Wood Pellets Burner
Wood Pellets Burner
Wood Pellets Burner
Bio comfort
100 step modulated
Woody Generation
Comfort Opop
Height 1050mm 850mm
Width 700mm 380mm
Depth 700mm 560mm
Chimney 130mm 130mm
Forward flow 1 1/4“ 1 1/4“
Back flow 1 1/4“ 1 1/4“
Lining 1/2“ 1/2“
Efficiency 93,3% 89,7% Dragex
Draught stabilizer
General guidelines:
The boiler should be installed by an authorized fitter and must
be installed in accordance with work supervision publication 42
( Danish ) covering equipment working with water.
The outlet duct should be no longer than 1m,
and should be fitted with a cleaning door.
The chimney draught should be at least 5 PA and should be stable,
a draught stabilizer should always be installed.
If combustion gases condense in the chimney (wet ash)
install a draught stabilizer in the chimney, or open the flue
(the flap inside at the back of the boiler)
as wide as possible to increase the temperature of the smoke.
The boiler must be spanned with a bypass to ensure the back flow is al-
ways kept above 55 degrees.
Outer auger:
6. Install the auger through the opening over the burner.
7. Ensure that the pipe slopes enough to allow the pellets to fall into the burner.
Boiler temperature
Smoke temperature (special apparatus)
Temperature of mechanical stoker
Current performance
Oxygen % (special apparatus)
Current light in combustion head
Press SET and the display will show SETUP for standard settings.
The UP button is used to increase the setting and for force-running the auger
( hold for longer than 5 seconds ).
The DOWN button is used to decrease the setting and switch the controls on/off
( hold for 10 seconds ).
.
SCREW CAPACITY
Temperature After setting the auger performance in 360 seconds the control will
Auto combustion automatically calculate the amount of pellets in low steam and high steam,
pellets in pause , and pellets for ignition
Man. combustion Under normal conditions these numbers will be correct.
Timer To increase combustion, set the value DOWN.
Cleaning / power
To reduce combustion, set the value UP.
O2 Control
CHIMNEY DRAUGHT
With a strong chimney draught the ventilator performance will be higher,
At low steam and during pause.
If the amount of chimney draught is increased,
the automatic calculation sets more pellets in low steam and during pause.
The smaller the chimney draught and the greater the back pressure of the boiler,
the lower the value must be.
The greater the chimney draught and the lower the back pressure of the boiler,
the higher the value must be.
YES/NO
Switching automatic calculations on/off.
If automatic calculation is on, only the auger performance can be set.
Manual
NBE pellet system
USER GUIDE
NEXT START
Switches on after a certain length of time; this is used when the boiler needs to be
turned on without anyone actually being present, e.g. at 4.00 in the morning.
CLOCK
The clock correctness depends on the feed from the power station.
The clock is calibrated every time when you set it,
and should match after 1-4 settings.
WARNING
The clock does not contain a battery and will lose its settings if there is a power
cut. Therefore always switch off using the ON/OFF button on the regulator.
MAXIMUM POWER
Setting maximum performance.
If the pellet burner rapidly reaches a high temperature,
the maximum performance should be reduced.
Manual
NBE Pellets Systems
Betjenings vejledning.
ONLY TO BE ADJUSTED
IF THERE IS A LAMBDA CONTROL MOUNTED ON THE BOILER. !!
OFF / DISPLAY / ON
Turns oxygen regulation on/off.
Oxygen regulation set to ON –
The burner sets the amount of pellets to suit the required percentage of oxygen.
Oxygen regulation set to DISPLAY –
You can read the percentage, but the burner does not set the amount of pellets.
The tighter the boiler, the more you get from oxygen regulation.
It is recommended to fit the chimney with a draught stabilizer,
this will reduce the draught and cut the amount of air flowing back into the boiler.
Ignition GAIN
Sets how much oxygen regulation should regulate when activated.
Pause Run
O2 SENSOR TUNE
O2 sensor Calibration of oxygen sensor to ensure it gives accurate readings.
Fine tune Hold the exhaust gas oxygen sensor in the air and calibrate it to give it a reference
value to the air (21% oxygen).
PID regulation WARNING! The oxygen sensor must be warm!
Temp. alarm
Ignition P - GAIN
Shifts performance in relation to deviation from required temperature.
Pause Run
O2 sensor I - GAIN
Shifts performance in relation to the time the pellet burner
Fine tune deviated from the required temperature.
PID regulation D - GAIN
Temp. alarm Shifts performance in relation to the temperature trend of the boiler.
The controls work in 100 step modulation and change these step automatically.
If you use the automatic calculation program after measuring the performance of the auger,
no further setting should be necessary.
The pellet burner must not smoke, but must be sealed tight.
(Take care that smoke does not mingle with condensed steam.)
Fuel type
The boiler is set up for wooden pellets Ø 5-8mm,
which do not burn to cinders!! ( Hard ashes )
Manual
NBE pellet system
CLEANING GUIDE
The boiler…
Clean the ash out of the boiler and brush off
all the surfaces to remove any deposits.
Be very careful of the ash in the backflow valve
and the chimney pipe.
The chimney-sweeper DO NOT CLEAN
the chimney pipe, you must do this yourself …
An old vacuum cleaner or ash bucket are
especially suitable,
as the ash does not normally contain carbon particles or tar.
Combustion heads…
Remove the ash and any cinders from the grate.
Remove any remnants of pellets from underneath the grate.
Wipe the flame indicator.
Ensure there is nothing in the ventilator.
VERY IMPORTANT!!!
THE COMBUSTION HEAD WILL
B BE DAMAGED IF THE GRATE IS
N NOT POSITIONED CORRECTLY!!!
Pellet hopper…
As the pellets you put in the hopper contain detritus,
the hopper should be completely emptied from time to time.
The more detritus there is in the hopper, the less the auger feeds,
which can interfere with the settings cause the burner to cut out.
The frequency with which you empty the pellet hopper depends entirely on the angle inside of the hopper
and the quality of the pellets you use.
ALARM 1. Burner grate not fitted correctly. Check the burner grate.
FAULTY IGNITION 2. Ash/cinders in the combustion head. Clean the combustion chamber!
3. Damp pellets. Change supplier/storage!
4. Ignition not fitted correctly. Fit into quadrangular holder.
5. Defective ignition. Change ignition/ignite manually!
6. Excessive chimney draught. Install a draught stabilizer in the chimney.
7. Photo sensor is faulty/covered in soot. Clean/change the sensor.
8. Blocked ventilator. Clean the ventilator and check that it works.
ALARM Boiler temperature has not exceeded 35 degrees after 2 Low burner performance.
LOW BOILER hours of operation, or has dropped below Check pellet feed/ventilator!
TEMPERATURE 35 degrees when running. Check that the temp. sensor is on the boiler.
ALARM 1. Plug on the burner is not fitted correctly. Check the plug on the burner !
PLUG NOT FITTED 2. Dirt in the plug. Clean any pellet reside from the plug.
3. Faulty sensor. Change the sensors (photo/temperature).
Burner goes out on “LOW STEAM” 1. Fuel supply instable. Check there is no sawdust at the entrance to the auger.
Weak flame 2. Pellets remain in pipe. Check the slope of the auger.
3. Low feed is set too low. Check that the auger drops into the combustion chamber.
4. Chimney draught estimated wrongly. Increase chimney draught and watch LX indicator at low
5. Amount in auger measured incorrectly. performance.
Measure the auger again for 360 seconds.
Burner goes out on “PAUSE” 1. Pellets supply instable. Check there is no sawdust at the entrance to the auger.
Weak flame 2. Pellets remain in pipe. Check the slope of the auger.
3. Chimney draught is set too low. Check that the auger drops into the combustion chamber.
4. Chimney draught too strong. Watch LX indicator during pause.
Increase chimney draught.
Install a draught stabilizer in the chimney.
Excessive pellet consumption / 1. Combustion set incorrectly. Check that the ash is dark grey!
boiler will not reach required tem- 2. Chimney draught too strong. Measure the chimney draught / install a draught stabilizer.
perature 3. Backflow valve installed incorrectly in the boiler. Check boiler, install backflow valve.
4. Bad boiler /low efficiency/ insulation. Measure smoke temperature, insulate the boiler!
5. Combustion chamber working too hard. Reduce performance of combustion chamber.
6. Damp pellets/poor quality. Use efficient pellets.
Boiler and burner are clogged up / 1. Too many pellets. Increase auger performance in calculation program.
black. 2. Lag set incorrectly. Reduce chimney draught.
3. Blocked ventilator. Clean the ventilator!
Support: www.pelletsburner.net
Manual
NBE Pellets Systems
ELECTRICAL WIRING DIAGRAMS
Manual
NBE Pellets Systems
WARANTY
All products purchased from NBE are naturally covered by the applicable Danish purchasing law.
Products come with a two-year warranty valid from the date of receipt.
However, this does not cover the exhaust gas oxygen sensor, electrical ignition or the combustion grate.
These are considered to be replaceable parts.
Diag. 2
Manual
NBE Pellets Systems
MOUNTING THE PELLET HOPPER
Manual
NBE Pellets Systems
EXCEPTION FOR PRESSURE EXPANSION
NBE
Jannich Hansen
Brinken 10
DK 9830 Oester Vraa
Landskronegade 33
2100 Copenhagen
Telephone 39152000
www.arbejdstilsynet.dk
Your contact JH
Our ref. 20030027413
Our contact.
G.Agersnap
Direct telephone
0045-3915265915
Re: Use of burner to burn wooden pellets type Woody, Scotte, Bio-comfort and
Boink in boiler equipment in relation to smaller, closed facilities in compliance with Work
Supervisor Regulations for Hot-water Heating Systems. (publ. 42/1980 para 4)
With regard to your query of 1 September 2006 concerning the use of the burner to burn wooden
pellets type Woody, Scotte, Bio-comfort and Boink in boiler equipment in relation to smaller,
closed facilities with pressure expansion, we can report that the Work Supervisor has perused the
submitted materials and can declare that the burner for wooden pellets type Woody, Scotte, Bio-
comfort and Boink can be installed in the heat facilities listed in paragraph 4 of the Work Supervi-
sor publication no. 42/1980, Regulations for Hot-water Heating Systems.
It is assumed that the boiler contains the requisite amount of water and that the entire heating fa-
cility is designed in exact compliance with the instructions given in publication 42/1980, and also
that the electricity supply will only be connected to a boiler with a fitted and connected thermostat
with the appropriate overheating safety fuse which must be manually reconnected after activation.
All heating in the boiler must take place by means of the pellet combustion chamber, and only
fuels listed in the instructions may be used. Otherwise the equipment must be installed with an
open expansion (compare paragraph 2 in publication 42/1980).
This decision is based on the enclosed instructions and diagrams, Test Report no. 300-ELAB-
0741, as well as the Power Dropout Test with readings recording the build-up of heat in the boiler
if the power supply to the equipment is interrupted.
Best regards,
G.Agersnap