G4 - AGK-ALL-ALL-EG-005-FO-05 Diesel Inspection and Test Checklist
G4 - AGK-ALL-ALL-EG-005-FO-05 Diesel Inspection and Test Checklist
G4 - AGK-ALL-ALL-EG-005-FO-05 Diesel Inspection and Test Checklist
Form
Project Number:
Revision: 1
Diesel Inspection and Test
Page 1 of 3
The purpose of this document is to ensure that Aggreko’s fleet of Diesel generators are setup correctly before hand over to the site Operations
manager.
Equipment Identification
Generator No. (Site) 04 (BRAHMANGAON 100MW)
Generator Plant No. 93-3500
SMR 34
Serial No. 33169144
Engine CPL 2227
Date of manufacture 19 JUNE 07
Type P.E734C2
Alternator Serial No. X17B065711
Date of manufacture N/A
Installed Calibration
Gempac (AGC)
Engine control system
Installed Calibration
Checks Result
Transformer Site ID 01
Transformer Plant No. XASS214001-4
LV Isolator ID Q10A
Nominal Settings (GEMPAC) As per protection document
Voltage 415V
Frequency 50Hz
Current 1798A
Pre-Commissioning Tests Power 104kW
Power Factor 0.90pf
Operation mode GRID
Checks
Oil and coolant
Oil level
HT circuit coolant level
LT circuit coolant level (QSK Only)
Cables and entry
Cable entry sealed
Cables are torque to 75nM
Trim% 100%
Type MX321 R448
Generator Output Circuit Breaker As per Protection document
Long time setting – Ir 0.7
Long time delay setting– tr 2 sec @ 6x Ir
Short time setting- Isd 2
Short time delay setting–tsd 0.3 sec ON
Instantaneous setting –Inst 4
Engine Shutdown switches (Danfoss) Standard set point
Low oil pressure shutdown N/A 30PSI (2BAR)
Low coolant pressure shutdown N/A 7PSI (0.5BAR)
High coolant temperature N/A 1000C
Auxiliary supplies
Batteries / Charger Measured value
Battery volts (Range 24-28VDC) 23.9
Charger output volts (Range 24-28VDC) 27.4
Fan protection and trip test Note/GEMPAC display
Radiator fan over load F6 set to 31A
Room fan over load F7 set to 17 A
Trip F6 HT radiator fan supply Fan Tripped
Trip F7room fan supply Fan Tripped
Engine sensors Note/GEMPAC display
Push RH external emergency stops Emergency Stop
Disconnect coolant temperature wire L19 in engine JB ü High Coolant Temp
Disconnect coolant pressure wire L27 in engine JB ü Low Coolant Pressure
Disconnect oil pressure wire L31 in engine JB ü Low Oil pressure
Off/ Local/ Remote switch operational
Auto Fuel
Turn and hold switch to manual, solenoid opens
Fill Tank until High alarm lights at 85%
Fill tank until High-High alarm lights at 90% and solenoid
shuts
Shut GEMPAC
Circuit breaker and shutdown test CB Trip
down Display
Test CB close inhibit by opening low voltage isolator
N/A
on transformer.
No Load Run Checks Disconnect ESD plug located in generator CB
Emergency Stop
enclosure.
Circuit breaker in test position Trip Generator ACB with Micrologic test unit N/A CB Trip
GEMPAC in Island mode
Adjust AVR volts pot to increase volts by 10% Gen Volts high
Adjust AVR volts pot to decrease volts by 10% Gen Volts Low
Disconnect oil pressure wire L31 in engine JB N/A Oil Pressure
Increase speed to 1650RPM (55Hz) Over-speed
Job Title:
Name:
6/19/2018
Signature: X
Signe d by: Paul va n de Graa f
Date: