Document ID: TE/QMS/F/02

Rev. No. : 00 Issued Date : 02/04/2018

Cable Description: 1100V, Solid Class 1 Copper Conductor, XLPE insulated,


Extruded PVC Type ST2 inner sheath, Galvanised Round wire armour,
Extruded FR-LSH PVC Type ST2 Outer sheath as per IS 7098 Part 1/1988

I Technical Data Sheet of LT XLPE Cable CABLE SIZE


II CABLE CODE LVIS09CXSWYL002C1.5SA002S

S.No Particulars 2 Core X 1.5 Sq.mm


1 Name of Manufacturer Polycab India Ltd.
2 Type of cable 2XWY
3 Voltage Grade V 1100
4 No of cores X size in sqmm 2 Core X 1.5 Sq.mm
5 Conductor
a) Material Plain annealed Copper as per Class 1 of IS:8130/2013
b) Max. d.c. resistance of conductor at 20° C (ohm/km) 12.1
c) Shape of the conductor Solid Circular
6 Insulation
a) Material XLPE as per IS 7098(Pt-1)/88, Latest
b) Nominal thickness (mm) 0.7
c) Core Identification Red,Black
7 Inner Sheath
a) Material Extruded PVC Type ST2 as per IS:5831/84
b) Minimum thickness (mm) 0.3
8 Armouring
a) Material Galvanised Steel
b) Type of armouring Round Wire
c) Nominal size of armour (mm) 1.4
d) Tolerance +/- 0.040
9 Outer Sheath
a) Material Extruded FR-LSH PVC Type ST2 as per IS:5831/84
b) Thickness (mm) 1.24 (Min.)
c) Colour of outer sheath. Black
10 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C (ohm/km) 15.4
b) Calculated Cable reactance (ohm/km) 0.106
c) Impedance of cable (ohm/km) 15.4
d Approx. Cable Capacitance (mfd/km) 0.16
Maximum conductor temperature under normal operating
11 90°C
conditions
Maximum conductor temperature at the termination of short
12 250°C
circuit

13 Short Circuit rating of conductor for the duration of 1 sec (kA) 0.21

14 Continuous Current carrying capacities :-


(a) In Ground at 30°C (A) 31
(b) In Air at 40°C (A) 27
IS 8130/2013,IS 7098 Part I/88, IS 5831/84, IS 3975/1999 etc. with latest up
15 Applicable Standard
to date amendments
16 Approx. overall diameter of the cable in mm 06 +/- 2.0
17 Minimum bending radius 12 times Overall diameter
18 Max. Tensile strength
(i) for Cables pulled with stocking (Newtons) 9 x D², D is the cable OD in mm
(ii) for Cables pulled with pulling eyes (N) 150

19 Embossing POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE FR-LSH

YEAR POLYCAB ELECTRIC 1100 VOLTS GRADE XLPE FR-LSH CABLE SIZE
20 Printing
CABLE TYPE WITH SEQUENTIAL MARKING at every one meter interval.

21 Standard Drum Length (Mtr.) 1000 ± 5%


22 Non- Standard Drum Length (Mtr.) Maximum 5% of order quantity
23 FR-LSH PROPERTIES
a) Oxygen Index Min. 29% as per ASTM D- 2863
b) Temperature Index Min. 250 Deg.C as per ASTM D- 2863
c) Smoke Density Rating Max. 60% as per ASTM D- 2843
d) Acid Gas Generation Max. 20% as per IEC- 754- 1
e) Flammability Test As per IEC:332-I

Note:-The values given above are subject to tolerances as per


the relevant standards.