In addition to the motor power and the starter type (direct, reversing, star-delta…),
4 main criteria have to be taken into account when choosing a motor starter:
b the operational voltage,
b the type of thermal protection, electro-mechanical or electronical,
b the type of magnetic protection, according to the switchboard’s Isc,
b the type of installation, according to the required availability level.
Operational voltage
Network’s operational voltage is a decisive parameter in the choice of motor protection.
Indeed, the operational voltage will have an impact on the device’s performances
and the installation constraints.
For instance, the voltage will influence:
b the breaking performances,
b the safety areas.
Motor protection
Protecting the motors to extend their lifetime
b Overheating in electrical motors is caused by copper and ferro-magnetic losses:
v the current I is proportional to the motor’s load. Copper losses are proportional
DD405318_SE
electrical parameters.
b Electromechanical thermal relays protect the motor against overloads.
b Electronical relays protect the motor against overloads, on the basis of very
sophisticated and highly accurate thermal patterns.
v These relays are able to make out several cases of motor overload, and to
transmit the information, thus allowing the operator to have a better understanding
of the true nature of the problem,
v These relays report for many complementary parameters, providing useful
informations to the operator, therefore giving him the opportunity to avoid motor
stops, or to re-start quickly if a stop has occurred.
v Examples:
- motor under-load can be the signal of a pump cavitation,
- phase inversion can be the indication of a maintenance error, that should be hard
to diagnose without that sign.
v In addition to the observation of currents, the electronical relays can monitor
the voltage, and consequently the power and the power factor. They can also watch
the leakage currents and measure the actual coil temperature whenever it has a
built-in sensor.
DD405342_SE
327
Circuit breaker
PB103219-14
NS80
GV2-GV3
GV7
LC1D
LC1F
LRD
Relay
Contactors Feeder
328
Aims of coordination
In case of a fault, the coordination’s purposes are:
b to protect of the people and the equipment,
b to permit continuity of service,
b to reduce maintenance costs (manpower and replacement equipment).
Type 1 coordination
Types of coordination as per IEC 60947-4-1
b Type 1 coordination: basic solution
v no continuity of service,
DD383429
Type 2 coordination
DD383430
Total coordination
329
b Advantages
v Wide choice of solutions.
v Suitable for all types of diagrams.
v Manual or automatic reset following a thermal fault.
v 2 starting classes (10 and 20).
v Type 2 coordination.
v Segregation of thermal and magnetic faults.
b Magnetic circuit-breaker + contactor + thermal protection
v For manufacturing and continuous and semi-continuous processes.
b Switch-disconnector fuse + contactor + thermal protection
v For all types of machines.
v For manufacturing and continuous and semi-continuous processes.
330
Presentation
The Spacial SFM compartmentalised enclosures system used for MCC are based
on the Spacial SF range.
They offer the same functions:
b Different possible configurations, combined side-by-side or back-to-back.
b The built-in partial doors and panels design allow to meet the required degree
of protection.
And the same advantages:
b Save time through all assembly phases.
b Enclosure robustness.
A distribution system
Vertical busbars positioned in a lateral compartment and horizontal busbars are
used to distribute electricity throughout the switchboard.
331
Type tested
Spacial SFM compartmentalised is totally type-tested in accordance with
IEC 61439-1&2.
b Certified by independant lab.
b As well as by a permanent control in Schneider Electric test laboratories.
b Type-tests are carried out:
v temperature-rise limit,
v dielectric properties,
v short-circuit withstand,
v effectiveness of the protective circuit,
v conformity of the clearance and creepage distances,
v mechanical operation,
v degree of protection.
Partitioning
PB502988-62
Form 2b
b Terminals for external conductors separated
from busbars.
b The functional units and the terminals are
separated from the busbars.
Form 3b
Separation of busbars from the functional units and
separation of all functional units from one another.
Separation of the terminals for external conductors
from the functional units, but not from each other.
b Protection against contact with live parts.
b Reduction in the risk of faults between the functional
units (propagation of electrical arcs, etc.).
Form 4b
Terminals for external conductors not in the same
compartment as the associated functional unit,
but in individual, separate, enclosed protected
spaces or compartments.
332
General data
PB502999-71
Applications MCC
Standards IEC 61439-1&2
Internal arc No
Seismic 3G
Installation Indoor
Mechanical data
Cable inlet Top / Bottom
Access Front / Rear Side
IP 54
IK 10
Form 4b type 7
Withdrability FFF
Dimensions H 2000 / W 600 & 800 / D 600 & 800
Color RAL 7035
Electrical data
Insulation voltage (Ui) 1000 V
Voltage rating(Ue) 415 V
Coordination Type 2
Frequency 50/60 Hz
Auxiliary circuit voltage 230 V
Degree of pollution 3
Rated current (IP>31) 2500 A (with Copper & Linergy)
Short circuit (Icw - 1s) 85 kA
333
The plain mounting plates can be used to install all the devices making up an
MCC motor starter on a single support.
Easy installation
Motor feeders can be prepared on a bench making the cut-outs needed.
PB502990-58
The quick-fixing system allows to hold the mounting plate during device installation
and wiring. The mounting plate can be fixed on the side partitions in adjustable depth
with a pitch of 50 mm.
Switchboard upgradeability
b Functional units with form partitioning 3b and 4b.
PB502991-66
Fixing kit
Mounting plate
334
70 - 15 28 GV7-RS40 LC1D40 3M 6M
70 - 18.5 34 GV7-RS40 LC1D50 3M 6M
70 - 22 40 GV7-RS50 LC1D80 3M 6M
70 - 30 55 GV7-RS80 LC1D80 3M 6M
70 - 37 66 GV7-RS80 LC1D80 3M 6M
70 - 45 80 GV7-RS100 LC1D115 4M 9M
70 - 55 100 GV7-RS150 LC1D150 6M 9M
70 - 75 135 GV7-RS150 LC1F185 9M 12M
70 - 90 160 GV7-RS220 LC1F225 9M 12M
70 - 110 200 GV7-RS220 LC1F265 9M 12M
(1) 2xLC1-D for reversing
335
336
337
35 85 15 28 GV2-P32 3xLC1D32 4M
70 - 15 28 GV7-RS40 3xLC1D80 9M
70 - 18.5 34 GV7-RS40 3xLC1D50 9M
70 - 22 40 GV7-RS50 3xLC1D80 9M
70 - 30 55 GV7-RS80 3xLC1D80 9M
70 - 45 80 GV7-RS100 3xLC1D115 12M
70 - 55 100 GV7-RS150 3xLC1D150 12M
70 - 75 135 GV7-RS150 3xLC1F185 16M
70 - 90 160 GV7-RS220 3xLC1F225 16M
70 - 110 200 GV7-RS220 3xLC1F265 16M
338
339
340
Linergy LGYE-LGY
a breakthrough in busbar systems
Discover how
Linergy LGYE-LGY
switchboards in your
hands.
341
Innovative technology
from an energy expert you can trust
Patented Linergy LGYE-LGY is backed by Schneider Electric’s decades
of expertise in electrical distribution systems and is certified IEC 61439-2
compliant by ASEFA.
PB502994-72
342
A revolutionary design
for greater efficiency
The Linergy line now includes horizontal busbars, helping you achieve
better electrical switchboard performance while optimizing busbar layout
and facilitating assembly.
343
IMG_0116-13
PD384627-13
IMG_0121-13
IMG_0119-14
PD384625-25
PD384626-28
PD384628
344
345
Busbar calculation
The following table indicates:
b the catalogue numbers of the bars to be used, depending on the permissible
current level in the busbars,
b the number of supports required, depending on the rated short-time withstand
current (Icw in kA rms / 1 second).
Busbar selection
Linergy busbars, L = 1670 mm
DB300923
DD384148b
DD384149b
DD384151b
346
Dd381233-LIN-7
DD381234-LIN-7
DD381235-LIN-7
DD381236-LIN-7
DD381237-LIN_7
630 A 800 A 1000 A 1250 A 1600 A
Permissible current for an ambient temp. of IP y 31 680 A 840 A 1040 A 1290 A 1650 A
35°C around the switchboard IP > 31 590 A 760 A 950 A 1170 A 1480 A
Number of profiles per phase 1
Cat. no. 04502 04503 04504 04505 04506
Busbar supports
DD380741-LIN
DD385383-EN
387.5 mm
max. Fixed support 04651
Characteristics An end stop must be fitted on the bottom support:
DD380742-LIN-12
Number depending y 25 3
700 mm
max.
on Icw y 30 - 3
(kA rms/1 s) y 40 - 3
y 50 - 4
y 60 - 5
y 65 - 5
y 75 - 7
y 85 - 8
Cat. no. 04651 (set of 2 upright adapters NSYSFPA and set of 2 40 mm universal cross-rail
NSYSUCR40200 for installation in Spacial SF busbar chamber)
Connections to the Linergy BS horizontal busbar
DD385409
y 1600 A
Characteristics Supplied with mounting hardware.
Reference include 1 connection only. Order 1 connection per phase.
Cat. no. 04602 (vertical connection)
04603 (vertical shifted connection) (1)
(1) Dedicated connection 04603 for Linergy LGYE busbar in 150 mm busbar chamber with horizontal jointing.
347
DD385352_1
DD385351_1
DD385350_1
DD385355_1
DD385354_1
DD385349_1
DD385353_1
60 60 60 60 60
100 100
23 23 23 23 23
31 31
DD381225-LIN
DB300925
Characteristics 2 fixed supports for Spacial SF wide cublicle are compulsory according compartment depth (400 or 500 mm).
1 fixed support for Spacial SF 300/400 wide chamber are compulsory. Fixed directly on framework.
If more supports are needed, add free supports.
In cubicle SFM: Number of y 15 2
W600/800 supports y 25 2
Busbar supports depending y 30 2
75 mm distance on Icw
between (kA rms/1 s) y 40 - 2
y 50 - 2
y 60 - 2+1 2
y 65 - 2+1
y 75 - 2+1
y 85 - 2+1
Cat. no. Fixed support D400 NSYMBHS4
D500 NSYMBHS5
Cat. no. Free support 04662
In busbar Number of y 15 1
chamber SF: supports y 25 1
W300/400 depending y 30 1
Busbar supports on Icw
y 40 1
75 mm distance (kA rms/1 s)
between y 50 1
y 60 1
y 65 1+1
y 75 1+1
y 85 1+1
Cat. no. Fixed support D600 NSYBHS600 NSYBHS600
D800 NSYBHS800 NSYBHS800
Cat. no. Free support 04662 04662
Joints
Up to 1600 A Up to 2500 A
630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A
DD385380b
DD385382b
DD385381b
04620 04624
Cat. no. 3 x 04620 (3P) 3 x 04621 (3P)
4 x 04620 + 04624 (4P) 4 x 04621 + 04624 (4P)
Note Reference 04624 is compulsory when installing jointed Linergy LGYE 4P busbars and must be fitted where the
frames meet. When installed at the bottom of a cubicle, the busbar must be partitioned.
Note: for accessories, see page 351.
348
Flat busbars
Up to 1600 A Up to 2500 A
In Spacial SF busbar chamber W300 D500/600/800 W300 D500/600/800
Pre-slotted copper, DD381505-LIN-EN
1675 mm length
Permissible current for an ambient IP > 31 750 A 900 A 1250 A 1600 A 1080 A 1250 A 1600 A 1850 A 2000 A 2500 A
temp. of 35°C around the switchboard
Busbar cross-section (mm) 60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10
Number of busbars per phase 1 2 1 2
Cat. no. 04516 04518 04516 04518 04525 04526 04528 04525 04526 04528
Busbar supports
100 mm
Description 3 fixed supports are compulsory to hold the busbar in position.
DD385370
max.
If more than 3 supports are needed, use free supports (in addition).
The bottom wedge support is used to place the busbar and ensure it is in the correct position.
350 mm
It does not count as a busbar support.
max.
350 mm
max. Number y 15 3 3
of supports y 25 3+2 3 3
350 mm
depending y 30 3+2 3+2 3
max.
on Icw
(kA rms/1 s) y 40 3+4 3+2 3+2
350 mm
y 50 3+4 3+2
max.
y 60 3+4 3+2
y 65 3+4 3+2
100 mm y 75 3+6 3+4
max.
y 85 3+4
Cat. no. of Spacial SF W300, D600 NSYBVS600 (fixed) + 04662 (free) + NSYAS600 (end stop support)
supports busbar chamber W300, D800 NSYBVS800 (fixed) + 04662 (free) + NSYAS800 (end stop support)
depending 75 mm distance
on distance between bars
between bars
and busbar
chamber
depth
DD385384
Characteristics For a busbar with 75 mm distance References 04636, 04637 are supplied individually:
between bars, the bars must be 1 connection per phase.
completely covered. Reference 04642 consists of 2 M8 x 140 screws which
Staggered assembly points between can replace the original M8 x 120 screws.
one bar and the next, to maintain the
necessary clearance distances.(1)
DD383399
1 vertical bar per 2 vertical bars 1 vertical bar per phase 2 vertical bars per phase
phase per phase
60 x 5 80 x 5 60 x 5 80 x 5 50 x 10 60 x 10 80 x 10 50 x 10 60 x 10 80 x 10
Cat. no. of the connection y 80 mm 04645 04636 04637 04637
piece depending on
horizontal busbar size
(1) Drill hole dimensions for 5 mm thick horizontal busbars. Drill hole dimensions for 10 mm thick horizontal busbars.
DD385424-EN
12.5
DD384320-LIN-EN
50/60/80/100
35 35 12.5
55 11 55
75 75
111 111
60
80
100
349
Flat busbars
Installation in Spacial SFM compartmentalised Hasta 1600 A Hasta 2500 A
Copper bar, 2000 mm length
Permissible current for an ambient temp. of 35°C 750 A 900 A 1250 A 1600 A 1600 A 1850 A 2000 A 2500 A
around the switchboard
Busbar cross-section (mm) 60 x 5 80 x 5 60 x 5 80 x 5 80 x 10 50 x 10 60 x 10 80 x 10
Number of busbars per phase 1 1 2 2 1 2 2 2
Total number of vertical modules (50 mm) 3
Nº cat. 04536 04538 04536 04538 04548 04545 04546 04548
Busbar supports
DD381225-LIN-15
DB300927
DB300926
In cubicle SFM: Characteristics 2 fixed supports for Spacial SF wide cublicle are compulsory according compartment depth (400 or 500 mm).
W600/800 with 1 fixed support for Spacial SF 300/400 wide chamber are compulsory. Fixed directly on framework.
75 mm distance If more supports are needed, add free supports.
between bars Number of y 15 2
supports y 25 2+1 2
depending on Icw y 30 2+1 2
(kA rms/1 s)
y 40 2+1 2
y 50 - 2+1 2
y 60 - 2+1
y 65 - 2+1
y 75 - 2+2 2+1
y 85 - - 2+1
Cat. no. Fixed support NSYMBHS4 (D400)
or NSYMBHS5 (D500)
Free support 04662
In busbar Number y 30 1
chamber SF: depending on Icw y 50 1+1 1
W300/400 with (kA rms/1 s) y 85 - 2
75 mm distance
Cat. no. Fixed support NSYBHS600 (D600) NSYBHS600 (D600)
between bars
depending on or NSYBHS800 (D800) or NSYBHS800 (D800)
depth Free support 04662 04662
Joints
Installation in Spacial SFP Up to 1600 A Up to 2500 A
1 vertical bar per phase 2 vertical bars per phase 1 vert. bar 2 vertical bars per phase
per phase
Busbar cross-section (mm) 60 x 5 80 x 5 60 x 5 80 x 5 80 x 10 50 x 10 60 x 10 80 x 10
Sliding joints with self-breaking lock nut 04640 04641
DD385385b
DD385386b
Cat. no. 04640 04641 04640 04641 04641 04640 04640 04641
Note: When installed at the bottom of a cubicle, the busbar must be partitioned.
350
Accessories
DD381218-LIN-15
DD381219-LIN-15
DD381222-LIN-10
Linergy screw Plain washer Identification
Linergy screw Characteristics Sold in lots of 20: 20 screws + 20 nuts + 20 contact washers, class 8.8.
The screws slide into the profile and are then locked in the desired position.
Cat. no. 25 mm length see the table "Connections on Linergy LGYE & LGY" below
39 mm length
Steel plain Characteristics M8 sold in lots of 20.
washers Cat. no. ext. Ø20 mm 04772
ext. Ø24 mm 04773
ext. Ø28 mm 04774
Brass plain Characteristics M8 sold in lots of 20 for connection of y 25 mm2 lugs to Linergy.
washers Cat. no. ext. Ø20 mm 04775
Identification Characteristics 12 clip-on supports + N, L1, L2, L3, PE, PEN labels.
Cat. no. 04794
Characteristics Linergy LGYE busbar screw plate kit after sales service.
Cat. no. 01130
M8 bolts
DD380737b
Torque nuts
DD380735b
20 M8 Characteristics Can be used to obtain the correct tightening torque (28 Nm) recommended by then manufacturer, without
torque nuts using a torque wrench. Torque nuts may be used for all electrical connections.
Cat. no. 04759
Voltage tap-offs
DD380736b
20 M10 voltage Characteristics For small lugs (on low-current cables or measurement tap-offs), insert a conducting washer (cat. no. 04775)
tap-offs for two between the busbar and the lug.
6.35 mm tab Cat. no. 04229
connectors
351
Form 2 partitioning
Lateral partitioning Rear partitioning
DB300928
DB300929
Diagramas
300/400 600/800 300/400 600/800
DB300962
DB300963
600/800 600/800
Características b Set of 2 vertical metallic separation which guarantees good b Vertical metallic separation which guarantee good insulation of the
insulation of the sides of the compartment (IP2x). back of the compartment (IP2x).
b Top and bottom ends have knock-outs for installation of horizontal b Pre-cuts of 40 x 70 mm for cable-glands using grommets ref 01215
busbars and pre-cuts of 40 x 70 mm for cable-glands using grommets when Form 4b is required on back installation.
ref 01215 when Form 4b is required. b Direct fixing on structure of enclosure.
b Partition extension required for D800 mm.
b Direct fixing on structure of enclosure.
Nº cat. D600: NSYMSC206 W600: NSYMBC206
D800: NSYMSC206 + NSYMSC202 W800: NSYMBC208
DB300960
DB300961
Diagramas
600/800 300/400 300/400 600/800 300/400
DB300964
DB300965
600/800
352
Separation of busbars from the functional units and separation of all functional units
from one another.
Separation of the terminals for external conductors from the functional units, but not
from each other.
b protection against contact with live parts
b reduction in the risk of faults between the functional units (propagation of
electrical arcs, etc.).
Form 3 partitioning
Horizontal partitioning
DB300931
W600 W800
Characteristics b A horizontal metal partition to separate functional units from one another and guarantees insulation of the compartments (IP2x).
b It is fixed to the front uprights of the enclosure and the side partitions.
b Quick fixing system with intermediate crossbar to ensure the degree of protection of the partial doors.
b Order by multiples of 2 (2, 4, 6…).
Cat. no. D400: NSYMTR64 D400: NSYMTR84
D500: NSYMTR65 D500: NSYMTR85
353
Separation of busbars from the functional units and separation of all functional units
from one another, including the terminals for external conductors which are an
integral part of the functional unit:
b Protection against contacts with live parts and reduction in the risk of faults
between the functional units (propagation of electrical arcs, etc.).
b Form 4a: terminal for external conductors in the same compartment as the
associated.
b Form 4b: Terminals for external conductors not in the same compartment as the
associated functional unit, but in individual, separate, enclosed protected spaces
or compartments.
Form 4b boxes
DB300932
DB300933
Characteristics b Metallic plain box composed by 2 parts that can be easily installed for side or rear connection to separate the terminals for external
conductors of the functional unit.
b Quick fixing system on the side or on the back partition.
b Available in 6 heights:
Cat. no. 3M: NSYBF4B3M 4M: NSYBF4B4M 5M: NSYBF4B5M 6M: NSYBF4B6M 8M: NSYBF4B8M 9M: NSYBF4B9M
PB500864-36
354
Common characteristics
b Spacial SFM framework with compartmentalised system that can be combined
side-by-side with busbar and cable chambers.
b Receive the cover panels and partial doors IP54.
b Material: steel.
b Finish: painted with epoxy-polyester resin.
b Colour: RAL 7035 grey.
b Possibility to order it assembled or kit supply.
Compartmentalised enclosure
Assembled supply
PB500207-16 Kit supply
PB500129-7
PB500127-13
PB500128-16
W600 W800 W600 W800
Characteristics b Structure: Top and bottom frame and vertical uprights H2000 mm.
b Useful height for doors H1800 mm /36M, when are installed the top and bottom fix panels for
modularity (mandatory for installation of partial doors).
b Equipped with removable roof, external fixing rear panel and top & bottom fixed panels
(H100 mm) to allow modularity of partial doors.
b 4 dimensions available.
Cat. no. D600: NSYSF20660M D600: NSYSF20860M - -
D800: NSYSF20680M D800: NSYSF20880M
Vertical uprights H2000 mm - - NSYSFV20 NSYSFV20
Top & Bottom frame with roof - - D600: NSYSFC66 D600: NSYSFC86
D800: NSYSFC68 D800: NSYSFC88
Rear panel - - NSYBP206 NSYBP208
Fixed panels for modularty H100 mm /2M - - See table below See table below
(intermediate crossbars included)
External claddings
Front Fix panel for modularity Frontal partial doors Side panels
PB500114-17
PB500640-50
PB500637-27
355
PB500739-14
PB500129-7
PB500130-7
PB500127-13
PB500128-16
W300 W400 W300 W400
Characteristics b Structure: Top and bottom frame and vertical uprights H2000 mm.
b Equipped with removable roof, external fixing rear panel and front plain door with 4 point locking
system with handle and DB 5 mm insert.
b 4 dimensions available.
Cat. no. D600: NSYSF20360 D600: NSYSF20460 - -
D800: NSYSF20380 D800: NSYSF20480
Vertical uprights H2000 mm - - NSYSFV20 NSYSFV20
Top & Bottom frame with roof - - D600: NSYSFC36 D600: NSYSFC46
D800: NSYSFC38 D800: NSYSFC48
Rear panel - - NSYBP203 NSYBP204
Front plain door - - NSYSFD203 NSYSFD204
356
PB502578-21
PB502581-13
PB502580-12
PB500115-15
PB502579-21
PB500116-15
PB500117-15
H (mm) W (mm) D (mm) Plain 1 entry 2 entries Front kit Side kit Front kit Side kit
2000 600 600 NSYEC66 NSYEC661 NSYEC662 NSYSPF6100 NSYSPS6100 NSYSPF6200 NSYSPS6200
2000 600 800 NSYEC68 NSYEC681 NSYEC682 NSYSPF6100 NSYSPS8100 NSYSPF6200 NSYSPS8200
2000 800 600 NSYEC86 NSYEC861 NSYEC862 NSYSPF8100 NSYSPS6100 NSYSPF8200 NSYSPS6200
2000 800 800 NSYEC88 NSYEC881 NSYEC882 NSYSPF8100 NSYSPS8100 NSYSPF8200 NSYSPS8200
2000 300 600 NSYEC36 NSYEC361 - NSYSPF3100 NSYSPS6100 NSYSPF3200 NSYSPS6200
2000 300 800 - NSYEC381 - NSYSPF3100 NSYSPS8100 NSYSPF3200 NSYSPS8200
2000 400 600 NSYEC64 NSYEC461 - NSYSPF4100 NSYSPS6100 NSYSPF4200 NSYSPS6200
2000 400 800 NSYEC84 NSYEC481 - NSYSPF4100 NSYSPS8100 NSYSPF4200 NSYSPS8200
Coupling kit 4 lifting eyebolts 4 lifting brackets Earthing cable Locks for partial doors
(3)
Possibility to replace standard insert by
one from the table below (CRN range) and
NSYFELB-12
PB500217-18
DD384440-18
PB502553-12
Lifting eyebolts
Lifting brackets
For more than 3 colomuns, lenghts > 1600 mm, see Lifting bars options on
Universal Enclosures catalogue.
357
358
Type tests
1 - Static load
2 - Hoisting
3 - Axial loads of metal inserts
4 - IK code
5 - IP code
6 - Thermal stability
7 - Resistance to heat
8 - Resistance to abnormal heat and to fire
9 - Dielectric strength
10 - Protective-circuit continuity
11 - Weather resistance
12 - Corrosion resistance
13 - Marking