deve-
lopment environment which includes energy management libraries and protocols. Integrated in the Z-NET4 platform, Web Factory allows to develop
html/web supervision pages loaded in the CPUs, to to start with the overall project. Data Recorder and Trend Viewer are flexible tools for data ac-
quisition, trend visualization, events, variables, alarms and more. than managing logs and archives. With the OPC Server technology it is possible to
exchange real-time data with Scada and other Client applications.

EASY SETUP
Plug&Play suite for SENECA
programmable instruments

Z-NET4
Complete configuration environment
for Z-PC Series systems

WEB FACTORY
HMI/Web editor integrato
in Z-NET4

DATA RECORDER
HMI/Web Editor (Z-NET4 built-in)

TREND VIEWER
Trend visualization software
(Z-NET4 built-in)

STRATON
IEC 61131 programming environment

OPC SERVER
Data exchange and real-time variables
management software

EASY Z-NET4 WEB DATA TREND STRATON OPC


SETUP FACTORY RECORDER VIEWER Server
License free free free USB key free USB key USB key
Hardware and I/O configuration ✓ ✓
Full system configuration ✓ ✓
Communication settings ✓ ✓ ✓ ✓ ✓
Variables advanced settings ✓ ✓ ✓
Alarms management ✓ ✓ ✓
Control logic ✓ ✓
Remote control functions ✓ ✓
Math functions ✓ ✓
Logs / events archive ✓
Diagnostic ✓ ✓ ✓ ✓
Data Acquisition ✓ ✓ ✓ ✓ ✓ ✓
Real-time variables simulation / acquisition ✓ ✓ ✓ ✓ ✓ ✓
Data visualization (graphics / trends) ✓ ✓ ✓
Data import / export ✓ ✓
Variables configuration import / export ✓ ✓ ✓ ✓

14 SENECA I Z-PC Line - Data Acquisition and Automation Systems


Data Acquisition
SERIEand
Z-PC
Automation
- DATA RECORDER
Systems
DATA RECORDER
Data Recorder is an open, scalable and economical software recorder based on Windows PC, ideal for testing
sessions, laboratories, rehearsal rooms, monitoring of process measurements. Physical data acquisitions is
made through Z-PC Line distributed I/O modules (with or without CPU), and in general from any ModBUS RTU
slave standard device.
Communication between hardware and PC can be serial (RS232/RS485/ModBUS RTU) or Ethernet / Mod-
BUS TCP, on wired or wireless physical medium. The licensing is managed with USB key and covers a vis-
ualization range from 2 to unlimited channels. The normalized graphic representation can be set with nibs or
display (digit). The real-time display offers multiple selection options: groups of channels, visualization range,
screen scrolling direction.

TOOLS / OPTIONS
Physical data acquisition via Windows & OPC tested Hand-held DAQ system ready-to-use
Minimum hardware SENECA Z-PC Line remote I/O system & supported
requirements
O.S. Windows 8 or later
RAM 128 MB
HD 3G
SVGA 800x600

HIGHLIGHTS

Software license from Real-time data Logging files (SQLite) Data and project integration
2 to unlimited channels recording with pen or displayed with Trend Viewer with Z-NET configuration
display (digit) software tool suite

PLUS package with math, Scheduling Serial, Ethernet, Wireless Advanced calibration for
report, alarm, multiclient recording connection support temperature sensors
functions

APPLICATION SCHEMES

MONITORING OF WATER TEST AND DATA ACQUISITION TEMPERATURE AND HUMIDITY MONITORING OF CLIMATIC
QUALITY PARAMETERS FOR ELECTRIC MOTORS MONITORING CHAMBERS

SENECA I Z-PC Line - Data Acquisition and Automation Systems 15


CONTACTS AND INFORMATIONS
Address
Headquarter: Via Austria 26 - 35127 Padova (I)
Tel. +39 049 8705 359 (408)
Fax +39 049 8706287
Web
General website: www.seneca.it
Documentation: www.seneca.it/en/cataloghi-flyers/
Tech support: www.seneca.it/en/supporto-e-assistenza
eCommerce: www.seneca.it/en/vetrina
E-mail
General information: info@seneca.it
Sales Office: sales@seneca.it
Quality Management: qualita@seneca.it
Product technical support: support@seneca.it

Follow us on Social Media 19C1347 - Pubblication Z-PC LINE 1911EN - December 2019

The information contained in this document may be modified or supplemented without notice for technical or commercial reasons.
Discrepancies and inaccuracies cannot be excluded, despite the continuous search for perfection. The contents of this document are as
follows which is, in any case, subject to periodic review.

You might also like