Siemens H-Pos: 400; 3EK7 420-4CH4-Z P12 M81 P31


System Information
Highest Voltage of Equipment (Um) 36,0 kV
Basic Insulation Level (BIL) 170 kV
Maximum altitude of installation (a.s.l.) 1 000 m
Neutral system earthing isolated
Power Frequency 48 ... 62 Hz
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 42,0 kV
Maximum continuous operating voltage (Uc / MCOV) 34,0 kV
Nominal discharge current (In, 8/20 µs) 10 kA
Line discharge class 1
Long duration impulse current withstand (2 ms) 325 A
High current impulse withstand (4/10 µs) 100 kA
Rated short circuit current (0,2 s) 20,0 kA
Maximum residual voltage at :
10 kA 1/2 µs 119 kV
5 kA 8/20 µs 104 kV
10 kA 8/20 µs 111 kV
20 kA 8/20 µs 128 kV
40 kA 8/20 µs 148 kV
500 A 30/60 µs 85,7 kV
1 kA 30/60 µs 89,0 kV
2 kA 30/60 µs 93,5 kV
Temporary overvoltage for 1 s 45,1 kV
Temporary overvoltage for 10 s 42,0 kV
Energy discharge capability - thermal 3,50 kJ/kVr
Energy discharge capability - impulse 1,50 kJ/kVr
Power Frequency withstand voltage (1min, wet), 113 kV
arrester complete
Lightning Impulse withstand voltage (1,2/50 µs), 242 kV
arrester complete
Mechanical data
Height (H) 400 mm
Minimum creepage distance 1 230 mm
Weight (G) 5,0 kg
Color of housing grey
Cantilever load, static (Fstat) 296 N
Cantilever load, dynamic (Fdyn) 425 N
Accessories
Line terminal Clamp, washer, nut M12
Ground terminal NEMA insulating bracket
M12, L=210 (P12)
Accessory 1 M81 (M12) Bird cap
Accessory 2 P31 (M12) Disconnector

_______________________________________________________________________________________________________________