DeltaV SIS Process Safety System Product Data Sheet

February 2021

DeltaV Safety Instrumented System (SIS)™


with IS Electronic Marshalling
„ Intrinsically Safe I/O anywhere you need it

„ Integrated galvanic isolation per channel

„ Optimized process reliability

„ Simplified safety lifecycle management

„ Flexibility to meet project needs

„ Reduces installed cost of system

„ Field mounted capable hardware

Introduction
The DeltaV SIS process safety system has a uniquely scalable
modular architecture that is based on the CHARMs Smart
Logic Solver (CSLS) and the unprecedented flexibility and ease
of use of the Emerson Electronic Marshalling solution. Each
CSLS provides I/O processing, SIL 3-capable logic solving,
and diagnostics in a single logic solver. The CSLS supports up
to 96 individually configurable channels, allowing flexibility for
implementing safety instrumented functions and is designed
specifically for multi-core home run cables or field junction box
installation. All communications are completely redundant
from the channel (LS IS CHARM) to the CSLS. Integrated
HART® I/O brings field diagnostics into the CSLS.

The addition of Intrinsically Safe (IS) LS CHARMs provides


significant savings in system design, installation cost, and ease
of maintenance expected with Electronic Marshalling, with the
added safety for field wiring to hazardous areas. The reduced
footprint and associated elimination of separate barriers
and the associated inter cabinet wiring makes for a more robust The DeltaV SIS process safety system has the world’s first CSLS,
installation with significant cost savings. using the power of predictive intelligence to increase the availability
of the entire safety instrumented function in combination with the
advantages of the Emerson Electronic Marshalling solution, using
IS LS CHARMs.
DeltaV SIS with IS Electronic Marshalling February 2021

Benefits CHARM to provide single channel fault isolation as well as


electrical isolation and energy limiting circuitry that meets
Optimized process reliability. Emerson has extended the IEC Ex ia ratings.
benefits of the PlantWeb® architecture to SIS’, with DeltaV SIS
Reduces installed cost of system. DeltaV SIS Electronic
using Intrinsically Safe (IS) LS CHARMs being a key component
Marshalling helps reduce overall system costs by eliminating
of the Smart SIS solution. Research shows that more than
internal cabinet cross wiring, reducing overall footprint,
90% of all faults in SIS applications occur in field instruments
simplifying SIF design, and reducing Factory Acceptance Test
and final elements. The DeltaV SIS process safety system
(FAT) activities. Electronic Marshalling provides separation
has the world’s first Smart Logic Solver using LS IS CHARMs.
between I&E hardware installation schedules and SIF
It communicates with intelligent field devices using the HART
development. Wiring can begin earlier knowing any late
protocol to diagnose faults before they cause spurious trips.
changes can be done without lifting a wire. The ability to read
This approach increases process availability and reduces
any input on the LSN allows more efficient cabinet designs
lifecycle costs.
and accommodates late scope changes to add I/O anywhere.
Flexibility to meet project needs. Whether you have an Adding additional SIF capacity does not require re-wiring I/O.
isolated wellhead or a large emergency shutdown device (ESD) Simply read the I/O signals from the proper CSLS, without lifting
application, the DeltaV SIS system scales to provide you with a wire.
the safety coverage you need for your SIL 1, 2 and 3 safety
Fully redundant communications. The CSLS architecture is
functions. Each CSLS provides I/O processing, SIL 3-capable
fully redundant. It starts with the two logic solvers on a carrier.
logic solving, and diagnostics. This means that processing
The carrier has redundant Safety Nework Ports (SNP) for
power is added as the system expands, and no additional
communication with primary and secondary LSN connections.
processors will ever be required. Scan rate and memory
There are two 24V DC input power connections. The carrier
usage are constant and independent of system size.
connects to the CHARM baseplates providing redundant power
Modularity also provides isolation of safety instrumented and communication buses to the LS IS CHARMs. Everything is
functions (SIFs). This isolation eliminates single-points of redundant down to the individual channel.
failure for improved availability and safety integrity.
Field mounted capable hardware. All components of the CSLS
The DeltaV SIS system looks for new hardware every scan, are rated for installation in Class 1/Div 2 or Zone 2 hazardous
so equipment can be added to a running system in real locations. The extended operating temperature ranges and G3
time. Online addition of new logic solvers will not interrupt environment rating allows them to be installed in field mounted
your process. junction boxes. This further reducing the footprint required in
central equipment rooms, as well as reduces the overall wiring
Simplified safety lifecycle management. The DeltaV SIS CSLSs
infrastructure of traditional multi-core instrumentation cable.
are SIL 3-rated for both simplex and redundant architectures.
Redundant pairs of CSLSs can be installed for increased process Plug and Play I/O. The DeltaV SIS CSLS has been designed
availability of your SIFs. for ease of use, both in physical installation and its software
tools. Components snap together with secure DIN-rail latches
Intrinsically Safe I/O anywhere you need it. The DeltaV SIS
and interlocking carrier connectors. Attach a series of 96 I/O
CSLS provides an unprecedented flexibility in safety system
channels to a DIN-rail in a matter of minutes. Insert the LS IS
I/O topology. Using standard Ethernet infrastructure hardware
CHARMs and auto sense the node to create the I/O definition
you can add safety related I/O anywhere you need it. From a
automatically in your DeltaV SIS configuration database. LS IS
local I/O cabinet to remote enclosures miles away, simply
CHARMs use a self keying system to automatically set a channel
install the CSLS and connect it to the LSN. Each CSLS can read
for a specific LS IS CHARM type. Users cannot mistakenly insert
the input signals from any other CSLS on the same LSN every
a LS IS CHARM into the wrong terminal block.
50 ms, the same as the inputs wired directly to its own LS IS
CHARM system. Field power is provided through a redundant 24V DC bus to
each LS IS CHARM. Each LS IS CHARM provides galvanically
Integrated galvanic Isolation per channel, each I/O channel
isolated field power through an internal isolation transformer,
has a dedicated LS IS CHARM that provides both signal
eliminating external wiring to barriers.
characterization and galvanic isolation for intrinsically
safe applications. IS barriers are integrated inside the LS IS

www.emerson.com/deltav 2
DeltaV SIS with IS Electronic Marshalling February 2021

Product Description The only difference between the two CSLSs is that one
communicates with the engineering and operator workstations
as well as the dedicated LSN. This CSLS has the Active light
For Use in SIL 3 Applications illuminated. The other CSLS is communicating only with
With a safe failure fraction (SFF) greater than 99%, both simplex the LSN.
and redundant installations of the DeltaV SIS CSLS meet the SIL
3 requirements of IEC 61508 with no restrictions. Redundant Logic Solver Switchover
CSLSs increase availability, but because both simplex and
In the event that a failure is detected in one of the CSLSs, the
redundant CSLSs provide hardware fault tolerance and safe
CSLS will automatically go into a failed state. In this condition,
failure fraction to meet SIL 3 requirements, redundancy does
there is no impact to the partner CSLS or the physical outputs.
not increase safety.
The partner CSLS continues to read inputs, execute logic, and
drive outputs. The transition from redundant to simplex is
SIF-based Approach completely bumpless.
The DeltaV SIS system design was based on IEC 61511 SIF
Both logic solvers in a redundant pair are monitored for
concept, where every logic solver is a container for a small
integrity alarms at all times, and an integrity error in either
number of SIFs. Unlike other system architectures, with
CSLS will notify the operator of a failure. Events that can cause
modular logic solving architecture, the logic solver is no longer
integrity alarms include:
a single point of failure for the entire process. If failures were
to occur, only the equipment tied to the logic solver would „ Hardware failure within a logic solver,
be affected. „ Communications failure between a logic solver and the LSN,
The DeltaV SIS SIF-based approach does not mean that all „ Communications failure between a redundant pair of logic
of the safety logic and I/O have to fit into one logic solver. solvers, and
All input data is made available to every logic Solver on the
LSN every 50ms the same as the local inputs on every CSLS. „ Removal of a logic solver from the carrier.

With DeltaV SIS logic solvers, neither the scan rate nor The health and status of both logic solvers and their channels
the execution of a SIF is altered by changes or additions are available in the Diagnostics Explorer.
to another SIF. DeltaV SIS logic solvers always execute When one CSLS of a redundant pair of logic solvers is removed
deterministically, every 50 ms, regardless of how much online, there is no disturbance to the process. When the
I/O is running on the system. missing CSLS is replaced with another, the new CSLS completes
its power-up self-tests before the active CSLS cross-loads the
Redundancy current database. In safe areas, failed CSLSs can be replaced
The redundant logic solvers include two CSLSs installed side-by- under power. In hazardous areas, appropriate installation
side on the CSLS Carrier. The CSLS Carrier has redundant power procedures must be followed.
and communication connections to the baseplates that are
wired to the field devices. Each CSLS of the redundant pair has Online proof testing
a separate power supply. Online proof testing can be performed on a redundant
No control strategy configuration is required to take advantage pair of logic solvers. The desired proof-test interval is set in
of CSLS redundancy because the DeltaV SIS auto-sense the configuration. The logic solvers perform the proof test
capability automatically recognizes the redundant pair of cards. automatically, with a warning provided to the operator before
the automatic proof test is started.
When redundancy is chosen, the two CSLSs run in parallel
at all times. Both read the inputs from the I/O terminals,
both execute the logic and both drive the outputs at the I/O
terminals. There is no concept of primary and backup or master
and slave, which is unlike any other safety system.

www.emerson.com/deltav 3
DeltaV SIS with IS Electronic Marshalling February 2021

Diagnostics The DeltaV SIS logic solver can also generate HART commands
to initiate a partial stroke test in a digital valve controller. The
The DeltaV SIS logic solvers execute extensive self-testing on a
operators can initiate partial stroke tests manually from their
continuous basis to detect potential faults. Faults detected by
operator workstations or they can be scheduled to occur
logic solver diagnostics can be associated with the logic solver
automatically based on the specified test interval. The results
itself or associated with field devices, field wiring, or other
from these tests are captured and integrated with the system
conditions not related to hardware.
event history. An alarm can be generated if a partial stroke test
DeltaV SIS provides standard alarms to annunciate faults fails, alerting maintenance that there is a potential problem
detected by logic solvers in the operator interface. No special with a valve.
configuration is required. When a diagnostic alarm occurs, it
appears on the alarm banner of the operator interface. The DeltaV SIS Electronic Marshalling
operator is shown the type of alarm (failed, maintenance, etc.), hardware includes:
as well as text for the active condition or “multiple conditions” if
„ CSLS Carrier (DIN rail mounted and supports a redundant
more than one alert condition is active for the particular alarm.
pair of CSLSs, redundant 24V DC power connectivity, and
redundant Ethernet Safety Network communication Ports).
Sequence of Events Capability
„ CSLS (provides redundant safety logic processing and
With DeltaV SIS, events are automatically generated as function
communication to up to 96 LS IS CHARMs).
blocks are executed within a module scan. Events are time
stamped with a resolution of <1 ms, and they are recorded in „ IS CHARM base plate (DIN rail mounted with interleaving
the sequence that they occur in the Event Chronicle. When power and bus connectors. Supports 12 LS IS CHARMS and
using standard function blocks such as input blocks, voter their terminal blocks).
blocks, and cause and effect blocks, a standard set of events
„ IS CHARM Terminal Block (removable terminal block
are automatically generated without special configuration or
providing terminal connections to field wiring and physical
programing required. For example, I/O failures, trip limits, first-
latch for LS IS CHARM).
outs, and other similar events are automatically time stamped
by function blocks and recorded in the Event Chronicle. When „ LS IS CHARMs (Logic Solver Characterization Module for each
a process variable exceeds the trip limit, DeltaV SIS records the field signal. Provides basic analog to digital conversion and
event along with the analog value and the trip condition. signal isolation to the redundant communication bus).

In general, when there is a plant event that triggers an ESD „ Cable Extenders that provide flexibility in carrier mounting.
from the SIS, one input will exceed a trip limit on one scan and
„ I/O bus termination (provides bus terminations for redundant
this will cause outputs to trip and more inputs will then change
I/O bus).
state. Sequence of Events Recording has been used to find that
first input that caused the trip by looking at all of the inputs „ Labeling features for base plate and channel identification.
in the plant. With the DeltaV SIS system, the operator simply Intrinsically Safe (IS) LS CHARMs are designed to meet IEC EX ia
filters the Event Chronicle for first-out trips, and the first-out is level of safety and are suitable for connecting to field devices
clearly visible. installed in Class 1 Division 1 Hazardous Locations or Zone 1/0
If higher resolution is required for some channels then they can Hazardous Areas. The CSLS and LS IS CHARMs are rated for
be wired to both the DeltaV SIS Logic Solver and also to a DeltaV installation in a Class 1 Division 2 Hazardous location, a Zone 2
Discrete Input Card for Sequence of Events, which provides a hazardous area or in the safe area.
resolution of 0.25 ms. The CSLS carrier is mounted to the top of a vertical DIN
rail and up to eight IS CHARM Baseplates are mounted below
Integrated HART it, snapping easily to the DIN rail as they are connected to
Integrated HART I/O brings field diagnostics into the logic each other. The bus termination assembly is attached at the
solver. Field device diagnostics information is not just for bottom. A standard DIN-rail lock is used to keep the entire
pass-through to AMS Device Manager; it is available inside assembly in place.
the logic solver.

www.emerson.com/deltav 4
DeltaV SIS with IS Electronic Marshalling February 2021

A pair of CSLSs installs on the carrier and communicates over a LS IS CHARMs can be added to any existing baseplate position
redundant Ethernet safety network with up to 15 other CSLSs and autosensed online. Additional CSLSs can be added online.
and 1 SZ controller, allowing great flexibility and ease of system
expansion. Safety Network Ports are available for copper only. LS IS CHARM Types
SZ controllers connect to both the area control network and A variety of analog and discrete LS IS CHARMs are available to
the LSN to isolate the CSLSs from the process control system. meet your specific requirements. The following LS IS CHARMs
The SZ controllers has replaceable Ethernet Isolation Ports for are available starting with v12.3.x:
connection to both LSN and the DeltaV Area Control network.
„ LS IS AI 4-20 mA HART
Starting in DeltaV v14.3 a new Keylock Ethernet Isolation Port,
in yellow color plastic, which enable the key inhibit unlock „ LS IS DI NAMUR
switch on the carrier to allow the key to inhibit the unlock
The following LS IS CHARMs are available starting v13.3.x:
command to all CSLSs on the LSN.
„ LS IS RTD
Only DeltaV SIS Smart Switches are supported on the LSN.
„ LS IS Thermocouple /mV
Each IS baseplate is ordered pre-loaded with 12 IS terminal
blocks that are ready to receive field wires from two-, three-, All LS IS CHARMs have a bi-color Power/Integrity LED that
and four-wire devices. Electronic Marshalling eliminates the indicates the health of the LS IS CHARM. The indications provide
need to partition the I/O wiring to specific channels based on clear, actionable instruction to the maintenance personnel.
signal type. Simply connect field signal multi-cores in an orderly
Green Solid: Normal Operation
fashion as desired. Install the appropriate LS IS CHARM to
complete the field circuit and the signal is ready to be used by Green Blink: Normal awaiting configuration
the CSLS. No cross-wiring required. Red Blink: Fault detected on wiring
All LS IS CHARMs are energy limited devices that prevent Red Solid: Internal Fault detected]
the possibility of an explosion, even if wires are accidently
shorted together. In addition, each LS IS CHARM acts as a Discrete LS-CHARMs have a Yellow LED to indicate the state of
circuit protection device and field wiring disconnect. Each LS IS the field signal. (On = circuit is energized)
CHARM provides surge protection to meet industry standards All LS-CHARMs meet ISA 71.04-1985 severity level G3 (harsh)
in the area of EMC. Under extreme overvoltage conditions due corrosion specifications
to incorrect field wiring, the LS IS CHARM will act as a fuse to
protect adjacent channels. Signal faults are thus isolated to the I/O Terminal Block Options
single LS IS CHARM.
LS IS CHARMs are designed to work with the IS Terminal Blocks,
LS IS CHARMs can be partially ejected to a locked position that which are light blue in color, designating the field wiring as
disconnects the field wiring from the system to perform field intrinsically safe. LS IS CHARMs are mechanically different and
maintenance actions or to remove power to a field device. will not install in non-IS terminal blocks, ensuring there is no
Activating the LS IS CHARM latch ejects the LS IS CHARM to error in the installation.
the detent position. Closing the latch locks the LS IS CHARM in
place and isolates the field wiring for field work. There are two different IS Terminal blocks available to meet the
wiring needs of field signals.
IS baseplate extenders and cables provide great flexibility to
the IS CHARM installation in existing cabinets or in custom „ IS Standard Terminal Block
enclosures. Cables are redundant, each carrying 24V DC „ IS Thermocouple / mV Terminal Block
field power, 6.3V DC LS-CHARM power and one of the
communication busses. The IS Terminal block has four terminals, supporting the
traditional discrete and analog two- and four-wire sensor
Bus termination provides added robustness for the field instrumentation signals as well two-, three-, and four-wire
communication bus and is installed at the end of the RTD Sensors.
physical bus.

Label features are available to identify channel usage and


baseplate identification to help with maintenance.

www.emerson.com/deltav 5
DeltaV SIS with IS Electronic Marshalling February 2021

The IS Thermocouple / mV Terminal Block is specially


designed for the usage with the LS IS Thermocouple / mV
CHARM. The IS Thermocouple / mV Terminal Block and
LS IS Thermocouple / mV CHARM can only be ordered as
an assembly.

LS IS CHARM Keying Posts


The IS Terminal Blocks contain keying posts that are
automatically set and locked to the unique position of the
installed LS IS CHARM. The keys prevent the insertion of an
incorrect LS IS CHARM during maintenance activities. The IS
Terminal Blocks are shipped with the keys in a neutral position
and are set when an LS IS CHARM is inserted. If needed, the keys
can be manually reset to allow a channel to be re-tasked for a
different signal type.

The keying mechanism consists of two keying posts that rotate


and lock into the IS terminal block base. Each LS IS CHARM type
is assigned a unique key setting.

IS CHARM Baseplates
IS CHARM baseplates are mechanically different than non-IS
baseplates, ensuring there is no error in the installation of the
IS CHARM Standard Terminal Block. Terminal Blocks or CHARMs (non-IS). A baseplate separator
is needed on the beginning and on the end of any IS CHARM
baseplate row, also in between any of the IS CHARM baseplates.
You can add IS CHARM baseplates to non-IS CHARM baseplates
and any of the other components, like the CSLS carrier, CHARM
baseplate extenders and CHARM baseplate terminators.

DeltaV SIS CSLS Capacities


Item Limit
Maximum number of CSLSs on a single SZ Controller 16

Maximum number of Remote I/O Nodes (CIOCs and/or WIOCs) reporting to a single SZ Controller. 4

Maximum number of secure parameters per CSLS 96

Maximum number of CSLS I/O channels on a single SZ Controller: 96 CHARMs I/O channels × 16 CSLS. 1536

Maximum number of CSLSs in a single DeltaV SIS system: 100 SZ controllers × 16 CSLS per SZ controller. 1600

www.emerson.com/deltav 6
DeltaV SIS with IS Electronic Marshalling February 2021

Hardware Specifications
Common Environmental Specifications (all components)
Operating temperature * -40 to 70°C (-40 to 158°F)

Storage temperature -40 to 85°C (-40 to 185°F)

Relative humidity 5 to 95% , non-condensing

Protection rating IP 20

Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3 Conformal coating

Shock 10 g ½-sine wave for 11 ms

Vibration 1mm Peak-to-Peak from 2 to 13.2 Hz; 0.7g from 13.2 to 150 Hz.
*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.

SZ Controller shown on Dual Vertical Safety Carrier.

www.emerson.com/deltav 7
DeltaV SIS with IS Electronic Marshalling February 2021

SZ Controller Ethernet Isolation Port or Keylock Ethernet Isolation Port.

SZ Controller shown on Dual Horizontal Safety Carrier.

www.emerson.com/deltav 8
DeltaV SIS with IS Electronic Marshalling February 2021

CSLS shown on CSLS Carrier.

CSLS Safety Network Port.

www.emerson.com/deltav 9
DeltaV SIS with IS Electronic Marshalling February 2021

IS CHARM Baseplate with Separator, IS CHARMs and Label Plates in Place.

CHARM Baseplate Terminator Top.

CHARM Baseplate Terminator Bottom.

www.emerson.com/deltav 10
DeltaV SIS with IS Electronic Marshalling February 2021

CHARM Baseplate Extender Top.

CHARM Baseplate Extender Bottom.

LS IS CHARM.

www.emerson.com/deltav 11
DeltaV SIS with IS Electronic Marshalling February 2021

IS CHARM Terminal Block.

IS CHARM Thermocouple / mV Terminal Block.

www.emerson.com/deltav 12
DeltaV SIS with IS Electronic Marshalling February 2021

Address Plug.

Address Plug Terminal Block for IS Baseplate.

www.emerson.com/deltav 13
DeltaV SIS with IS Electronic Marshalling February 2021

SZ Controller Hardware
Specifications for SZ Controller and Carriers
Capacity One (simplex) or two (redundant) SZ Controllers

Input Power +24V DC ±10% at 1 A maximum

Battery Power +5.0 to +12.6V DC at 30 uA typical

Redundant Ethernet Connections Through Copper twisted pair: 10/100BASE-TX with RJ45 connectors;
Replaceable Ethernet Isolation Ports (EIPs) or Full duplex operation - 100 m distance
Keylock Ethernet Isolation Ports
Dual Vertical Safety Carrier Mounting DIN rail latch to vertical orientated T-type rail

Dual Horizontal Safety Carrier Mounting DIN rail latch to horizontally orientated T-type rail

Specifications for SZ Controller


Number of SZs per System 100

Input Power +24V DC ± 10% at 325 mA maximum for simplex; 575 mA maximum for redundant

Heat Dissipation (Redundant) Seven Watts maximum for simplex; 13 Watts maximum for redundant

Fuse Protection (Internal) Internal non-replaceable fuse

Mounting One or two slots on the Dual Vertical or Horizontal Safety Carrier

Communication Redundant Ethernet connections through Dual Vertical


or Horizontal Safety Carrier to the:
a) LSN
b) Area Control Network (ACN) or Modbus TCP ports
Network Addressing Auto Assigned during commissioning

Modbus TCP Addressing Manual, Slave only

DST Limit 400

Max Data Values Sent 4000/second

Max Data Values Received 500/second

Max Unsolicited Client Nodes 120

BPCS Module Execution Rates 100ms, 200ms, 500ms, 1s, 2s, 5s, 10s, 30s, 60s

LED Indicators
Green – Power Indicates DC power is applied.

Red – Error Indicates an error condition.

Green – Active/Standby Indicates operating mode of each SZ

Yellow Flashing – Pri./Sec. CN Indicates valid control network communication

www.emerson.com/deltav 14
DeltaV SIS with IS Electronic Marshalling February 2021

CSLS Hardware
Specifications for CSLS Carrier
Capacity One (simplex) or two (redundant) CSLS and one (simplex) or
two (redundant) Power Modules
Input Power (Redundant) +24V DC ± 10% at 12.5 A maximum

Output Power to SIS CHARMs +24V DC ± 10% at 10 A maximum

Redundant Ethernet Connections Through Replaceable Safety +6.3V DC at 4 A maximum

Network Ports (SNPs) Copper twisted pair: 10/100BASE-TX with RJ45 connectors;
Full duplex operation - 100 m distance
Mounting DIN rail latch to vertical orientated T-type rail

Specifications for CSLS


Number of I/O Channels 96 Channels, Individually defined signal types

Number of CSLSs per SZ Controller 16

Number of CSLSs per System 1600

I/O Update Rates 50ms

Power Requirement of CSLS +24V DC ± 10% at 325 mA maximum for simplex;


575 mA maximum for redundant (CHARMs are additional)
Power Requirement of Power Modules +24V DC ± 10% at 1.5 Amps maximum simplex and redundant

Power Modules Output to LS-CHARMs +6.3V DC ± 3% at 4 Amps maximum

Heat Dissipation per Carrier with Redundant CSLS Pair 18 Watts maximum, which includes:
„ 13 Watts for redundant CSLS (7 Watts for simplex)
„ Three Watts for redundant Power Modules
„ One Watt per Safety Network Port

Fuse Protection (Internal) Internal non-replaceable fuse

Mounting One or two slots on the CSLS Carrier

Communication Redundant Ethernet connections through CSLS Carrier SNPs

Network Addressing Auto Assigned during commissioning

LED Indicators

Green – Power Indicates DC power is applied.

Red – Error Indicates an error condition.

Green – Active/Standby Indicates operating mode of each CSLS

Yellow Flashing – Pri./Sec. CN Indicates valid control network communication.

www.emerson.com/deltav 15
DeltaV SIS with IS Electronic Marshalling February 2021

IS CHARMs Baseplate Hardware


Specifications for IS CHARM Baseplate
Number of Channels per Baseplate 12

Number of Baseplates per CSLS Eight

Addressing One Address Plug (One through Eight)

Terminal Blocks IS Standard Terminal Block (Light Blue)


IS Thermocouple / mV Terminal Block (Light Blue)
Shield Connections One Screw Cage terminal per channel, plus One for cable shield
0.32 – 2.5 mm2 / 22 – 14 AWG
Gold-plated connectors for shield continuity
Wire Strip Length 7 - 9 mm / 0.28 – 0.36 in.

Mounting DIN rail Latch to T-type rail

Specifications for Baseplate Termination, Top and Bottom


Shield Connections Two Screw Cage Terminals
0.32 – 2.5 mm2 / 22 - 14 AWG
Wire Strip Length 7 - 9 mm / 0.28 – 0.36 in.

Specifications for Baseplate Extenders, Top and Bottom


Primary Bus Connection Nine-pin D-shell,
Primary RS-485 communications bus Primary 24V DC field
power Primary CHARM power
Secondary Bus Connection Nine-pin D-shell,
Secondary RS-485 communications bus Secondary 24V DC
field power Secondary CHARM power
Specifications for Extender Cables
Maximum Bus Length A maximum of four extender pairs can be used and only one
extender pair can exceed 0.5 meters (1.64 feet).
Available Cable Lengths 2 m, 1 m, 0.5 m (6.7 ft, 3.3 ft, 1.6 ft )

www.emerson.com/deltav 16
DeltaV SIS with IS Electronic Marshalling February 2021

Specifications for IS Terminal Block


Number of Connections Four Screw Cage terminals
0.32 – 2.5 mm2 / 22 – 14 AWG
Strip Length 7 - 9 mm / 0.28 – 0.36 in.

Maximum Current 45 mA at 28V DC max.*

Color Light Blue

Specifications for IS Thermocouple / mV Terminal Block


Number of Connections Two Screw Cage terminals
0.32 – 2.5 mm2 / 22 – 14 AWG
Strip Length 7 - 9 mm / 0.28 – 0.36 in.

Color Light Blue

Specifications for Address Plug Terminal Block


Number of Connections none

Color Black

*Actual Current draw is determined by type of CHARM and associated field devices.

www.emerson.com/deltav 17
DeltaV SIS with IS Electronic Marshalling February 2021

LS IS Analog Input CHARM


Specifications for LS IS AI 4-20 mA HART CHARM
Sensor Types 4-20 mA with or without HART
Supports two-wire and four-wire device types
Nominal Signal Range (Span) 4-20 mA, (0-20 mA optional)

Full Signal Range 0 to 22 mA

Input Impedance 360 Ω

Field Power (2-wire) 16.0 V(min) at 20 mA

Accuracy Over Temperature Range 0.1% of span (0-60°C)


0.25% of span (over -40 -70°C)
Repeatability 0.05% of span

Resolution 16 bit A/D converter

Calibration None required

DC/50/60 Hz Common Mode Rejection N/A

Isolation Galvanically isolated according to EN 60079-11.


Voltage peak value 375V DC.
CHARM Power Req. 60 mA max @ 24V DC ±10%

CHARM Heat Dissipation 0.86 W

HART Support HART v7 pass-through for AMS


HART v7 variable and device status available to control
HART Data Update Rates Typically less than one second but dependent on HART
communication loading and the capability of the HART device

www.emerson.com/deltav 18
DeltaV SIS with IS Electronic Marshalling February 2021

Simplified Circuit and Connection Diagrams for LS IS AI-CHARM 4 to 20 mA HART Two-Wire and Four-Wire transmitters.

www.emerson.com/deltav 19
DeltaV SIS with IS Electronic Marshalling February 2021

LS IS RTD CHARM
Specifications for LS IS RTD Input CHARM
Sensor Types RTD input (Types listed in Table)

Sensor Configuration Two-Wire, three-wire, or four-wire

Full Scale Signal Range See Table next page

Accuracy See Table next page

Repeatability 0.05% of span

Resolution 24 bit A/D converter / Depends upon the sensor type

Calibration None required

Sensor Excitation Current 0.5 mA in Two-Wire and four-wire configurations


0.25 mA in 3-wire
DC/50/60 Hz Common Mode Rejection 90dB typical

Isolation Galvanically isolated according to EN 60079-11.


Voltage peak value 375V DC.
Open Sensor Detection Yes

CHARM Power Req. 23 mA max @ 24V DC

CHARM Heat Dissipation 0.60 W

RTD, ohms Sensor Type Specifications


25° Reference Temperature Drift
Sensor Type Operating Range Resolution
Accuracy (4-wire) (4-wire)
Pt100 -200 to 850°C ± 0.50°C ± 0.015°C/°C ~0.02° C
Pt200 -200 to 850°C ± 0.40°C ± 0.014°C/°C ~0.02° C
Pt500 -200 to 850°C ± 0.34°C ± 0.014°C/°C ~0.02° C
Pt1000 -200 to 260°C ± 0.14°C ± 0.006°C/°C ~0.01° C
Ni120 -80 to 260°C ± 0.18°C ± 0.003°C/°C ~0.01° C
Ni100 -80 to 260°C ± 0.12°C ± 0.003°C/°C ~0.01° C
Ni200 -80 to 260°C ± 0.11°C ± 0.003°C/°C ~0.01° C
Ni500 -80 to 260°C ± 0.08°C ± 0.003°C/°C ~0.01° C
Ni1000 -80 to 140°C ± 0.06°C ± 0.003°C/°C ~0.01° C
Cu10 -200 to 260°C ± 0.70°C ± 0.020°C/°C ~0.01° C
Resistance/User Defined* 0 to 2,000 Ω ± 0.50 Ω ± 0.020 Ω/°C ~0.031 Ω
* The Callendar-Van Dusen linearization equation can be used with user defined Pt RTDs.
Refer to Recommended I/O Practices in DeltaV Books online for usage information.

www.emerson.com/deltav 20
DeltaV SIS with IS Electronic Marshalling February 2021

Simplified Circuit and Connection Diagrams for LS IS RTD CHARM.

LS IS Thermocouple / mV CHARM
Specifications for LS IS Thermocouple/mV Input CHARM
Sensor Types B, E, J, K, N, R, S, T, uncharacterized
•Thermocouple Low level voltage source (±20 mV, ±50 mV, and ±100 mV)
•mV
Full Scale Signal Range See Table next page

Accuracy See Table next page

Repeatability 0.05% of span

Resolution 24 Bit A/D converter / Depends upon the sensor type

Calibration None required

Cold Junction Compensation(CJC) Accuracy Range ± 0.7°C


-40 to 85°C
Temperature Drift 0.03°C/°C

Isolation Galvanically isolated according to EN 60079-11,


voltage peak value 375V DC.
Open Sensor Detection Yes

CHARM Power Req. 23 mA max @ 24V DC

CHARM Heat Dissipation 0.60 W

www.emerson.com/deltav 21
DeltaV SIS with IS Electronic Marshalling February 2021

Sensor Type Specifications


Sensor 25° Reference Temperature Nominal Full Operating
Type Accuracy1 Drift Resolution Scale Range
B ± 2.50°C ± 0.07°C/°C ~0.024°C 0 to 1820°C 250 to 400°C
± 1.70°C ± 0.05°C/°C 400 to 1820°C
E ± 0.60°C ± 0.03°C/°C ~0.018°C -270 to 1000°C -200 to 1000°C

J ± 0.70°C ± 0.03°C/°C ~0.022°C -210 to 1200°C -200 to 1200°C

K ± 1.20°C ± 0.05°C/°C ~0.025°C -270 to 1372°C -200 to 1370°C

N ± 1.10°C ± 0.04°C/°C ~0.024° C -270 to 1300°C -200 to 1300°C

R ± 1.70°C ± 0.06°C/°C ~0.028°C -50 to 1768°C -50 to 1767°C

S ± 1.90°C ± 0.07°C/°C ~0.028°C -50 to 1768°C -50 to 1767°C

T ± 0.70°C ± 0.02°C/°C ~0.01°C -270 to 400°C -200 to 400°C

± 100 mV 50 μV ± 2.5 μV/°C ~0.0031mV -100 to 100 mV -100 to 100 mV

± 50 mV 40 μV ± 1.7 μV/°C ~0.0015mV -50 to 50 mV -50 to 50 mV

± 20 mV 20 μV ± 0.8 μV/°C ~0.0006mV -20 to 20 mV -20 to 20 mV


1
Total error is made up of the 25 C reference accuracy value, plus the CJC accuracy value, plus the sensor accuracy value

Simplified Circuit and Connection Diagram for LS IS Thermocouple/mV CHARM with IS Thermocouple/mV Terminal Block.

www.emerson.com/deltav 22
DeltaV SIS with IS Electronic Marshalling February 2021

LS IS Discrete Input CHARM


Specifications for LS IS DI NAMUR CHARM
Sensor Types NAMUR Sensors, Dry Contacts

Detection Level for On > 2.1 mA

Detection Level for Off < 1.2 mA

Channel Impedance 1kOhm ± 10%

Wetting Voltage 8V DC ± 1V DC

Fault detection capable with NAMUR sensor or with an optional „ Guaranteed short circuit: <100 Ω
field resistor pack* as shown on Option 2 in diagram below „ Guaranteed good status: 360 Ω to 20 kΩ
(Option 1 in diagram below is not fault detection capable) „ Guaranteed open circuit: > 75 kΩ

Configurable Channel Types: Dry contact or discrete state sensor changing <2 Hz
•Discrete Input
Isolation Galvanically isolated according to EN 60079-11.
Voltage peak value 375V DC.
CHARM Power Req. 28 mA max @ 24V DC ±10%

CHARM Heat Dissipation 0.57 W


*VS6904 End of Line Resistance Module can be used for option 2, see DeltaV SIS Conditioning Components PDS for more info.

Simplified Circuit and Connection Diagram for LS IS DI NAMUR CHARM.

www.emerson.com/deltav 23
DeltaV SIS with IS Electronic Marshalling February 2021

System Compatibility „ CSA

CSA C22.2 No. 213


DeltaV SIS with IS Electronic Marshalling hardware requires:
DeltaV SIS v12.3 or later software. CSA C22.2 No. 61010-1

SZ Controllers with DeltaV SIS v12.3 or later software. CSA C22.2 No. 60079-0

„ CSLS (CSLS): LS IS CHARMs installed on IS CHARM baseplates CSA C22.2 No. 60079-11
can be connected to a CSLS carrier, using a baseplate
CSA C22.2 No. 60079-15
separator and a special fuse in each of the two power supply
lines of the CSLS carrier. „ ATEX

„ Non-IS CHARM Baseplates: Non-IS CHARM baseplates EN60079-0


can be extended with IS CHARM baseplates, using a EN60079-11
baseplate separator.
EN60079-15
„ IS CHARM Baseplates: IS CHARM baseplates cannot be
extended with non-IS CHARM Baseplates. EN60079-26

„ Baseplate Extender: IS CHARM baseplates can be connected „ IEC-Ex


to CHARM baseplate extenders using baseplate separators. IEC60079-0
„ Baseplate Terminator: IS CHARM baseplates can be IEC60079-11
connected to CHARM baseplate terminators using
baseplate separators. IEC60079-15

„ DeltaV SIS Smart Switches: Refer to installation instructions IEC60079-26


for rules governing IS wiring. „ Marine Certifications: IACS E10

DNV-GL Marine Certificate


Certifications
„ Wurldtech: SZ Controller
The following certifications are available on DeltaV SIS with
Achilles Communications Certification Level 1 (v12.3)
IS Electronic Marshalling (see actual certificates for exact
certifications for each product): Achilles Communications Certification Level 2 (v.13.3.1)

„ CE

EMC- EN 61326-1

„ FM

FM 3600

FM 3610

FM 3611

ANSI/ISA 60079-0

ANSI/ISA 60079-11

ANSI/ISA 60079-15

www.emerson.com/deltav 24
DeltaV SIS with IS Electronic Marshalling February 2021

Hazardous Area/Location „ ATEX

Installation:
DeltaV SIS with IS Electronic Marshalling can be installed and
used based on the following Standards (see actual certificates II 3 (1) G Ex nA [ia Ga] IIC Gc
for exact product markings for each product):
Field Circuits:
„ FM (USA)
II (1) G [Ex ia Ga] IIC
Installation: II (1) D [Ex ia Da] IIIC

Class I, Division 2, Groups A, B, C, D, T4 „ IEC-Ex


Class I, Zone 2 AEx nAc IIC
Installation:
Field Circuits:
Ex nA [ia Ga] IIC Gc
Class I, Division 1, Groups A, B, C, D
Field Circuits:
Class II, Division 1, Groups E, F, G
Class III [Ex ia Ga] IIC
Class I, Zone 0 [AEx ia] IIC [Ex ia Da] IIIC

„ cFM (Canada) Tamb = - 40 to +70°C

Installation:

Class I, Division 2, Groups A, B, C, D, T4


Class I, Zone 2 Ex nA IIC

Field Circuits:

Class I, Division 1, Groups A, B, C, D


Class II, Division 1, Groups E, F, G
Class III
Class I, Zone 0 [Ex ia] IIC

Regarding the Installation instructions please refer to the following Documents:

ATEX/IECEx Installation Instructions IS-CHARM Subsystem 12P6523


Control Drawing DeltaV IS-CHARMs Subsystem 12P6122
Control Drawing DeltaV LS IS-CHARMs 12P6123

www.emerson.com/deltav 25
DeltaV SIS with IS Electronic Marshalling February 2021

Ordering Information
SZ Controllers and CSLSs

Description Model Number


Redundant SZ Controller Assembly (vertical carrier) – Includes 2 SZ Controllers, SS3001
Dual Vertical Safety Carrier, 2 Ethernet Isolation Ports for twisted copper, 2 Power Plugs
Redundant SZ Controller Assembly (horizontal carrier) – Includes 2 SZ Controllers, SS3003
Dual Horizontal Safety Carrier, 2 Ethernet Isolation Ports for twisted copper, 2 Power Plugs
Redundant SZ Controller Assembly (keylock - vertical carrier) – Includes 2 SZ Controllers, SS3002
Dual Vertical Safety Carrier, 2 Keylock Ethernet Isolation Ports for twisted copper, 2 Power Plugs
Redundant SZ Controller Assembly (keylock - horizontal carrier) – Includes 2 SZ Controllers, SS3004
Dual Horizontal Safety Carrier, 2 Keylock Ethernet Isolation Ports for twisted copper, 2 Power Plugs
Redundant CSLS Assembly - Copper, (Includes CSLS Carrier, Two CSLSs, SS6501T01
Two Power Modules, Two single Safety Network Ports for twisted copper, Two Power Plugs)
Redundant CSLS Carrier Assembly - Copper, SS6501T05
(Includes CSLS Carrier, Two single Safety Network Ports for twisted copper, Two Power Plugs)
Redundant CSLS, (Includes Two CSLSs and Two Power Modules) SS6502

CSLS IS CHARM Baseplates

Description Model Number


CSLS IS CHARMS Baseplate Assembly with Standard IS CHARM Terminal Blocks, SS4608T01
includes IS CHARMS Baseplate, IS CHARM Address Terminal Block,
12 IS CHARM Standard Terminal blocks and a Baseplate Separation Wall
CSLS Baseplate Address Plugs

Description Model Number


Addressing Plugs, includes Address Plugs One through eight SS4602

Addressing Plugs, includes Address Plugs One through four SS4613

CSLS Baseplate Extenders, Terminators, & Cables

Description Model Number


CSLS Baseplate Terminator, Top (Male), SS4604T03
(Includes a Baseplate Identifier and a Baseplate Separation Wall)
CSLS Baseplate Terminator, Bottom (Female), SS4604T04
(Includes a Baseplate Identifier and a Baseplate Separation Wall)
CSLS Baseplate Extender with Cable Connectors, Top (Male), SS4603T05
(Includes a Baseplate Identifier and a Baseplate Separation Wall)
CSLS Baseplate Extender with Cable Connectors, Bottom (Female), SS4603T06
(Includes a Baseplate Identifier and a Baseplate Separation Wall)
CSLS Baseplate Cables, includes two 0.5 m cables SS4605T02

CSLS Baseplate Cables, includes two 1 m cables SS4605T03

CSLS Baseplate Cables, includes two 2 m cables SS4605T04

www.emerson.com/deltav 26
DeltaV SIS with IS Electronic Marshalling February 2021

CSLS Baseplate Labeling

Description Model Number


CSLS Baseplate Identifiers, Package of nine SS4606T03

CSLS Baseplate Channel Identifier Labels, Package of eight SS4606T02

Each vertical DIN rail requires a DIN Rail stop to lock baseplates in position. Order VE4054DRS, which is a box of 5.

Ordering Information
LS IS CHARMs

Description Model Number


LS IS DI NAMUR SS4305T01

LS IS AI 4-20 mA HART SS4307T01

LS IS Thermocouple/mV SS4309T01*

LS IS RTD SS4310T01*

IS CHARMs and IS Terminal Block Assemblys

Description Model Number


LS IS Thermocouple/mV CHARM with IS Thermocouple/mV Terminal Block SS4309T51*

Additional Ordering Information for IS CHARM Protection Cover


IS CHARM Protection Cover

Description Model Number


IS CHARM Protection Cover; Package of 12 SS6104

www.emerson.com/deltav 27
DeltaV SIS with IS Electronic Marshalling February 2021

Simplified Circuit and Connection Diagram for IS CHARM Protection Cover.


When the I.S. CHARM Protection Cover is installed, all terminals on the I.S. CHARM Terminal Block are shorted! The shortened Terminals
can be connected to Chassis Ground, while allowing the ground to be daisy-chained to the next I.S. CHARM Terminal block, where the next
I.S. CHARM Protection Cover got installed.

www.emerson.com/deltav 28
DeltaV SIS with IS Electronic Marshalling February 2021

Prerequisites
DeltaV SIS with IS Electronic Marshalling hardware requires DeltaV SIS v12.3. or later software.

„ LS IS Thermocouple/mV CHARM requires DeltaV SIS v13.3. or later software to be able to configure and use the CHARM.

„ LS IS RTD CHARM requires DeltaV SIS v13.3. or later software to be able to configure and use the CHARM.

„ Only DeltaV SIS Smart Switches are supported on the LSN.

„ Keylock Ethernet Isolation Port requires DeltaV SIS v14.3 or later software

IS CHARM FUSE

Description Model Number


Fuse Holder and Fuse Assembly for 24V DC Power Supply of CHARM I/O CARD SS4610T01*

* Two of these Fuse Assemblies have to be ordered with any SS6501T01 or SS6501T05, when used with IS CHARM baseplates.

Outside Dimensions of the Fuse Hold.

www.emerson.com/deltav 29
DeltaV SIS with IS Electronic Marshalling February 2021

SZ and CSLS Spare part ordering Information


SZ and CSLS Spare Parts

Description Model Number


Power Terminal Plug for CSLS, and Dual Vertical and Horizontal Safety Carriers KJ4005X1-BF1

Ethernet Isolation Port; twisted copper; for Dual Vertical or Horizontal Safety Carriers KL1604X1-BA1

Keylock Ethernet Isolation Port; twisted copper; for Dual Vertical or Horizontal Safety Carriers KL1604X1-BB1

Power Module for CSLS Carriers KL1501X1-BA1

Set of 2 Replacement Keys for Keylock Switch on CSLS and Dual Vertical SS6201
and Horizontal Safety Carriers

LS IS CHARM Labeling part ordering Information


LS IS CHARM I/O Labeling Parts

Description Model Number


Channel Identifier Labels for CSLS IS CHARM Baseplates; Package of eight SS4609T01

CSLS IS Charm Baseplate Separation Wall; Package of nine SS4609T02

Replacement Fuse for SE4610T01 Fuseholder Assembly KL4510X1-FA1

Replacement Fuseholder for SE4610T01 Fuseholder Assembly KL4510X1-GA1

©2021, Emerson. All rights reserved.


The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their
use or applicability. All sales are governed by our terms and conditions, which are available on
Contact Us request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/contactus at any time without notice.