TAS 203-94 - Criteria For Testing Products Subject To Cyclic Wind Pressure Loading
TAS 203-94 - Criteria For Testing Products Subject To Cyclic Wind Pressure Loading
TAS 203-94 - Criteria For Testing Products Subject To Cyclic Wind Pressure Loading
Florida · State · [ 2010 Florida Building Code: Test Protocols (First Printing) ]
Chapter No. 203-94 - Criteria for Testing Products Subject to Cyclic Wind
Pressure Loading
Reverse
Links
Table of Contents
Section 1. Scope:
Section 2. Referenced Documents:
Section 3. Terminology:
Section 4. Significance and Use:
Section 5. Test Specimen:
Section 6. Procedure:
Section 7. Apparatus:
Section 8. Hazards:
Section 9. Testing Facilities (for a more detailed description see TAS 301-94):
Section 10. Format of Test:
Section 11. Test Reports:
Section 12. Recording Deflections:
Section 13. Additional Testing:
Section 14. Product Marking:
1. Scope:
1.1 This protocol covers procedures for conducting the cyclic wind pressure loading test required by the Florida
Building Code, Building and TAS 201-94.
2. Referenced Documents:
3. Terminology:
3.1 Definitions - For definitions of terms used in this protocol, refer to the Florida Building Code, Building.
3.3 Specimen - The entire assembled, unit submitted for test, including anchorage devices and structure to which
product is to be mounted.
3.4 Positive (Negative) Cyclic Load - the specified differential in static air pressure, creating an inward (outward)
loading, for which the specimen is to be tested under repeated conditions, expressed in pounds per square foot.
3.5 One Cycle - Beginning at the specified static air pressure, the application of positive cyclic test load, and returning
ecodes.cyberregs.com/cgi-exe/cpage.dll?pg=nbdrx&rp=/indx/ST/fl/st/b1400v10/st_fl_st_b1400v10_tas203.htm&sid=2013033007494944711&aph=0&cid=iccf&uid… 1/6
3/30/13 E-Codes
to the specified static air pressure, followed by the application of negative cyclic test load.
3.6 Design Wind Load - The uniform static air pressure difference, inward or outward, for which the specimen would be
designed under service load conditions using the Florida Building Code, Building Section 1620.
3.7 Test Chamber - An airtight enclosure of sufficient depth to allow unobstructed deflection of the specimen during
pressure cycling, including ports for air supply and removal, and equipped with a device to measure test pressure
differentials.
3.8 Maximum Deflection - The maximum displacement measured to the nearest 1/8 inch attained from an original
position while the maximum load is being applied.
3.9 Permanent Deformation - The permanent displacement measured to the nearest 1/8 inch from an original position
that remains after the applied test load has been removed.
3.10 Specimen Failure - A change in condition of the specimen indicative of deterioration under repeated load or
incipient failure, such as cracking, fastener loosening, local yielding, or loss of adhesive bond.
4.1 This test method is a standard procedure for determining compliance with Sections 1625, Table 1625.4 and Table
1626 of the Florida Building Code, Building. This test method is intended to be used for installations of exterior
windows, glazing, wall cladding, exterior doors, skylights, glass block, storm shutters, and other similar device used
as external protection of the building envelope. This test method consists of supplying air to and exhausting air from
the chamber in accordance with a specific test loading program at the rate required to maintain the test pressure
differential across the specimen, and observing, measuring, and recording the deflection, deformations, and nature of
any distress or failures of the specimen.
5. Test Specimen:
5.1 Test specimen - All parts of the test specimen shall be full size, using the same materials, details, methods of
construction and methods of attachment as proposed for actual use. The specimen shall consist of the entire
assembled unit attached to a given type of structural framing of the building, and shall contain all devices used to
resist wind forces and windborne debris. When testing glazed products, the material used to make such glazed
product windborne debris resistant (i.e. fillers, film and similar), shall be an integral part, factory applied, of such
glazed product.
In the case of windows, doors, and sliding glass doors, a pressure treated nominal 2 × 4 wood buck #3 Southern Pine
shall be used for attachment of the specimen to the test frame/stand/chamber. Such wood buck will become part of
the approval.
In the case of storm panels, they must be tested in worst case scenarios where attachments are directly to CBS
block. Figure 1 shows the basic three (3) configurations that shall be required; one per each of the three (3) required
specimens. Each storm panel specimen shall consist of minimum three (3) panels.
ecodes.cyberregs.com/cgi-exe/cpage.dll?pg=nbdrx&rp=/indx/ST/fl/st/b1400v10/st_fl_st_b1400v10_tas203.htm&sid=2013033007494944711&aph=0&cid=iccf&uid… 2/6
3/30/13 E-Codes
5.1.1 Locking mechanisms shall be permanently mounted on the specimen. Such locking mechanism shall
require no tools to be latched in the locked position. Devices such as pins shall be permanently secured to the
specimen through the use of chains or wires which must be of corrosion resistant material. This section does
not apply to specimens referenced in Section 2413 of the Florida Building Code, Building.
5.1.2 Products that are not categorized as means of egress/escape and are provided with more than one single
action locking mechanism, shall be provided with permanently posted instructions on latching for high wind
pressures.
5.1.3 Specimen and fasteners, when used, shall not become disengaged during test procedure.
5.2 If the impact test is to be performed on the test specimen, such test shall be conducted prior to performing the
test described in this protocol.
5.3 All locking mechanisms should be in place when performing this test.
6. Procedure:
6.1 Preparation - Remove from the test specimen any sealing or construction material that is not normally used when
installed in or on a building. Fit the specimen with its structural framing into or against the chamber opening. The
outdoor side of the specimen shall face the higher pressure side for positive loads; the indoor side shall face the higher
pressure side for negative loads. Support and secure the specimen by the same number and type of anchors to be
approved for normal installation of the specimen in the building.
6.2 Support and secure the test specimen by the same number and type of anchors normally used in installing the
unit in the building.
6.3 Load the specimen using the cycles specified in section Table 1625.4 and/or Table 1626 of the Florida Building
Code, Building whichever of these apply.
6.4 In the case of Table 1625.4 of the Florida Building Code, Building Section 6.3 of this protocol must be repeated for
negative pressures.
6.5 Assemblies shall be tested with no resultant failure or distress and shall have a recovery of at least 90% over
maximum deflection. Test Temperature. The test shall be conducted at a test temperature range of 59 to 95 degrees F
(15 to 35 degrees C).
7. Apparatus:
ecodes.cyberregs.com/cgi-exe/cpage.dll?pg=nbdrx&rp=/indx/ST/fl/st/b1400v10/st_fl_st_b1400v10_tas203.htm&sid=2013033007494944711&aph=0&cid=iccf&uid… 3/6
3/30/13 E-Codes
7.1 The description of the apparatus is general in nature. Any equipment, properly certified, calibrated, and approved
by Authority Having Jurisdiction capable of performing this test within the allowable tolerance is permitted.
7.2.1 Test Chamber - The test chamber, to which the specimen is mounted, shall be provided with pressure
tabs to measure the pressure difference across the test specimen and shall be so located that the reading is
unaffected by the velocity of air supplied to or from the chamber. The specimen mounting frame must not
deflect under test load in such manner that the performance of the specimen will be affected.
7.2.2 Pressure-Measuring Apparatus - The pressure-measuring apparatus shall measure the test pressure
difference within a tolerance of ±2%
7.2.3 Deflection-Measuring System - The deflection-measuring system shall measure the deflection within a
tolerance of 0.01 inch.
7.2.4 Air System - A controllable blower, a compressed-air supply, an exhaust system, or reversible
controllable blower designed to provide the required maximum air pressure difference across the specimen. The
system shall provide an essentially cyclic static air-pressure difference for the required test period.
7.3 Calibration of Equipment - The pressure-measuring apparatus and the deflection-measuring system shall be
calibrated and certified by an independent qualified agency approved by the Authority Having Jurisdiction, at two-year
intervals.
7.3.1 The calibration report shall include: the date of the calibration, the name of the agency conducting the
calibration, methods and equipment used in the calibration process, the equipment being calibrated and any
pertinent comments.
8. Hazards:
8.1 Testing facilities must take all necessary precautions to protect the observers during the entire test procedure. All
observers shall always be at a safe distance away from specimen and apparatus. Safety regulations must be followed
in order to avoid any injuries to any and all observers.
9.1 Any testing facility wishing to perform this test must first obtain the approval of the Authority Having Jurisdiction.
Such approval shall only be given to those facilities which show that they are properly equipped to perform the
complete test. Testing facilities shall request, in writing, approval of their facilities. Such request shall contain the
ability of the facility to perform all aspects of the test, all equipment used in the performance of the test, name of
independent agency calibrating their equipment, location of facilities, personnel involved in the testing, a quality control
program, a safety program and any other pertinent information which will clearly indicate that such facility is in the
business of performing independent testing. The Authority Having Jurisdiction will visit the site and reserve the right to
order any changes necessary to accept the facility for testing.
9.2 Approval of facilities to perform the test described in this protocol, does not constitute an approval of such facilities
to perform other tests not specifically mentioned in this protocol.
The manufacturer shall notify the Authority Having Jurisdiction seven (7) working days prior to the performing of the
test. The Authority Having Jurisdiction reserves the right to observe the test. The Authority Having Jurisdiction must be
ecodes.cyberregs.com/cgi-exe/cpage.dll?pg=nbdrx&rp=/indx/ST/fl/st/b1400v10/st_fl_st_b1400v10_tas203.htm&sid=2013033007494944711&aph=0&cid=iccf&uid… 4/6
3/30/13 E-Codes
notified of the place and time the test will take place. The test must be recorded on video and retained by the
laboratory per TAS 301.
11.1 Date of the test and the report, and report number.
11.4 Identification of the specimen (manufacturer, source of supply, dimension, model types, material, procedure of
selection and any other pertinent information).
11.5 Detailed drawings of the specimen showing dimensioned section profiles, type of framing specimen was attached
to, panel arrangement, installation and spacing of anchorage, locking arrangement, sealant, hardware, product
markings and their location, and any other pertinent construction details. Any deviation from the drawings or any
modifications made to the specimen to obtain the reported values shall be noted on the drawings and in the report.
11.6 Maximum deflection recorded and mechanism used to make such determination.
11.7 Permanent deformation (provide cross section diagram to show where it occurred).
11.8 Name, address, signature and seal of Florida professional engineer, witnessing the test and preparing the report.
Engineer shall be part of the laboratory’s permanent staff or under laboratory’s contract. (See TAS 301-94.)
11.9 A tabulation of pressure differences exerted across the specimen during the test and their duration.
11.11 A description of the condition of the test specimens after testing, including details of any damage and any other
pertinent observations.
11.12 When the tests are made to check conformity of the specimen to a particular specification, an identification or
description of that specification.
11.13 A statement that the tests were conducted in accordance with this test method.
11.14 A statement of whether or not, upon completion of all testing, the specimens meet the requirements of Section
1606 of the Florida Building Code, Building and this protocol.
11.15 A statement as to whether or not tape or film, or both were used to seal against air leakage, and whether in the
judgment of the test engineer, the tape or film influenced the results of the test.
11.16 Signatures of persons responsible for supervision of the tests and a list of official observers.
11.17 All data not required herein, but useful to a better understanding of the test results, conclusions or
recommendations, should be appended to the report.
Maximum Deflection
ecodes.cyberregs.com/cgi-exe/cpage.dll?pg=nbdrx&rp=/indx/ST/fl/st/b1400v10/st_fl_st_b1400v10_tas203.htm&sid=2013033007494944711&aph=0&cid=iccf&uid… 5/6
3/30/13 E-Codes
Permanent Deformation
13.1 Prior to conducting the test described in this protocol, all specimen must have successfully completed the test
specified in protocol TAS 201-94.
13.2 Any product when installed that is subjected to weathering, where such weathering can affect the integrity of the
product, the manufacturer shall contact the Authority Having Jurisdiction for additional testing requirements such as
but not limited to moisture, U.V., accelerated aging, and other similar tests.
13.3 The Authority Having Jurisdiction reserves the right to require any additional testing necessary to assure full
compliance with the intent of the Florida Building Code, Building.
13.4 Some products, such as exterior doors, exterior windows, skylights, and wall cladding shall be required to be
successfully tested under TAS 202-94 prior to conducting tests under this protocol.
14.1 Any and all approved products shall be permanently labeled with the manufacturer’s name, city, state, and the
following statement: "Product Approved."
14.2 Permanently labeled shall be a metallic label fixed permanently to the frame of the specimen by rivets or
permanent adhesive. See Section 14.2.1 of this protocol for storm panels.
14.2.1 Permanent label on storm panels could be printed directly on each panel at intervals not to exceed 36
inches with nonremovable paint or ink.
14.3 Any instructions for operations shall be permanently mounted on the specimen in an area not subject to be
painted or concealed. Storm panels may be excluded from this section.