TDS H07RNF Electra Cables - Current Rating
TDS H07RNF Electra Cables - Current Rating
TDS H07RNF Electra Cables - Current Rating
Application
Used for medium and heavy mechanical loads, in dry and wet areas, also outdoor.
Could be installed under or on plaster, in rocks, concrete, but not in pre-stressed
concrete. Cable suitable for fixed industrial and home installation, for operating
conditions with possible fire or explosion hazard, for mobile energy users, machine
tools and agricultural machines, for construction sites at medium mechanical loads, for
large kettles, heating plates, hand lamps, electrical tools such as drills, circular saws
and electrical tools for household use, same as for generator engines or machines on
construction sites and craftsman i.e. agricultural plants. Permitted fixed laying on crane
and machine elements etc. Permitted voltages up to 1000 V AC at protected laying in
tubes or devices, and as connecting rotor cable for engines. Also suitable for cooling
installations. Resistant to oil, ozone and UV irradiation.
Cable Construction:
Bare copper conductor, fine wired stranded, class 5 acc. to IEC
Conductor:
60228 / HD 383 / DIN VDE 0295
Ethylene-propylene rubber (EPR) compound, EI4 acc. to DIN
Insulation:
VDE 0282 part 1
Cores identification by colours according to colours list.
Outer Sheath: EM2 Rubber compound acc. to. DIN VDE 0282 part 1
-1-
Technical Data
Temperature range:
In normal duty: -25 °C up to +60 °C
Maximal temp.: +85 °C
In short circuit of max. 5 s: up to 200 °C
Nominal voltage: Uο/U = 450/750 V
Test voltage: 2500 V
Insulation Resistance: 20MΩ/ km
Maximal operating voltage:
Alternating current three-phase and
Uο/U = 476/825 V
single-phase:
for fixed installation: 6D (D is maximum cable outer diameter)
Flame Retardant: IEC 60332-1-2
Ozone resistance: acc. to DIN VDE 0472 part 805
Approval: VDE approved cable
Cable marking:
◁ VDE ▷ 40036288 H07RN-F AZ mm2 <Year>
ELECTRA CABLES =meters=
-2-
Dimensional Data:
-3-
H07RN-F2950 2 x 95.0 40.2 - 51 279 1710 3140
Article number Number of Outer Permissible Copper Weight
cores and diameter current free index (kg/km)
mm2 per (mm) air @ 30°C (kg/km)
conductor (A)
H07RN-F2010E 3 G 1.0 8.3 - 10.7 17 27 124
H07RN-F2015E 3 G 1.5 9.2 - 11.9 22 40.5 157
H07RN-F2025E 3 G 2.5 10.9 - 14.0 30 67.5 220
H07RN-F2040E 3 G 4.0 12.7 - 16.2 39 108 310
H07RN-F2060E 3 G 6.0 14.1 - 18.0 52 162 395
H07RN-F2100E 3 G 10.0 19.1 - 24.2 71 270 725
H07RN-F2160E 3 G 16.0 21.8 - 27.6 95 432 980
H07RN-F2250E 3 G 25.0 26.1 - 33.0 120 675 1400
H07RN-F2350E 3 G 35.0 29.3 - 37.1 147 945 1830
H07RN-F2500E 3 G 50.0 34.1 - 42.9 180 1350 2510
H07RN-F2700E 3 G 70.0 38.4 - 48.3 231 1890 3310
H07RN-F2950E 3 G 95.0 43.3 - 54.0 279 2565 4290
H07RN-F21200E 3 G 120.0 47.4 - 60.0 324 3240 5275
H07RN-F21500E 3 G 150.0 52-66 371 4050 6485
Dimensions provided are approximate values and could differ from the actual values upon production.
We reserve the right to make any changes to the information provide here
-5-