Unpack the V7 PROFIBUS-DP Option and verify that all components are present and undamaged. Part V7 PROFIBUS-DP Option Card Ring Kit Mounting Bracket M38 Screw 6 Ground Wire (150mm) 8.5 Ground Wire (220mm) 12.5 Ground Wire (320mm) Installation Guide (IG.V7.12) Qty. 1 1 1 1 1 1 1
Profibus Cable Connector
S2 S1
CN1 - Modular Plug CN3 - Modular Plug RJ45 Female RJ45 Male
CN1 Connector
Back Front
Connect power to the drive and verify that the drive functions correctly. This includes running the drive from the operator keypad. Refer to the V7 Technical Manual, TM.V7.01, for information on connecting and operating the drive. Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level.
Ground Wires
E E
E
Remove the CN2 protective cover by carefully clipping the three tabs
Option mounting bracket Align hole in mounting bracket with nib on front of the V7 drive Secure mounting bracket to V7 drive with M3x8 screw
CN2 Cover
Prepare the drive for the V7 PROFIBUS-DP Option. Remove the V7 operator keypad and terminal cover. Remove the plastic protective cover from over the CN2 connector and install the option mounting bracket provided on to the drive.
Connect the ground wire provided to the ground connector on the back of the V7 PROFIBUS-DP Option. Mount the V7 PROFIBUS-DP Option onto the drive Align the CN1 connector on the back of the option with its mating CN2 connector on the front of the drive. Simultaneously align the CN3 connector, the male RJ45 connector, on the back of the option with the CN1 connector, the female RJ45 connector, on the front of the drive. Align the tabs on the option with their corresponding slots on the front of the drive. Press the option and the drive together until the tabs lock into their associated slots. Secure the option to the V7 drive by tightening the locking screw at the topcenter of the option. Connect the ground wire from the V7 PROFIBUS-DP Option to ground terminal on the V7 drive. Reinstall the operator keypad and all drive covers.
E
Tab
Slot
CN1 - CN2
Tab
Slot
Yaskawa Electric America, Inc www.drives.com IG.V7.12, Page 1 of 4 Date: 07/01/04, Rev: 04-07
Connect the V7 to the PROFIBUS-DP communication network. Determine the type of connector on the V7 PROFIBUS-DP Option. Connector Style A is a modified Phoenix pluggable connector. The modification can be seen on the back of the connector as a small circuit board. Connector Style B is a standard, unmodified Phoenix pluggable connector.
Connector Style A
Connector Style B
1 2 3 4 5 6
1 2 3 4 5 6
Set the node address Set the node address for the drive setting the 10s digit with S2 and the 1s digit with S1. All devices on the network must have unique node addresses. Check the network layout to verify that the node address selected is unique and falls between 3 99. Node addresses 0 and 1 are typically reserved for master controllers. Node address 2 is typically reserved for diagnostic equipment. Address = (Switch 2 x 10) + (Switch 1 x 1) Example: Set node address to 15 Set address switch 2 to "1 Set address switch 1 to "5"
901
23
S2
901
23
7 8
Set network termination If this drive is either the first or the last device on the network, including any PLC and/or PROFIBUS-DP Master, and active termination is not used, set the termination resistor switch to ON. If this device is not the first or last device on the network or active termination is used, set the termination resistor switch to OFF. Active termination is the recommended termination method and is required for networks operating above 1.5Mbps. Active termination will eliminate the possibility of network failure due to the removal of a device with termination set to ON. The Siemens PROFIBUS Terminator part number is 6ES7 9720DA00-0AA0.
OFF
ON
Secure the V7 PROFIBUS-DP Option to the drive by tightening the recessed screw located at the top center of the option. Configure the PROFIBUS network for the drive. Refer to the documentation included with the PROFIBUS configuration utility supplied with the PROFIBUSDP Master controller. Apply power to the drive and verify that the diagnostic LEDs on the front of the V7 PROFIBUS-DP Option are in their correct state. LED Display PWR Solid Green COM Solid Green ERR OFF WD Flashing Green
Content Normal
4 56
S1
Cause
7 8
4 56
Yaskawa Electric America, Inc www.drives.com IG.V7.12, Page 2 of 4 Date: 07/01/04, Rev: 04-07
Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the drive to be completely discharged. Measure the DC BUS voltage and verify that it is at a safe level. Reinstall the operator keypad and terminal cover. Set parameters n003, n004 and n035 to their appropriate values Addr Param Function Data 0 103h n003 Operation Method Selection 1 2 3 0 1 2 3 104h n004 Reference Selection 4 5 6 7 8 9 0 123h n035 Frequency Reference Unit Selection 1 2-39 40-3999 LED Status Indicators and Diagnostics LED Display PWR COM ERR WD Content Cause Power is not being fed from the drive. OFF OFF OFF OFF Power OFF Power is not being provided to the option unit due to poor option unit connection. Option unit CPU error. Error in Drive unit. Counter measures Check the main circuit wiring on the drive. Cycle drive power. Turn of the drive power. Check the option unit connection to the drive. Cycle drive power. Cycle drive power. Replace option unit if fault persists. Cycle drive power. Replace drive if fault persists. Check whether the address set in the PROFIBUS-DP Master differs from the address of the option unit. Check that the master is functioning properly. Check that the termination resistor is correctly connected to the communication line. Check whether the communication line is correctly connected (disconnected or poor connection). Check that the communication line is separated from the main power line. Check whether the address is duplicated with any other devices within the PROFIBUS-DP network. Wait for WD LED to start flashing. Terminal Serial Communication +/- Limits - Description Operator keypad 1 Default
OFF OFF
Solid Green
OFF
Flashing Red
Solid Green
Com Error
A fault has occurred rendering communication impossible. Option unit under initialization Normal communication possible.
Yaskawa Electric America, Inc www.drives.com IG.V7.12, Page 3 of 4 Date: 07/01/04, Rev: 04-07
Copies of this Installation Guide along with all technical manuals in pdf format and support files may be obtained from either the CD supplied with the drive or from www.drives.com . Printed copies of any Yaskawa manuals may be obtained by contacting the nearest Yaskawa office. Information on PROFIBUS and PROFIBUS-DP may be obtained from either the PROFIBUS Organization or at www.profibus.com . Reference documents: V7 Technical Manual TM.V7.01 V7 MODBUS Technical Manual TM.V7.11 V7 PROFIBUS-DP Option Technical Manual TM.V7.12 V7 PROFIBUS-DP Option Installation Guide IG.V7.12 MODBUS is a registered trademark of Schneider Automation, Inc. PROFIBUS and PROFIBUS-DP are registered trademarks of PROFIBUS Nutzerorganisation e.V.
YASKAWA ELECTRIC AMERICA, INC. Drives Division 16555 W. Ryerson Rd., New Berlin, WI 53151, U.S.A. Phone: (800) YASKAWA (800-927-5292) Fax: (262) 782-3418 Internet: http://www.drives.com YASKAWA ELECTRIC AMERICA, INC. Chicago-Corporate Headquarters 2121 Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: (800) YASKAWA (800-927-5292) Fax: (847) 887-7310 Internet: http://www.yaskawa.com MOTOMAN INC. 805 Liberty Lane, West Carrollton, OH 45449, U.S.A. Phone: (937) 847-6200 Fax: (937) 847-6277 Internet: http://www.motoman.com YASKAWA ELECTRIC CORPORATION New Pier Takeshiba South Tower, 1-16-1, Kaigan, Minatoku, Tokyo, 105-0022, Japan Phone: 81-3-5402-4511 Fax: 81-3-5402-4580 Internet: http://www.yaskawa.co.jp YASKAWA ELETRICO DO BRASIL COMERCIO LTDA. Avenida Fagundes Filho, 620 Bairro Saude Sao Paolo-SP, Brasil CEP: 04304-000 Phone: 55-11-5071-2552 Fax: 55-11-5581-8795 Internet: http://www.yaskawa.com.br YASKAWA ELECTRIC EUROPE GmbH Am Kronberger Hang 2, 65824 Schwalbach, Germany Phone: 49-6196-569-300 Fax: 49-6196-888-301 MOTOMAN ROBOTICS AB Box 504 S38525, Torsas, Sweden Phone: 46-486-48800 Fax: 46-486-41410 MOTOMAN ROBOTEC GmbH Kammerfeldstrabe 1, 85391 Allershausen, Germany Phone: 49-8166-900 Fax: 49-8166-9039 YASKAWA ELECTRIC UK LTD. 1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, Scotland, United Kingdom Phone: 44-12-3673-5000 Fax: 44-12-3645-8182
YASKAWA ELECTRIC KOREA CORPORATION Paik Nam Bldg. 901 188-3, 1-Ga Euljiro, Joong-Gu, Seoul, Korea Phone: 82-2-776-7844 Fax: 82-2-753-2639 YASKAWA ELECTRIC (SINGAPORE) PTE. LTD. Head Office: 151 Lorong Chuan, #04-01, New Tech Park Singapore 556741, Singapore Phone: 65-282-3003 Fax: 65-289-3003 TAIPEI OFFICE (AND YATEC ENGINEERING CORPORATION) 10F 146 Sung Chiang Road, Taipei, Taiwan Phone: 886-2-2563-0010 Fax: 886-2-2567-4677 YASKAWA JASON (HK) COMPANY LIMITED Rm. 2909-10, Hong Kong Plaza, 186-191 Connaught Road West, Hong Kong Phone: 852-2803-2385 Fax: 852-2547-5773 BEIJING OFFICE Room No. 301 Office Building of Beijing International Club, 21 Jianguomanwai Avenue, Beijing 100020, China Phone: 86-10-6532-1850 Fax: 86-10-6532-1851 SHANGHAI OFFICE 27 Hui He Road Shanghai 200437 China Phone: 86-21-6553-6600 Fax: 86-21-6531-4242 SHANGHAI YASKAWA-TONJI M & E CO., LTD. 27 Hui He Road Shanghai 200437 China Phone: 86-21-6533-2828 Fax: 86-21-6553-6677 BEIJING YASKAWA BEIKE AUTOMATION ENGINEERING CO., LTD. 30 Xue Yuan Road, Haidian, Beijing 100083 China Phone: 86-10-6232-9943 Fax: 86-10-6234-5002 SHOUGANG MOTOMAN ROBOT CO., LTD. 7, Yongchang-North Street, Beijing Economic & Technological Development Area, Beijing 100076 China Phone: 86-10-6788-0551 Fax: 86-10-6788-2878 YEA, TAICHUNG OFFICE IN TAIWAIN B1, 6F, No.51, Section 2, Kung-Yi Road, Taichung City, Taiwan, R.O.C. Phone: 886-4-2320-2227 Fax:886-4-2320-2239
Yaskawa Electric America, Inc www.drives.com IG.V7.12, Page 4 of 4 Date: 07/01/04, Rev: 04-07