Standard Dimensions
& Joint Detail QuadCore™ t
40 40
Profiled Intermediate
sealing filler support
200 mm
2
Flat Roof Panel KS100 ERO Europanel Jumbo
Product Data Sheet
Length ≤ 3 m ± 5 mm
Length > 3 m ± 10 mm
Width ± 4 mm
Guarantee
Thickness > 100 mm ± 2 mm Kingspan will provide product guarantees on an individual
project basis. Guarantees are typically up to 5 years in a
Squareness of Panel Cut End ≤ 0,6%
non-marine / geothermal environment. All guarantees are
subject to maintenance regime.
Specialist coatings are available for marine and other more
Insulation Core corrosive areas.
QuadCore™ hybrid insulation foam is a thermosetting material.
It does not melt, flow or drip when exposed to fire. It forms
a strong char that helps protect the foam core and prevent Environmental Rating
flame spread within the panels. λ =0.018 W/m.K.
Europanel Jumbo panels are zero ODP (Ozone Depleting
Potential) and have a low GWP (Global Warming Potential.
Panels are CFC, HCFC and HFC-free, free from halogenated
flame retardants and 100% recyclable.
3
Flat Roof Panel KS100 ERO Europanel Jumbo
Product Data Sheet
Pressure 6,74 5,17 4,13 3,29 2,55 1,97 1,55 1,25 1,02
Single 100
Suction -6,97 -5,52 -4,54 -3,66 -2,95 -2,43 -2,04 -1,74 -1,50
Pressure 6,74 5,17 4,13 3,29 2,55 1,97 1,55 1,25* 1,02*
Double 100
Suction -6,97 -5,52 -4,54 -3,83 -3,29 -2,86 -2,52 -2,25* -2,01*
Pressure 6,74 5,17 4,13 3,29* 2,55* 1,97* 1,55* 1,25* 1,02*
Triple 100
Suction -6,97 -5,52 -4,54 -3,83* -3,29* -2,86* -2,52* -2,25* -2,01*
1 Values have been calculated using the method described in BS EN 14509, for color group 1.
2 The following deflection limits have been used:
– Pressure loading L /200.
– Suction loading L /200.
3 The above-mentioned calculations apply to panels with standard steel skin strength specification:
– fy=350 MPa (S350GD) for the INTERNAL trapezoidal skin
– fy=250 MPa (S250GD) for the EXTERNAL skin with Box linear.
4 All panel thicknesses have been calculated with a minimum support width of 200 mm. Larger support widths are possible.
5 The actual wind suction resisted by the panel is dependent upon the number of fasteners.
6 The fastener calculation should be carried out in accordance with the appropriate standards. Kingspan recommends WKRET-MET KLIMAS
screws that have tight screw thread pitch. The actual span resisted by the panel is dependent on the number of fasteners. Each project must
be checked by Kingspan Technical Department Structural Engineer.
7 For intermediate values linear interpolation may be used.
8 The allowable steelwork tolerance between bearing planes of adjacent supports is ± 5mm.
* The mentioned spans are possible but the maximum length a single panel can be manufactured is defined by logistical limitations e.g. 11,95m
for containers. Contact Kingspan Customer Service for special length requirements.