FB107:COM Product Data Sheet

D301237X012 July 2013

FloBoss™ 107 Communication Modules


Communication modules add communication ports to a module is installed in slot 2, the communication port (COM2)
FloBoss™ 107 Flow Manager (“FB107”). The FB107’s central on the CPU is redirected to the type of module installed in slot
processor unit (CPU) provides three built-in communication 2. Use ROCLINK™ 800 Configuration Software to configure
ports. You can add one communication module, resulting in a the modules.
maximum of four communication ports per FB107.
Each communication module uses a separate channel from
The communication modules provide solutions to suit the other modules and has a common ground (“single-
applications including: ended”). The field interface protects the electronics in the
module. Each module reduces the effect of noise on
 EIA-232 (RS-232) provides point-to-point asynchronous communication errors through filtering.
serial communications. EIA-232 (RS-232) communications
commonly provide the physical interface for connecting LEDs display the RX (receive) and TX (transmit) signals for the
serial devices, such as gas chromatographs and radios. The EIA-232 (RS-232) communication module. LEDs display the A
EIA-232 (RS-232) communication module provides (transmit/receive+) and B (transmit/receive −) signals for the
essential hand-shaking lines required for radio EIA-485 (RS-485) communication module.
communications, including Request to Send (RTS).
The FB107 supports communication protocols, including ROC
 EIA-485 (RS-485) provides asynchronous serial protocol and Modbus protocol. An FB107 can act as a Modbus
communications for multi-drop units on a serial network slave device (ASCII or RTU) or it can function as a Modbus host
over long distances using inexpensive twisted-pair cables. on COM1, 2, or 3.
Each communication module plugs into a module slot on the
main FB107 unit, which provides power and control signals to
activate COM3.You can install a communication module in
slot 1 or 2 on the main FB107. When a communication

EIA-232 (RS-232) Communication Module EIA-485 (RS-485) Communication Module

Remote Automation Solutions


FB107:COM July 2013

FB107 EIA-232 (RS-232) Communication Module


Field Wiring Terminals

Terminal Label Definition


1 TX Transmit
2 RX Receive
3 RTS Request To Send
4 NC No Connection
5 NC No Connection
6 GND – (Common)

Communications
Meets EIA-232 (RS-232) standard for single-ended data transmission over distances of up to 15 m (50 ft).
Data Rate Selectable from 300 to 115.2 K baud.
Format Asynchronous, 7 or 8-bit (software-configurable) with full handshaking.
Parity None, odd, or even (software-configurable).
LEDs RX (receive) and TX (transmit) signals for COM3 on the EIA-232 (RS-232) communication
module.
Protocols ROC, Modbus host and slave (RTU or ASCII).

Power
Power Requirements 30 mW, supplied by backplane.
Receive 21 mW
Transmit 50 mW

Physical
Dimensions 82.55 mm H by 25.4 mm W by 127 mm L
(3.25 in. H by 1.0 in. W by 5.0 in. L)
Weight 90.7 g (3.2 oz.)
Wiring 16 to 24 AWG at the removable terminal block.

Environmental
Same as the unit in which it is installed.

Approvals
Same as the unit in which it is installed.

2 www.EmersonProcess.com/Remote
July 2013 FB107:COM

FB107 EIA-485 (RS-485) Communication Module

Field Wiring Terminals

Terminal Label Definition


1 A Receive / Transmit +
2 B Receive / Transmit –
3 NC No Connection
4 NC No Connection
5 NC No Connection
6 GND – (Common)

Communications
Meets EIA-485 (RS-485) standard for differential data transmission over distances of up to 1220 m (4000 ft).
Data Rate Selectable from 300 to 115.2 K baud.
Format Asynchronous, 7 or 8-bit (software-configurable).
Parity None, odd, or even (software-configurable).
LEDs A and B indicate communication activity status.
Protocols ROC, Modbus host and slave (RTU or ASCII).

Power
Power Requirements 30 mW, supplied by backplane.
Receive 27 mW
Transmit 35 mW

Physical
Dimensions 82.55 mm H by 25.4 mm W by 127 mm L
(3.25 in. H by 1.0 in. W by 5.0 in. L)
Weight 90.7 g (3.2 oz.)
Wiring 16 to 24 AWG at the removable terminal block.

Environmental
Same as the unit in which it is installed.

Approvals
Same as the unit in which it is installed.

www.EmersonProcess.com/Remote 3
FB107:COM July 2013

Headquarters:
Emerson Process Management
Remote Automation Solutions
6005 Rogerdale Road
Houston, TX 77072 U.S.A.
T +1 281 879 2699 | F +1 281 988 4445
www.EmersonProcess.com/Remote
Europe:
Emerson Process Management
Remote Automation Solutions
Unit 8, Waterfront Business Park
Dudley Road, Brierly Hill
Dudley UK DY5 1LX
T +44 1384 487200 | F +44 1384 487258
www.EmersonProcess.com/Remote
North American/Latin America:
Emerson Process Management
Remote Automation Solutions
6005 Rogerdale Road © 2006-2013 Remote Automation Solutions, a business unit of Emerson Process
Houston TX USA 77072 Management. All rights reserved.
T +1 281 879 2699 | F +1 281 988 4445 Bristol, Inc., Bristol Canada, BBI SA de CV and Emerson Process Management Ltd, Remote
www.EmersonProcess.com/Remote Automation Solutions division (UK), are wholly owned subsidiaries of Emerson Electric Co.
Middle East/Africa: doing business as Remote Automation Solutions, a business unit of Emerson Process
Emerson Process Management Management. FloBoss, ROCLINK, Bristol, Bristol Babcock, ControlWave, TeleFlow, Helicoid,
Remote Automation Solutions OpenEnterprise, and METCO are trademarks of Remote Automation Solutions. AMS,
Emerson FZE PlantWeb and the PlantWeb logo are marks of Emerson Electric Co. The Emerson logo is a
P.O. Box 17033 trademark and service mark of the Emerson Electric Co. All other marks are property of their
Jebel Ali Free Zone – South 2 respective owners.
Dubai U.A.E. The contents of this publication are presented for informational purposes only. While every
T +971 4 8118100 | F +971 4 8865465 effort has been made to ensure informational accuracy, they are not to be construed as
www.EmersonProcess.com/Remote warranties or guarantees, express or implied, regarding the products or services described
Asia-Pacific: herein or their use or applicability. Remote Automation Solutions reserves the right to modify
Emerson Process Management or improve the designs or specifications of such products at any time without notice. All sales
Remote Automation Solutions are governed by Remote Automation Solutions’ terms and conditions which are available
1 Pandan Crescent upon request. Remote Automation Solutions does not assume responsibility for the
Singapore 128461 selection, use or maintenance of any product. Responsibility for proper selection, use and
T +65 6777 8211| F +65 6777 0947 maintenance of any Remote Automation Solutions product remains solely with the purchaser
www.EmersonProcess.com/Remote and end-user.

Remote Automation Solutions

You might also like