5 - Aaac
5 - Aaac
5 - Aaac
All Aluminium Allloy Conductors (AAAC): These are made out of high strength Aluminium-Magnesium-Silicon alloy. As compared to
conventional ACSR, AAAC are of lighter weight, comparable strength & current carrying capacity, lower electrical losses and superior corrosion
resistance, This has given AAAC a wide acceptance in the distribution and transmission lines.. This conductor has a minimum conductivity of
52.5% IACS.
Construction
Aluminum Alloy 6201 Wires, concentrically stranded over a central wire of Aluminum 6201.
Features:
• High strength to weight ratio
• Better Sag Characteristics
• Improved electrical Properties
• Excellent resistance to corrosion
Available with Non-Specular (Dull) Surface Finish and Color Coated as per customized requirements.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ASTM B 399
Code Word Conductor size Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(kcmil) (mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
- 1439.2 729 61 3.90 35.10 1999.00 207.00 0.04597 693 897
- 1348.8 685 61 3.78 34.02 1878.00 194.00 0.04893 671 865
- 1259.6 638 61 3.65 32.85 1751.00 181.00 0.05248 646 831
- 1165.1 590 61 3.51 31.59 1620.00 167.00 0.05675 620 794
- 1077.4 547 61 3.38 30.42 1502.00 156.00 0.06120 595 760
Greeley 927.2 470 37 4.02 28.14 1289.00 135.00 0.07133 547 694
Flint 740.8 375 37 3.59 25.13 1028.00 107.00 0.08944 482 607
Elgin 652.4 331 19 4.71 23.55 908.30 97.00 0.10120 449 564
Darien 559.5 284 19 4.36 21.80 778.30 83.10 0.11810 412 514
Cairo 465.4 236 19 3.98 19.90 648.60 69.20 0.14170 371 461
Canton 394.5 200 19 3.66 18.30 548.50 58.60 0.16760 337 417
Butte 312.8 159 19 3.26 16.30 435.10 46.50 0.21120 295 362
Alliance 246.9 125 7 4.77 14.31 343.20 37.80 0.26780 256 313
Amherst 195.7 99.3 7 4.25 12.75 272.50 30.00 0.33730 224 272
Anaheim 155.4 78.6 7 3.78 11.34 215.60 23.80 0.42640 195 236
Azusa 123.3 62.4 7 3.37 10.11 171.30 18.90 0.53650 170 205
Ames 77.47 39.2 7 2.67 8.01 107.50 12.40 0.85470 129 154
Alton 48.69 24.7 7 2.12 6.36 67.80 7.83 1.35600 98 116
Akron 30.58 15.5 7 1.68 5.04 42.58 4.92 2.15900 74 88
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ASTM B 399
AWG Conductor size Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(kcmil) (mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
- 1750 886 61 4.30 38.70 2431.0 251.00 0.03781 767 1002
- 1500 759 61 3.98 35.82 2082.0 215.00 0.04414 708 918
- 1250 631 61 3.63 32.67 1732.0 179.00 0.05306 642 826
- 1000 508 37 4.18 29.26 1393.0 146.00 0.06597 571 727
- 900 456 37 3.96 27.72 1250.0 131.00 0.07351 538 682
- 800 404 37 3.73 26.11 1109.0 116.00 0.08285 503 636
- 750 381 37 3.62 25.34 1045.0 109.00 0.08796 487 613
- 700 354 37 3.49 24.43 971.2 101.00 0.09464 467 587
- 650 330 37 3.37 23.59 905.5 94.90 0.10150 449 563
- 600 303 37 3.23 22.61 831.9 91.00 0.11049 428 535
- 550 279 37 3.10 21.70 766.2 83.90 0.11995 408 510
- 500 253 19 4.12 20.60 695.0 74.20 0.13224 386 480
- 450 228 19 3.91 19.55 626.0 66.80 0.14683 364 451
- 400 203 19 3.69 18.45 557.5 59.50 0.16486 340 421
- 350 178 19 3.45 17.25 487.3 52.00 0.18860 315 388
- 300 152 19 3.19 15.95 416.7 46.60 0.22059 287 353
- 250 126 19 2.91 14.55 346.7 38.80 0.26509 258 316
0000 211.6 107 7 4.42 13.26 294.7 32.50 0.31188 234 285
000 167.8 84.9 7 3.93 11.79 233.0 25.70 0.39450 204 247
00 133.1 67.3 7 3.50 10.50 184.8 20.40 0.49738 178 215
0 105.6 53.5 7 3.12 9.36 146.8 17.00 0.62592 155 187
2 66.36 33.5 7 2.47 7.41 92.0 10.60 0.99870 118 140
4 41.74 21.1 7 1.96 5.88 57.9 6.69 1.58600 89 106
6 26.24 13.2 7 1.55 4.65 36.2 4.18 2.53610 67 79
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
Code Word Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
13-A2-7 Fredericton 15.30 7 1.67 5.01 41.78 4.67 2.1540 74 88
21-A2-7 Whitehorse 24.34 7 2.10 6.30 66.46 7.42 1.3540 98 116
27-A2-7 - 30.69 7 2.36 7.08 83.79 9.36 1.0740 112 134
34-A2-7 Halifax 38.70 7 2.65 7.95 105.7 11.8 0.8516 129 154
42-A2-7 Regina 48.84 7 2.98 8.94 133.3 14.9 0.6752 148 178
54-A2-7 Montreal 61.59 7 3.35 10.05 168.1 18.8 0.5351 170 205
67-A2-7 Winnipeg 77.62 7 3.76 11.28 211.9 23.7 0.4246 195 236
85-A2-7 Toronto 97.86 7 4.22 12.66 267.2 29.9 0.3368 224 272
107-A2-7 Vancouver 123.4 7 4.74 14.22 336.9 37.6 0.2671 256 313
127-A2-19 - 145.8 19 3.13 15.65 400.0 44.5 0.2271 282 346
135-A2-7 - 155.6 7 5.32 15.96 424.8 47.5 0.2118 293 360
135-A2-19 Calgary 155.6 19 3.23 16.15 426.9 47.5 0.2128 293 360
152-A2-19 - 175.0 19 3.42 17.10 480.0 53.4 0.1893 314 386
170-A2-19 Edmonton 196.2 19 3.63 18.15 538.2 59.8 0.1688 335 414
177-A2-19 - 204.1 19 3.70 18.50 560.0 62.3 0.1622 343 424
201-A2-19 Brockville 231.8 19 3.94 19.70 636.0 70.7 0.1429 369 458
203-A2-19 - 233.3 19 3.95 19.75 640.0 71.2 0.1420 370 460
228-A2-19 - 262.4 19 4.19 20.95 720.0 80.0 0.1262 396 493
242-A2-19 Quebec 278.2 19 4.32 21.60 763.2 84.9 0.1190 410 511
253-A2-19 - 291.6 19 4.42 22.10 800.0 88.9 0.1136 421 526
279-A2-37 - 320.8 37 3.32 23.24 882.1 97.8 0.1035 444 556
282-A2-19 - 324.5 19 4.66 23.30 890.4 99.0 0.1020 447 560
304-A2-37 - 349.9 37 3.47 24.29 962.3 107.0 0.09486 466 586
322-A2-37 - 370.9 37 3.57 24.99 1020.0 113.0 0.08949 482 606
329-A2-37 - 379.1 37 3.61 25.27 1042.0 116.0 0.08757 487 614
355-A2-37 - 408.2 37 3.75 26.25 1123.0 125.0 0.08131 508 642
363-A2-37 - 417.3 37 3.79 26.53 1147.0 127.0 0.07955 514 650
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
380-A2-37 - 437.4 37 3.88 27.16 1203.0 133.0 0.07589 528 669
403-A2-37 - 463.6 37 3.99 27.93 1275.0 141.0 0.07160 545 692
405-A2-37 - 466.6 37 4.01 28.07 1283.0 142.0 0.07115 547 695
443-A2-37 - 510.0 37 4.19 29.33 1403.0 156.0 0.06509 575 732
456-A2-37 - 524.9 37 4.25 29.75 1443.0 160.0 0.06324 584 745
470-A2-37 - 540.7 37 4.31 30.17 1487.0 165.0 0.06139 593 758
483-A2-37 - 556.4 37 4.38 30.66 1530.0 170.0 0.05966 603 771
507-A2-37 - 583.2 37 4.48 31.36 1604.0 178.0 0.05692 618 792
524-A2-37 - 602.7 37 4.55 31.85 1657.0 184.0 0.05507 629 807
557-A2-61 - 641.5 61 3.66 32.94 1767.0 196.0 0.05182 650 837
564-A2-61 - 649.1 61 3.68 33.12 1788.0 198.0 0.05121 654 842
604-A2-61 - 695.5 61 3.81 34.29 1915.0 212.0 0.04780 679 876
608-A2-61 - 699.8 61 3.82 34.38 1927.0 213.0 0.04750 681 879
645-A2-61 - 741.8 61 3.93 35.37 2043.0 226.0 0.04481 702 909
659-A2-61 - 758.1 61 3.98 35.82 2088.0 231.0 0.04385 710 921
685-A2-61 - 788.2 61 4.06 36.54 2171.0 240.0 0.04218 725 941
709-A2-61 - 816.5 61 4.13 37.17 2249.0 249.0 0.04072 738 960
725-A2-61 - 834.5 61 4.17 37.53 2298.0 255.0 0.03983 747 972
760-A2-61 - 874.8 61 4.27 38.43 2409.0 267.0 0.03800 765 998
765-A2-61 - 880.9 61 4.29 38.61 2426.0 269.0 0.03774 768 1002
806-A2-61 - 927.3 61 4.40 39.60 2554.0 283.0 0.03585 788 1031
811-A2-61 - 933.1 61 4.41 39.69 2570.0 285.0 0.03563 790 1035
861-A2-61 - 991.4 61 4.55 40.95 2730.0 302.0 0.03353 815 1070
912-A2-91 - 1050.0 91 3.83 42.13 2894.0 320.0 0.03170 837 1104
1013-A2-91 - 1166.0 91 4.04 44.44 3216.0 356.0 0.02853 881 1168
1140-A2-91 - 1312.0 91 4.28 47.08 3618.0 400.0 0.02536 930 1242
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
1234-A2-91 - 1420.0 91 4.46 49.06 3916.0 433.0 0.02343 964 1294
1267-A2-91 - 1458.0 91 4.52 49.72 4020.0 445.0 0.02283 975 1311
1393-A2-91 - 1604.0 91 4.74 52.14 4422.0 489.0 0.02075 1015 1374
1520-A2-91 - 1750.0 91 4.95 54.45 4824.0 534.0 0.01902 1051 1432
1524-A2-91 - 1754.0 91 4.95 54.45 4836.0 535.0 0.01897 1052 1434
1773-A2-91 - 2041.0 91 5.34 58.74 5628.0 623.0 0.01630 1112 1534
1844-A2-91 - 2123.0 91 5.45 59.95 5853.0 648.0 0.01568 1127 1559
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ABNT NBR 10298
Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
15.52 7 1.68 5.04 42.90 4.93 2.1588 74 88
24.71 7 2.12 6.36 67.80 7.85 1.3557 98 116
39.19 7 2.67 8.01 107.50 12.45 0.8547 129 154
62.44 7 3.37 10.11 171.30 19.00 0.5365 170 205
78.55 7 3.78 11.34 215.50 23.91 0.4264 195 236
99.30 7 4.25 12.75 272.50 30.22 0.3373 224 272
125.09 7 4.77 14.31 343.20 38.07 0.2678 256 313
158.59 19 3.26 16.30 435.10 46.75 0.2112 295 362
199.90 19 3.66 18.30 548.50 58.93 0.1676 337 417
236.38 19 3.98 19.90 648.60 69.69 0.1417 371 461
283.67 19 4.36 21.80 778.30 83.63 0.1181 412 514
331.04 19 4.71 23.55 908.30 97.59 0.1012 449 564
374.53 37 3.59 25.13 1027.60 108.00 0.0894 482 607
469.62 37 4.02 28.14 1288.50 135.50 0.0713 547 695
547.34 61 3.38 30.42 1501.80 156.20 0.0612 595 760
590.25 61 3.51 31.59 1619.50 168.40 0.0568 619 794
638.27 61 3.65 32.85 1751.30 182.10 0.0525 646 831
684.55 61 3.78 34.02 1878.30 195.30 0.0489 671 866
728.70 61 3.90 35.10 1999.40 207.90 0.0460 693 897
33.54 7 2.47 7.41 92.00 10.66 0.9987 118 140
53.52 7 3.12 9.36 146.80 17.01 0.6259 155 187
67.35 7 3.50 10.50 184.80 20.50 0.4974 178 215
84.91 7 3.93 11.79 233.00 25.84 0.3945 204 247
107.41 7 4.42 13.26 294.70 32.69 0.3119 234 285
126.37 19 2.91 14.55 346.70 38.90 0.2651 258 316
151.85 19 3.19 15.95 416.70 46.75 0.2206 287 353
177.62 19 3.45 17.25 487.30 52.36 0.1886 315 388
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ABNT NBR 10298
Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
203.19 19 3.69 18.45 557.50 59.90 0.1649 340 421
228.14 19 3.91 19.55 626.00 67.26 0.1468 364 451
253.30 19 4.12 20.60 695.00 74.68 0.1322 386 480
279.26 37 3.10 21.70 766.20 84.12 0.1200 408 510
303.18 37 3.23 22.61 831.90 91.32 0.1105 428 535
330.03 37 3.37 23.59 905.50 95.20 0.1015 449 563
353.95 37 3.49 24.43 971.20 102.10 0.0946 467 587
380.81 37 3.62 25.34 1044.90 109.90 0.0880 486 613
404.31 37 3.73 26.11 1109.30 116.60 0.0829 503 635
455.70 37 3.96 27.72 1250.40 131.50 0.0735 538 682
507.74 37 4.18 29.26 1393.10 146.50 0.0660 571 727
631.30 61 3.63 32.67 1732.10 180.10 0.0531 642 825
758.90 61 3.98 35.82 2082.30 216.50 0.0441 709 918
885.84 61 4.30 38.70 2430.60 252.70 0.0378 767 1002
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - IS 398 PART-IV
Actual Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL2
(Used in Austria)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in Germany)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in Switzerland)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL4
(Used in Belgium)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter