F01S300 cabinet

The F01S300 cabinet can be configured with MA5603T and MA5616 service units. It can be
Configured with different built-in service boards to provide GPON, POTS, xDSL, and E1 services.
Cabinet Installation
The F01S300 cabinet can be installed on a concrete pedestal or an elevated platform.The cabinet is
configured with lifting rings. Therefore, it can be hoisted in a safe and reliable way, and installed easily.

High Security
1.Prominent performance in electromagnetic compatibility (EMC) and anti-attack
2.Superior water and dust resistance, meeting requirements of the IP55 protection rating
3.Level-based maintenance by isolating the equipment compartment from the cable distribution
compartment (these two compartments have different door locks and support external locks to provide
better security; they do not support external locks when being configured with electronic door locks)
4.Excellent performance in anti-theft by fastening bolts at the bottom inside the cabinet
Convenient Maintenance
1.Components inside the equipment compartment of the F01S300 cabinet are frontserviceable.
2.The built-in main distribution frame (MDF) in the cable distribution compartment of the F01S300
cabinet supports wire seating from the front side. The built-in optical distribution frame (ODF) supports
pre-deployment of device-side optical ports and fibers, user-side external optical cable splicing, and
device-side and user-side (internal and external) fiber patching.
3.The F01S300 cabinet provides a portable illuminator, facilitating nighttime maintenance.
4.The AC maintenance socket inside the F01S300 cabinet supplies power to an external maintenance
terminal. The folder on the cabinet door can be unfolded to function as a console, onto which the
maintenance terminal can be placed for onsite maintenance.
Prominent Monitoring
The F01S300 cabinet uses internal service devices and sensors to monitor the cabinet environment,
battery, surge protection module, and door status in real time and remotely report alarms.
Integrated Structure Design
1.The F01S300 cabinet is integrated with service, power supply, monitoring, temperature control, and
cable distribution units. This design minimizes the installation costs and space. The F01S300 cabinet
can be installed quickly onsite to satisfy the demand for quick deployment.
2.The sealed design protects the F01S300 cabinet against dust, moisture, and rain, and ensures reliable
running in harsh environment.
3.The battery power backup or remote power supply ensures the normal running of the F01S300
cabinets used in areas with unstable mains supply.
4.The F01S300 cabinet supports both MDF and ODF. Therefore, the F01S300 cabinet can

1
accommodate the MA5603T to provide copper line/copper-fiber/optical fiber access.
Structure
Structure of the F01S300 cabinet (configured with an ETP4830 power system and providing
copper/fiber-copper access)

Door Lock
The F01S300 cabinet is configured with HW-2802 door locks (specifically, HW-2802A for the
equipment compartment and HW-2802B for the cable distribution compartment). These locks are
configured with different keys, meeting customer demands for level-based maintenance., the F01S300
cabinet can be configured with an electronic door lock to provide better protection for devices inside the
cabinet.
Power Supply System
The power supply unit inside the F01S300 cabinet consists of the AC power distribution unit (PDU),
DC PDU, power system, and battery set.
General Power Distribution (When an ETP4830 Power System is used)
The AC power cable is led into the cabinet from the bottom of the battery compartment, and then
connected to the mains AC circuit breaker or diesel generator AC circuit breaker inside the AC PDU.
The AC PDU divides the power supply into the 4 channels:
1.One channel supplies power to the maintenance socket.
2.One channel supplies power to intelligent heating modules of the battery compartment and equipment
compartment.
3.One channel after being converted to DC power supply by the ETP4830 power system, supplies
power to the service unit, fan control board, and illuminator through the DC PDU.The ETP4830 power
system also provides 1 output for the DC PDU for connecting to a battery set. In this way, the ETP4830
power system is able to manage the battery set.
4.One channel is reserved.

2
General power distribution of the F01S300 cabinet Figure

ETP4830 Power System


An AC-powered cabinet uses the ETP4830 power system to convert the AC power to the DC power for
power distribution. The small and modular ETP4830 power system supports easy installation and
maintenance, effective LCD interface management, and excellent security specifications design. The
power system supports a maximum of 30 A output current.
Function
The ETP4830 power system supports the following functions:
1-Converts AC input to DC inputs and provides the DC inputs for communication devices.
2-Communicates with the upper device using a COM or an RS485/RS232 serial port; sends control
signals based on the values of monitored parameters or the control command sent by the upper device;
detects power distribution parameters, power supply module parameters, and auxiliary digital parameters in
real time.
3-Connects to one group of lead acid batteries and uses a site monitoring unit (SMU) to manage the
batteries. Manages battery charging and discharging, ensuring efficient battery usage
4-Connects to a sensor transfer box using a DB50 port, detecting analog parameters and digital parameters,
and outputting control signals.
5-Uses the SMU to monitor all running parameters for the ETP4830 power system in real time,
determines the working status, and reports alarms in a timely manner
Appearance
ETP4830 power system Figure

3
Configuration
Components of the ETP4830 power system Table
Component Configuration
ETP4830-A1 AC and DC power 1
distribution subrack
Monitoring module SMU01B 1
Rectifier module R4815N1 1 to 2 (optional)
Mapping between the quantity of power supply modules of the ETP4830 power system and the
maximum output current Table
Quantity of Rectifier Modules Maximum Output Current
1 15 A
2 30 A
Communication Ports on the Monitoring Module
The following Table describes the communication ports on the SMU01B monitoring module. A user
can set the baud rate of the device using the LCD interface of the monitoring module. The baud rates
9600 bit/s and 19200 bit/s are automatically negotiated.
Communication ports on the SMU01B monitoring module Table
Communication Communicati Communication Description
Port on Mode Parameter
COM RS485/RS232 Baud rate: 19200 bit/s or Used as a serial port,
9600 bit/s communicating with the upper
device
RS485/RS232 RS485/RS232 Baud rate: 19200 bit/s or Used as a serial port, supporting the
9600 bit/s northbound/southbound
communications
Note:The COM port and the RS485/RS232 ports are used in active and standby mode
Indicators
Indicators on the R4815N1 rectifier module table
Indicator Color Status Description
Power indicator Green Steady on Normal
Blinking There is AC input, and the PSU is in the manual query
status
Off No AC input
Alarm indicator Yellow Steady on A protection mechanism is triggered. After the fault is
rectified, the rectifier module can be restored to the normal
state
Blinking Communication between the PSU and the SMU is
disrupted
Off Normal
Fault indicator Red Steady on An unrecoverable fault occurs
Blinking Software is being loaded
Off Normal
lists the indicators on the SMU01B monitoring module. Table
Indicator Color Status Description
RUN Green Off The monitoring module is faulty or there is no
DC power input
Blinking at a frequency of The monitoring module is working properly and
0.5 Hz communicating with the upper device properly
Blinking at a frequency of 4 The monitoring module works properly but does
Hz not communicate with the upper device properly
ALM Red Off The system does not generate any critical alarms
Steady on The system generates critical alarms

4
Input Terminal

Output Terminal

Output branch fuse in the ETP4830 power system Figure

Mapping between the fuses of the output tributaries and the load tributaries Table
Fuse of the Output Load Tributary
Tributary
FU-1 (20 A) LOAD1 (20 A) for FAN
FU-2 (20 A) LOAD2 (20 A) for DEVICE
FU-BT (20 A) BATT (20 A), used for connecting to batteries
Batteries
The F01S300 cabinet uses a set (four batteries per set) of 50 Ah, 92 Ah, or 100 Ah batteries as the
backup power. These batteries are connected in series to form a battery set.
The battery used as the backup power of the device refers to the battery whose power can be restored
through charging after the battery is discharged. The battery can be charged in two modes: equalized
charging and floating charging. The meanings of the two modes are as follows:
1-Equalized charging: A charging method with a higher voltage used to balance the battery voltage and
capacity and also be used to renew the capacity rapidly.
2-Floating charging: A method of maintaining a battery in a charged condition by continuous, long-
term, constant voltage charging, at a level sufficient to balance battery self-discharge.

5
Appearance 50 Ah Battery Figure Appearance 92/100 Ah Battery Figure

Specifications of the 50 Ah battery Table Specifications of the 92/100 Ah battery Table

3 U AC PDU
A 3 U AC power distribution unit (PDU) is used in an AC-powered cabinet. The PDU draws in power
from the AC mains supply or a diesel generator for AC power distribution and power supply protection.
The 3 U AC PDU has the following functions:
1-Provides one AC input and four AC outputs.
2-Supports a 40 kA surge protector and provides a dry contract port for remote alarming.
3-Provides comprehensive and reliable grounding system and protection circuit, ensuring power supply
reliability and device safety for the communications system.
Appearance of the 3 U AC PDU figure

Configuration
The 3 U AC PDU consists of the circuit breaker, surge protector, decoupling coil, and residual
Current device (RCD)

6
Configuration components Table

Working Principle
Figure -5 Working principle of the 3 U AC PDU (when the output voltage of Load1 and Load3 is 220 V)

Input Terminal
Input terminals of the 3 U AC PDU Figure

7
Output Terminal
Output terminals of the 3 U AC PDU Figure

The output terminals of the 3 U AC PDU are connected as follows:


-Load1 connected to the maintenance socket
-Load2 connected to the ETP4830 power system
-Load3 connected to the battery heater
-Load4 connected to the heater in the cabinet or remaining unused
-Ground point connected to the ground bar near the cabinet
-SPD ALARM connected to the signal transfer box
Surge Protector
The 3 U AC PDU uses a 40 kA surge protector, protecting the power system and the powered
Devices from the surge voltage caused by lightning strikes
Specifications of the surge protector Table

DPD50-3-5S DC PDU
The DPD50-3-5S DC power distribution unit (PDU) works with the ETP4830 power system for
DC power distribution The DPD50-3-5S DC PDU leads in three DC inputs from the ETP4830 power
system and provides five DC outputs, each output controlled by a separate switch.
Figure -9 Appearance of the DPD50-3-5S DC PDU

8
Working principle of the DPD50-3-5S DC PDU Figure

The DPD50-3-5S DC PDU provides five DC outputs: LOAD00, LOAD10, LOAD11, LOAD12, and
LOAD20, among which LOAD20 is subdivided into three tributaries (LOAD20-1, LOAD20-2, and
LOAD20-3) for connecting to more loads
Input Terminal

The input terminals of the DPD50-3-5S DC PDU are connected to the ETP4830 power system as
follows:
INPUT0 connected to the BATT output port of the power system
INPUT1 connected to the LOAD2 output port of the power system
INPUT2 connected to the LOAD1 output port of the power system
Output Terminal

Output Switch

Table -9 Mapping between the output switches and the loads

NOTE
LOAD00 connects to the battery.
LOAD10, LOAD11, LOAD12, LOAD20-1, LOAD20-2, and LOAD20-3 connect to different loads of
The power supply system.
Maintenance Socket
The maintenance socket is connected to the maintenance terminal to facilitate onsite maintenance.
Maintenance sockets include the European standard socket and the universal socket. You can select one
type based on your requirements.

9
Monitoring System
In an F01S300 cabinet, the signal transfer box collects the information about monitored parameters, and
the power monitoring module processes and reports the parameters to the control board of the device. In
this way, the F01S300 cabinet monitors the environment, power units,and other main components
inside the cabinet
Monitoring Principle (When an ETP4830 Power System is used)

CCU
The CCU is used to monitor electronic door locks.
Appearance of the CCU Figure

10
MUE02A Sensor Transfer Box

Sensor
The F01S300 like FD012000cabinet provides the temperature sensor, door status sensor, battery
temperature sensor, smoke sensor, and water sensor to monitor environmental parameters for service
units inside the cabinet.
Door sensor

Temperature sensor and Environment Temperature Sensor (NTC type)

Smoke sensor

Water sensor

11
Temperature Control Unit
The F01S300 cabinet provides a built-in temperature control unit for heat dissipation and heating. The
temperature control unit controls the temperature inside the cabinet within a proper range and ensures
that the device inside the cabinet functions properly.
The temperature control unit inside the F01S300 cabinet consists of two 175 mm cabinet fans and one
HAU02A-01 intelligent heating module (optional).
Heat Dissipation
The F01S300 cabinet uses a wall-mounted heat exchange structure and two fans for internal and
external cycles to dissipate heat for the cabinet.
The heat dissipation system contains two independent air cycles (internal cycle and external cycle).
Acentric fans for the internal and external cycles enable air convection for cooling the sealed area.
Specifically, the air inside the sealed area is cooled through heat exchange with the air outside the
cabinet, and heat is transferred through the wall-mounted heat exchange structure
Heat dissipation of the F01S300 cabinet Figure

175mm Cabinet Fan


The temperature sensor on the cabinet fan detects the ambient temperature and automatically adjusts the
fan speed to dissipate heat out of the cabinet.
Appearance of the 175mm cabinet fan Figure

12
Technical specifications of the 175mm cabinet fan Table

Heating
An intelligent heating module can be installed at the right side of the battery compartment or the left
side of the equipment compartment. A fan in the heating module blows air to dissipate heat generated
by the heating module. In this way, the battery compartment or equipment compartment is heated and
the heat inside the compartment is balanced, ensuring optimal operating temperature for the battery set
or service units.
As a temperature control device, an HAU03A-01 intelligent heating module enables equipment to
function properly in a low-temperature environment.
Appearance of the HAU03A-01 Intelligent Heating Module Figure

Specifications of the HAU03A-01 intelligent heating module Table

Fan Control Board (FCB)


FCB has a built-in monitoring unit to reports the values of heat exchanger monitoring parameters to the
control board and implement the following functions:
-Monitoring fans for the internal and external cycles, and detecting fan speed
-Monitoring the temperature sensor
-Starting and stopping the heater, and detecting heater faults
When detecting any fault associated with the preceding aspects, the FCB reports a heat exchanger fault.

13
FCB appearance Figure

The FCB monitors the temperature ranging from -45°C (-49°F) to +70°C (+158°F) with a precision of ±
1°C . The FCB provides a temperature sensor and can connect to two outside temperature sensors.The
host can communicate with two FCBs using the RS485 cascading interfaces. The FCB identifies cabinet
types using digital parameters configured in DIP switches or using e-labels so that different fans and
environment parameters can be configured on the cabinet. The FCB supports the output of dry contact
alarms. The FCB identifies cabinet types using digital parameters configured in DIP switches or using
e-labels so that different fans and environment parameters can be configured on the cabinet. The FCB
supports online software loading. Fans can be controled by a host or the FCB.The FCB provides a red
indicator and a green indicator to indicate the operating status.
FCB operating principles Figure

Description of the indicators on the FCB Table

14
Checking the Connection from Heat Exchanger to Control System
In the F01S300 cabinet, the heat exchanger is monitored by the ETP4830. Therefore, environment
monitoring parameters of the heat exchanger no need to be independently configured. To check the
connection from the heat exchanger to the control system.The cable from the FCB to the control system
is connected as follows:
-One end of the cable is a RJ45 connector, connected to COM IN port on FCB.
-The other end is a RJ45 connector, inserted to JTD6 port of the MUE02A
Checking Environment Monitoring Cables in the F01S300 Cabinet
Figure shows the connections of environment monitoring cables in the F01S300 cabinet. Table
describes the cable connections. By referring to the cable connection diagram, check whether the
connections from the sensors to the sensor transfer box (MUE02A), from the sensor transfer box to the
SMU01B, and from the SMU01B to the control system are correct.
Connections of environment monitoring cables in the F01S300 cabinet Figure

15
The cable from the FCB to the control system is connected as follows:
-One end of the cable is a RJ45 connector, connected to COM IN port.
-The other end is a RJ45 connector, inserted to JTD6 port of the MUE02A
Cable Distribution System
The F01S300 cabinet provides a built-in main distribution frame (MDF) and a built-in optical
Distribution frame (ODF) for service access and service upstream transmission.
Appearance of the cable distribution compartment (for copper access or integrated fiber and copper access)

16
6-Core Integrated Splicing and Termination Unit
The 6-core integrated splicing and termination unit is used to connect the optical fiber and the optical
communication device.The main functions of the 6-core integrated splicing and termination unit are as
follows:
-Fixing and protecting optical fibers.
-Protecting the cores of the optical fibers with jacket peeled.
-Splicing optical fibers.
-Distributing optical fibers.
-Routing optical fibers.
-Storing optical fibers.

17
Configuration
F01S300 Cabinet Configured with MA5603T

MA5603T
384 POTS/VDSL2/ADSL2+/(POTS + VDSL2)
288 (POTS + VDSL2/ADSL2+)
32 GPON + 256 POTS/VDSL2/ADSL2+
32 GPON + 192 (POTS + ADSL2+)