Spectra 12 Series
Explosion Proof, Pressure and
Differential Pressure Switches UNITED ELECTRIC
CONTROLS
Terminal #1 Common
DO NOT TURN
Terminal #2 Normally Closed
SWITCH HOUSING
MOUNT VIA Terminal #3 Normally Open
PRESSURE
CONNECTION Ground
figure 1
figure 1
RECOMMENDED PRACTICES AND WARNINGS
Part II - Adjustments United Electric Controls Company recommends careful consideration
of the following factors when specifying and installing UE pressure
Tools Needed and temperature units. Before installing a unit, the Installation and
Flathead screwdriver with 3/16” or 1/4” wide blade Maintenance instructions provided with unit must be read and under-
stood.
1. Connect control to pressure source. • To avoid damaging unit, proof pressure and maximum temperature
2. With power disconnected, slide cover toward electrical terminations while twisting limits stated in literature and on nameplates must never be exceeded,
it to over-come friction. even by surges in the system. Operation of the unit up to maximum
pressure or temperature is acceptable on a limited basis (e.g., start-up,
3. Connect power to terminals or leads. testing) but continuous operation must be restricted to the designated
4. Insert screwdriver into adjustment slot and turn left (clockwise) to increase adjustable range. Excessive cycling at maximum pressure or tempera-
setting or right (counterclock-wise) to decrease setting.(See figure 2). ture limits could reduce sensor life.
• A back-up unit is necessary for applications where damage to a pri-
For setting on RISE, apply desired pressure and turn adjustment left (clockwise) until mary unit could endanger life, limb or property. A high or low limit
switch clicks (circuit across N.O. and COM terminals closes). switch is necessary for applications where a dangerous runaway
For setting on FALL, apply pressure equal to normal system operating pressure. condition could result.
Reduce source pressure to setpoint value. Turn adjustment right (counter clockwise) • The adjustable range must be selected so that incorrect, inadvertent
until switch clicks (circuit across N.C. and COM terminals closes). or malicious setting at any range point cannot result in an unsafe
system condition.
• Install unit where shock, vibration and ambient temperature fluc-
tuations will not damage unit or affect operation. Orient unit so that
Dimensions moisture does not enter the enclosure via the electrical connection.
When appropriate, this entry point should be sealed to prevent mois-
Standard Configuration ture entry.
• Unit must not be altered or modified after shipment. Consult UE if
Dimension A modification is necessary.
Types Inches mm NPT
2 47∕8" 123.9 1/2"
• Monitor operation to observe warning signs of possible damage to
3 47∕8" 123.9 1/2" unit, such as drift in set point or faulty display. Check unit immedi-
4 47∕8" 123.9 1/4" ately.
5 47∕8" 123.9 1/2"
6 47∕8" 123.9 1/4"
• Preventative maintenance and periodic testing is necessary for criti-
7 513∕32" 137.5 1/2" cal applications where damage could endanger property or person-
8 47∕8" 123.9 1/4" nel.
9 513∕32" 137.5 1/2"
K1-K3 611∕16" 169.9 1/8" • For all applications, a factory set unit should be tested before use.
K4-K6 615∕16" 176.2 1/8" • Electrical ratings stated in literature and on nameplate must not be
P1-P3 53/8" 136.5 1/4" exceeded. Overload on a switch can cause damage, even on the first
cycle. Wire unit according to local and national electrical codes,
using wire size recommended in installation sheet.
• Do not mount unit in ambient temp. exceeding published limits.
LIMITED WARRANTY
Seller warrants that the product hereby purchased is, upon delivery,
free from defects in material and workmanship and that any such
figure 2 product which is found to be defective in such workmanship or mate-
rial will be repaired or replaced by Seller (Ex-works, Factory, Watertown,
Pressure Massachusetts. INCOTERMS); provided, however, that this warranty applies
only to equipment found to be so defective within a period of 36 months
from the date of manufacture by the Seller. Seller shall not be obligated
under this warranty for alleged defects which examination discloses are
due to tampering, misuse, neglect, improper storage, and in any case
where products are disassembled by anyone other than authorized Seller’s
representatives. EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND
REPLACEMENT STATED ABOVE, SELLER DISCLAIMS ALL WARRANTIES
Type 2, 3, 5 Sensor Type 4, 6, 8, P1-P3 Sensor Type 7, 9 Sensor
WHATSOEVER WITH RESPECT TO THE PRODUCT, INCLUDING ALL
IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR ANY
PARTICULAR PURPOSE.
Differential Pressure
LIMITATION OF SELLER’S LIABILITY
Seller’s liability to Buyer for any loss or claim, including liability incurred
in connection with (i) breach of any warranty whatsoever, expressed or
implied, (ii) a breach of contract, (iii) a negligent act or acts (or negligent
failure to act) committed by Seller, or (iv) an act for which strict liability
will be inputted to seller, is limited to the “limited warranty” of repair
and/or replacement as so stated in our warranty of product. In no event
shall the Seller be liable for any special, indirect, consequential or other
Type K1-K3 Type K4-K6 damages of a like general nature, including, without limitation, loss of
profits or production, or loss or expenses of any nature incurred by the
Types K1-K3 and K4-K6 shown with mounting bracket attached
buyer or any third party.
UE specifications subject to change without notice.
Option M515 DIN Connection
UNITED ELECTRIC
CONTROLS
180 Dexter Avenue, P.O. Box 9143
Watertown, MA 02471-9143 USA
Telephone: 617 926-1000 Fax: 617 926-2568
http://www.ueonline.com
figure 3
EMCO5M503
IM12-03