BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change.

1/6

Selection: Open Screw Compressors OS


Input Values
Compressor type Screws, open drive
Refrigerant R717
Reference temperature Dew point temp.
Liq. subc. (in condenser) 2.00 K
Suct. gas superheat 1.00 K
Operating mode Standard
Speed 3500 /min
Useful superheat 100%
Additional cooling Automatic
Max. discharge gas temp. 80.0 °C
Cooling capacity 100 %

Overview
A
Evaporating SST -10.00 °C
Condensing SDT 35.0 °C
Qe Pe EER Ratio
kW kW W/W %
Total 312 94.7 3.29 --
OSKA7452-K 155.8 47.4 3.29 50.0
OSKA7452-K 155.8 47.4 3.29 50.0
BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change. 2/6

Application Limits
OSKA7452

Standard OSKA7452

Legend
BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change. 3/6

Result
A
Evaporating SST -10.00 °C
Condensing SDT 35.0 °C
Compressor Total OSKA7452-K OSKA7452-K
Cooling capacity 100% 100%
Cooling capacity 312 kW 155.8 kW 155.8 kW
Cooling capacity * -- 152.9 kW 152.9 kW
Evaporator capacity 312 kW 155.8 kW 155.8 kW
Shaft power 94.7 kW 47.4 kW 47.4 kW
Condenser capacity 358 kW 179.1 kW 179.1 kW
Ratio -- 50.0 % 50.0 %
COP/EER 3.29 3.29 3.29
COP/EER * -- 3.23 3.23
Mass flow LP 1022 kg/h 511 kg/h 511 kg/h
Mass flow HP 1022 kg/h 511 kg/h 511 kg/h
Operating mode Standard Standard Standard
Liquid temp. -- 33.0 °C 33.0 °C
Oil volume flow 4.30 m³/h 2.15 m³/h 2.15 m³/h
Cooling method External External External
Oil cooler outlet 57.0 °C 57.0 °C 57.0 °C
Oil cooler load 48.1 kW 24.0 kW 24.0 kW
Recommended driving motor -- 62.0 kW 62.0 kW
Discharge gas temp. w/o cooling 145.6 °C 145.6 °C 145.6 °C

Consider notes in detailed resp. part load calculation!

*According to EN12900 (5K suction gas superheat, 0K liquid subcooling)


BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change. 4/6

Technical Data: OSKA7452-K


Dimensions and Connections

Technical Data
Technical Data
Displacement (2900 RPM 50 Hz) 192 m³/h
Displacement (3500 RPM 60 Hz) 232 m³/h
Allowed speed range 1450 .. 4000 min-1
Sens of rotation (compressor) links / counter-clockwise
Weight 176 kg
Max. pressure (LP/HP) 19 / 28 bar
Connection suction line 76 mm - 3 1/8''
Connection suction line (NH3) DN 80
Connection discharge line 54 mm - 2 1/8''
Connection discharge line (NH3) DN 50
Adapter for ECO (NH3) DN 20 (Option)
Oil type NH3 Reniso KC68 , SHC 226E
Extent of delivery (Standard)
Suction shut-off valve Standard
Pressure relief valve Standard
Check valve Standard
Oil injection kit Standard
Built in oil filter Standard
discharge gas temperature monitoring SE-B2
Discharge gas temperature sensor Standard
Start unloading Standard
Capacity control 100-75-50% (Standard)
Protective charge Standard
Available Options
Oil flow control Option
Discharge shut-off valve Option
ECO connection with shut-off valve Option
Coupling housing Option
BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change. 5/6
Open Screw Compressors OS

Open Screw Compressors OS


OSK = Application for air.conditioning and medium temperature cooling.
OSN = Application for low temperature cooling.
OSH = Application for air-conditioning and heat pumps.

Notes regarding application limits (see "T.Data - Limits")


* Ranges are valid for standart operation and at full-load conditions.
* With high pressure conditions, part-laod operation is partly limited (see application limits in applications manual SH-500 / 
SH-510).
* With Economizer operation the maximum admissible evaporation temperature is shifted by 10 K downward (otherwise
there is a danger of excessive compression and overlaod of the motor because of a higher mass flow). At pull-down
conditions from higher evaporation temperatures, the ECO injection must remain closed until the evaporation temperature is
below the maximum admissible value and a stable operation is achieved (e.g. control of the ECO solenoid valve by means
of a low pressure cut-out). The use of the ECO-System with higher evaporation temperatures requires individual
consultation with Bitzer.

OS53..OS74
* Capacity control with ECO operation at the same time is limited to one single regulating step (CR 75 %). At CR 50 % the
ECO injection should be closed.
* Combined operation (ECO + CR 50 %) is possible under certain conditions, control and system design, however, require
individual consultation with Bitzer.

Motor Selection
The required driving motor is selected for starting conditions at direct start as well as at star-delta-start with start unloading
(50 % capcaity regulation). The starting conditions refer to the following defined operation points resp. to the maximum
application limit of the compressor. Should the evaporation- or the condensing temperature of the plant be higher at the start, an
individual motor selection is necessary.

Evaporation temperature for motor selection


HH H M L
R134a  +20 °C +12,5 °C -5 °C
R404A / R507A +7,5 °C -5 °C -15 °C
R22 +12,5 °C -5 °C -10 °C
R407C +12,5 °C -5 °C
NH₃ +25 °C +12,5 °C -5 °C -10 °C
The stated motor data refer to IEC motors at which the pull-up torque should not fall below 90 % of the max. torque. In addition
the following starting torque (referring to direct start) must be reached:
* open screw compressors 120 %
Should the motor not fulfil these criteria, an individual selection is also necessary.

Lubricants and additional cooling for NH3 applicationsOil


Type Viscosity Discharge gas Oil injection
temp. (°C) temp. (°C)
Reniso KM32 MO 32 ca. 60 .. max. max. 50
100
Reniso KS46 MO 46 ca. 60 .. max. 80 max. 60
(100 [1])
Reniso KC68 MO 68
Reflo 68A MO (HT) 58
SHC226E PAO 68
[1] 100°C only after consultation with BITZER
Further information on the selection of lubricants can be found in the Application Manuals SH-500 and SH-510.
Legend of connection positions according to "Dimensions":
1 High pressure connection (HP)
1a Additional high pressure connection
1b Connection for high pressure transmitter (HP)
2 Low pressure connection (LP)
2a Additional low pressure transmitter (LP)
2b Connection for low pressure transmitter (LP)
3 Discharge gas temperature sensor connection (HP)
4 Connection for economiser (ECO)
HS.85: ECO valve with connection pipe (option)
BITZER Software v6.17.1 rev2582 29/04/2021 / All data subject to change. 6/6

HS.95, OS.85, OS.95: ECO valve (option)


5 Oil injection connection
6 Oil pressure connection for HS.85 and OS.85:
Oil drain (compressor housing)
7 Oil drain (motor housing)
7a Oil drain (suction gas filter)
7b Oil drain out of shaft seal (maitenance connection)
7c Oil drain tube (shaft seal)
8 Threaded bore for foot fastening
9 Threaded bore for pipe support (ECO and LI line)
10 Maitenance connection (oil filter)
11 Oil drain (oil filter)
12 Monitoring of oil stop valve
OS.85: Monitoring rotation direction and oil stop valve
13 Oil filter monitoring
14 Oil flow switch
15 Earth screw for housing
16 Pressure relief (oil filter chamber)
17 Maitenance connection for shaft seal
18 Liquid injection (LI)
19 Compressor module
20 Slider position indicator
21 Oil level switch
22 Connection for oil pressure transmitter
23 Connection for oil and gas return
(for systems with flooded evaporator adaptor optional)
24 Acces to oil circulation restrictor
SL Suction gas line
DL Discharge gas line
Dimensions can show tolerances according to EN ISO 13920-B.