MS-7 Series: Addressable Devices
MS-7 Series: Addressable Devices
MS-7 Series: Addressable Devices
MS-7 Series
Manual Fire Alarm Pull Stations
General
The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide
variety of configurations. The pull stations comply with the Americans with Disabilities
Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille
text are engraved in the handle. All pull stations include a key lock/reset which is keyed
alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull
stations.
The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors
and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the
group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response
speed up to five times greater than earlier designs.
mounted or semi-flush mounted on a standard BG12TR: Trim ring for semi-flush mount, plastic
double-gang, or 4-inch (10.2 cm) square electrical box.
NY-PLATE: NYC backplate for manual pull station
An optional trim ring (BG12TR) may also be used for
**For use with the Gamewell-FCI analog addressable
semi-flush mounting.
control panels only.
2
MS-7 Series Technical Specifications
SYSTEMS STANDARDS For a complete listing of all
compliance approvals and
Material: Lexan® The MS-7 Series is designed to comply with the following certifications, please visit:
Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) standard: http://www.gamewell-
Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D UL Standard: UL 864 9th Edition fci.com/en-US/
documentation/Pages/
(14 x 10.1 x 3.2 cm) AGENCY LISTINGS AND APPROVALS Listings.aspx
Operating Temperature: These listings and approvals apply to the modules LEXAN® is a registered
(MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) specified in this document. In some cases, certain trademark of GE Plastics, a
(MS-7LOB): -30° to 150° F (-35° to 66° C) modules or applications may not be listed by certain subsidiary of General Electric
Relative Humidity : approval agencies, or listing may be in process. Company.
(MS-7AF, MS-7ASF): 10 to 93% (non-condensing) Consult factory for latest listing status.
Velociti® and Gamewell-FCI
(MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) UL: S2465 are registered trademarks of
FM: 3023594 Honeywell International Inc.
Alarm Current: .0030 amp. 0.007 for LED
MEA FDNY: 67-02-E Vol. VII
Supervisory Current: UL® is a registered trademark
CSFM: of Underwriter’s Laboratories
(MS-7AF, MS-7ASF): .00030 amps.
7160-1703:0119 Inc.
TEMPERATURE AND HUMIDITY RANGES
7160-1703:0170
This system meets NFPA requirements for operation at 0 This document is not intended
7160-1703:0109 to be used for installation
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). ISO 9001 Certification purposes. We try to keep our
product information up-to-
However, the useful life of the system's standby batteries
date and accurate. We cannot
and the electronic components may be adversely affected cover all specific applications
by extreme temperature ranges and humidity. Therefore, or anticipate all requirements.
it is recommended that this system and its peripherals be All specifications are subject to
installed in an environment with a normal room change without notice.
temperature of 15 – 27°C/60 – 80°F.