3G3HV-PCMA2 Voltage/Current Conversion Card (For The 3G3HV Only)
3G3HV-PCMA2 Voltage/Current Conversion Card (For The 3G3HV Only)
3G3HV-PCMA2 Voltage/Current Conversion Card (For The 3G3HV Only)
Specifications
! Caution Not following a precaution given as a “Caution” Model Input Output Output
can result in injury to people or damage to the specifications specifications accuracy
product or system. 3G3HV-PCMA2 0 to 10 V 4 to 20 mA 3%
(see note 1) (see note 2)
Items listed under caution may also have serious consequences de- Note 1. This output is proportional to the input.
pending on the circumstances, so be sure to heed these items at all 2. This refers to the accuracy of the input voltage, and
times. does not include the multi-function analog output error.
Mounting Procedure • Output Terminals
1, 2, 3... 1. Be sure to turn OFF Inverter power prior to mounting. Terminal board code No. Function
If the power is ON, wait the prescribed amount of time TC 1 4 to 20-mA output terminal
after the power is turned OFF, as indicated on the front
cover of the Inverter, and then remove the front cover. 2 Output terminal common
Make sure the charge indicator for the nearest termi- • Wire Thickness
nals is not lit.
Terminal code Wire thickness (mm2) Type of wire
2. Mount the Voltage/Current Conversion Card to the
Inverter control circuit board. TC (1, 2) Stranded wire: 0.5 to 1.25 Shielded twisted-
Align and insert the four supports on the control circuit Single wire: 0.5 to 1.25 pair wire
board into the mounting holes on the Card, and push • Solderless Terminal Sizes
the Card until it clicks into place.
For better reliability and easier wiring, we recommend using solder-
3. Make sure the 2CN connector on the Card slides less terminals for output signal and control circuit terminal wiring.
securely into the 2CN connector of the control circuit
board. d1 dia. Wire Model d2 d2
4. Connect the ground wire (E) on the Card to the E(G) thickness
ground terminal for the shielded wire on the control cir- 0.5 mm2 A1 0.5-8 WH 1.00 2.60
cuit board. 0.75 mm2 A1 0.75-8 GY 1.20 2.80
5. Connect the voltage signal input line of the Card to the
1 mm2 A1 1-8 RD 1.40 3.00
AM terminal of the control circuit terminals on the
Inverter. 1.5 mm2 A1 1.5-8 BK 1.70 3.50
6. Replace the Inverter cover once the Card is mounted (Manufacturer: Phoenix Contact)
and wired to peripheral devices.
Front View Side View d2 dia.
• Wiring Procedure for Output and Control Circuit Terminals
1, 2, 3... 1. Use a thin-slotted screwdriver to loosen the terminal
screws.
2. Insert the wire from underneath the terminal block.
3G3HV-PCMA2 3. Tighten the terminal screws firmly.
Voltage/Current
Supporting Thin-slotted screwdriver
Conversion Card
bracket Control circuit
2CN (Volt- Blade of
terminal block
age/Current screwdriver
Strip the end for
Conversion
7 mm if no sold-
Card con-
erless terminal
nector)
is used.
Control cir-
cuit board
3G3HV-PCMA2 3.5 mm
Ground ter- max.
minal for
shielded Blade thickness:
Wire
wire 0.6 mm max.
Control circuit AM (multi-function
terminals analog output)
Wiring
• Peripheral Device Wiring Example
3-phase, SYSDRIVE
200 VAC 3G3HV
(400 VAC)
L1 (R) T1 (U)
L2 (S) T2 (V)
L3 (T) T3 (W)
Measuring
Voltage/Current Conversion Card equipment
250 Ω
OMRON Corporation
Systems Components Division
14F Nissei Bldg.
Note 1. Be sure to connect the ground wire (E) of the Voltage/ 1-6-3, Osaki, Shinagawa-ku,
Current Conversion Card to the E(G) ground terminal Tokyo 141 Japan
Tel: (03)3779-9038/Fax: (03)3779-9041
for the shielded wire.
2. Install the output signal wire of the Voltage/Current Regional Headquarters
Conversion Card at least 30 cm away from the power OMRON EUROPE B.V.
supply line and other power lines. Wegalaan 67-69, NL-2132 JD Hoofddorp
3. Use twisted-pair shielded wire for the output signal of The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
the Voltage/Current Conversion Card, and make sure
that the end is shielded. OMRON ELECTRONICS, INC.
1 East Commerce Drive, Schaumburg, IL 60173
Also, use tape or other insulation to keep shielded wire U.S.A.
sections from contacting other signal wires or devices. Tel: (847)843-7900/Fax: (847)843-8568
4. Make sure that the signal wire length is less than 50 m OMRON ASIAPACIFIC PTE. LTD.
in order to minimize the effects of noise. 510 Thomson Road #13-03
SLF Bldg.
1129 Singapore
Tel: (65)353-2611/Fax: (65)353-5391
Note: Specifications subject to change without notice.
Printed in Japan Cat. No. I517-E1-1