ALL ALUMINUM ALLOY CONDUCTOR (AAAC)

All Aluminium Allloy Conductors (AAAC): These are made out of high strength Aluminium-Magnesium-Silicon alloy. As compared to
conventional ACSR, AAAC are of lighter weight, comparable strength & current carrying capacity, lower electrical losses and superior corrosion
resistance, This has given AAAC a wide acceptance in the distribution and transmission lines.. This conductor has a minimum conductivity of
52.5% IACS.

Construction
Aluminum Alloy 6201 Wires, concentrically stranded over a central wire of Aluminum 6201.

Aluminum Alloy 6201 Wires Aluminum Alloy 6201 Wires

Features:
• High strength to weight ratio
• Better Sag Characteristics
• Improved electrical Properties
• Excellent resistance to corrosion

Available with Non-Specular (Dull) Surface Finish and Color Coated as per customized requirements.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ASTM B 399
Code Word Conductor size Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(kcmil) (mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
- 1439.2 729 61 3.90 35.10 1999.00 207.00 0.04597 693 897
- 1348.8 685 61 3.78 34.02 1878.00 194.00 0.04893 671 865
- 1259.6 638 61 3.65 32.85 1751.00 181.00 0.05248 646 831
- 1165.1 590 61 3.51 31.59 1620.00 167.00 0.05675 620 794
- 1077.4 547 61 3.38 30.42 1502.00 156.00 0.06120 595 760
Greeley 927.2 470 37 4.02 28.14 1289.00 135.00 0.07133 547 694
Flint 740.8 375 37 3.59 25.13 1028.00 107.00 0.08944 482 607
Elgin 652.4 331 19 4.71 23.55 908.30 97.00 0.10120 449 564
Darien 559.5 284 19 4.36 21.80 778.30 83.10 0.11810 412 514
Cairo 465.4 236 19 3.98 19.90 648.60 69.20 0.14170 371 461
Canton 394.5 200 19 3.66 18.30 548.50 58.60 0.16760 337 417
Butte 312.8 159 19 3.26 16.30 435.10 46.50 0.21120 295 362
Alliance 246.9 125 7 4.77 14.31 343.20 37.80 0.26780 256 313
Amherst 195.7 99.3 7 4.25 12.75 272.50 30.00 0.33730 224 272
Anaheim 155.4 78.6 7 3.78 11.34 215.60 23.80 0.42640 195 236
Azusa 123.3 62.4 7 3.37 10.11 171.30 18.90 0.53650 170 205
Ames 77.47 39.2 7 2.67 8.01 107.50 12.40 0.85470 129 154
Alton 48.69 24.7 7 2.12 6.36 67.80 7.83 1.35600 98 116
Akron 30.58 15.5 7 1.68 5.04 42.58 4.92 2.15900 74 88
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ASTM B 399
AWG Conductor size Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(kcmil) (mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
- 1750 886 61 4.30 38.70 2431.0 251.00 0.03781 767 1002
- 1500 759 61 3.98 35.82 2082.0 215.00 0.04414 708 918
- 1250 631 61 3.63 32.67 1732.0 179.00 0.05306 642 826
- 1000 508 37 4.18 29.26 1393.0 146.00 0.06597 571 727
- 900 456 37 3.96 27.72 1250.0 131.00 0.07351 538 682
- 800 404 37 3.73 26.11 1109.0 116.00 0.08285 503 636
- 750 381 37 3.62 25.34 1045.0 109.00 0.08796 487 613
- 700 354 37 3.49 24.43 971.2 101.00 0.09464 467 587
- 650 330 37 3.37 23.59 905.5 94.90 0.10150 449 563
- 600 303 37 3.23 22.61 831.9 91.00 0.11049 428 535
- 550 279 37 3.10 21.70 766.2 83.90 0.11995 408 510
- 500 253 19 4.12 20.60 695.0 74.20 0.13224 386 480
- 450 228 19 3.91 19.55 626.0 66.80 0.14683 364 451
- 400 203 19 3.69 18.45 557.5 59.50 0.16486 340 421
- 350 178 19 3.45 17.25 487.3 52.00 0.18860 315 388
- 300 152 19 3.19 15.95 416.7 46.60 0.22059 287 353
- 250 126 19 2.91 14.55 346.7 38.80 0.26509 258 316
0000 211.6 107 7 4.42 13.26 294.7 32.50 0.31188 234 285
000 167.8 84.9 7 3.93 11.79 233.0 25.70 0.39450 204 247
00 133.1 67.3 7 3.50 10.50 184.8 20.40 0.49738 178 215
0 105.6 53.5 7 3.12 9.36 146.8 17.00 0.62592 155 187
2 66.36 33.5 7 2.47 7.41 92.0 10.60 0.99870 118 140
4 41.74 21.1 7 1.96 5.88 57.9 6.69 1.58600 89 106
6 26.24 13.2 7 1.55 4.65 36.2 4.18 2.53610 67 79
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
Code Word Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity

No. of Complete 20°C


Individual wire Conductor
Aluminium @ 75°C @ 85°C
diameter
Wires
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
10-A2-7 11.51 7 1.45 4.35 31.42 3.51 2.863 62 74
16-A2-7 18.42 7 1.83 5.49 50.28 5.62 1.790 83 98
25-A2-7 28.77 7 2.29 6.87 78.56 8.78 1.145 108 129
40-A2-7 46.04 7 2.89 8.67 125.7 14.0 0.7159 143 172
63-A2-7 72.51 7 3.63 10.89 198.0 22.1 0.4545 187 226
100-A2-19 115.10 19 2.78 13.90 315.8 35.1 0.2877 246 300
125-A2-19 143.9 19 3.10 15.50 394.7 43.9 0.2302 280 343
160-A2-19 184.2 19 3.51 17.55 505.2 56.2 0.1798 323 399
200-A2-19 230.2 19 3.93 19.65 631.5 70.2 0.1439 368 456
250-A2-19 287.7 19 4.39 21.95 789.4 87.8 0.1151 417 521
315-A2-37 362.5 37 3.53 24.71 997.0 111.0 0.09156 475 598
400-A2-37 460.4 37 3.98 27.86 1266.0 140.0 0.07210 543 689
450-A2-37 517.9 37 4.22 29.54 1424.0 158.0 0.06409 580 739
500-A2-37 575.5 37 4.45 31.15 1583.0 176.0 0.05768 614 786
560-A2-37 644.5 37 4.71 32.97 1772.0 197.0 0.05150 652 839
630-A2-61 725.1 61 3.89 35.01 1997.0 221.0 0.04585 694 898
710-A2-61 817.2 61 4.13 37.17 2251.0 249.0 0.04068 739 961
800-A2-61 920.8 61 4.38 39.42 2536.0 281.0 0.03610 785 1027
900-A2-61 1036 61 4.65 41.85 2853.0 316.0 0.03209 832 1096
1000-A2-91 1152 91 4.02 44.22 3177.0 351.0 0.02888 876 1161
1120-A2-91 1289 91 4.25 46.75 3554.0 393.0 0.02582 923 1231
1250-A2-91 1439 91 4.49 49.39 3966.0 439.0 0.02313 969 1303
1400-A2-91 1611 91 4.75 52.25 4442.0 491.0 0.02065 1017 1377
1500-A2-91 1726 91 4.91 54.01 4760.0 526.0 0.01928 1045 1423
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A4
Code Word Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity

No. of Complete 20°C


Individual wire Conductor
Aluminium @ 75°C @ 85°C
diameter
Wires
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
10-A4-7 10.61 7 1.39 4.17 28.96 2.65 2.8630 62 73
16-A4-7 16.97 7 1.76 5.28 46.34 4.24 1.7900 82 97
25-A4-7 26.52 7 2.20 6.60 72.41 6.63 1.1450 107 128
40-A4-7 42.43 7 2.78 8.34 115.9 10.6 0.7159 142 170
63-A4-7 66.83 7 3.49 10.47 182.5 16.7 0.4545 186 225
100-A4-19 106.1 19 2.67 13.35 291.1 26.5 0.2877 244 297
125-A4-19 132.6 19 2.98 14.90 363.8 33.2 0.2302 278 340
160-A4-19 169.7 19 3.37 16.85 465.7 42.4 0.1798 321 395
200-A4-19 212.2 19 3.77 18.85 582.1 53.1 0.1439 365 452
250-A4-19 265.2 19 4.22 21.10 727.6 66.3 0.1151 415 517
315-A4-37 334.2 37 3.39 23.73 919.0 83.6 0.09156 473 593
400-A4-37 424.3 37 3.82 26.74 1167.0 106.0 0.07210 540 684
450-A4-37 277.4 37 4.05 28.35 1313.0 119.0 0.06409 577 733
500-A4-37 530.4 37 4.27 29.89 1459.0 133.0 0.05768 611 779
560-A4-37 594.1 37 4.52 31.64 1634.0 149.0 0.05150 649 832
630-A4-61 668.3 61 3.74 33.66 1841.0 167.0 0.04585 691 891
710-A4-61 753.20 61 3.97 35.73 2074.0 188.0 0.04068 736 954
800-A4-61 848.70 61 4.21 37.89 2337.0 212.0 0.03610 782 1019
900-A4-61 954.80 61 4.46 40.14 2629.0 239.0 0.03209 829 1088
1000-A4-91 1062.00 91 3.85 42.35 2928.0 266.0 0.02888 873 1152
1120-A4-91 1188.00 91 4.08 44.88 3276.0 297.0 0.02582 920 1222
1250-A4-91 1326.00 91 4.31 47.41 3656.0 332.0 0.02313 967 1293
1400-A4-91 1485.00 91 4.56 50.16 4095.0 371.0 0.02065 1015 1367
1500-A4-91 1591.00 91 4.72 51.92 4387.0 398.0 0.01928 1044 1413

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
13-A2-7 Fredericton 15.30 7 1.67 5.01 41.78 4.67 2.1540 74 88
21-A2-7 Whitehorse 24.34 7 2.10 6.30 66.46 7.42 1.3540 98 116
27-A2-7 - 30.69 7 2.36 7.08 83.79 9.36 1.0740 112 134
34-A2-7 Halifax 38.70 7 2.65 7.95 105.7 11.8 0.8516 129 154
42-A2-7 Regina 48.84 7 2.98 8.94 133.3 14.9 0.6752 148 178
54-A2-7 Montreal 61.59 7 3.35 10.05 168.1 18.8 0.5351 170 205
67-A2-7 Winnipeg 77.62 7 3.76 11.28 211.9 23.7 0.4246 195 236
85-A2-7 Toronto 97.86 7 4.22 12.66 267.2 29.9 0.3368 224 272
107-A2-7 Vancouver 123.4 7 4.74 14.22 336.9 37.6 0.2671 256 313
127-A2-19 - 145.8 19 3.13 15.65 400.0 44.5 0.2271 282 346
135-A2-7 - 155.6 7 5.32 15.96 424.8 47.5 0.2118 293 360
135-A2-19 Calgary 155.6 19 3.23 16.15 426.9 47.5 0.2128 293 360
152-A2-19 - 175.0 19 3.42 17.10 480.0 53.4 0.1893 314 386
170-A2-19 Edmonton 196.2 19 3.63 18.15 538.2 59.8 0.1688 335 414
177-A2-19 - 204.1 19 3.70 18.50 560.0 62.3 0.1622 343 424
201-A2-19 Brockville 231.8 19 3.94 19.70 636.0 70.7 0.1429 369 458
203-A2-19 - 233.3 19 3.95 19.75 640.0 71.2 0.1420 370 460
228-A2-19 - 262.4 19 4.19 20.95 720.0 80.0 0.1262 396 493
242-A2-19 Quebec 278.2 19 4.32 21.60 763.2 84.9 0.1190 410 511
253-A2-19 - 291.6 19 4.42 22.10 800.0 88.9 0.1136 421 526
279-A2-37 - 320.8 37 3.32 23.24 882.1 97.8 0.1035 444 556
282-A2-19 - 324.5 19 4.66 23.30 890.4 99.0 0.1020 447 560
304-A2-37 - 349.9 37 3.47 24.29 962.3 107.0 0.09486 466 586
322-A2-37 - 370.9 37 3.57 24.99 1020.0 113.0 0.08949 482 606
329-A2-37 - 379.1 37 3.61 25.27 1042.0 116.0 0.08757 487 614
355-A2-37 - 408.2 37 3.75 26.25 1123.0 125.0 0.08131 508 642
363-A2-37 - 417.3 37 3.79 26.53 1147.0 127.0 0.07955 514 650
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
380-A2-37 - 437.4 37 3.88 27.16 1203.0 133.0 0.07589 528 669
403-A2-37 - 463.6 37 3.99 27.93 1275.0 141.0 0.07160 545 692
405-A2-37 - 466.6 37 4.01 28.07 1283.0 142.0 0.07115 547 695
443-A2-37 - 510.0 37 4.19 29.33 1403.0 156.0 0.06509 575 732
456-A2-37 - 524.9 37 4.25 29.75 1443.0 160.0 0.06324 584 745
470-A2-37 - 540.7 37 4.31 30.17 1487.0 165.0 0.06139 593 758
483-A2-37 - 556.4 37 4.38 30.66 1530.0 170.0 0.05966 603 771
507-A2-37 - 583.2 37 4.48 31.36 1604.0 178.0 0.05692 618 792
524-A2-37 - 602.7 37 4.55 31.85 1657.0 184.0 0.05507 629 807
557-A2-61 - 641.5 61 3.66 32.94 1767.0 196.0 0.05182 650 837
564-A2-61 - 649.1 61 3.68 33.12 1788.0 198.0 0.05121 654 842
604-A2-61 - 695.5 61 3.81 34.29 1915.0 212.0 0.04780 679 876
608-A2-61 - 699.8 61 3.82 34.38 1927.0 213.0 0.04750 681 879
645-A2-61 - 741.8 61 3.93 35.37 2043.0 226.0 0.04481 702 909
659-A2-61 - 758.1 61 3.98 35.82 2088.0 231.0 0.04385 710 921
685-A2-61 - 788.2 61 4.06 36.54 2171.0 240.0 0.04218 725 941
709-A2-61 - 816.5 61 4.13 37.17 2249.0 249.0 0.04072 738 960
725-A2-61 - 834.5 61 4.17 37.53 2298.0 255.0 0.03983 747 972
760-A2-61 - 874.8 61 4.27 38.43 2409.0 267.0 0.03800 765 998
765-A2-61 - 880.9 61 4.29 38.61 2426.0 269.0 0.03774 768 1002
806-A2-61 - 927.3 61 4.40 39.60 2554.0 283.0 0.03585 788 1031
811-A2-61 - 933.1 61 4.41 39.69 2570.0 285.0 0.03563 790 1035
861-A2-61 - 991.4 61 4.55 40.95 2730.0 302.0 0.03353 815 1070
912-A2-91 - 1050.0 91 3.83 42.13 2894.0 320.0 0.03170 837 1104
1013-A2-91 - 1166.0 91 4.04 44.44 3216.0 356.0 0.02853 881 1168
1140-A2-91 - 1312.0 91 4.28 47.08 3618.0 400.0 0.02536 930 1242
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A2
(Properties for A2 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
1234-A2-91 - 1420.0 91 4.46 49.06 3916.0 433.0 0.02343 964 1294
1267-A2-91 - 1458.0 91 4.52 49.72 4020.0 445.0 0.02283 975 1311
1393-A2-91 - 1604.0 91 4.74 52.14 4422.0 489.0 0.02075 1015 1374
1520-A2-91 - 1750.0 91 4.95 54.45 4824.0 534.0 0.01902 1051 1432
1524-A2-91 - 1754.0 91 4.95 54.45 4836.0 535.0 0.01897 1052 1434
1773-A2-91 - 2041.0 91 5.34 58.74 5628.0 623.0 0.01630 1112 1534
1844-A2-91 - 2123.0 91 5.45 59.95 5853.0 648.0 0.01568 1127 1559

ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A4


(Properties for A4 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
13-A4-7 Fredericton 14.11 7 1.60 4.80 38.51 3.53 2.1540 73 87
21-A4-7 Whitehorse 22.44 7 2.02 6.06 61.26 5.61 1.3540 97 115
27-A4-7 - 28.29 7 2.27 6.81 77.23 7.07 1.0740 111 133
34-A4-7 Halifax 35.67 7 2.55 7.65 97.40 8.92 0.8516 128 153
42-A4-7 Regina 44.99 7 2.86 8.58 122.8 11.3 0.6752 147 176
54-A4-7 Montreal 56.77 7 3.21 9.63 155.0 14.2 0.5351 169 203
67-A4-7 Winnipeg 71.55 7 3.61 10.83 195.3 17.9 0.4246 194 234
85-A4-7 Toronto 90.2 7 4.05 12.15 246.3 22.6 0.3368 222 269
107-A4-7 Vancouver 1113.7 7 4.55 13.65 310.6 28.4 0.2671 254 310
127-A4-19 - 134.4 19 3.00 15.00 368.7 33.6 0.2271 280 343
135-A4-7 - 143.4 7 5.11 15.33 391.6 35.9 0.2118 291 357
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A4
(Properties for A4 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
135-A4-19 Calgary 143.4 19 3.10 15.50 393.5 35.9 0.2128 291 357
152-A4-19 - 161.3 19 3.29 16.45 442.4 40.3 0.1893 312 383
170-A4-19 Edmonton 180.8 19 3.48 17.40 496.1 45.2 0.1688 333 411
177-A4-19 - 188.1 19 3.55 17.75 516.2 47.0 0.1622 341 421
201-A4-19 Brockville 213.7 19 3.78 18.90 586.2 53.4 0.1429 367 454
203-A4-19 - 215.0 19 3.80 19.00 589.9 53.8 0.1420 368 456
228-A4-19 - 241.9 19 4.03 20.15 663.7 60.5 0.1262 394 489
242-A4-19 Quebec 256.4 19 4.15 20.75 703.5 64.1 0.1190 407 507
253-A4-19 - 268.8 19 4.24 21.20 737.4 67.2 0.1136 418 521
279-A4-37 - 295.7 37 3.19 22.33 813.0 73.9 0.1035 441 552
282-A4-19 - 299.1 19 4.48 22.40 820.7 74.8 0.1020 445 556
304-A4-37 - 322.5 37 3.33 23.31 887.0 80.6 0.09486 463 581
322-A4-37 - 341.9 37 3.43 24.01 940.2 85.5 0.08949 479 602
329-A4-37 - 349.4 37 3.47 24.29 960.9 87.4 0.08757 485 609
355-A4-37 - 376.3 37 3.60 25.20 1035.0 94.1 0.08131 505 637
363-A4-37 - 384.6 37 3.64 25.48 1058.0 96.2 0.07955 512 645
380-A4-37 - 403.2 37 3.72 26.04 1109.0 101.0 0.07589 525 663
403-A4-37 - 427.4 37 3.83 26.81 1175.0 107.0 0.07160 542 686
405-A4-37 - 430.0 37 3.85 26.95 1183.0 108.0 0.07115 544 689
443-A4-37 - 470.1 37 4.02 28.14 1293.0 118.0 0.06509 572 726
456-A4-37 - 483.8 37 4.08 28.56 1330.0 121.0 0.06324 581 739
470-A4-37 - 498.4 37 4.14 28.98 1371.0 125.0 0.06139 590 752
483-A4-37 - 512.8 37 4.20 29.40 1410.0 128.0 0.05966 600 764
507-A4-37 - 537.6 37 4.30 30.10 1478.0 134.0 0.05692 615 786
524-A4-37 - 555.6 37 4.37 30.59 1528.0 139.0 0.05507 626 801
557-A4-61 - 591.3 61 3.51 31.59 1628.0 148.0 0.05182 647 830
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - CAN/CSA-C61089-11, Type-A4
(Properties for A4 Conductors Sizes Equivalent to Canadian A1 Sizes)
Code Word Conductor Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Name Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
564-A4-61 - 598.3 61 3.53 31.77 1648.0 150.0 0.05121 651 835
604-A4-61 - 641.0 61 3.66 32.94 1765.0 160.0 0.04780 676 870
608-A4-61 - 645.1 61 3.67 33.03 1777.0 161.0 0.04750 678 873
645-A4-61 - 683.8 61 3.78 34.02 1883.0 171.0 0.04481 699 902
659-A4-61 - 698.8 61 3.82 34.38 1925.0 175.0 0.04385 707 914
685-A4-61 - 726.5 61 2.89 26.01 2001.0 182.0 0.04218 697 881
709-A4-61 - 752.6 61 3.96 35.64 2073.0 188.0 0.04072 735 953
725-A4-61 - 769.2 61 4.01 36.09 2118.0 192.0 0.03983 744 965
760-A4-61 - 806.3 61 4.10 36.90 2221.0 202.0 0.03800 762 991
765-A4-61 - 812.0 61 4.12 37.08 2236.0 203.0 0.03774 765 995
806-A4-61 - 854.7 61 4.22 37.98 2354.0 214.0 0.03585 785 1023
811-A4-61 - 860.1 61 4.24 38.16 2369.0 215.0 0.03563 787 1027
861-A4-61 - 913.8 61 4.37 39.33 2517.0 229.0 0.03353 812 1062
912-A4-91 - 967.6 91 3.68 40.48 2668.0 242.0 0.03170 835 1095
1013-A4-91 - 1075.0 91 3.88 42.68 2964.0 269.0 0.02853 878 1160
1140-A4-91 - 1209.0 91 4.11 45.21 3335.0 302.0 0.02536 928 1233
1234-A4-91 - 1309.0 91 4.28 47.08 3610.0 327.0 0.02343 962 1285
1267-A4-91 - 1344.0 91 4.34 47.74 3705.0 336.0 0.02283 973 1302
1393-A4-91 - 1478.0 91 4.55 50.05 4076.0 370.0 0.02075 1013 1364
1520-A4-91 - 1613.0 91 4.75 52.25 4446.0 403.0 0.01902 1049 1422
1524-A4-91 - 1617.0 91 4.76 52.36 4457.0 404.0 0.01897 1050 1424
1773-A4-91 - 1881.0 91 5.13 56.43 5187.0 470.0 0.01630 1111 1523
1844-A4-91 - 1957.0 91 5.23 57.53 5395.0 489.0 0.01568 1126 1549

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ABNT NBR 10298
Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
15.52 7 1.68 5.04 42.90 4.93 2.1588 74 88
24.71 7 2.12 6.36 67.80 7.85 1.3557 98 116
39.19 7 2.67 8.01 107.50 12.45 0.8547 129 154
62.44 7 3.37 10.11 171.30 19.00 0.5365 170 205
78.55 7 3.78 11.34 215.50 23.91 0.4264 195 236
99.30 7 4.25 12.75 272.50 30.22 0.3373 224 272
125.09 7 4.77 14.31 343.20 38.07 0.2678 256 313
158.59 19 3.26 16.30 435.10 46.75 0.2112 295 362
199.90 19 3.66 18.30 548.50 58.93 0.1676 337 417
236.38 19 3.98 19.90 648.60 69.69 0.1417 371 461
283.67 19 4.36 21.80 778.30 83.63 0.1181 412 514
331.04 19 4.71 23.55 908.30 97.59 0.1012 449 564
374.53 37 3.59 25.13 1027.60 108.00 0.0894 482 607
469.62 37 4.02 28.14 1288.50 135.50 0.0713 547 695
547.34 61 3.38 30.42 1501.80 156.20 0.0612 595 760
590.25 61 3.51 31.59 1619.50 168.40 0.0568 619 794
638.27 61 3.65 32.85 1751.30 182.10 0.0525 646 831
684.55 61 3.78 34.02 1878.30 195.30 0.0489 671 866
728.70 61 3.90 35.10 1999.40 207.90 0.0460 693 897
33.54 7 2.47 7.41 92.00 10.66 0.9987 118 140
53.52 7 3.12 9.36 146.80 17.01 0.6259 155 187
67.35 7 3.50 10.50 184.80 20.50 0.4974 178 215
84.91 7 3.93 11.79 233.00 25.84 0.3945 204 247
107.41 7 4.42 13.26 294.70 32.69 0.3119 234 285
126.37 19 2.91 14.55 346.70 38.90 0.2651 258 316
151.85 19 3.19 15.95 416.70 46.75 0.2206 287 353
177.62 19 3.45 17.25 487.30 52.36 0.1886 315 388
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - ABNT NBR 10298
Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire Conductor @ 75°C @ 85°C
Wires diameter
(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)
203.19 19 3.69 18.45 557.50 59.90 0.1649 340 421
228.14 19 3.91 19.55 626.00 67.26 0.1468 364 451
253.30 19 4.12 20.60 695.00 74.68 0.1322 386 480
279.26 37 3.10 21.70 766.20 84.12 0.1200 408 510
303.18 37 3.23 22.61 831.90 91.32 0.1105 428 535
330.03 37 3.37 23.59 905.50 95.20 0.1015 449 563
353.95 37 3.49 24.43 971.20 102.10 0.0946 467 587
380.81 37 3.62 25.34 1044.90 109.90 0.0880 486 613
404.31 37 3.73 26.11 1109.30 116.60 0.0829 503 635
455.70 37 3.96 27.72 1250.40 131.50 0.0735 538 682
507.74 37 4.18 29.26 1393.10 146.50 0.0660 571 727
631.30 61 3.63 32.67 1732.10 180.10 0.0531 642 825
758.90 61 3.98 35.82 2082.30 216.50 0.0441 709 918
885.84 61 4.30 38.70 2430.60 252.70 0.0378 767 1002

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - IS 398 PART-IV
Actual Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


15 3 2.50 5.39 40.15 4.33 2.3040 73 86
22 7 2.00 6.00 60.16 6.45 1.5410 91 108
34 7 2.50 7.50 94.00 10.11 0.9900 118 141
55 7 3.15 9.45 149.20 16.03 0.6210 156 188
80 7 3.81 11.43 218.26 23.41 0.4250 195 237
100 7 4.26 12.78 272.86 29.26 0.3390 223 271
125 19 2.89 14.45 342.51 36.64 0.2735 254 310
148 19 3.15 15.75 406.91 43.50 0.2290 281 345
173 19 3.40 17.00 474.02 50.54 0.1969 307 378
200 19 3.66 18.30 549.40 58.66 0.1710 334 412
232 19 3.94 19.70 636.67 68.05 0.1471 364 451
288 37 3.15 22.05 794.05 84.71 0.1182 412 515
346 37 3.45 24.15 952.56 101.58 0.0984 457 575
400 37 3.71 25.97 1101.63 117.40 0.0829 503 635
465 37 4.00 28.00 1280.50 136.38 0.0734 539 684
525 61 3.31 29.79 1448.39 146.03 0.0651 576 734
570 61 3.45 31.05 1573.71 158.66 0.0598 603 772
604 61 3.55 31.95 1666.00 167.99 0.0568 620 796
642 61 3.66 32.94 1771.36 178.43 0.0534 641 825
695 61 3.81 34.29 1919.13 193.25 0.0492 670 864
767 61 4.00 36.00 2115.54 213.01 0.0446 705 914
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - AS 1531
Code Name Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


Diamond 34.36 7 2.50 7.50 94.3 9.64 0.9670 120 143
Dolomite 41.58 7 2.75 8.25 113.0 11.60 0.7990 134 161
Emerald 49.48 7 3.00 9.00 135.0 13.90 0.6710 149 179
Garnet 77.31 7 3.75 11.25 211.0 21.70 0.4300 194 234
Jade 111.33 7 4.50 13.50 304.0 31.20 0.2980 240 293
Jasper 124.00 7 4.75 14.25 339.0 34.80 0.2680 256 313
Opal 157.60 19 3.25 16.25 433.0 44.20 0.2120 294 361
Patronite 182.80 19 3.50 17.50 503.0 51.30 0.1830 320 395
Pearl 209.80 19 3.75 18.75 576.0 58.80 0.1590 347 430
Ruby 261.60 37 3.00 21.00 721.0 73.50 0.1280 393 490
Ruthenium 307.00 37 3.25 22.75 845.0 86.10 0.1090 431 540
Rutile 336.70 19 4.75 23.75 924.0 94.40 0.0991 455 571
Sapphire 408.50 37 3.75 26.25 1120.0 115.0 0.0819 506 640
Spinel 506.10 61 3.25 29.25 1400.0 135.0 0.0662 570 726
Tantalum 586.90 61 3.50 31.50 1620.0 156.0 0.0572 617 791
Topaz 673.40 61 3.75 33.75 1860.0 179.0 0.0498 665 857
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - IEC 61089- Type A2
Code Number Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


16 18.4 7 1.83 5.49 50.40 5.43 1.7896 83 98
25 28.8 7 2.29 6.87 78.70 8.49 1.1453 108 129
40 46.0 7 2.89 8.67 125.90 13.58 0.7158 143 172
63 72.5 7 3.63 10.89 198.30 21.39 0.4545 187 226
100 115 19 2.78 13.90 316.30 33.95 0.2877 246 300
125 144 19 3.10 15.50 395.40 42.44 0.2302 280 343
160 184 19 3.51 17.55 506.10 54.32 0.1798 323 399
200 230 19 3.93 19.65 632.70 67.91 0.1439 368 456
250 288 19 4.39 21.95 790.80 84.88 0.1151 417 521
315 363 37 3.53 24.71 998.90 106.95 0.0916 475 598
400 460 37 3.98 27.86 1268.40 135.81 0.0721 543 689
450 518 37 4.22 29.54 1426.90 152.79 0.0641 579 739
500 575 37 4.45 31.15 1585.50 169.76 0.0577 614 786
560 645 61 3.67 33.03 1778.40 190.14 0.0516 652 839
630 725 61 3.89 35.01 2000.70 213.90 0.0458 694 898
710 817 61 4.13 37.17 2254.80 241.07 0.0407 738 961
800 921 61 4.38 39.42 2540.80 271.62 0.0361 785 1027
900 1036 91 3.81 41.91 2861.10 305.58 0.0321 832 1096
1000 1151 91 4.01 44.11 3179.00 339.53 0.0289 876 1160
1120 1289 91 4.25 46.75 3560.50 380.27 0.0258 923 1232
1250 1439 91 4.49 49.39 3973.70 424.41 0.0231 970 1303
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - IEC 61089- Type A3
Code Number Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


16 18.6 7 1.84 5.52 50.80 6.04 1.7896 83 98
25 29.0 7 2.30 6.90 79.50 9.44 1.1453 108 129
40 46.5 7 2.91 8.73 127.10 15.10 0.7158 143 172
63 73.2 7 3.65 10.95 200.20 23.06 0.4545 188 227
100 116 19 2.79 13.95 319.30 37.76 0.2877 246 300
125 145 19 3.12 15.60 399.20 47.20 0.2302 280 344
160 186 19 3.53 17.65 511.00 58.56 0.1798 323 399
200 232 19 3.95 19.75 638.70 73.20 0.1439 368 457
250 290 19 4.41 22.05 798.40 91.50 0.1151 418 522
315 366 37 3.55 24.85 1008.40 115.29 0.0916 476 599
400 465 37 4.00 28.00 1280.50 146.40 0.0721 544 690
450 523 37 4.24 29.68 1440.50 164.70 0.0641 580 739
500 581 37 4.47 31.29 1600.60 183.00 0.0577 614 786
560 651 61 3.69 33.21 1795.30 204.96 0.0516 652 840
630 732 61 3.91 35.19 2019.80 230.58 0.0458 695 899
710 825 61 4.15 37.35 2276.20 259.86 0.0407 739 961
800 930 61 4.40 39.60 2564.80 292.80 0.0361 785 1028
900 1046 91 3.83 42.13 2888.30 329.40 0.0321 833 1097
1000 1162 91 4.03 44.33 3209.30 366.00 0.0289 876 1161
1120 1301 91 4.27 46.97 3594.40 409.92 0.0258 923 1233
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL2
(Used in Finland)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


178-AL2 AAAC 178 178 19 3.45 17.3 487.6 57.73 0.1880 315 388
346-AL2 AAAC 346 346 37 3.45 24.2 952.8 112.41 0.0969 461 579
638-AL2 AAAC 638 638 61 3.65 32.9 1764.0 201.06 0.0527 645 829

ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL2


(Used in Spain)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


28-AL2 D 28 27.8 7 2.25 6.75 76.0 9.05 1.1930 106 126
43-AL2 D 40 43.1 7 2.80 8.40 117.7 14.01 0.7704 137 164
55-AL2 D 56 54.6 7 3.15 9.45 148.9 17.73 0.6087 158 190
76-AL2 D 80 75.5 19 2.25 11.3 207.4 24.55 0.4420 191 231
117-AL2 D 110 117.0 19 2.80 14.0 321.2 38.02 0.2854 247 302
148-AL2 D 145 148.1 19 3.15 15.8 406.5 48.12 0.2255 284 348
188-AL2 D 180 188.1 19 3.55 17.8 516.3 59.24 0.1776 326 402
279-AL2 D 280 279.3 37 3.10 21.7 769.3 90.76 0.1200 408 510
381-AL2 D 400 381.0 61 2.82 25.4 1053.0 123.82 0.0882 486 613
454-AL2 D 450 454.5 61 3.08 27.7 1256.1 147.71 0.0740 536 680
547-AL2 D 550 547.3 61 3.38 30.4 1512.7 177.88 0.0614 594 759
638-AL2 D 630 638.3 61 3.65 32.9 1764.0 201.06 0.0527 645 830

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL2
(Used in Austria)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


24-AL3 25 24.25 7 2.10 6.30 66.2 7.15 1.3566 98 116
34-AL3 35 34.36 7 2.50 7.50 93.8 10.14 0.9572 120 144
49-AL3 50 49.48 7 3.00 9.00 135.1 14.60 0.6647 150 180
66-AL3 70 65.81 19 2.10 10.5 180.7 19.41 0.5026 177 214
93-AL3 95 93.27 19 2.50 12.5 256.0 27.51 0.3546 217 264
117-AL3 120 116.99 19 2.80 14.0 321.2 34.51 0.2827 248 303
147-AL3 150 147.12 37 2.25 15.8 405.3 43.40 0.2256 284 348
182-AL3 185 181.62 37 2.50 17.5 500.3 53.58 0.1827 320 395
243-AL3 240 242.54 61 2.25 20.3 670.3 71.55 0.1373 378 470
299-AL3 300 299.43 61 2.50 22.5 827.5 88.33 0.1112 426 533
400-AL3 400 400.14 61 2.89 26.0 1105.9 118.04 0.0832 502 634
452-AL3 450 451.54 61 3.07 27.6 1247.9 133.20 0.0737 537 681
500-AL3 500 499.83 61 3.23 29.1 1381.4 147.45 0.0666 568 723
626-AL3 625 626.20 91 2.96 32.6 1737.7 184.73 0.0534 640 823
802-AL3 800 802.09 91 3.35 36.9 2225.8 236.62 0.0417 730 948
1000-AL3 1000 999.71 91 3.74 41.1 2774.3 294.91 0.0291 868 1141

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in Germany)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


16-AL3 16 15.9 7 1.70 5.10 43.4 4.69 2.0701 76 90
24-AL3 25 24.2 7 2.10 6.30 66.2 7.15 1.3566 98 116
34-AL3 35 34.4 7 2.50 7.50 93.8 10.14 0.9572 120 144
49-AL3 50 49.5 7 3.00 9.00 135.1 14.60 0.6647 150 180
48-AL3 50 48.3 19 1.80 9.00 132.7 14.26 0.6841 147 177
66-AL3 70 65.8 19 2.10 10.5 180.7 19.41 0.5026 177 214
93-AL3 95 93.3 19 2.50 12.5 256.0 27.51 0.3546 217 264
117-AL3 120 117.0 19 2.80 14.0 321.2 34.51 0.2827 248 303
147-AL3 150 147.1 37 2.25 15.8 405.3 43.40 0.2256 284 348
182-AL3 185 181.6 37 2.50 17.5 500.3 53.58 0.1827 320 395
243-AL3 240 242.5 61 2.25 20.3 670.3 71.55 0.1373 378 470
299-AL3 300 299.4 61 2.50 22.5 827.5 88.33 0.1112 426 533
400-AL3 400 400.1 61 2.89 26.0 1105.9 118.04 0.0832 502 634
500-AL3 500 499.8 61 3.23 29.1 1381.4 147.45 0.0666 568 723
626-AL3 625 626.2 91 2.96 32.6 1737.7 184.37 0.0534 640 823
802-AL3 800 802.1 91 3.35 36.9 2225.8 236.62 0.0417 730 948
1000-AL3 1000 999.7 91 3.74 41.1 2774.3 294.91 0.0334 816 1073

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in Switzerland)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


16-AL3 16 15.9 7 1.70 5.10 43.4 4.69 2.0701 76 90
25-AL3 25 25.2 7 2.14 6.42 68.7 7.43 1.3064 100 119
35-AL3 35 34.9 7 2.52 7.56 95.3 10.30 0.9421 122 145
50-AL3 50 50.1 7 3.02 9.06 136.9 14.79 0.6660 150 180
50-AL3 50 50.0 19 1.83 9.15 137.2 14.74 0.6619 150 181
70-AL3 70 70.3 19 2.17 10.9 192.9 20.73 0.4707 184 223
95-AL3 95 94.8 19 2.52 12.6 260.2 27.96 0.3490 219 267
120-AL3 120 120.4 19 2.84 14.2 330.4 35.51 0.2748 253 308
150-AL3 150 149.7 37 2.27 15.9 412.5 44.17 0.2217 286 352
185-AL3 185 184.5 37 2.52 17.6 508.4 54.44 0.1799 323 399
239-AL3 240 239.4 37 2.87 20.1 659.4 70.61 0.1387 376 467
301-AL3 300 301.3 37 3.22 22.5 830.0 88.88 0.1102 428 536
299-AL3 300 299.4 61 2.50 22.5 827.5 88.33 0.1112 426 533
403-AL3 400 402.9 61 2.90 26.1 1113.6 118.86 0.0826 504 636
497-AL3 500 496.7 61 3.22 29.0 1372.9 146.54 0.0670 566 720
551-AL3 550 550.6 61 3.39 30.5 1521.6 162.42 0.0605 598 765
548-AL3 550 548.4 91 2.77 30.5 1521.8 161.78 0.0610 596 762
600-AL3 600 600.4 61 3.54 31.9 1659.3 177.11 0.0555 627 804
601-AL3 600 601.1 91 2.90 31.9 1668.0 177.32 0.0556 626 804
802-AL3 800 802.1 91 3.35 36.9 2225.8 236.62 0.0417 730 948
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in United Kingdom)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


19-AL3 BOX 18.8 7 1.85 5.55 51.4 5.55 1.7480 84 99
24-AL3 ACACIA 23.8 7 2.08 6.24 64.9 7.02 1.3828 97 115
30-AL3 ALMOND 30.1 7 2.34 7.02 82.2 8.88 1.0926 111 133
35-AL3 CEDAR 35.5 7 2.54 7.62 96.8 10.46 0.9273 123 147
42-AL3 DEODAR 42.2 7 2.77 8.31 115.2 12.44 0.7797 136 163
48-AL3 FIR 47.8 7 2.95 8.85 130.6 14.11 0.6875 147 176
60-AL3 HAZEL 59.9 7 3.30 9.90 163.4 17.66 0.5494 167 202
72-AL3 PINE 71.6 7 3.61 10.8 195.6 21.14 0.4591 186 225
84-AL3 HOLLY 84.1 7 3.91 11.7 229.5 24.79 0.3913 205 248
90-AL3 WILLOW 89.7 7 4.04 12.1 245.0 26.47 0.3665 213 258
119-AL3 OAK 118.9 7 4.65 14.0 324.5 35.07 0.2767 251 306
151-AL3 MULBERRY 150.9 19 3.18 15.9 414.3 44.52 0.2192 288 354
181-AL3 ASH 180.7 19 3.48 17.4 496.1 53.31 0.1830 320 394
211-AL3 ELM 211.0 19 3.76 18.8 579.2 62.24 0.1568 350 433
239-AL3 POPLAR 239.4 37 2.87 20.1 659.4 70.61 0.1387 376 467
303-AL3 SYCAMORE 303.2 37 3.23 22.6 835.2 89.40 0.1095 430 538
362-AL3 UPAS 362.1 37 3.53 24.7 997.5 106.82 0.0917 475 598
479-AL3 YEW 479.0 37 4.06 28.4 1319.6 141.31 0.0693 555 706
498-AL3 TOTARA 498.1 37 4.14 29.0 1372.1 146.93 0.0666 567 722
587-AL3 RUBUS 586.9 61 3.50 31.5 1622.0 173.13 0.0567 620 794
659-AL3 SORBUS 659.4 61 3.71 33.4 1822.5 194.53 0.0505 659 849
821-AL3 ARAUCARIA 821.1 61 4.14 37.3 2269.4 242.24 0.0406 740 962
996-AL3 REDWOOD 996.2 61 4.56 41.0 2753.2 293.88 0.0334 816 1072
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL3
(Used in Italy)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


35-AL3 35/7 34.9 7 2.52 7.56 95.30 10.30 0.9421 122 145
49-AL3 50/7 49.5 7 3.00 9.00 135.10 14.60 0.6647 150 180
68-AL3 70/19 68.3 19 2.14 10.70 187.60 20.16 0.4840 181 219
95-AL3 95/19 94.8 19 2.52 12.60 260.20 27.96 0.3490 219 267
125-AL3 120/19 125.5 19 2.90 14.50 344.50 37.02 0.2636 259 316
147-AL3 150/37 147.1 37 2.25 15.80 405.30 43.40 0.2256 284 348
185-AL3 185/37 184.5 37 2.52 17.60 508.40 54.44 0.1799 323 399
196-AL3 200/37 196.4 37 2.60 18.20 541.20 57.95 0.1690 335 414
244-AL3 240/37 244.4 37 2.90 20.30 673.30 72.10 0.1358 380 473
304-AL3 300/61 304.2 61 2.52 22.70 840.80 89.75 0.1094 430 538
403-AL3 400/61 402.9 61 2.90 26.10 1113.60 118.86 0.0826 504 636

NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL4
(Used in Belgium)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


34-AL4 35 34.4 7 2.50 7.50 93.8 11.17 0.9593 120 144
55-AL4 55 54.6 7 3.15 9.45 148.9 17.73 0.6042 158 190
93-AL4 95 93.3 19 2.50 12.5 256.0 30.31 0.3554 217 264
153-AL4 153 152.8 19 3.20 16.0 419.5 49.66 0.2169 290 356
210-AL4 210 210.3 37 2.69 18.8 579.3 68.34 0.1582 348 431
228-AL4 228 227.8 37 2.80 19.6 627.6 74.04 0.1460 365 453
248-AL4 248 247.8 37 2.92 20.4 682.6 80.53 0.1342 383 476
298-AL4 298 297.6 37 3.20 22.4 819.8 96.71 0.1118 425 531
313-AL4 313 312.6 37 3.28 23.0 861.3 101.61 0.1064 437 547
366-AL4 366 366.2 37 3.55 24.9 1008.9 115.36 0.0908 478 602
446-AL4 446 445.7 61 3.05 27.5 1231.7 144.84 0.0749 532 675
475-AL4 475 475.4 61 3.15 28.4 1313.8 154.50 0.0702 552 701
570-AL4 570 570.2 61 3.45 31.1 1576.0 185.33 0.0585 609 780
621-AL4 621 620.9 61 3.60 32.4 1716.0 195.58 0.0537 638 820
926-AL4 926 926.3 91 3.60 39.6 2570.4 291.77 0.0362 784 1027
117-AL4 117 117.0 19 2.80 14.0 321.2 38.02 0.2833 248 303
148-AL4 148 148.1 19 3.15 15.8 406.5 48.12 0.2239 285 349
182-AL4 182 181.6 37 2.50 17.5 500.3 59.03 0.1831 320 395
198-AL4 198 198.0 37 2.61 18.3 545.3 64.34 0.1680 337 416
265-AL4 265 265.0 37 3.02 21.1 730.1 86.14 0.1255 398 495
288-AL4 288 288.3 37 3.15 22.1 794.3 93.71 0.1154 417 521
318-AL4 318 318.4 37 3.31 23.2 877.1 103.47 0.1045 441 553
709-AL4 709 709.2 91 3.15 34.7 1968.0 230.48 0.0472 684 884
851-AL4 851 850.7 91 3.45 38.0 2360.7 276.47 0.0394 751 979
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.
ALL ALUMINUM ALLOY CONDUCTOR (AAAC) - EN 50182-Type-AL4
(Used in France)
Code Old code Sectional Area Stranding Diameter of Weight Rated Strength DC Resistance @ Current Capacity
Complete 20°C
No. of Aluminium Individual wire
Conductor @ 75°C @ 85°C
Wires diameter

(mm²) (No.) (mm) (mm) (Kg/Km) KN (Ω/Km) (Ampere) (Ampere)


22-AL4 22 22.0 7 2.00 6.00 60.0 7.15 1.4989 92 109
34-AL4 34 34.4 7 2.50 7.50 93.8 11.17 0.9593 120 144
55-AL4 55 54.6 7 3.15 9.45 148.9 17.73 0.6042 158 190
76-AL4 76 75.5 19 2.25 11.3 207.4 24.55 0.4388 192 232
117-AL4 117 117.0 19 2.80 14.0 321.2 38.02 0.2833 248 303
148-AL4 148 148.1 19 3.15 15.8 406.5 48.12 0.2239 285 349
182-AL4 182 181.6 37 2.50 17.5 500.3 59.03 0.1831 320 395
228-AL4 228 227.8 37 2.80 19.6 627.6 74.04 0.1460 365 453
288-AL4 288 288.3 37 3.15 22.1 794.3 93.71 0.1154 417 521
366-AL4 366 366.2 37 3.55 24.9 1008.9 115.36 0.0908 478 602
570-AL4 570 570.2 61 3.45 31.1 1576.0 185.33 0.0585 609 780
851-AL4 851 850.7 91 3.45 38.0 2360.7 276.47 0.0394 751 979
1144-AL4 1144 1143.5 91 4.00 44.0 3173.4 360.22 0.0293 870 1152
1596-AL4 1600 1595.9 127 4.00 52.0 4427.5 502.72 0.0210 1010 1367
NOTE :
Current capacity based on referenced conductor temperature, 0.56 m/s wind, 0 m Elevation, 0.45 Emmisivity, 0.80 absorptivity, 45°C Ambient temperature, 1045 W/m² Solar radiation.
Customized conductor sizes based on customer's requirement can also be designed.