Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Bimed Ex Cable Glands Catalogue

Download as pdf or txt
Download as pdf or txt
You are on page 1of 49

CONTENTS

Company Introduction Page 2-3

4 Function Ex d/e Glands for Armoured (DORADO) Page 4-6

4 Function Ex d/e Glands for Armoured Cable (ORION) Page 7-8

1 Function Ex d IIC - Ex e/Ex i Liquidtight Straight Fittings (HYDRUS) Page 9-10


1 Function Ex d IIC - Ex e/Ex i Liquidtight 450 Fittings (SCORPIUS) Page 11
1 Function Ex d IIC - Ex e/Ex i Liquidtight 900 Fittings (LUPUS) Page 12
1 Function Ex-d IIC - Ex-e II - Ex-td Brass Cable Gland (OCTANS) Page 13
1 Function Ex-d IIC - Ex-e II - Ex-td EMC Brass Cable Gland (VELA) Page 14
1 Function Ex e II - Ex d Link Cable glands for non armoured cables (CARINA) Page 15
BU & BM Type for Flat Seals (FSEAL) Page 16

Ex e II - Ex d IIC Male plugs (AQUILA) Page 17-18


Ex e IIC - Ex d IIC Adaptors - Enlarger - (APUS) Page 19-20
Ex e IIC - Ex d IIC Adaptors - Reducer - (GRUS) Page 21-22
Ex e IIC - Ex d IIC Adaptors - Coupling - (ARIES) Page 23-24
Ex e IIC - Ex d IIC Adaptors - Nipple - (PAVO) Page 25-26

Ex e IIC Ventilation Plug (HYDRA) Page 27-28

Ex-e II - Ex-i PA6 Cable Glands (LYRA) Page 29-31


Ex-e II - Ex-i PA6 Plugs (DRACO) Page 32

Pvc Shroud For DORADO Page 33-34


Pvc Shroud For ORION Page 35
Pvc Shroud For OCTANS & VELA Page 36
Earth Tags (ET) Page 37
Lock Nuts for Ex Glands Page 38

Ex Technical Information Page 39-44

Size Equivalent Thread Page 45


Introduction
The Bimed company has started its activity in 1978 as a medical and mechanical
components manufacturer. After various development and reorganization steps during
its life, Bimed has today become a large organization working in a 20,000 square meter
facility with a staff of more then 300 people in 4 global divisions which Turkiye, North
America, Germany and Egypt. 16 constitute the quality assurance department and 10
for the research and development division. By adding precision engine spindles and
other mechanical parts to the production line, the company diversified its products.

Our products can be classified as follows:

• Cable fitting elements, as plastic and metallic cable glands


• Pressure balance elements, ventilation glands and ventilation plugs
• Plastic connectors for the white and automotive industries
• Gas springs for the automotive and furniture industries
• Disposable medical products.

Bimed manufactures cable fitting elements which are designed for multipurpose
applications in electrical, electronic and automotive industries. Our production capacity
is supported by both manual and fully automated assembly lines. All our products
conform to the relevant international and national standards of the end user
countries.Tight control is imposed at all the stages of the production process and all the
nonconformities are immediately eliminated. To achieve this, a full traceability system
is developed in accordance with the EN ISO 9001:2008 standard. As a result, Bimed has
been able to establish an international reputation for its consistently high quality
production standards. Various custom products as requested by our customers, at the
and due to the 30 years experiance in Gland Activites Bimed Designed new Ex glands
series which has been approved by IMQ Italy according to new standards. Bimed also
gain ATeX 100 and IEC Ex Factory Inspection from CESI Italy.

02
Introduction
Bimed is constantly working to achieve customer satisfaction, by meeting requested
requirements with its standard and customized products. Most often, our research and
development department produces completely new items in accordance with client
demands. These activities help us gain the praise and high appreciation of our
customers. Because of High standards need for Hazardous Area Bimed start to invest
for own Laboratuary which has been certified by IMQ according to EN60079-0/2009.
With a worldwide market base, the Bimed distribution network has been established to
ensure that the needs of this global market are well understood and fully satisfied. Our
products have been expanded to and distributed in more than 30 countries. Bimed has
a merit-based leadership in the cable gland and connector sector established on its
reputation for quality and innovation. This philosophy has been instrumental in the
development of a product line that is constantly growing to reflect the changing
industry needs and advancements in technology. With the above resume about Bimed
we intend to emphasize the Bimed production philosophy and let it serve as
certification for the large product line manufactured by all our divisions.

Bimed Electrical Laboratory was established in 1998 with a few test devices made by
Bimed. In 2001, an engineer started to work in Bimed Electrical Laboratory and the
tests were carried out by him. After 2003, the lab was moved to a larger place and
Bimed started to buy new test devices.Between 2009-2010 within the scope of a
project (Turkish Scientific And Technical Researches Institution), Bimed received
support from the Institution and bought the rest of the devices in the laboratory. In
2011, due to an organizational change, the laboratory test personnel were separated
from process control personnel.Now, Bimed built up a new laboratory test team and
still continues on investing new test devices. Bimed laboratory has a few special test
devices that only a few laboratory has. Laboratory has dust chamber, climatic cabinet,
owens, voltage drop test machine, dynascope, CTI test device, IP X5-X6-X7-X8-X9K test
devices, corrosion cabinet….etc. Bimed Laboratory has accredited by IMQ in Italy
according to some cable gland tests in EN 60079-0 , EN 60079-1 standards in 2011 and
will be accredited İntertek Sweeden in August 2012 according to EN 60335-1 ,EN 60529
,EN 50262 ,EN 61984 ,EN 60998-2-2 standards.

03
4 Function EX d / e
Glands for Armoured Cable
SPECIAL FEATURES 4 Function EX d / e
AND BENEFITS OF DORADO Glands for Armoured Cable
(A) No need to change, to remove or to adjust any internal components as long as the
diameter of the used cable is within the declared clamping range.

(B) The swiveling “shielding cone” (6) for clamping armor is secured to the “upper
body” (8) and “lower body” (1) by o-rings which prevent the shielding cone from being
lost when cable glands are disassembled for cable installation.

(C) For the periodic inspection purpose the internal parts and can be removed with a
simple "pulling" movement, because they are fixed only with the o-rings.In result the
glands are inspectable without any need to damage the cable or any part.

(D) High strain relief, IP rating and explosion proof protection is obtained through the
special shape of lower (2) and upper (10) seal.

(E) Because of the design of seals (2) and (10) these cable glands can be used for a
wider spectrum of cable diameters/clamping ranges.

(F) Hexagon nuts for most cable gland sizes are of the same size (SW). Fewer wrench
sizes are required.

(G) Cable glands are deluge proof because of two o-rings (5) and (7) on the shielding
cone (6). Water intrusion will be trapped between the o-rings and won’t get in contact
with armor.

Item Item Description


1 Lower body
2 Lower seal
3 O-ring
4 Grounding cone
5 O-ring
6 Swivel retainer
7 O-ring
8 Upper body
9 Washer
10 Upper seal
11 Pressure Cap
12 O-ring
13 Armoured wire
14 Armoured cable

05
4 Function EX d / e
Glands for Armoured Cable DORADO
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 036
Examination & Test Report Number 43AL00050
Safety Requirements EN 60079-0;EN 60079-1;EN 60079-7;prEN 60079-11; EN
60529;EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II
M2/2GD EX d I Mb; Ex d IIC Gb/ Ex e I Mb; Ex e IIC Gb
Suitable for use in Equipment ZONE1, ZONE2, ZONE21, ZONE 22, Gas
Groups IIA, IIB, IIC, Mining IM2
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66 – IP68 (EN 60529)
Marking BMD BA.. CE0722 II 2GD Exd IIC GB / Exe IIC Gb Ta-30ºC
+120ºC Ex tb IIIC Db IP66/68 IMQ 10 ATEX 036
Deluge Proof Option Standard
Temperature Classes -30°C / +100°C with NBR Sealing Ring
-40°C / +120°C with CHLOROPRENE Sealing Ring
-60°C / +180°C with SILICONE Sealing Ring
Material Brass - Stainless Steel
Order Type Thread Material Plated Sealing
Encoding BA01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BA01MBNS
BA01NXC

M M Ø, Sealing Ring Dimension Cable Gland Dimensions Armor


Type ANSI ASME ISO pitch Acceptence
B1.20.1 1,5 D Min-Max D1 Min- Max H Min L Min CH1 CH2 CH3 D2 Min Range mm.
BA 01SN (3/8") 01SM (16) 3,0-8,5 6,0-12,0 57,5 14,0 22 22 22 24 0,7-1,5
BA 01N (3/8") 01M (16) 4,0-12,0 9,0-18,0 57,5 16,0 24 24 24 27 0,7-1,2
BA 1N (1/2") 1M (20) 4,0-12,0 9,0-18,0 68,5 16,0 24 24 24 27 0,7-1,5
BA 2N (3/4") 2M (25) 9,0-20,0 14,0-26,0 81,0 18,0 36 36 36 41 1,2-2,1
BA 3N (1") 3M (32) 15,0-26,0 20,0-33,0 106,5 18,0 48 48 48 52 1,0-2,1
BA 4N (1 1/4") 4M (40) 20,0-32,0 29,0-41,0 112,5 18,0 55 55 55 61 1,2-2,6
BA 5N (1 1/2") 5M (50) 22,0-35,0 36,0-52,0 119,5 20,0 60 60 60 68 1,8-3,2
BA 6N (2") 6M (63) 35,0-45,0 42,0-62,0 149,0 20,0 74 74 74 84 2,7-4,2
BA 7N (2 1/2") 7M (75) 45,0-60,0 54,0-78,0 164,0 20,0 90 90 90 104 2,4-4,5
BA 8N (3") 8M (90) 60,0-72,0 63,0-88,0 190,0 20,0 110 110 110 129 2,3-4,1
BA 10N (4") 10M (110) 75,0-85,0 88,0-105,0 222,0 20,0 135 135 130 155 2,4-4,2

D1

Item Item Description CH3


1 Lower body
2 Lower sealing ring
3 O-ring
4 Grounding cone
5 Swivel braid retainer Position
marking
6 Middle body
7 Upper pressure washer D2
8 Upper sealing ring
9 Upper body H

CH2

D2

CH1

9 8 7 6 3 5 3 4 3 2 1 3 M

06
4 Function EX d / e
Glands for Armoured Cable
4 Function EX d / e
Glands for Armoured Cable ORION
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 037
Examination & Test Report Number 43AL00047
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007
/ EN 60079-11:2010/ EN 60079-31:2009/ EN 61241-0 /
EN 61241-1
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX I M2/ Ex
II 2GD EX d I Mb/Ex e I Mb / EX d IIC Gb / Ex e IIC Gb /
Ex tb IIIC Db
Suitable for use in Equipment ZONE1, ZONE2, ZONE21, ZONE22, Gas
Groups IIA, IIB, IIC, Mining IM2
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD KBA.. CE0722 II 2GD Exd IIC GB / Exe IIC Gb Ta-
30°C +120°C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 037
Temperature Classes -30°C / +100°C with NBR Sealing Ring
-40°C / +120°C with CHLOROPRENE Sealing Ring
-60°C / +180°C with SILICONE Sealing Ring
Material Brass - Brass - Stainless Steel
Order Type Thread Material Plated Sealing
Encoding KBA01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example KBA01MBNS
KBA01NXC
M Sealing Ring
M Cable Glands Dimensions Armor Acceptence
Type ANSI ASME Dimensions Ø
ISO Pitch 1,5 Range mm.
B1.20.1 H min L min CH1 CH2 CH3 D2 min D min-max D1 min-max
KBA 0SN (1/4") 0SM (12) 55,0 15,0 17,0 17,0 17,0 19,0 1,0-4,0 3,0-5,5 0,1-0,7
KBA 01SN (3/8") 01SM (16) 47,0 16,0 22,0 26,0 26,0 29,0 3,0-8,5 6,0-12,0 0,7-1,2
KBA 01N (3/8") 01M (16) 48,0 16,0 25,0 29,0 29,0 31,5 6,0-12,0 8,5-16,0 0,7-1,2
KBA 1SN (1/2") 1SM (20) 47,0 16,0 24,0 26,0 26,0 29,0 3,0-8,5 6,0-12,0 0,7-1,2
KBA 1N (1/2") 1M (20) 47,0 16,0 25,0 29,0 29,0 31,5 6,0-12,0 8,5-16,0 0,7-1,2
KBA 1LN (1/2") 1LM(20) 50,0 16,0 28,0 30,0 30,0 35,0 8,5-14,5 12,0-20,0 0,8-1,3
KBA 2SN (3/4" 2SM (25) 48,0 18,0 29,0 29,0 29,0 31,5 6,0-12,0 8,5-16,0 0,7-1,2
KBA 2N (3/4") 2M(25) 53,0 18,0 32,0 34,0 34,0 37,0 8,5-16,0 12,0-21,0 0,8-1,3
KBA 2LN (3/4") 2LM (25) 60,0 18,0 36,0 40,0 40,0 44,0 12,0-20,0 16,0-26,0 1,0-1,6
KBA 3SN (1") 3SM (32) 52,0 21,0 40,0 40,0 40,0 44,0 12,0-20,0 16,0-26,0 1,0-1,6
KBA 3N (1") 3M (32) 78,0 21,0 48,0 52,0 52,0 57,0 15,0-26,0 20,0-33,0 1,0-1,8
KBA 4SN (1 1/4") 4SM (40) 78,0 21,0 48,0 52,0 52,0 57,0 15,0-26,0 20,0-33,0 1,0-1,8
KBA 4N (1 1/4") 4M (40) 89,0 21,0 55,0 60,0 60,0 66,0 20,0-32,0 29,0-41,0 1,5-2,2
KBA 5SN (1 1/2") 5SM (50) 97,0 21,0 60,0 70,0 75,0 82,0 22,0-35,0 33,0-48,0 2,0-2,7
KBA 5N (1 1/2") 5M (50) 100,0 21,0 70,0 70,0 74,0 83,0 27,0-41,0 36,0-52,0 2,0-2,7
KBA 6SN (2") 6SM (63) 106,0 21,0 75,0 80,0 80,0 89,5 35,0-45,0 43,0-57,0 2,5-3,5
KBA 6N (2") 6M (63) 107,0 21,0 85,0 85,0 85,0 94,0 40,0-52,0 47,0-60,0 2,0-3,0
KBA 7SN(2 1/2") 7SM (75) 107,0 21,0 85,0 85,0 85,0 94,0 40,0-52,0 47,0-60,0 2,0-3,0
KBA 7N(2 1/2") 7M (75) 125,0 20,0 90,0 95,0 100,0 110,5 45,0-60,0 54,0-70,0 1,8-3,0
KBA 8SN (3") 8SM (M80) 124,5 20,0 90,0 95,0 100,0 110,5 45,0-60,0 54,0-70,0 1,8-3,0
KBA 8N(3") 8M (80) 154,0 20,0 110,0 115,0 115,0 127,0 60,0-72,0 63,0-80,0 1,8-3,5

Item Item Description


D2
1 Lower Body
Position
2 Lower sealing ring D1 marking
3 O-Ring
4 Grounding cone
5 Swivel braid retainer
6 Middle body
7 Upper sealing ring
8 Pressure cap CH3

H
CH2

CH1

8 7 6 3 5 4 3 2 1 3
M

08
1 Function Ex-d IIC / Ex-e II / Ex-i / Ex-td
Cable Glands
1 Function Ex-d IIC / Ex-e II / Ex-i
HYDRUS Liquidtight Straight Fittings
Technical details
Approved by IMQ
Examination Certificate Number 11 ATEX 038 X
Examination & Test Report Number 43AL00002
Safety Requirements EN 60079-0;EN 60079-1;EN 60079-7;prEN 60079-11 EN
60529;EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BLS.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30°C
+120°C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
Temperature Classes -30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BLS01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BLS01MBNS
BLS01NXC

M Cable Glands Dimensions


P Sealing Ring Dimensions Ø
Type ANSI ASME S1+S2+S3 S1+S2 S1
H Min. L Min. CH1 CH2 CH3 FD L1 Min.
B1.20.1 Min. Max.
BLS 02N (1/4”) 66 16 29 27 27 13,8 20 3,0 12,0 3-6 6-9 9-12
BLS 01N (3/8”) 66 16 29 27 27 13,8 20 3,0 12,0 3-6 6-9 9-12
BLS 1N (1/2”) 66 16 29 27 27 13,8 20 3,0 12,0 3-6 6-9 9-12
BLS 2N (3/4”) 73 16 35 33 33 18,7 20 10,0 18,0 10-13 13-18
BLS 3N (1”) 89 20 45 42 43 24,0 25 14,0 24,0 14-17 17-20 20-24
BLS 4N (1 1/4”) 106 20 54 51 52 32,0 25 22,0 32,0 22-26 26-32
BLS 5N (1 1/2”) 106 20 63 60 60 37,0 39 26,0 35,0 26-30 30-35

Cable Glands Dimensions


M P Sealing Ring Dimensions Ø
Type S1+S2+S3 S1+S2 S1
ISO Pitch 1,5 H Min. L Min. CH1 CH2 CH3 FD L1 Min.
Min. Max.
BLS 02M (M12) 66 16 29 27 27 13,8 20 3,0 12,0 3-6 6-9 9-12
BLS 01M (M16) 66 16 29 27 27 13,8 20 3,0 12,0 3-6 6-9 9-12
BLS 1M (M20) 66 16 29 27 27 13,8 20 10,0 16,0 10-13 13-16
BLS 2M (M25) 73 16 35 33 33 18,7 20 10,0 18,0 10-13 13-18
BLS 3M (M32) 89 16 45 42 43 24,0 25 14,0 20,0 14-17 17-20
BLS 4M (M40) 106 16 54 51 52 32,0 25 14,0 24,0 14-17 17-20 20-24
BLS 5M (M50) 106 16 63 60 60 37,0 39 22,0 28,0 22-26 26-28

P - Sealing Combination
FD

Seal S1
Item Item Description
1 O-ring
2 Lower Body
3 Seal S1
CH3 Seal S2 4 Seal S2
5 Seal S3
6 Middle body
H
CH2
7 Ferrule
8 Plastic ring
9 Cap
Position Seal S3
marking
L1

CH1

9 8 7 6 3 4 5 2 1

10
1 Function Ex-d IIC / Ex-e II / Ex-i
Liquidtight 450 Fittings SCORPIUS
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 038 X
Examination & Test Report Number 43AL00002
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007 /
EN 60079-11:2010
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex tb IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BLQ.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30⁰C
+120⁰C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
Temperature Classes -30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BLQ01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BLQ01MBNS
BLQ01NXC

M Cable Glands Dimensions P Sealing Ring


Type ANSI ASME Dimensions Ø S1+S2+S3 S1+S2 S1
H Min. L Min. CH1 CH2 CH3 CH4 FD G R L1 Min.
B1.20.1 Min. Max.
BLQ 02N (1/4”) 96 16 29 27 27 22 13,8 33,0 8,0 20 3,0 12,0 3-6 6-9 9-12
BLQ 01N (3/8”) 96 16 29 27 27 22 13,8 33,0 8,0 20 3,0 12,0 3-6 6-9 9-12
BLQ 1N (1/2”) 96 16 29 27 27 22 13,8 33,0 8,0 20 3,0 12,0 3-6 6-9 9-12
BLQ 2N (3/4”) 107 16 35 33 33 28 18,7 38,0 7,6 20 10,0 18,0 10-13 13-18
BLQ 3N (1”) 127 20 45 42 42 35 24,0 47,5 7,0 25 14,0 24,0 14-17 17-20 20-24
BLQ 4N (1 1/4”) 146 20 54 51 51 45 32,0 55,5 7,8 25 22,0 32,0 22-26 26-32
BLQ 5N (1 1/2”) 196 20 63 60 60 55 37,0 77,0 11,3 39 26,0 35,0 26-30 30-35

Cable Glands Dimensions P Sealing Ring


M
Type Dimensions Ø S1+S2+S3 S1+S2 S1
ISO pitch 1,5 H Min. L Min. CH1 CH2 CH3 CH4 FD G R L1 Min.
Min. Max.
BLQ 02M (M12) 96 16 29 27 27 22 13,8 33,0 8,0 20 3,0 12,0 3-6 6-9 9-12
BLQ 01M (M16) 96 16 29 27 27 22 13,8 33,0 8,0 20 3,0 12,0 3-6 6-9 9-12
BLQ 1M (M20) 96 16 29 27 27 22 13,8 33,0 8,0 20 10,0 16,0 10-13 13-16
BLQ 2M (M25) 107 16 35 33 33 28 18,7 38,0 7,6 20 10,0 18,0 10-13 13-18
BLQ 3M (M32) 127 20 45 42 42 35 24,0 47,5 7,0 25 14,0 20,0 14-17 17-20
BLQ 4M (M40) 146 20 54 51 51 45 32,0 55,5 7,8 25 14,0 24,0 14-17 17-20 20-24
BLQ 5M (M50) 196 20 63 60 60 55 37,0 77,0 11,3 39 22,0 28,0 22-26 26-28
Item Item Description
P - Sealing Combination
1 O-Ring
2 Lower Body
3 Seal S1
Seal S1
CH

4 Seal S2
1

CH
2
5 Seal S3
FD

6 Middle body
7 Upper body
8 Ferrule
Seal S2
9 Plastic ring
10 Cap Position
marking

H CH3
CH3
Seal S3 R

L1

CH4

G
M
P

10 9 8 7 6 3 4 5 2 1

11
1 Function Ex-d IIC / Ex-e II / Ex-i
LUPUS Liquidtight 900 Fittings
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 038 X
Examination & Test Report Number 43AL00002
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007 /
EN 60079-11:2010
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex tb IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BLN.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30⁰C
+120⁰C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
Temperature Classes -30°C to +120°C NBR sealing ring
-40°C to +100°C Neoprene sealing ring
-60°C to +180°C Silicon sealing ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BLN01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BLN01MBNS
BLN01NXC

M Cable Glands Dimensions P Sealing Ring


S1+S2+
Type ANSI ASME H L L1 Dimensions Ø S1+S2 S1
CH1 CH2 CH3 CH4 FD G C R S3
B1.20.1 Min. Min. Min. Min. Max.
BLN 02N (1/4”) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 3,0 12,0 3-6 6-9 9-12
BLN 01N (3/8”) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 3,0 12,0 3-6 6-9 9-12
BLN 1N (1/2”) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 3,0 12,0 3-6 6-9 9-12
BLN 2N (3/4”) 98 16 35 33 33 28 18,7 52,0 81,5 7,6 20 10,0 18,0 10-13 13-18
BLN 3N (1”) 120 20 45 42 42 35 24,0 61,0 101,0 7,0 25 14,0 24,0 14-17 17-20 20-24
BLN 4N (1 1/4”) 133 20 54 51 51 45 32,0 70,5 124,0 7,8 25 22,0 32,0 22-26 26-32
BLN 5N (1 1/2”) 143 20 63 60 60 55 37,0 89,0 136,0 11,3 39 26,0 35,0 26-30 30-35

Cable Glands Dimensions P Sealing Ring


M S1+S2+
Type H L L1 Dimensions Ø S1+S2 S1
ISO Pitch 1,5 CH1 CH2 CH3 CH4 FD G C R S3
Min. Min. Min. Min. Max.
BLN 02M (M12) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 3,0 12,0 3-6 6-9 9-12
BLN 01M (M16) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 3,0 12,0 3-6 6-9 9-12
BLN 1M (M20) 87 16 29 27 27 22 13,8 45,0 73,5 8,0 20 10,0 16,0 10-13 13-16
BLN 2M (M25) 98 16 35 33 33 28 18,7 52,0 81,5 7,6 20 10,0 18,0 10-13 13-18
BLN 3M (M32) 117 20 45 42 42 35 24,0 61,0 101,0 7,0 25 14,0 20,0 14-17 17-20
BLN 4M (M40) 130 20 54 51 51 45 32,0 70,5 124,0 7,8 25 14,0 24,0 14-17 17-20 20-24
BLN 5M (M50) 140 20 63 60 60 55 37,0 89,0 136,0 11,3 39 22,0 28,0 22-26 26-28

P - Sealing Combination
CH
1

CH
FD

2 Item Item Description


Seal S1
1 O-Ring
2 Lower Body
3 Seal S1
10
4 Seal S2
Seal S2 5 Seal S3
9 6 Middle body
7 Upper body
R 8 Ferrule
Position 9 Plastic ring
H
marking 10 Cap
8
CH3
Seal S3
CH3
CH4

G
M

7 6 3 4 5 2 1

12
1 Function Ex-d IIC / Ex-e II / Ex-td
Brass Cable Gland OCTANS
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 038 X
Examination & Test Report Number 43L00002
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007 /
EN 60079-11:2010 / EN 60079-31:2009
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb
Suitable for use in ZONE1, ZONE2, ZONE21, ZONE22 for Gas Groups IIA, IIB,
IIC
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BU.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30⁰C
+120⁰C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
-30⁰C / +100⁰C with NBR Sealing Ring
Temperature Classes -40⁰C / +120⁰C with NEOPRENE Sealing Ring
-60⁰C / +180⁰C with SILICONE Sealing Ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BU01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BU01MBNS
BU01NXC
M Dimensions
M P Ø Sealing Ring
Type ANSI ASME S1+S2+S3 S1+S2 S1
ISO pitch 1,5 L L1 min CH H min Dimension min-max
B1.20.1
BU 01M (16) 01N (3/8") 40 16 22 20 3,0-12,0 3-6 6-9 9-12
BU 1M (20) 1N (1/2") 40 16 22 20 3,0-12,0 3-6 6-9 9-12
BU 12M (20) 12N (1/2") 45 16 28 20 10,0-16,0 10-12 12-14,5 14,5-16
BU 2M (25) 2N (3/4") 40 16 28 20 10,0-18,0 10-12 12-14,5 14,5-18
BU 23M (25) 23N (3/4") 50 16 35 25 14,0-20,0 14-17 17-20
BU 3M (32) 3N (1") 43 16 35 25 14,0-24,0 14-17 17-20 20-24
BU 34M (32) 34N (1") 53 16 45 39 22,0-28,0 22-24 24-27 27-28
BU 4M (40) 4N (11/4") 45 18 45 39 22,0-32,0 22-24 24-27 27-32
BU 45M (40) 45N (11/4") 55 18 50 32 26,0-34,0 26-28 28-31 31-34
BU 5M (50) 5N (11/2") 46 18 55/50 32 26,0-35,0 26-28 28-31 31-35
BU 56M (50) 56N (11/2") 63 18 55/58 38 35,0-44,0 35-38 38-41 41-44
BU 6M (63) 6N (2") 53 18 68/58 38 35,0-45,0 35-38 38-41 41-45
BU 67M (63) 67N (2") 62 18 75/80 25 46,0-56,0 46-48 48-52 52-56
BU 7M (75) 7N (21/2") 64 20 80 25 46,0-62,0 46-51 51-57 57-62
BU 78M (75) 78N (21/2") 75 20 95 36 60,0-70,0 60-63 63-69 69-70
BU 8M (90) 8N (3") 75 20 95 36 60,0-75,0 60-63 63-69 69-75
BU 810M (90) 810N (3") 77 20 105 38 75,0-85,0 75-79 79-82 82-85
BU 10M (100) 10N (4") 77 20 105 38 75,0-85,0 75-79 79-82 82-85
BU 11M (110) 11N (4") 77 20 115 38 85,0-95,0 85-89 89-92 92-95

P - Sealing Combination
CH Position
marking
Seal S1 P

Item Item Description Seal S2


1 O-ring
2 Lower Body
3 Seal S3
H
4 Seal S2
5 Seal S1 L
6 Cap Seal S3

L1

6 5 4 3 2 1

13
1 Function Ex-d IIC / Ex-e II / Ex-td
VELA EMC Brass Cable Gland
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 038 X
Examination & Test Report Number 43AL00002
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007 /
EN 60079-11:2010 / EN 60079-31:2009
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex tb IIIC Db
Suitable for use in ZONE1, ZONE2, ZONE21, ZONE22 for Gas Groups IIA, IIB,
IIC
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BS.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30⁰C
+120⁰C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
Temperature Classes -30⁰C / +100⁰C with NBR Sealing Ring
-40⁰C / +120⁰C with NEOPRENE Sealing Ring
-60⁰C / +180⁰C with SILICONE Sealing Ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BS01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BS01MBNS
BS01NXC
Cable Gland Dimensions P
M
M Sealing Ring
Type ANSI ASME S1+S2+S3 S1+S2 S1
ISO pitch 1,5 H min L1 min L min CH dimension Ø
B1.20.1
min-max
BS 01MΔ (16) 01NΔ (3/8") 41 20 16 22 3,0-12,0 3-6 6-9 9-12
BS 1MΔ (20) 1NΔ (1/2") 41 20 16 22 3,0-12,0 3-6 6-9 9-12
BS 2MΔ (25) 2NΔ (3/4") 43 20 16 28 10,0-18,0 10-13 13-18
BS 3MΔ (32) 3NΔ (1") 51 25 20 35 14,0-24,0 14-17 17-20 20-24
BS 4MΔ (40) 4NΔ (1 1/4") 59 25 20 45 22,0-32,0 22-26 26-32
BS 5MΔ (50) 5NΔ (1 1/2") 60 39 20 55 26,0-35,0 26-30 30-35

P - Sealing Combination

CH Position
marking Seal S1
P

Seal S2

L1 Item Item Description


H Seal S3 1 O-ring
2 Lower Body
3 Tapered Spring
4 Spring Ring
5 Seal S3
L 6 Seal S2
7 Seal S1
8 Cap

8 7 6 5 4 3 2 1

14
Ex e II - Ex d Link Cable glands
for non armoured cables CARINA
Technical details
Approved by IMQ
Examination Certificate Number IMQ 11 ATEX 038 X
Examination & Test Report Number 43AL00002
Safety Requirements EN 60079-0:2009 / EN 60079-1:2007 / EN 60079-7:2007 /
EN 60079-11:2010
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex tb IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD BM.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-30⁰C
+120⁰C Ex tb IIIC Db IP66/68 IMQ 11 ATEX 038X
Temperature Classes -30⁰C / +100⁰C with NBR Sealing Ring
-40⁰C / +120⁰C with NEOPRENE Sealing Ring
-60⁰C / +180⁰C with SILICONE Sealing Ring
Material Brass – Stainless Steel

Order Type Thread Material Plated Sealing


Encoding BM01 N (Npt) B (Brass) N (Nickel Only for N (NBR)
M (Metric) X (Stainless Brass) C (Chloroprene)
Steel) S (Silicone)
Example BM01MBNS
BM01NXC
Cable Glands Dimensions P Sealing Ring Dimensions Ø
M-M1 M-M1
Type S1+S2+S3 S1+S2 S1
ANSI ASME B1.20.1 ISO Pitch 1,5 L Min. L1-L2 Min. CH CH1 H mm Min. Max.
BM 01 (3/8") 01M (M16) 60 16 22 24 20 3 12 3-6 6-9 9-12
BM 1 (1/2") 1M (M20) 58 16 22 24 20 3 12 3-6 6-9 9-12
BM 12 (1/2") 12M (M20) 60 16 285 30 20 10 16 10-13 13-16
BM 2 (3/4") 2M (M25) 58 16 28 30 20 10 18 10-13 13-18
BM 23 (3/4") 23M (M25) 62 16 35 35 25 14 20 14-17 17-20
BM 3 (1") 3M (M32) 68 20 35 35 25 14 24 14-17 17-20 20-24
BM 34 (1") 34M (M32) 77 20 45 45 39 22 28 22-26 26-28
BM 4 (1 1/4") 4M (M40) 67 20 45 45 39 22 32 22-26 26-32
BM 45 (1 1/4") 45M (M40) 77 20 50 50 32 26 34 26-30 30-34
BM 5 (1 1/2") 5M (M50) 68 20 55 50 32 26 35 26-30 30-35
BM 56 (1 1/2") 56M (M50) 85 20 55 60 38 35 44 35-38 38-44
BM 6 (2") 6M (M63) 75 20 68 65 38 35 45 35-38 38-45
BM 67 (2") 67M (M63 84 20 75 80 25 46 57 45-49 49-53 53-57
BM 7 (2 1/2") 7M (M75) 96 26 80 80 25 46 62 49-51 51-57 57-62
BM 78 (2 1/2") 78M (M75) 108 26 95 95 36 60 70 60-63 63-69 69-70
BM 8 (3") 8M (M90) 108 26 95 95 36 60 75 60-63 63-69 69-75
BM 810 (3") 810M (M90) 110 26 105 105 38 75 82 75-79 79-82
BM 10 (4") 10M (M100) 110 26 115 115 38 75 85 75-79 79-82 82-85
BM 11 (4") 11M (M110) 110 26 115 115 38 85 95 85-89 89-92 92-95
M1
P - Sealing Combination
P

Seal S1

Position
marking
Item Item Description Seal S2
L2
1 O-ring
2 Lower Body
3 Seal S3
4 Seal S2
5 Seal S1
Seal S3 L
6 Female Body
CH1

CH2

L1

M
6 5 4 3 2 1

15
BU & BM Type
FSEAL for Flat Seal
Technical details
Type Sealing Bushing BU2 - BM2
O.N. CE 0722
Group II 2GD Ex TIIIC Db IP 66/IP 68
Execution Ex d IIC Gb / Ex e IIC Gb
Examination & test report number 43AL00002
Laboratory IMQ
Certificate IMQ ATEX 11 038X
Material & -30⁰C / +100⁰C NBR Sealing
Operating Temperature -40⁰C / +120⁰C CHLOROPRENE Sealing
-60⁰C / +180⁰C SILICONE Sealing

Cable Dimensions Ø Seal Dimensions


Type Thread Size
A mm B mm D mm D1 mm D2 mm L1 mm L2 mm L3 mm L mm R mm
FxA1 5,0 12,2 2,5
FxB1 6,0 8,5 3,0
NPT 1/2" M20 19,0 15,0 16,8 7,2 8,5 8,5 24,2
FxC1 5,5 11,7 2,75
FxD1 6,0 12,2 3,0
FxA2 5,0 12,8 2,5
FxB2 6,0 8,5 3,0
NPT 3/4" M25 24,2 21,0 10,0 12,0 22,0
FxC2 5,5 11,7 2,75
FxD2 6,0 14,0 3,0

1 D

B A

R
L1

L
L2

L3

D1

D2

2 D

B A

R
L1

L2

D2

16
Ex-e II / Ex-d IIc Plugs &
Ex-d IIC / Ex-e II C Adaptors
Ex e II - Ex d IIC
Male plugs AQUILA
Technical details
Type B-TS
O.N. Ex 0722
Group II 2GD Ex Td A21
Execution Ex de IIC IP66/68
Examination & test report number 43AL00002
Laboratory IMQ
Certificate IMQ ATEX 16 U
Material Δ Brass – Stainless Steel – Galvanised Steel

The male plugs can be used with circuits Ex i.These male plugs should have a part painted light
blue.The male can be also GAS UNI ISO 7/1 and GK GAS UNI 6125.For chosen male plugs see
example B.Minimum thread lenght :L must be min. 5 threads engaged for cylindirical threads and
min. 5 construction threads for tapered threads. Thread tolerance in according ISO 965I – 965III
for dimensions ISO pitch 1,5 - GAS UNI ISO 228/1 – PG DIN 40430 – NPT ANSI ASME B1.20.1 M =
male thread hub.The threads can be also intermediate for ISO pitch 1,5 (Example M33; M42; M14
and other).The male plugs can be have also the sunk key.

Order Type Thread Material Plated


Encoding B-TS01 N (Npt) B (Brass) N (Nickel Only for
M (Metric) X (Stainless Brass)
P (Pg) Steel)
C (Gas) Z (Galvanised
Steel)
Example B-TS01MBN
B-TS01NX

M M
Type ISO H mm L mm CH mm GAS UNI ISO H mm L mm CH mm
pitch 1,5 228/1
B-TS 02M (M12) 21 14 17 02C (1/4”) 23 16 18
B-TS 01M (M16) 21 14 22 01C (3/8”) 23 16 22
B-TS 1M (M20) 21 14 25 1C (1/2”) 23 16 25
B-TS 2M (M25) 21 14 30 2C (3/4”) 23 16 32
B-TS 3M (M32) 21 14 37 3C (1”) 27 20 37
B-TS 4M (M40) 23 16 45 4C (1 1/4”) 27 20 45
B-TS 5M (M50) 23 16 55 5C (1 1/2”) 27 20 55
B-TS 6M (M63) 23 16 70 6C (2”) 27 20 65
B-TS 7M (M75) 25 18 85 7C (2 1/2”) 30 20 85
B-TS 8M (M90) 25 18 100 8C (3”) 30 20 95
B-TS 10M (M110) 25 18 120 10C (4”) 30 20 120

M M
Type PG H mm L mm CH mm ANSI ASME H mm L mm CH mm
DIN 40430 B1.20.1
B-TS 1P (7) 22 15 17 02N (1/4”) 20 16 15
B-TS 2P (9) 22 15 20 01N (3/8”) 20 16 20
B-TS 3P (11) 22 15 25 1N (1/2”) 22 18 24
B-TS 4P (13,5) 22 15 25 2N (3/4”) 22 18 27
B-TS 5P (16) 22 15 27 3N (1”) 25 21 35
B-TS 6P (21) 22 15 35 4N (1 1/4”) 25 21 45
B-TS 7P (29) 22 15 42 5N (1 1/2”) 26 21 50
B-TS 8P (36) 22 15 55 6N (2”) 26 21 65
B-TS 9P (42) 22 15 60 7N (2 1/2”) 33 28 75
B-TS 10P (48) 22 15 65 8N (3”) 33 28 90
10N (4”) 33 28 115

CH

Item Item Description


1 O-ring
H
2 Body
L

2 1

18 33
Ex e IIC - Ex d IIC Adaptors (Enlarger)
APUS Metric / Metric & Metric / Npt
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RB.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
B-RB 2 M 1 N B
Metric/Pg-Metric/Pf
Code Size (F) Type Size (M) Type (Δ) Material
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf
female male
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg thread thread
also are availible on request.
Thread Type Sizes
M 02 01 1 2 3 4 5 6 7 8 10
METRIC EN 60423 12 16 20 25 32 40 50 63 75 90 110
N 02 01 1 2 3 4 5 6 7 8 10
NPT ANSI B1.20.1 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
C 02 01 1 2 3 4 5 6 7 8 10
PF JIS B0202 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
P 1 2 3 4 5 6 7 8 9 10
PG DIN 40430 7 9 11 13,5 16 21 29 36 42 48
Metric / Metric
EN 60423 EN 60423 Dimensions mm
Type
FØ MØ DØ H TL TL1 SW
B-RB02M02MΔ M12x1.5 M12x1.5 7,0 33,5 15,0 15,0 18,0
B-RB01M02MΔ M16x1.5 M12x1.5 7,0 33,5 15,0 15,0 22,0
B-RB01M01MΔ M16x1.5 M16x1.5 10,0 33,5 15,0 15,0 22,0
B-RB1M02MΔ M20x1.5 M12x1.5 7,0 34,0 15,0 15,0 25,0
B-RB1M01MΔ M20x1.5 M16x1.5 10,0 34,0 15,0 15,0 25,0
B-RB1M1MΔ M20x1.5 M20x1.5 14,0 34,0 15,0 15,0 25,0
B-RB2M01MΔ M25x1.5 M16x1.5 10,0 34,0 15,0 15,0 30,0
B-RB2M1MΔ M25x1.5 M20x1.5 14,0 34,0 15,0 15,0 30,0
B-RB2M2MΔ M25x1.5 M25x1.5 19,0 34,0 15,0 15,0 30,0
B-RB3M1MΔ M32x1.5 M20x1.5 14,0 34,0 15,0 15,0 36,0
B-RB3M2MΔ M32x1.5 M25x1.5 19,0 34,0 15,0 15,0 36,0
B-RB3M3MΔ M32x1.5 M32x1.5 26,0 34,0 15,0 15,0 36,0
B-RB4M2MΔ M40x1.5 M25x1.5 19,0 37,0 18,0 15,0 45,0
B-RB4M3MΔ M40x1.5 M32x1.5 26,0 37,0 18,0 15,0 45,0
B-RB4M4MΔ M40x1.5 M40x1.5 34,0 40,0 18,0 18,0 45,0
B-RB5M3MΔ M50x1.5 M32x1.5 26,0 37,0 18,0 15,0 55,0
B-RB5M4MΔ M50x1.5 M40x1.5 34,0 40,0 18,0 18,0 55,0
B-RB5M5MΔ M50x1.5 M50x1.5 44,0 40,0 18,0 18,0 55,0
B-RB6M5MΔ M63x1.5 M50x1.5 44,0 40,5 18,0 18,0 68,0
B-RB6M6MΔ M63x1.5 M63x1.5 57,0 40,5 18,0 18,0 70,0
B-RB7M6MΔ M75x1.5 M63x1.5 57,0 40,5 18,0 18,0 80,0
B-RB7M7MΔ M75x1.5 M75x1.5 69,0 40,5 18,0 18,0 85,0
B-RB8M7MΔ M90x1.5 M75x1.5 69,0 43,5 21,0 18,0 95,0
B-RB8M8MΔ M90x1.5 M90x1.5 84,0 47,0 21,0 21,0 95,0
B-RB10M8MΔ M110x1.5 M90x1.5 84,0 47,0 21,0 21,0 115,0
B-RB10M10MΔ M110x1.5 M110x1.5 104,0 47,0 21,0 21,0 120,0
Metric / Npt
EN 60423 ANSI B1.20.1 Dimensions mm
Type
FØ MØ DØ H TL TL1 SW
B-RB02M02NΔ M12x1.5 NPT 1/4" 8,0 33,0 15,0 15,0 18,0
B-RB01M02NΔ M16x1.5 NPT 1/4" 8,0 33,5 15,0 15,0 22,0
B-RB01M01NΔ M16x1.5 NPT 3/8" 12,0 33,5 15,0 15,0 22,0
B-RB1M01NΔ M20x1.5 NPT 3/8" 12,0 34,0 15,0 15,0 25,0
B-RB1M1NΔ M20x1.5 NPT 1/2" 14,5 34,0 15,0 15,0 25,0
B-RB2M1NΔ M25x1.5 NPT 1/2" 14,5 34,0 15,0 15,0 30,0
B-RB2M2NΔ M25x1.5 NPT 3/4" 19,0 34,0 15,0 15,0 30,0
B-RB3M2NΔ M32x1.5 NPT 3/4" 19,0 34,0 15,0 15,0 36,0
B-RB3M3NΔ M32x1.5 NPT 1" 26,0 34,0 15,0 15,0 36,0
B-RB4M3NΔ M40x1.5 NPT 1" 26,0 37,0 18,0 15,0 45,0
B-RB4M4NΔ M40x1.5 NPT 1 1/4" 35,0 40,0 18,0 18,0 45,0
B-RB5M4NΔ M50x1.5 NPT 1 1/4" 35,0 40,0 18,0 18,0 55,0
B-RB5M5NΔ M50x1.5 NPT 1 1/2" 40,0 40,0 18,0 18,0 55,0
B-RB6M5NΔ M63x1.5 NPT 1 1/2" 40,0 40,5 18,0 18,0 68,0
B-RB6M6NΔ M63x1.5 NPT 2" 51,0 40,5 18,0 18,0 68,0
B-RB7M6NΔ M75x1.5 NPT 2" 51,0 40,5 18,0 18,0 80,0
B-RB7M7NΔ M75x1.5 NPT 2 1/2" 62,0 40,5 18,0 18,0 80,0
B-RB8M7NΔ M90x1.5 NPT 2 1/2" 62,0 44,0 21,0 18,0 95,0
B-RB8M8NΔ M90x1.5 NPT 3" 75,0 47,0 21,0 21,0 95,0
B-RB10M8NΔ M110x1.5 NPT 3" 75,0 47,0 21,0 21,0 115,0
B-RB10M10NΔ M110x1.5 NPT 4" 100,0 47,0 21,0 21,0 120,0

19
Ex e IIC - Ex d IIC Adaptors (Enlarger)
Npt / Npt & Npt / Metric APUS
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RB.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility. TL SW TL1
Npt/Pg-Npt/Pf Item Item Description
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf 1 O-ring
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg 2 Body
also are availible on request.

F D M

2 1 H
Npt / Npt
ANSI B1.20.1 ANSI B1.20.1 Dimensions mm
Type
FØ MØ DØ H TL TL1 SW
B-RB02N02NΔ NPT 1/4" NPT 1/4" 8,0 33,0 15,0 15,0 18,0
B-RB01N02NΔ NPT 3/8" NPT 1/4" 8,0 33,5 15,0 15,0 20,0
B-RB01N01NΔ NPT 3/8" NPT 3/8" 12,0 33,5 15,0 15,0 20,0
B-RB1N01NΔ NPT 1/2" NPT 3/8" 13,0 34,0 15,0 15,0 25,0
B-RB1N1NΔ NPT 1/2" NPT 1/2" 14,5 34,0 15,0 15,0 25,0
B-RB2N1NΔ NPT 3/4" NPT 1/2" 14,5 34,0 15,0 15,0 30,0
B-RB2N2NΔ NPT 3/4" NPT 3/4" 19,0 34,0 15,0 15,0 32,0
B-RB3N2NΔ NPT 1" NPT 3/4" 20,0 34,0 15,0 15,0 36,0
B-RB3N3NΔ NPT 1" NPT 1" 25,0 34,0 15,0 15,0 36,0
B-RB4N3NΔ NPT 1 1/4" NPT 1" 27,0 37,0 18,0 15,0 45,0
B-RB4N4NΔ NPT 1 1/4" NPT 1 1/4" 33,0 40,5 18,0 18,0 45,0
B-RB5N4NΔ NPT 1 1/2" NPT 1 1/4" 35,0 40,5 18,0 18,0 55,0
B-RB5N5NΔ NPT 1 1/2" NPT 1 1/2" 40,0 40,5 18,0 18,0 55,0
B-RB6N5NΔ NPT 2" NPT 1 1/2" 41,0 40,5 18,0 18,0 65,0
B-RB6N6NΔ NPT 2" NPT 2" 52,0 40,5 18,0 18,0 65,0
B-RB7N6NΔ NPT 2 1/2" NPT 2" 53,0 40,5 18,0 18,0 80,0
B-RB7N7NΔ NPT 2 1/2" NPT 2 1/2" 62,0 40,5 18,0 18,0 80,0
B-RB8N7NΔ NPT 3" NPT 2 1/2" 62,0 43,5 21,0 18,0 95,0
B-RB8N8NΔ NPT 3" NPT 3" 75,0 47,0 21,0 21,0 95,0
B-RB10N8NΔ NPT 4" NPT 3" 75,0 47,0 21,0 21,0 120,0
B-RB10N10NΔ NPT 4" NPT 4" 100,0 47,0 21,0 21,0 120,0
Npt / Metric
ANSI B1.20.1 EN 60423 Dimensions mm
Type
FØ MØ DØ H TL TL1 SW
B-RB02N02MΔ NPT 1/4" M12x1.5 7,0 33,5 15,0 15,0 18,0
B-RB01N02MΔ NPT 3/8" M12x1.5 7,0 33,5 15,0 15,0 20,0
B-RB01N01MΔ NPT 3/8" M16x1.5 10,0 33,5 15,0 15,0 20,0
B-RB1N01MΔ NPT 1/2" M16x1.5 10,0 34,0 15,0 15,0 25,0
B-RB1N1MΔ NPT 1/2" M20x1.5 14,0 34,0 15,0 15,0 25,0
B-RB2N1MΔ NPT 3/4" M20x1.5 14,0 34,0 15,0 15,0 30,0
B-RB2N2MΔ NPT 3/4" M25x1.5 19,0 34,0 15,0 15,0 30,0
B-RB3N2MΔ NPT 1" M25x1.5 19,0 34,0 15,0 15,0 36,0
B-RB3N3MΔ NPT 1" M32x1.5 26,0 34,0 15,0 15,0 36,0
B-RB4N3MΔ NPT 1 1/4" M32x1.5 26,0 37,0 18,0 15,0 45,0
B-RB4N4MΔ NPT 1 1/4" M40x1.5 34,0 40,0 18,0 18,0 45,0
B-RB5N4MΔ NPT 1 1/2" M40x1.5 34,0 40,0 18,0 18,0 55,0
B-RB5N5MΔ NPT 1 1/2" M50x1.5 40,0 40,0 18,0 18,0 55,0
B-RB6N5MΔ NPT 2" M50x1.6 44,0 40,5 18,0 18,0 65,0
B-RB6N6MΔ NPT 2" M63x1.5 51,0 40,5 18,0 18,0 68,0
B-RB7N6MΔ NPT 2 1/2" M63x1.6 57,0 40,5 18,0 18,0 80,0
B-RB7N7MΔ NPT 2 1/2" M75x1.5 62,0 40,5 18,0 18,0 80,0
B-RB8N7MΔ NPT 3" M75x1.5 69,0 43,5 21,0 18,0 95,0
B-RB8N8MΔ NPT 3" M90x1.5 78,0 47,0 21,0 21,0 95,0
B-RB10N8MΔ NPT 4" M90x1.5 84,0 47,0 21,0 21,0 120,0
B-RB10N10MΔ NPT 4" M110x1.5 103,0 47,0 21,0 21,0 120,0

20 33
Ex e IIC - Ex d IIC Adaptors (Reducer)
GRUS Metric / Metric & Metric / Npt
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RA.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
Metric/Pg-Metric/Pf B-RA 2 M 1 N B
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf Code Size (F) Type Size (M) Type (Δ) Material
female male
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg
thread thread
also are availible on request.
Thread Type Sizes
M 02 01 1 2 3 4 5 6 7 8 10
METRIC EN 60423 12 16 20 25 32 40 50 63 75 90 110
N 02 01 1 2 3 4 5 6 7 8 10
NPT ANSI B1.20.1 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
C 02 01 1 2 3 4 5 6 7 8 10
PF JIS B0202 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
P 1 2 3 4 5 6 7 8 9 10
PG DIN 40430 7 9 11 13,5 16 21 29 36 42 48

Metric/Metric
EN 60423 EN 60423 Dimensions mm
Type
MØ FØ H TL SW
B-RA01M02MΔ M16x1.5 M12x1.5 19,0 15,0 22,0
B-RA1M02MΔ M20x1.5 M12x1.5 19,0 15,0 25,0
B-RA1M01MΔ M20x1.5 M16x1.5 19,0 15,0 25,0
B-RA2M01MΔ M25x1.5 M16x1.5 19,0 15,0 30,0
B-RA2M1MΔ M25x1.5 M20x1.5 19,0 15,0 30,0
B-RA3M1MΔ M32x1.5 M20x1.5 19,0 15,0 36,0
B-RA3M2MΔ M32x1.5 M25x1.5 19,0 15,0 36,0
B-RA4M2MΔ M40x1.5 M25x1.5 22,0 18,0 45,0
B-RA4M3MΔ M40x1.5 M32x1.5 22,0 18,0 45,0
B-RA5M3MΔ M50x1.5 M32x1.5 23,0 18,0 55,0
B-RA5M4MΔ M50x1.6 M40x1.5 23,0 18,0 55,0
B-RA6M4MΔ M63x1.5 M40x1.5 23,0 18,0 70,0
B-RA6M5MΔ M63x1.6 M50x1.5 23,0 18,0 70,0
B-RA7M5MΔ M75x1.5 M50x1.5 24,0 18,0 85,0
B-RA7M6MΔ M75x1.5 M63x1.5 24,0 18,0 85,0
B-RA8M6MΔ M90x1.5 M63x1.5 29,0 21,0 100,0
B-RA8M7MΔ M90x1.5 M75x1.5 29,0 21,0 100,0
B-RA10M7MΔ M110x1.5 M75x1.5 31,0 21,0 120,0
B-RA10M8MΔ M110x1.5 M90x1.5 31,0 21,0 120,0
Metric/Npt
EN 60423 ANSI B1.20.1 Dimensions mm
Type
MØ FØ H TL SW
B-RA01M02NΔ M16x1.5 NPT 1/4" 19,0 15,0 22,0
B-RA1M02NΔ M20x1.5 NPT 1/4" 19,0 15,0 25,0
B-RA2M1NΔ M25x1.5 NPT 1/2" 19,0 15,0 30,0
B-RA3M1NΔ M32x1.5 NPT 1/2" 19,0 15,0 36,0
B-RA3M2NΔ M32x1.5 NPT 3/4" 19,0 15,0 36,0
B-RA4M2NΔ M40x1.5 NPT 3/4" 22,0 18,0 45,0
B-RA4M3NΔ M40x1.5 NPT 1" 22,0 18,0 45,0
B-RA5M3NΔ M50x1.5 NPT 1" 23,0 18,0 55,0
B-RA5M4NΔ M50x1.6 NPT 1 1/4" 23,0 18,0 55,0
B-RA6M4NΔ M63x1.5 NPT 1 1/4" 23,0 18,0 70,0
B-RA6M5NΔ M63x1.6 NPT 1 1/2" 23,0 18,0 70,0
B-RA7M5NΔ M75x1.5 NPT 1 1/2" 24,0 18,0 85,0
B-RA7M6NΔ M75x1.5 NPT 2" 24,0 18,0 85,0
B-RA8M6NΔ M90x1.5 NPT 2" 29,0 21,0 100,0
B-RA8M7NΔ M90x1.5 NPT 2 1/2" 29,0 21,0 100,0
B-RA10M7NΔ M110x1.5 NPT 2 1/2" 31,0 21,0 120,0
B-RA10M8NΔ M110x1.5 NPT 3" 31,0 21,0 120,0

21
Ex e IIC - Ex d IIC Adaptors (Reducer)
Npt / Npt & Npt / Metric GRUS
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RA.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
Npt/Pg-Npt/Pf Item Item Description F
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf 1 O-ring
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg 2 Body
also are availible on request.
SW

TL

M
2 1

Npt/Npt
ANSI B1.20.1 ANSI B1.20.1 Dimensions mm
Type
MØ FØ H TL SW
B-RA01N02NΔ NPT 3/8" NPT 1/4" 19,0 15,0 22,0
B-RA1N02NΔ NPT 1/2" NPT 1/4" 19,0 15,0 25,0
B-RA1N01NΔ NPT 1/2" NPT 3/8" 19,0 15,0 25,0
B-RA2N01NΔ NPT 3/4" NPT 3/8" 19,0 15,0 30,0
B-RA2N1NΔ NPT 3/4" NPT 1/2" 19,0 15,0 30,0
B-RA3N1NΔ NPT 1" NPT 1/2" 19,0 15,0 36,0
B-RA3N2NΔ NPT 1" NPT 3/4" 19,0 15,0 36,0
B-RA4N1NΔ NPT 1 1/4" NPT 1/2" 22,0 18,0 45,0
B-RA4N2NΔ NPT 1 1/4" NPT 3/4" 22,0 18,0 45,0
B-RA4N3NΔ NPT 1 1/4" NPT 1" 22,0 18,0 45,0
B-RA5N1NΔ NPT 1 1/2" NPT 1/2" 23,0 18,0 55,0
B-RA5N2NΔ NPT 1 1/2" NPT 3/4" 23,0 18,0 55,0
B-RA5N3NΔ NPT 1 1/2" NPT 1" 23,0 18,0 55,0
B-RA5N4NΔ NPT 1 1/2" NPT 1 1/4" 23,0 18,0 55,0
B-RA6N4NΔ NPT 2" NPT 1 1/4" 23,0 18,0 65,0
B-RA6N5NΔ NPT 2" NPT 1 1/2" 23,0 18,0 65,0
B-RA7N5NΔ NPT 2 1/2" NPT 1 1/2" 24,0 18,0 75,0
B-RA7N6NΔ NPT 2 1/2" NPT 2" 24,0 18,0 75,0
B-RA8N6NΔ NPT 3" NPT 2" 29,0 21,0 95,0
B-RA8N7NΔ NPT 3" NPT 2 1/2" 29,0 21,0 95,0
B-RA10N7NΔ NPT 4" NPT 2 1/2" 31,0 21,0 120,0
B-RA10N8NΔ NPT 4" NPT 3" 31,0 21,0 120,0
Npt/Metric
ANSI B1.20.1 EN 60423 Dimensions mm
Type
MØ FØ H TL SW
B-RA01N02MΔ NPT 3/8" M12x1.5 19,0 15,0 22,0
B-RA1N02MΔ NPT 1/2" M12x1.5 19,0 15,0 25,0
B-RA1N01MΔ NPT 1/2" M16x1.5 19,0 15,0 25,0
B-RA2N01MΔ NPT 3/4" M16x1.5 19,0 15,0 30,0
B-RA2N1MΔ NPT 3/4" M20x1.5 19,0 15,0 30,0
B-RA3N1MΔ NPT 1" M20x1.5 19,0 15,0 36,0
B-RA3N2MΔ NPT 1" M25x1.5 19,0 15,0 36,0
B-RA4N2MΔ NPT 1 1/4" M25x1.5 22,0 18,0 45,0
B-RA4N3MΔ NPT 1 1/4" M32x1.5 22,0 18,0 45,0
B-RA5N3MΔ NPT 1 1/2" M32x1.5 23,0 18,0 55,0
B-RA5N4MΔ NPT 1 1/2" M40x1.5 23,0 18,0 55,0
B-RA6N4MΔ NPT 2" M40x1.5 23,0 18,0 65,0
B-RA6N5MΔ NPT 2" M50x1.5 23,0 18,0 65,0
B-RA7N5MΔ NPT 2 1/2" M50x1.5 24,0 18,0 75,0
B-RA7N6MΔ NPT 2 1/2" M63x1.5 24,0 18,0 75,0
B-RA8N6MΔ NPT 3" M63x1.5 29,0 21,0 95,0
B-RA8N7MΔ NPT 3" M75x1.5 29,0 21,0 95,0
B-RA10N7MΔ NPT 4" M75x1.5 31,0 21,0 120,0
B-RA10N8MΔ NPT 4" M90x1.5 31,0 21,0 120,0

22 33
Ex e IIC - Ex d IIC Adaptors (Coupling)
ARIES Metric / Metric
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RM.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
B-RM 2 M 1 N B
Metric/Pg-Metric/Pf
Code Size (F) Type Size (M) Type (Δ) Material
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf
female male
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg thread thread
also are availible on request.
Thread Type Sizes
M 02 01 1 2 3 4 5 6 7 8 10
METRIC EN 60423 12 16 20 25 32 40 50 63 75 90 110
N 02 01 1 2 3 4 5 6 7 8 10
NPT ANSI B1.20.1 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
C 02 01 1 2 3 4 5 6 7 8 10
PF JIS B0202 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
P 1 2 3 4 5 6 7 8 9 10
PG DIN 40430 7 9 11 13,5 16 21 29 36 42 48

Metric / Metric
EN 60423 EN 60423 Dimensions (mm)
Type
F F1 D H TL TL1 SW
B-RM02M02MΔ M12x1.5 M12x1.5 9,5 32,0 15,0 15,0 18,0
B-RM01M02MΔ M16x1.5 M12x1.5 9,5 33,0 15,0 15,0 20,0
B-RM01M01MΔ M16x1.5 M16x1.5 13,0 33,0 15,0 15,0 20,0
B-RM1M01MΔ M20x1.5 M16x1.5 13,5 32,0 15,0 15,0 25,0
B-RM1M1MΔ M20x1.5 M20x1.5 16,0 32,0 15,0 15,0 25,0
B-RM2M1MΔ M25x1.5 M20x1.5 17,0 33,0 15,0 15,0 32,0
B-RM2M2MΔ M25x1.5 M25x1.5 22,0 33,0 15,0 15,0 32,0
B-RM3M2MΔ M32x1.5 M25x1.5 22,0 34,0 15,0 15,0 36,0
B-RM3M3MΔ M32x1.5 M32x1.5 29,0 32,0 15,0 15,0 36,0
B-RM4M3MΔ M40x1.5 M32x1.5 29,0 37,0 18,0 15,0 45,0
B-RM4M4MΔ M40x1.5 M40x1.5 37,0 38,0 18,0 18,0 45,0
B-RM5M4MΔ M50x1.5 M40x1.5 37,5 40,0 18,0 18,0 55,0
B-RM5M5MΔ M50x1.5 M50x1.5 47,0 38,0 18,0 18,0 55,0
B-RM6M5MΔ M63x1.5 M50x1.5 47,0 41,0 18,0 18,0 68,0
B-RM6M6MΔ M63x1.5 M63x1.5 60,0 38,0 18,0 18,0 68,0
B-RM7M6MΔ M75x1.5 M63x1.5 60,0 41,0 18,0 18,0 80,0
B-RM7M7MΔ M75x1.5 M75x1.5 72,0 38,0 18,0 18,0 80,0
B-RM8M7MΔ M90x1.5 M75x1.5 72,0 45,0 21,0 18,0 95,0
B-RM8M8MΔ M90x1.5 M90x1.5 87,0 44,0 21,0 21,0 95,0
B-RM10M10MΔ M110x1.5 M110x1.5 107,0 44,0 21,0 21,0 120,0

23
Ex e IIC - Ex d IIC Adaptors (Coupling)
Npt / Npt & Npt / Metric ARIES
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RM.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
Npt/Pg-Npt/Pf H
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf SW
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg
also are availible on request.

F F1

TL D TL1

Npt / Npt
ANSI B1.20.1 ANSI B1.20.1 Dimensions (mm)
Type
F F1 D H TL TL1 SW
B-RM02N02NΔ NPT 1/4" NPT 1/4" 9,5 32,0 15,0 15,0 18,0
B-RM01N02NΔ NPT 3/8" NPT 1/4" 9,5 33,0 15,0 15,0 20,0
B-RM01N01NΔ NPT 3/8" NPT 3/8" 12,5 32,0 15,0 15,0 20,0
B-RM1N01NΔ NPT 1/2" NPT 3/8" 13,0 33,0 15,0 15,0 25,0
B-RM1N1NΔ NPT 1/2" NPT 1/2" 16,0 32,0 15,0 15,0 25,0
B-RM2N1NΔ NPT 3/4" NPT 1/2" 16,0 33,0 15,0 15,0 32,0
B-RM2N2NΔ NPT 3/4" NPT 3/4" 21,0 32,0 15,0 15,0 32,0
B-RM3N2NΔ NPT 1" NPT 3/4" 21,0 33,0 15,0 15,0 36,0
B-RM3N3NΔ NPT 1" NPT 1" 27,0 32,0 15,0 15,0 36,0
B-RM4N3NΔ NPT 1 1/4" NPT 1" 35,5 37,0 18,0 15,0 45,0
B-RM4N4NΔ NPT 1 1/4" NPT 1 1/4" 36,0 38,0 18,0 18,0 45,0
B-RM5N4NΔ NPT 1 1/2" NPT 1 1/4" 41,5 39,0 18,0 18,0 55,0
B-RM5N5NΔ NPT 1 1/2" NPT 1 1/2" 41,5 38,0 18,0 18,0 55,0
B-RM6N5NΔ NPT 2" NPT 1 1/2" 41,5 42,0 18,0 18,0 65,0
B-RM6N6NΔ NPT 2" NPT 2" 53,5 38,0 18,0 18,0 65,0
B-RM7N6NΔ NPT 2 1/2" NPT 2" 53,5 41,0 18,0 18,0 80,0
B-RM7N7NΔ NPT 2 1/2" NPT 2 1/2" 64,0 40,0 18,0 18,0 80,0
B-RM8N7NΔ NPT 3" NPT 2 1/2" 64,0 46,0 21,0 18,0 95,0
B-RM8N8NΔ NPT 3" NPT 3" 80,0 44,0 21,0 21,0 95,0
B-RM10N8NΔ NPT 4" NPT 3" 81,0 45,0 21,0 21,0 120,0
B-RM10N10NΔ NPT 4" NPT 4" 105,0 45,0 21,0 21,0 120,0
Npt / Metric or Metric / Npt
ANSI B1.20.1 EN 60423 Dimensions (mm)
Type
F F1 D H TL TL1 SW
B-RM02N02MΔ NPT 1/4" M12x1.5 9,5 32,0 15,0 15,0 18,0
B-RM01N02MΔ NPT 3/8" M12x1.5 9,5 33,0 15,0 15,0 20,0
B-RM01N01MΔ NPT 3/8" M16x1.5 12,5 32,0 15,0 15,0 20,0
B-RM1N01MΔ NPT 1/2" M16x1.5 14,0 32,0 15,0 15,0 25,0
B-RM1N1MΔ NPT 1/2" M20x1.5 16,0 32,0 15,0 15,0 25,0
B-RM2N1MΔ NPT 3/4" M20x1.5 17,0 33,0 15,0 15,0 32,0
B-RM2N2MΔ NPT 3/4" M25x1.5 22,0 32,0 15,0 15,0 32,0
B-RM3N2MΔ NPT 1" M25x1.5 22,5 33,0 15,0 15,0 36,0
B-RM3N3MΔ NPT 1" M32x1.5 28,0 32,0 15,0 15,0 36,0
B-RM4N3MΔ NPT 1 1/4" M32x1.5 29,0 37,0 18,0 15,0 45,0
B-RM4N4MΔ NPT 1 1/4" M40x1.5 35,5 38,0 18,0 18,0 45,0
B-RM5N4MΔ NPT 1 1/2" M40x1.5 38,0 39,0 18,0 18,0 55,0
B-RM5N5MΔ NPT 1 1/2" M50x1.5 42,0 39,0 18,0 18,0 55,0
B-RM6N5MΔ NPT 2" M50x1.5 48,0 39,0 18,0 18,0 65,0
B-RM6N6MΔ NPT 2" M63x1.5 54,0 39,0 18,0 18,0 68,0
B-RM7N6MΔ NPT 2 1/2" M63x1.5 60,0 40,0 18,0 18,0 80,0
B-RM7N7MΔ NPT 2 1/2" M75x1.5 64,0 40,0 18,0 18,0 80,0
B-RM8N7MΔ NPT 3" M75x1.5 72,0 44,0 21,0 18,0 95,0
B-RM8N8MΔ NPT 3" M90x1.5 79,5 46,0 21,0 21,0 95,0
B-RM10N8MΔ NPT 4" M90x1.5 87,0 49,0 21,0 21,0 120,0
B-RM10N10MΔ NPT 4" M110x1.5 105,0 45,0 21,0 21,0 120,0

24 33
Ex e IIC - Ex d IIC Adaptors (Nipple)
PAVO Metric / Metric
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RN.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
Metric/Pg-Metric/Pf B-RN 2 M 1 N B
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf Code Size (F) Type Size (M) Type (Δ) Material
female male
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg
thread thread
also are availible on request.
Thread Type Sizes
M 02 01 1 2 3 4 5 6 7 8 10
METRIC EN 60423 12 16 20 25 32 40 50 63 75 90 110
N 02 01 1 2 3 4 5 6 7 8 10
NPT ANSI B1.20.1 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
C 02 01 1 2 3 4 5 6 7 8 10
PF JIS B0202 1/4 3/8 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4
P 1 2 3 4 5 6 7 8 9 10
PG DIN 40430 7 9 11 13,5 16 21 29 36 42 48

Metric / Metric
EN 60423 EN 60423 Dimensions (mm)
Type
M M1 D H TL TL1 SW
B-RN02M02MΔ M12x1.5 M12x1.5 7,0 46,0 15,0 15,0 18,0
B-RN01M01MΔ M16x1.5 M16x1.5 10,0 48,0 15,0 15,0 20,0
B-RN1M1MΔ M20x1.5 M20x1.5 14,0 48,0 15,0 15,0 24,0
B-RN2M2MΔ M25x1.5 M25x1.5 19,0 50,0 15,0 15,0 32,0
B-RN3M3MΔ M32x1.5 M32x1.5 26,0 50,0 15,0 15,0 36,0
B-RN4M4MΔ M40x1.5 M40x1.5 34,0 56,0 18,0 18,0 45,0
B-RN5M5MΔ M50x1.5 M50x1.5 44,0 58,0 18,0 18,0 55,0
B-RN6M6MΔ M63x1.5 M63x1.5 57,0 58,0 18,0 18,0 70,0
B-RN7M7MΔ M75x1.5 M75x1.5 69,0 62,0 18,0 18,0 85,0
B-RN8M8MΔ M90x1.5 M90x1.5 84,0 68,0 21,0 21,0 100,0
B-RN10M10MΔ M110x1.5 M110x1.5 100,0 69,0 21,0 21,0 120,0

25
Ex e IIC - Ex d IIC Adaptors (Nipple)
Npt / Npt & Npt / Metric PAVO
Technical details
Approved by IMQ
Manufacturer BIMED
Examination Certificate Number IMQ 12 ATEX 003 U
Safety Requirements EN 60079-0 / EN 60079-1 / EN 60079-7 / EN 60079-31
Equipment Marking Flameproof Ex-d and Increased Safety Ex-e EX II 2GD EX d
IIC Gb / Ex e IIC Gb / Ex t IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Marking BMD B-RN.. CE0722 II 2GD Exd IIC Gb / Exe IIC Gb Ta-
30⁰C +120⁰C Ex t IIIC Db IP66/68 IMQ 12 ATEX 003 X
Temperature Classes -30⁰C / +120⁰C
Material (Δ) B – Brass
X – Stainless Steel
Z-Galvanized steel
Please ask for stock availibility.
Npt/Pg-Npt/Pf Item Item Description H
Pg/Pg-Pg/Metric-Pg/Npt-Pg/Pf 1 O-ring SW
Pf/Pf-Pf/Metric-Pf/Npt-Pf/Pg 2 Body
also are availible on request.

M1 D M

TL1
TL

1 2 1

Npt / Npt
ANSI B1.20.1 ANSI B1.20.1 Dimensions (mm)
Type
M M1 D H TL TL1 SW
B-RN02N01NΔ NPT 1/4" NPT 1/4" 8,0 46,0 15,0 15,0 18,0
B-RN02N02NΔ NPT 1/4" NPT 3/8" 8,0 48,0 15,0 15,0 20,0
B-RN01N02NΔ NPT 3/8" NPT 3/8" 12,0 48,0 15,0 15,0 20,0
B-RN01N1NΔ NPT 3/8" NPT 1/2" 12,0 48,0 15,0 15,0 24,0
B-RN1N1NΔ NPT 1/2" NPT 1/2" 15,5 48,0 15,0 15,0 24,0
B-RN1N2NΔ NPT 1/2" NPT 3/4" 15,5 50,0 15,0 15,0 32,0
B-RN2N2NΔ NPT 3/4" NPT 3/4" 19,0 50,0 15,0 15,0 32,0
B-RN2N3NΔ NPT 3/4" NPT 1" 19,0 50,0 15,0 15,0 36,0
B-RN3N3NΔ NPT 1" NPT 1" 25,0 50,0 15,0 15,0 36,0
B-RN3N4NΔ NPT 1" NPT 1 1/4" 25,0 53,0 15,0 18,0 45,0
B-RN4N4NΔ NPT 1 1/4" NPT 1 1/4" 33,0 56,0 18,0 18,0 45,0
B-RN5N5NΔ NPT 1 1/2" NPT 1 1/2" 40,0 58,0 18,0 18,0 55,0
B-RN6N6NΔ NPT 2" NPT 2" 52,0 58,0 18,0 18,0 65,0
B-RN7N7NΔ NPT 2 1/2" NPT 2 1/2" 62,0 62,0 18,0 18,0 80,0
B-RN8N8NΔ NPT 3" NPT 3" 75,0 68,0 21,0 21,0 95,0
B-RN10N10NΔ NPT 4" NPT 4" 100,0 69,0 21,0 21,0 120,0
Npt / Metric or Metric / Npt
ANSI B1.20.1 EN 60423 Dimensions (mm)
Type
F F1 D H TL TL1 SW
B-RN02N02MΔ NPT 1/4" M12x1.5 7,0 46,0 15,0 15,0 18,0
B-RN01N01MΔ NPT 3/8" M16x1.5 10,0 48,0 15,0 15,0 20,0
B-RN1N1MΔ NPT 1/2" M20x1.5 14,0 48,0 15,0 15,0 24,0
B-RN2N2MΔ NPT 3/4" M25x1.5 19,0 50,0 15,0 15,0 32,0
B-RN3N3MΔ NPT 1" M32x1.5 26,0 50,0 15,0 15,0 36,0
B-RN4N4MΔ NPT 1 1/4" M40x1.5 33,0 56,0 18,0 18,0 45,0
B-RN5N5MΔ NPT 1 1/2" M50x1.5 40,0 58,0 18,0 18,0 55,0
B-RN6N6MΔ NPT 2" M63x1.5 52,0 58,0 18,0 18,0 70,0
B-RN7N7MΔ NPT 2 1/2" M75x1.5 62,0 62,0 18,0 18,0 85,0
B-RN8N8MΔ NPT 3" M90x1.5 75,0 68,0 21,0 21,0 100,0
B-RN10N10MΔ NPT 4" M110x1.5 100,0 69,0 21,0 21,0 120,0

26 33
Ex-e IIC
Ventilation Plug
Ex e IIC
HYDRA Ventilation Plug
Technical details
Approved by IBExU
Examination Certificate Number IBExU 10 ATEX 1169 U
Safety Requirements EN 60079-0/EN 60079-7/EN 60079-31
Equipment Marking Flameproof Ex-e / Ex-tb and Increased Safety Ex
II 2G Ex e IIC Gb / Ex IID Ex tb IIIC Db
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66
Marking RST DAE... IBExU 10 ATEX 1169 U Ex II2D
Temperature Classes -40⁰C to +105⁰C
Material Stainless Steel

ΔP=1 Psi=70 mBar Average Water Instrusion Recomm.


Thread Dimensions (mm)
Type Air Permeability in lt/hour pressure in Bar Hole Diam.
size
TD TL H D SW S M H UH S M H UH (mm)
MBBVP-01L M12x1,5 12,0 10,0 11,0 17,0 17,0 16,0 25,0 120,0 300,0 0,9 0,5 0,2 0,1 12,5
MBBVP-01 M12x1,5 12,0 6,0 15,2 17,0 17,0 16,0 25,0 120,0 300,0 0,9 0,5 0,2 0,1 12,5
In order to choose the right ventilation plug unit (pressure balance elements) for a
specific application, the working principles of the unit must be known first Ventilation plugs are
D
permeable to "gases and vapours, e.g. air" but impermeable to "liquids and dust, e.g. water".
The permeability resistance to liquids depends on the pore size and structure of the membrane

28
inside these devices.
If the working conditions of water (the most common liquid) are studied, it is possible to
H SW say that the water intrusion pressure goes down as air permeability increases. The relevant
specifications are collected in tabulated data.
Of the relevant parameters, the "Pressure Balance" function depends on the differantial
pressure between the inner and the outer environnements of the enclosure. As a reference
TL pressure, 70 mBar (70mBar = 1 Psi) value is choosen to present data. Under normal conditions,
air circulation exists for all differential pressure levels. But the volume flow rate is very low for
smaller values and obviously increases with increasing pressure values. Of course the air flow
TD rate also depends on the properties of the membrane (classified as standard, medium, high
and ultra high permeability types).
If there is no water pressure danger (if the device is not immersed in the water), it is
Item Item Description always better to choose highly permeable elements for good circulation even for low
1 Cap differantial pressure levels.
2 Vent Plug ring In essence, there is air circulation in the enclosure from the inside to the outside when
3 Teflon Seal the device is heating up due to its operation. Similarly, a circulation in reverse direction occurs
4 Membran during the cooling period. It should also be noted that there is always a level of humidity in air,
5 Body hence some water in the form of vapour is also circulated with air. However condensed water
6 O-ring is blocked by the water repellent membrane unless the differential pressure exceeds the
intrusion pressure threshold.
After this technical overview, the utility of the "Ventilation Plugs" can be listed as follows;
• Prevention of pressure increase inside the enclosure. The pressure sensitive elements
are not threatened.
• Limiting of temperature increase by the air circulation. The temperature sensitive
elements are not threatened.
• Added flexibility for maintenance. In traditional units, when the enclosures are heated,
generaly the dilated air goes out from the seals but can not return back when the device is
colder. Because of the vacuum formed inside the enclosure, the gaskets are exposed to large
pressure levels. In result, it is very difficult to open the covers for maintenance. Especially in
“luminaires” it is obligatory to change the bulbs when the device is cold. The ventilation plugs
in our system prevent these kind of limitations.
• Prevention of accidental water suction into the system. During the cooling period, we
know that there is air circulation from the outside to the inside. Hence, if the enclosure is wet
1 2 3 4 3 5 6 from rain or due to other reasons, some water may be sucked inside the enclosure if there is
no ventilation plug.
• Prevention of exposure to hot, humid, compressed gases. There is always a level of
humidity in the enclosure due to atmospheric conditions. Hence when the device is hot, all the
components will be exposed to a hot, humid and compressed environment without the
ventilation plug.
To conclude, the ventilation plug can reduce and even fully eliminate the adverse effects
of humidity in the environment. Water drops on the bottom of the enclosure are normal,but
the inherent damage becomes insignificant due to the existence of a ventilation plug.

28 33
Ex-e II / Ex-i
PA6 Cable Glands & Male Plugs
Ex e II / Ex i
PA6 Cable Glands LYRA
Technical details
Approved by IMQ
Examination Certificate Number IMQ 08 ATEX 012 X
Examination & Test Report 43AI00015-43AI00015.1
Number
Safety Requirements EN 60079-0:2006 / EN 60079-7:2007 EN 60079-11:2007 / EN
61241-0:2006 / EN 61241-1:2004
Equipment Marking Increased Safety "e" and Intrinsic Safety "i" Ex II 2GD Ex e II ,
Ex i, Ex tD A21 ( The Cable Glands Ex e II can be used with
circuits Ex i. These Cable Glands Should Have a nut painted
Light Blue)
Suitable for use in ZONE1, ZONE2 for Groups IIA, IIB, IIC
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Temperature Classes -20⁰C / +80⁰C
For equivalence PG threads see Table A. Thread tollerance in according ISO 965-1 / - 965-3 for
dimensions ISO pitch 1,5 and PG DIN 40430.Can be use also threads ANSI ASME B1.20.1 NPT.

Table A
Standard threads
Metric 12 16 20 25 32 40 50 63
Equivalence threads
Pg 7 9-11 13,5-16 21 29 36 42 48

R
M Dimensions mm
Type Ø Standard Rubber
ISO pitch 1,5
min-max L H min CH CH1
BM-XS 12 3,0-6,5 8 31 15 15
BM-XS 12 3,0-6,5 15 31 15 15
BM-X1 16 4,5-10,0 10 38 19 19
BM-X1L 16 4,5-10,0 15 43 19 19
BM-X2 20 6,0 - 12,0 10 41 24 24
BM-X2L 20 6,0 - 12,0 15 46 24 24
BM-X3 20 10,0-14,0 10 42 27 27
BM-X4 20 10,0-14,0 15 46,5 27 27
BM-X5 25 13,0-18,0 10 47 33 33
BM-X6 25 13,0-18,0 15 52 33 33
BM-XEU25 25 11,0-17,0 8 42,5 29 29
BM-XEU32 32 15,0-21,0 10 50 36 36
BM-X7 32 18,0-25,0 15 58,5 42 42
BM-XEU40 40 19,0-28,0 10 55 46 46
BM-X8 40 22,0-32,0 18 68 53 53
BM-X9 50 30,0-38,0 18 69 60 60
BM-X10 63 34,0-44,0 18 71 65 65

CH1

R
Cable glands

Case thickness

Flat washer
for IP protection degree

Item Item Description


H
1 Cap
Lock nut
2 Seal
3 Body

CH1

1 2 3

30 33
Ex e II / Ex i
LYRA PA6 Cable Glands
The cable glands Ex d and Ex e ,can be used with circuits Ex i.These cable glands should
have a part painted light blue .
1- Ex d Junction box with Ex i circuits or terminal blocks and energy circuits or terminal
blocks
2- Ex e junction box with Ex i terminal blocks and Ex eterminal blocks
3- Ex e junction box with Ex i terminal blocks.

Example of use of Ex d or Ex e cable glands for Ex i circuits or terminal blocks

1) Ex d Junction box

Circuits or terminal Ex d cable glands


Inner Ex i circuits or
blocks separator
Light blue
terminal blocks

Inner energy circuits


Ex d cable glands or terminal blocks

2) Ex e Junction box

Ex i terminal blocks Circuits or terminal Ex e cable glands


Light blue blocks separator

Ex e cable glands Ex e terminal blocks

3) Ex e Junction box painted light blue

Ex e cable glands
Ex i terminal blocks
Light blue

Light blue
Ex e cable glands

31
33
Ex e II / Ex i
PA6 Male Plugs DRACO
Technical details
Approved by IMQ
Examination Certificate Number IMQ 08 ATEX 012 X
Examination & Test Report Number 43AI00015-43AI00015.1
EN 60079-0:2006 / EN 60079-7:2007 EN 60079-11:2007 /
Safety Requirements
EN 61241-0:2006 / EN 61241-1:2004
Increased Safety "e" and Intrinsic Safety "i" Ex II 2GD Ex e
II , Ex i, Ex tD A21
Equipment Marking ( The Cable Glands Ex e II can be used with circuits Ex i.
These Cable Glands Should Have a nut painted Light
Blue)
Suitable for use in ZONE1, ZONE2 for Groups IIA, IIB, IIC
For Gas & Dust potentially explosive atmospheres
Degree Of Protection IP66-IP68 (EN 60529)
Temperature Classes -20⁰C / +80⁰C

M Dimensions
Type
ISO pitch 1,5 H min L min S min D min CH
BP-X02 12 8 15 3 6 15
BP-X01 16 10 15 3 10 19
BP-X1 20 10 15 3 12 23
BP-X2 25 10 15 3 18 28
BP-X3 32 15 20 3 25 36
BP-X4 40 18 27 5 32 46
BP-X5 50 18 27 5 38 55
BP-X6 63 18 27 5 44 69

CH
2 max

L S
H

Detail A
Detail A Thread profile
D
60°
M

1,5
R 0,188

See Example "A" for IP protection degree and clamping note:

The plugs Ex e II,can be used with circuits Ex i.These cable glands should have a nut painted
R 0,188
light blue.The plugs must be supplayed with the flat washer for IP protection degree
Example "A" Case thickness

Flat washer
for IP protection degree

Lock nut

32 33
Accessories
for Ex Glands
Pvc Shroud
For DORADO SHROUD
Technical details
Material Pvc

Dimensions
Type
Ø D mm H mm
BMSH M16 KA 25,0 87,5
BMSH M20 KA 27,5 99,5
BMSH M25 KA 43,0 115,5
BMSH M32 KA 54,5 146,0
BMSH M40 KA 64,5 161,0
BMSH M50 KA 69,5 161,0
BMSH M63 KA 84,5 195,5
BMSH M75 KA 104,5 220,0
BMSH M90 KA 127,0 257,0
BMSH M110 KA 147,0 293,0
H

 D

34 33
Pvc Shroud
SHROUD For ORION
Technical details
Material Pvc

Dimensions
Type
Ø D mm H mm
BMSH M16 KBA (3,0-8,5) 29,1 75,4
BMSH M16 KBA (6,0-12,0) 31,7 74,9
BMSH M20 KBA (3,0-8,5) 29,1 75,4
BMSH M20 KBA (6,0-12,0) 31,7 74,9
BMSH M20 KBA (8,5-14,5) 35,2 79,4
BMSH M25 KBA (6,0-12,0) 31,7 74,9
BMSH M25 KBA (8,5-16,0) 37,2 83,9
BMSH M25 KBA (12,0-20,0) 44,2 86,6
BMSH M32 KBA (12,0-20,0) 44,2 86,6
BMSH M32 KBA (15,0-26,0) 57,2 115,5
BMSH M40 KBA (15,0-26,0) 57,2 115,5
BMSH M40 KBA (20,0-32,0) 66,2 125,1
BMSH M50 KBA (22,0-35,0) 82,2 141,6
BMSH M50 KBA (27,0-41,0) 83,2 139,6
BMSH M63 KBA (35,0-45,0) 89,7 148,0
BMSH M63 KBA (40,0-52,0) 94,2 151,8
BMSH M75 KBA (40,0-52,0) 94,2 151,8
H

 D

35
33
Pvc Shroud
For OCTANS & VELA SHROUD
Technical details
Material Pvc

Dimensions
Type
Ø D mm H mm
BMSH M16 BU (3,0-12,0) 24,6 56,2
BMSH M20 BU (3,0-12,0) 24,6 56,2
BMSH M20 BU (10,0-18,0) 31,1 67,7
BMSH M25 BU (10,0-18,0) 31,1 67,7
BMSH M25 BU (14,0-24,0) 39,1 72,7
BMSH M32 BU (14,0-24,0) 39,1 72,7
BMSH M32 BU (22,0-32,0) 49,6 91,9
BMSH M40 BU (22,0-32,0) 49,6 91,9
BMSH M40 BU (26,0-34,0) 56,1 88,0
BMSH M50 BU (26,0-35,0) 61,1 88,0
BMSH M50 BU (35,0-44,0) 70,1 93,9
BMSH M63 BU (35,0-45,0) 75,1 95,7
BMSH M63 BU (46,0-56,0) 89,1 100,9
BMSH M75 BU (46,0-62,0) 89,1 100,9
H

 D

36 33
Earth
ET Tags
Technical details
Material Brass or Nickel plated

Type Dimensions
Un plated Ni plated A e mm C mm D E mm F mm G mm
BMET M16 KA BMET M16 KA (Ni) M16 1,5 25,0 M6 48,75 30,0 12,5
BMET M20 KA BMET M20 KA (Ni) M20 1,5 28,6 M6 53,55 33,0 12,5
BMET M25 KA BMET M25 KA (Ni) M25 1,5 34,0 M6 59,50 36,0 13,0
BMET M32 KA BMET M32 KA (Ni) M32 1,5 42,0 M12 73,00 41,0 22,0
BMET M40 KA BMET M40 KA (Ni) M40 1,5 54,0 M14 86,50 46,5 26,0
BMET M50 KA BMET M50 KA (Ni) M50 1,5 67,0 M14 111,50 63,5 29,0
BMET M63 KA BMET M63 KA (Ni) M63 1,5 77,0 M14 125,50 72,5 29,0
BMET M75 KA BMET M75 KA (Ni) M75 1,5 89,0 M14 137,50 77,0 32,0
BMET M90 KA BMET M90 KA (Ni) M90 1,5 109,5 M14 167,00 94,5 35,5
BMET M110 KA BMET M110 KA (Ni) M110 1,5 138,0 M14 214,00 125,0 40,0

D e
F
E

37
33
Lock Nuts
for Ex Glands NUTS

STANDARD PA6 LOCK NUTS


Technical details
Polyamide 6, 30% Glass Fibre
Material
Reinforced
Operating Temperature -20 °C up to +100 °C

Technical Information
Thread Codes
H mm D mm D
Type SW mm
M12x1,5 5 18 19,5 BML-2S
M16x1,5 5 22 24,2 BML-21
M20x1,5 6 26 28,6 BML-22 SW
M25x1,5 6 32 35,0 BML-23 H
M32x1,5 7 41 46,1 BML-24
M40x1,5 7 50 55,3 BML-25
M50x1,5 8 60 66,1 BML-26
M63x1,5 8 75 82,5 BML-27

STANDARD BRASS LOCK NUTS


Technical details
Material Brass or Nickel plated
Technical Information
Thread Codes
H mm D mm
Type SW mm
M12X1,5 15 2,8 16,6 BMBL-01
SW
M16X1,5 19 3,0 21,0 BMBL-02
M20X1,5 24 3,5 26,5 BMBL-03 H

M25X1,5 30 4,0 33,0 BMBL-04


M32X1,5 36 5,0 39,5 BMBL-05
M40X1,5 46 5,0 51,0 BMBL-06
M50X1,5 60 5,0 66,0 BMBL-07
D
M63X1,5 70 6,0 77,0 BMBL-08
M72X2,0 77 7,0 86,0 BMBL-09
M75X2,0 80 7,0 89,6 BMBL-10
M80X2,0 90 8,0 99,3 BMBL-11
M85X2,0 95 8,0 106,2 BMBL-12
M90X2,0 100 8,0 112,0 BMBL-13

EMC BRASS LOCK NUTS


Technical Details
Material Brass, Nickel plated
Special design shape for
painted enclosures.
Technical Information
Thread Codes
H mm D mm
Type SW mm
M12X1,5 15 3,3 16,5 BMEL-01 SW

M16X1,5 19 3,5 21,0 BMEL-02


H
M20X1,5 24 3,5 26,5 BMEL-03
M25X1,5 30 3,5 33,0 BMEL-04
M32X1,5 36 4,0 39,5 BMEL-05
M40X1,5 46 4,6 51,0 BMEL-06 D

M50X1,5 60 5,6 66,0 BMEL-07


M63X1,5 70 6,7 77,0 BMEL-08

38 33
WASHER Washer
Technical Details
Material NBR, 70±5 Shore

Technical Information
Thread Codes
D mm d mm S mm
Type
M12 15,5 10,3 1,5 BMSW-21
M16 25,5 15,5 1,5 BMSW-22
M20 26,5 19,5 1,5 BMSW-23
M25 31,5 24,5 1,5 BMSW-24
M32 41,5 31,5 1,5 BMSW-25
M40 49,5 39,5 1,5 BMSW-26
M50 62,5 49,5 1,5 BMSW-27
M63 75,0 62,5 1,5 BMSW-28
M75 86,0 74,5 1,5 BMSW-29
M90 102,0 89,5 1,5 BMSW-30
M110 123,0 109,5 1,5 BMSW-31

d D

39
33
Ex
Technical Information
The intent of this section of the catalogue is to identify important features that may be useful in the selection and installation of
explosion protected electrical equipment.

There are numerous different regulations, codes, guidelines and standards for the design, installation and maintenance of electrical
and non-electrical systems for use in potentially explosive atmospheres. The type of operational facility, geographic location, operator
practice, local and national legislation, authority having jurisdiction, will determine many of the design and installation rules permitted.
A fixed or floating petroleum facility located offshore for example would not be designed or classified in the same manner as an
onshore petrochemical facility.

1.What is an explosion?
According to DIN EN 1127-1:1997, an explosion is an oxidation or decay reaction generating an increase in temperature or pressure or
both simultaneously.

So that an explosion can occur, three conditions must be fulfilled; see the explosion triangle diagram.
Fuel
Oxygen
Source of ignition
If one removes one of these three conditions, an explosion cannot occur.
Potentially explosive atmosphere: A potentially explosive atmosphere is understood to be a mixture of a combustible material and
oxygen. Oxygen is generally present as a component of air. Combustible materials can be gases, fluids, vapors, mist or dusts.
The terms "potentially explosive atmosphere" and "flammable mixture" are frequently used as synonyms. This mixture or atmosphere
can be caused to explode by a source of ignition.
The capacity to explode depends on the material used, its flammability and the mixture with air or oxygen. If the mixture is the result
of mixing with oxygen from the air which has a different composition from that normally found in the environment, then the
proportion of oxygen must be examined closely. If the proportion of oxygen falls below a certain value dependent on the material,
known as the oxygen limit concentration, then this mixture cannot be ignited.

This effect is exploited in what is known as initiation in which oxygen is replaced by an inert gas, one which is not suited to oxidation.
All the same, the concentration of the flammable material in the air mixture must lie between the lower and upper explosion limit.

Potentially explosive atmospheres can arise intentionally or unintentionally. The former are often present in production processes. In
these cases the potentially explosive atmosphere is present where the appropriate materials are used in the presence of ambient air.
These may be areas where glues or paints are drying or being applied, in the vicinity of fermentation tanks in alcohol production, in
areas where materials are being ground down such as in corn mills and numerous other places. Unintentional potentially explosive
atmospheres are created when a fault occurs. This might be for example when a gas pipeline bursts, when an outlet valve is
unintentionally opened, or leaks from boilers due to lack of servicing occur.
2.Explosion Prevention
Preventing potentially explosive atmospheres (primary explosion prevention)
By primary explosion prevention are understood all the measures which prevent a potentially explosive atmosphere from occurring.
Here for example it is possible to replace a potentially explosive material by another with no danger of explosion, (e.g.: replace paints
containing solvents by water-based paints). Furthermore, the materials can be isolated, i.e.: to prevent the admission of air and thus of
oxygen. If it is not possible to prevent a potentially explosive atmosphere, then measures must be taken which prevent ignition of the
potentially explosive atmosphere.
Avoiding sources of ignition (secondary explosion prevention)
By avoiding sources of ignition, once again one of the conditions of the explosion triangle is removed. Thus an explosion cannot occur.
In the Workplace Directive 99/92/EC, or alternatively in IEC Standard 60079-10, all potentially explosive areas are to be divided into
zones by the plant operator. The higher and longer the probability of the occurrence of a dangerous, potentially explosive atmosphere
is, the more demanding the requirements on the devices in use are. In the zones, the probable effectiveness of sources of ignition
must be prevented.
The following examples could be considered possible sources of ignition: Cf: DIN EN 1127-1, draft April 2009

• hot surfaces
• flames and hot gases
• mechanically generated sparks
• electrical systems
• electric equalizing currents /cathodic corrosion protection
• static electricity
• lightning strike
• electromagnetic waves / high frequency
• ionizing radiation
• ultrasound
• adiabatic compression and shock waves
• exothermic reactions

39
Ex
Technical Information
2.1.Tertiary explosion prevention
If it is not possible to ensure that the occurrence of a potentially explosive atmosphere is prevented, and if it is not possible to exclude
its ignition, then additional explosion prevention measures must be applied. The objective is to control or limit the effects of an
explosion.

Tertiary explosion prevention is thus applied when the measures of primary and secondary explosion prevention are not sufficient.

This can be carried out for example by means of the following measures:
• constructive explosion prevention, i.e.: explosion proof construction which can withstand the explosion blast
• flashback arresters
• automatic foam extinguishing systems
• pressure release and pressure equalization systems.

3.Explosion Protection Type


In Explosion Protection, what is meant by "type of explosion protection" are the special measures which are applied to electrical
operating facilities to prevent the ignition of a surrounding potentially explosive atmosphere.

The construction guidelines and conditions for electrical devices are laid down in IEC Standard 60079-ff.
Besides the type of explosion protection for electrical devices, there are other types of explosion protection for non-electrical devices.
These types of explosion protection are laid down in DIN EN 13463-ff.

From here on, only the types of explosion protection which apply to electrical devices will be considered.
Intrinsically safe "i"
Type of explosion protection

For the use of these devices in a potentially explosive area, only intrinsically safe circuits are used. Current and voltage are limited so
that the minimum ignition energy and the ignition temperature of an explosive mixture cannot be reached.
Norm:
EN 60079-11 - IEC 60079-11
Increased safety "e"
Type of explosion protection

The production of sparks, arcs or excessive temperatures which might act as a source of ignition are prevented by additional measures
and an increased degree of safety.
Norm:
EN 60079-7 / IEC 60079-7
Flameproof enclosures "d"
Type of explosion protection

The components which could cause the ignition of a potentially explosive mixture are built into an enclosure which is capable of
withstanding the pressure of an explosion. Furthermore, it is ensured that the explosion inside the enclosure cannot be transmitted
beyond the enclosure and ignite the external potentially explosive atmosphere.
Norm:
EN60079-1 / IEC 60079-1
Pressurized enclosure "p"
Type of explosion protection

The enclosure of a possible source of ignition is filled with a protective gas. Due to the overpressure created in the interior of the
enclosure, a potentially explosive atmosphere cannot penetrate into the interior of the enclosure. If necessary, the gas is kept
permanently flowing through the enclosure.
Norm:
EN 60079-2 / IEC 60079-2
Oil immersion "o"

40
Ex
Technical Information
The components which could ignite a potentially explosive atmosphere are built into an enclosure, which is filled with a protective
fluid, e.g.: oil. Thus the source of ignition and the potentially explosive atmosphere are kept apart.
Norm:
EN 60079- 6
IEC 60079-6

Encapsulation "m"
Type of explosion protection

The components which could ignite a potentially explosive atmosphere are encapsulated in a casting compound. Thus once again the
source of ignition and the potentially explosive atmosphere are kept separated.
Norm:
EN 60079-18 / IEC 60079-18
Sand filling "q"
Type of explosion protection

The components of an operating facility which might be a source of ignition are surrounded by an enclosure which is filled with quartz
sand. When used correctly, the potentially explosive atmosphere cannot be ignited.
Norm:
EN 60079-5
IEC 60079-5
Protection with "tD" enclosure
Type of explosion protection:

This type of explosion protection only applies to "Dust” areas, i.e.: Zones 20, 21 or 22. In this case it is ensured that none or only a
limited amount of dust can penetrate the enclosure which surrounds the source of ignition.
Here a distinction must be mad Dust-tight IP 6X Dust-protected IP 5X
Norm:
IEC 60079-0 / IEC 61241-1

4.Potentially Explosive Atmospheres


An explosive atmosphere is defined as: Flammable substances in the form of gases, vapours, mists, dusts or fibres mixed with air.
and/or Under atmospheric conditions, which after ignition has occurred, combustion spreads to the entire unburned mixture.

5.Area Classification (Classification of Locations)


The purpose of area classification is to provide a basis for the correct selection, installation and location of electrical and non-electrical
equipment in those areas. Areas must be classified depending on the properties of the flammable vapours, liquids, gases, mists,
combustible dusts or fibres that may be present and the likelihood that a flammable or combustible concentration or quantity is
present.
The aim of area classification is to avoid ignition of flammable releases that may occur in the operation of facilities. The intent is to
reduce to an acceptable minimum level the probability of a flammable atmosphere and an ignition source occurring at the same time.

6.IEC
6.1. Area Classification (Zones)
Area classification is the division of a facility into three dimensional hazardous areas and non-hazardous areas and the sub-division of
the hazardous area into Zones.

Hazardous areas may be sub-divided into three Zones, as shown below;

Gas
FLAMMABLE GASES AND VAPOURS
An area in which an explosive atmosphere is constantly present, or present for
Zone 0 long periods.
An area in which an explosive atmosphere is likely to occur in normal
Zone 1 operation. (Rough Guide: 10 hours or more per year but less than 1,000 hours
per year)
An area in which an explosive atmosphere is not likely to occur in normal
Zone 2 operation and if it occurs it will exist only for a short time. (Rough Guide: Less
than 10 hours per year)

41
Ex
Technical Information
Dust
COMBUSTIBLE DUSTS
An area in which combustible dust, as a cloud, is present continuously or
frequently during normal operation in sufficient quantity to be capable of
Zone 20 producing an explosive concentration of combustible dust in a mixture with
air.
An area in which combustible dust, as a cloud, is occasionally present during
Zone 21 normal operation in a sufficient quantity to be capable of producing an
explosive concentration of combustible dust in a mixture with air.
An area in which combustible dust, as a cloud, may occur infrequently and
persist for only a short period, or in which accumulations of layers of
Zone 22 combustible dust may give rise to an explosive concentration of combustible
dust in a mixture with air.

6.2. Classification Society


A Classification Society may also enforce requirements for the design of installations of facilities. These requirements, which are in
addition to statutory requirements, may influence the design and installation of the electrical systems. Classification Societies include
ABS, DNV and Lloyds Register.

6.3.Design and Installation of Electrical Systems for

Hazardous (Classified) Areas

There are numerous regulation codes, guidelines and standards for the design, selection and installation of electrical equipment in
potentially explosive atmospheres. These requirements are in addition to the requirements for installations in non-hazardous areas.
There are several types of protection, i.e. construction techniques, available for electrical apparatus in hazardous areas. The type of
protection permitted will depend upon the applicable installation codes and rules to be adopted.
The selection of electrical apparatus should be in accordance with the following;

• Classification of the hazardous area.


• Temperature class or ignition temperature of the gas, liquid, vapours, mist, dust or fibre.
• Where applicable, the gas, vapour or dust classification in relation to the group or sub-group of the electrical apparatus.
• External influences and ambient temperature.

6.4.Apparatus Selection According to Zones

• 6.4.1.Apparatus for use in Zone 0

Intrinsic safety “ia”

• 6.4.2.Apparatus for use in Zone 1

Electrical apparatus permitted for use in Zone 0, or


Flameproof enclosure “d”
Pressurized apparatus “p”
Powder filling “q”
Oil immersion “o”
Increased safety “e”
Intrinsic safety “ib”
Encapsulation “m”

• 6.4.3.Apparatus for use in Zone 2

Electrical apparatus permitted for use in Zone 0 and Zone 1, or


Electrical apparatus designed specifically for Zone 2 (e.g. type of protection 'n') or
Electrical apparatus complying with the requirements of a recognised standard for industrial electrical apparatus, which
does not, in normal operation, have ignition -capable hot surface and does not in normal operation produce arcs or sparks.
This equipment must be in an enclosure with a degree of protection and mechanical strength suitable for the environment and
be assessed by a person who is familiar with the requirements of any relevant standards and codes of practice.

• 6.4.4.Apparatus for use in Zones 20, 21 and 22

IEC/EN 61241-0- Electrical apparatus for use in the presence of combustible dust. General requirements. and
IEC/EN 61241-1 - Electrical apparatus for use in the presence of combustible dust. Protection by enclosures “tD”.

42
Ex
Technical Information
6.5.Apparatus selection according to the ignition temperature of the gas or vapour

The equipment must be selected so that its maximum surface temperature will not reach the ignition of any gas or vapour that may be
present.

MAXIMUM SURFACE
TEMPERATURE CLASS OF IGNITION TEMPERATURE OF
TEMPERATURE OF ELECTRICAL
ELECTRICAL APPARATUS GAS OR VAPOUR
APPARATUS
T1 450°C >450°C
T2 300°C >300°C<450°C
T3 200°C >200°C<300°C
T4 135°C >135°C<200°C
T5 100°C >100°C<200°C
T6 85°C >85°C<100°C

If the marking of the electrical apparatus does not include an ambient temperature range, the apparatus is only for use within an
ambient temperature range from -20°C to +40°C.

6.6.Apparatus selection according to apparatus grouping

The grouping of gases and vapours are classified into Group I and Group II categories. Group I is relevant to atmospheres containing
firedamp (a mixture of gases, composed mostly of methane,

Group II is intended for use in all other places with potentially explosive atmospheres. Group II electrical apparatus with types of
protection 'd' and 'i' are further sub-divided into apparatus group IIA, IIB or IIC. Electrical apparatus with type of protection 'n' may also
be sub-divided if it contains certain devices or components.

GAS / VAPOUR SUB-DIVISION APPARATUS SUB-GROUP PERMITTED


IIA (typical gas propane) IIA, IIB or IIC
IIB (typical gas ethylene) IIB or IIC
IIC (typical gases acetylene and hydrogen) IIC

More Information Regarding Of Apparatus Groups;

Devices which are intended for use in potentially explosive atmospheres are divided into two groups. Cf: IEC Standard 60079-0:20

Group I: Electrical operating facilities for mine workings susceptible to firedamp


Group II: Electrical operating facilities for use in all other potentially explosive areas with the exception of mine workings susceptible to
firedamp

Group II is divided into sub-groups IIA, IIB and IIC. The letter indicates the maximum experimental safe gap (maximum width of the gap
on a flashback arrester through which ignition cannot be transmitted). This depends on the explosive material. The degree of danger
increases from A to C.

IIA IIB IIC


sub-group IIA for example town gas, hydrogen sulphide sub-group IIC includes hydrogen,
covers diesel, petrol, ethane, and ethylene for example acetylene and carbon
methane and carbon monoxide. belong in sub-group IIB. disulphide.

Group III stands for electrical operating facilities for potentially explosive dust atmospheres.

IIIA IIIB IIIC


combustible suspended non-conductive dust conductive dust
particles

7.Device Category
The Device Category is determined depending on the corresponding potentially explosive Zone in which a device is to be used.

Categories in Group I:
M1: high degree of safety, safe even if two independent faults occur
M2: high degree of safety

Categories in Group II:


1 : very high degree of safety
2 : high degree of safety
3 : normal degree of safety

Device Avoidance of effective Presence of potentially


Degree of safety Approved for Zone
Category sources of ignition explosive atmosphere
2 Seldom or for short
3 In normal use Normal
22 periods
Including in the event 1, 2
2 High Occasionally
of normal faults 21, 22
Including in the event 0, 1, 2 For long periods,
1 Very high
of infrequent faults 20, 21, 22 constantly or frequently
As an example: For use in Zone 1 of Group II, a device must be used which belongs at least to Category 2, or preferably Cat.1.

43
Ex
Technical Information
8.Equipment Protection Level (EPL)
In accordance with IEC Standard 60079-0 (2007), devices for potentially explosive areas are divided into three protection levels (for
devices in mine workings susceptible to firedamp, two protection levels are laid down):

EPL Ga or Da: device with "very high" protection level for use in potentially explosive areas, in the normal operation of which,
foreseeable or infrequent faults/malfunctions represent no danger of ignition.
EPL Gb or Db: device with "high" protection level for use in potentially explosive areas, in the normal operation of which, foreseeable
or infrequent faults/malfunctions represent no danger of ignition.
EPL Gc or Dc: device with "increased" protection level for use in potentially explosive areas, in the normal operation of which, no
danger of ignition exists and which is equipped with various additional protective measures which guarantee, in the event of
commonly foreseeable faults in the device, that no danger of ignition exists.
The letters "G" and "D" determine whether the device is suitable for potentially explosive areas due to gas (G) or for areas with
combustible dust (D).
Devices for mine workings susceptible to firedamp:
EPL Ma: device with "very high" protection level for installation in mine workings susceptible to firedamp which guarantees the
necessary degree of safety, with which in normal operation, foreseeable or infrequent faults/malfunctions represent no danger of
ignition, even if the device is still in operation when the gas escape occurs.
EPL Mb: device with "high" protection level for installation in mine workings susceptible to firedamp which guarantees the necessary
degree of safety, with which in normal operation, foreseeable or infrequent faults/malfunctions represent no danger of ignition in the
time between when the gas escape occurs and the device is switched off.
The areas of application of operating facilities of a given category, or alternatively of a given EPL in the corresponding potentially
explosive area, is shown in the table.

Category EPL Zone


Gas
1G Ga 0,1,2
2G Gb 1,2
3G Gc 2
Dust
1D Da 20,21,22
2D Db 21,22
3D Dc 22
mine workings susceptible to firedamp
M1 Ma permanent using
M2 Mb stopping in ex atmosphere

IP Classification Codes
Basis of IP Rating System
International Standard IEC 60529 outlines an international classification system that describes the sealing characteristics of electrical
equipment. The classification system defines the level of protection provided by enclosures to prevent the ingress of foreign objects
and moisture into the electrical equipment. The classification system uses the "IP" code, or "Ingress Protection" code, to define the
level of seal. The IP code uses a system of two numerical digits to define the level of both foreign object and moisture protection.
Although the IP classification is primarily used for establishing the level of seal in electrical equipment, it is adapted herein for
determining the level of seal in passive electrical components.
Degrees of Protection (Foreign Bodies) - 1st Digit
The first digit of the IP code indicates the degree of protection against solid foreign objects from entering the electrical device. The
table below outlines the level of protection against foreign objects for each level.
Degrees of Protection (Moisture) - 2nd Digit
The second digit of the IP code indicates the degree of protection against the ingress of various forms of moisture (e.g. drip, spray,
submersion, etc.) into the component. Tests to determine the level of protection are carried out with fresh water and do not take into
account the use of solvents.

Foreign Bodies Moisture


IP Level 1st IP Level 2nd
Description of Protection Level Description of Protection Level
Digit Digit
0 Not protected 0 Not protected
Protected against solid foreign objects of 50 mm
1 1 Protected against vertically falling water drops
diameter and greater - back of hand
Protected against solid foreign objects of 12,5 Protected against vertically falling water drops
2 2
mm diameter and greater / finger when enclosure is tilted up to 15°
Protected against solid foreign objects of2,5 mm Protected against water sprayed at an angle up
3 3
diameter and greater / tool to 60 ° on either side of the vertical
Protected against solid foreign objects of1,0 mm Protected against water splashed against the
4 4
diameter and greater / wire component from any direction
Protected from the amount ofdust that would Protected against water projected in jets from
5 5
interfere with normal operation /wire any direction
Protected against water projected in powerful
6 Dust tight / wire 6 jets from any direction
Protected against temporary immersion in
7 water
Protected against continuous immersion in
8 water, or as specified by the user

Example of an IP code

IP 3 4 A component with this IP code indicates that a component is


Code letters protected against ingress of solid foreign objects having a diameter
1st digit of 2,5 mm and greater; and is protected against harmful effects due
2nd digit to water splashed against the component from any direction.

44
Size Equivalent
Thread
PARALEL THREAD
Pg Thread to DIN 40430 Code (P)
Size Pitch (mm) Major Diameter (mm) Minor Diameter (mm) Thread Angle * Max. Ø Clerance Diameter
PG 7 1,270 12,5 11,28 80° 12,7
PG 9 1,410 15,2 13,86 80° 15,4
PG 11 1,410 18,6 17,26 80° 18,8
PG 13,5 1,410 20,4 19,06 80° 20,7
PG 16 1,410 22,5 21,16 80° 22,8
PG 21 1,588 28,3 26,78 80° 28,6
PG 29 1,588 37,0 35,48 80° 37,4
PG 36 1,588 47,0 45,48 80° 47,5
PG 42 1,588 54,0 52,48 80° 54,5
PG 48 1,588 59,3 57,78 80° 59,8
Pipe Thread to ISO 228/1 Code (C)
Number Of Threads * Max. Ø Clerance
Size Pitch (mm) Major Diameter (mm) Minor Diameter (mm) Thread Angle
(per inch.) Z Diameter
3/8" 1,337 16,662 14,95 19 55° 17,0
1/2" 1,814 20,955 18,631 14 55° 21,3
3/4" 1,814 26,441 24,117 14 55° 26,8
1" 2,309 33,249 30,291 11 55° 33,7
1 1/4" 2,309 41,910 38,952 11 55° 42,4
1 1/2" 2,309 47,803 44,845 11 55° 48,3
2" 2,309 59,614 56,656 11 55° 60,2
2 1/2" 2,309 75,184 72,226 11 55° 75,7
3" 2,309 87,884 84,926 11 55° 88,5
4" 2,309 113,030 110,072 11 55° 114,0
NPSM Thread to ANSI ASME B1.20.1 Code (N)
Number Of Threads
Size Pitch (mm) Major Diameter (mm) Thread Angle * Max. Ø Clerance Diameter
(per inch.) Z
3/8" 1,411 17,140 18 60° 17,7
1/2" 1,814 21,340 14 60° 21,8
3/4" 1,814 26,670 14 60° 27,2
1" 2,209 33,400 11,5 60° 33,9
1 1/4" 2,209 42,160 11,5 60° 42,7
1 1/2" 2,209 48,260 11,5 60° 48,8
2" 2,209 60,325 11,5 60° 60,8
2 1/2" 3,175 73,020 8 60° 73,5
3" 3,175 88,900 8 60° 89,4
4" 3,175 114.30 8 60° 114,8

TAPERED THREAD 1.4722


GAS thread to UNI ISO 7/1 Code (G)
Number Of Threads * Max. Ø Clerance
Size Pitch (mm) Major Diameter (mm) Minor Diameter (mm) Thread Angle
(per inch.) Z Diameter
3/8" 1,337 16,662 14,95 19 55° 17,2
1/2" 1,814 20,955 18,631 14 55° 21,5
3/4" 1,814 26,441 24,117 14 55° 26,9
1" 2,309 33,249 30,291 11 55° 33,8
1 1/4" 2,309 41,910 38,952 11 55° 42,4
1 1/2" 2,309 47,803 44,845 11 55° 48,3
2" 2,309 59,614 56,656 11 55° 60,1
2 1/2" 2,309 75,184 72,226 11 55° 75,7
3" 2,309 87,884 84,926 11 55° 88,4
4" 2,309 113,030 110,072 11 55° 114,0
GAS GK Thread to UNI 6125 Code (K)
Number Of Threads * Max. Ø Clerance
Size Pitch (mm) Major Diameter (mm) Minor Diameter (mm) Thread Angle
(per inch.) Z Diameter
3/8" 1,337 16,662 14,95 19 55° 17,2
1/2" 1,814 20,955 18,631 14 55° 21,5
3/4" 1,814 26,441 24,117 14 55° 26,9
1" 2,309 33,249 30,291 11 55° 33,8
1 1/4" 2,309 41,910 38,952 11 55° 42,4
1 1/2" 2,309 47,803 44,845 11 55° 48,3
2" 2,309 59,614 56,656 11 55° 60,1
2 1/2" 2,309 75,184 72,226 11 55° 75,7
3" 2,309 87,884 84,926 11 55° 88,4
4" 2,309 113,030 110,072 11 55° 114,0
* Valid for non threaded holes. Not lover than major diameter or rod diameter

45