Solar inverter

All the material & workmanship shall be of reputed make and have proven successful in
the respective uses in similar services & under similar conditions.

The solar inverter /power conditioning unit shall be suitable for interfacing with SCADA system and all
necessary transducers shall be included
1.0 STANDARDS

Standard Description
Photovoltaic systems - Power conditioners – Procedure for
IS/IEC 61683 - 1999
measuring efficiency
Safety of power converters for use in photovoltaic power systems-
IEC 62109-1 -2010
Part1:General requirements
Safety of power converters for use in photovoltaic power systems
IEC 62109-2- 2011
Part2:Particular requirements for inverters
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards-
IEC 61000-6-2- 2016
Immunity standard for industrial environments
Electromagnetic compatibility (EMC) - Part 6-4: Generic standards-
IEC 61000-6-4-2018
Emission standard for industrial environments
Utility-interconnected photovoltaic inverters – Test procedure
IS 16169/IEC62116 - 2014
of islanding prevention measures
IEC60068-2-1:2007 Environmentaltesting-Part2-1:Tests-TestA:Cold
IEC 60068-2-2:2007 Environmental testing-Part2-2:Tests-TestB:Dryheat
Environmental testing - Part 2-14: Tests - Test N: Change of
IEC 60068-2-14:2009
temperature
 Visual Inspection
 Performance Test and measurement of AC & DC parameters
 DC reverse polarity protection
 Islanding Protection
 Over Voltage & Under Voltage withstand
 Over Frequency & Under Frequency withstand
 Night consumption