DAC-1146 (E) Catalog Sheet
DAC-1146 (E) Catalog Sheet
DAC-1146 (E) Catalog Sheet
DAC-1146 / DAC-1146E
Description Specifications
The DAC-1146 is a fully programmable, Native BACnet® Advanced Application
Controller that either communicates on Twisted-Pair Ethernet 10-BaseT using BACnet BACnet Device Profile
BACnet Advanced Application Controller
IP and BACnet over Ethernet (DAC-1146E) or an RS-485 LAN using the BACnet MS/TP
(B-AAC)
protocol (DAC-1146). It is designed for a wide-range of applications that have medium
local I/O requirements. It also supports BACstat® and other Delta LINKnet devices. Inputs
11 Universal Inputs (10-bit) supporting:
0-5 VDC
0-10 VDC
10 kΩ Thermistor
Dry Contact (using 10 kΩ Thermistor
jumper setting)
4-20 mA
Outputs
6 Binary TRIAC Outputs (jumper
configured for internal or external
power)
4 Analog Outputs (0-10 VDC)
Device Addressing
Application Features Set via DIP switches and jumpers, or
The DAC-1146 is suitable for controlling Fully programmable in GCL+ software setup
various packaged units and equipment with Connectors
medium I/O requirements such as small air Super Capacitor for real-time clock and
SRAM backup which requires no Removable screw-type terminal
handling units, boilers, and chillers. maintenance (DAC-1146E) connectors
Wiring Class
The fully programmable DAC-1146 can be Supports 10 BACstat network sensors Class 2 / SELV
tailored to specific applications by creating on LINKnet for room sensing and
Power
and modifying BACnet objects and GCL+ control, or 2 Delta Field Modules on
24 VAC 50/60 Hz @ 14 VA, 86 VA with
programs. LINKnet for I/O expansion
fully-loaded Binary Outputs
Actuator power terminal (24 VAC) for BACstat is a registered trademark of Delta Controls Inc.
each analog output (can be powered BACnet is a registered trademark of American Society of
internally or from an auxiliary Heating, Refrigerating and Air-Conditioning Engineers
transformer) (ASHRAE).
Service port
deltacontrols.com
Application Controllers
Technology
DAC-1146
16-bit processor
Actuator Power 1 MB flash memory
24 VAC NET2 Port Jumper Binary (TRIAC) Analog (0-10 VDC) Binary Outputs 127 KB SRAM memory for database
Power Out Service Port Outputs 1-6 Outputs 7-10 Power Source
Selectors DAC-1146E
16-bit processor
2 MB flash memory
319 KB SRAM memory for database
Real-time clock
Super Capacitor for 72-hour backup
of realtime clock and SRAM
Communications Ports
DNA
Main LAN
Jumper
Ethernet (10-BaseT)
BACnet IP, BACnet over Ethernet
(DAC-1146E only)
or
RS-485 NET1
BACnet MS/TP up to 76800 bps, max
99 devices per port
24 VAC NET1 Ethernet Device Address Switches Inputs 1 - 11 Ground Lug
SubLAN
Power In Port Port Input Type
(DAC-1146E only) RS-485 NET2
Selectors Delta LINKnet up to 76800 bps, max
Power LED Scan LED
10 devices on LINKnet with no more
than 2 DFM devices
Optional Modbus up to 38400 bps,
max 5 devices
Ambient
0° to 55°C (32° to 131°F)
Ordering
10 to 90% RH (non-condensing)
Order the DAC-1146 with the desired options according to the following product numbers:
Dimensions
DAC-1146 Delta Application Controller 11 inputs, 4 AOs, 6 BOs, MS/TP 26.2 x 10.7 x 4.9 cm
DAC-1146E Delta Application Controller 11 inputs, 4 AOs, 6 BOs, Ethernet (10⅜ x 4¼ x 115/16 in.) with housing
Note: When using Ethernet, MS/TP protocol is not available (RS-485 ports can be used Weight
for LINKnet and/or special interfaces only). 428 g (0.944 lb.) with housing
Compliance
Accessories CE
FCC
DZNR-768 Delta Network Repeater for BACnet MS/TP EAC
TRM-768 Delta Network Terminator for BACnet MS/TP Listings
CON-768BT Bluetooth wireless service tool C-UL Listed
DFF099-CDT Additional 50 credit blocks for the Modbus flash key UL 916 Listed
BTL Listed
DFF099-KEY Modbus flash upgrade key with 50 credits pre-loaded
deltacontrols.com