Product Manual 26635 (Revision C, 7/2016) : L-Series Position Controller With CAN Capability
Product Manual 26635 (Revision C, 7/2016) : L-Series Position Controller With CAN Capability
Product Manual 26635 (Revision C, 7/2016) : L-Series Position Controller With CAN Capability
(Revision C, 7/2016)
Original Instructions
This publication may have been revised or updated since this copy was produced.
To verify that you have the latest revision, check manual 26455 , Revision Status &
Distribution Restrictions of Woodward Technical Publications, on the publications
Revisions page of the Woodward website:
www.woodward.com/publications
Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is
believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly
undertaken.
Manual 26635
Copyright © Woodward 2012–2016
All Rights Reserved
Manual 26635 L-Series Position Controller w/ CAN Capability
Contents
Woodward i
L-Series Position Controller w/ CAN Capability Manual 26635
Contacting Woodward’s Support Organization ....................................................81
Technical Assistance ............................................................................................82
APPENDIX A. L-SERIES CONFIGURATION SUMMARY .................................. 83
APPENDIX B. L-SERIES CONTROL SPECIFICATIONS ................................... 85
REVISION HISTORY .................................................................................. 89
DECLARATIONS ....................................................................................... 90
ii Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Acronyms/Abbreviations
AUX auxiliary
EEPROM electrically-erasable programmable read-only memory
EMC electro-magnetic compatibility
GUI graphic user interface
I/O inputs/outputs
Isoch isochronous
ITB integrated throttle body
L-Series Woodward electronic engine governor that contains both a rotary
actuator and a controller circuit board
MPU magnetic pick up
OEM original equipment manufacturer
PWM pulse-width modulated
rpm revolutions per minute
RS-232 a communications standard
TPS throttle position sensor
Woodward iii
L-Series Position Controller w/ CAN Capability Manual 26635
iv Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward v
L-Series Position Controller w/ CAN Capability Manual 26635
Regulatory Compliance
European Compliance for CE Marking:
These listings are limited only to those units bearing the CE Marking.
EMC Directive: Declared to Directive 2014/30/EU of the European
Parliament and of the Council of 26 February 2014 on
the harmonization of the laws of the Member States
relating to electromagnetic compatibility (EMC)
The L-Series is suitable for use in Class I, Division 2, Groups A, B, C, D per CSA
for Canada and U.S. or non-hazardous locations only.
vi Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Chapter 1.
General Information
This manual does not contain instructions for the operation of the complete
engine system. For engine or plant operating instructions, contact the plant-
equipment manufacturer.
This version of the manual applies to all CAN-capable L-Series Position Control
models with software 5418-6084, 5418-6638, or 5418-7022. The software
version can be identified on the Identification tab of the Service Tool.
Intended Applications
The L-Series control is designed for various industrial applications, including but
not limited to generator sets, welders, portable refrigeration units, irrigation
pumps, chipper shredders, and mobile industrial gas or gasoline reciprocating
engines. Key environmental characteristics of these applications include
extended industrial operating temperatures (–40 to +105 °C/–40 to +221 °F),
Industrial EMC Requirements, electrical transients, and lower operating voltages
(12/24 V).
Introduction
The L-Series provides a building-block approach to total engine management.
The modular bi-directional actuator design easily attaches to fuel pumps, mixers,
or throttle bodies. For information on Woodward throttle body applications, refer
to manual 26249 (ITB and LC-50).
Woodward also offers a non-CAN position control version and L-Series versions
for Speed Control applications (manual 26250) and Process Control applications
(manual 26251).
Woodward 1
L-Series Position Controller w/ CAN Capability Manual 26635
The L-Series position control accepts a position command and drives the 0–60
degree output shaft to the commanded position based on an internal shaft
position sensor. The high-efficiency torque motor delivers 0.34 N·m (0.25 lb-ft)
nominally over 60° travel range to operate fuel or air control devices (see
specifications in Appendix B for torque performance over the full product
temperature range).
The L-Series position control accepts either a PWM command, a CAN command,
or a 0–5 V command for output positioning. The command signals are issued by
the appropriate supervisory engine management system, and the L-Series must
be set up properly in software to expect the correct signal for the application. The
position command input can also be set up with a primary and a backup input,
providing redundancy.
For status purposes, a relay driver output is available that changes state
whenever a fault or error condition is experienced by the L-Series controller.
If the system so requires, the L-Series provides a direct position output signal in
the form of a dc voltage. The TPS (throttle position sensor) output represents full
counterclockwise (CCW) to clockwise (CW) rotation of the actuator shaft, and
thus gives the operator an external position indication after installation and while
the unit is operating.
Programmable Features
Control setup and tuning is accomplished through the use of a PC (personal
computer), Woodward Service Tool software, and a programming harness. The
features identified below are described in Chapters 2 and 4. Briefly, the
programmable features include:
General Setup Parameters
o Position Demand Select (Primary/Backup; CAN, PWM or Analog)
o Fail Position
o Min Position Direction (CCW or CW)
o Actuator Curve Selection (Linear or Non-linear)
o CAN Setup
PWM Setup Parameters
o PWM Drive Select (Push-Pull, High-Side Drive or Low-Side Drive)
o PWM Offset
Valve Position Control Parameters
Non-Linear Actuator Settings
o Position Request (5 curve input points)
o Actuator Position (5 curve output points)
Discrete Output Settings
o Output’s Non-Fault Condition (ON or OFF)
o Fault Selections as Discrete Output Indications
Fault Settings
o Latching or Non-Latching Fault Indications
o Position Error Magnitude & Delay
o Fault Selections as Alarms or Shutdowns
2 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward 3
L-Series Position Controller w/ CAN Capability Manual 26635
Chapter 2.
System Description/Application Overview
System Operation
On power-up, the L-Series actuator will establish its identity based on the CAN ID
inputs and ensure that service tool communications are not active prior to
initializing CAN communications. The actuator will immediately drive to maintain
the position commanded by the supervisory control.
Position Demand
(Analog/PWM/CAN)
Power Input
(10-32Vdc)
RS-232
Service Tool
The supply voltage failure levels are below 6.25 V and above 33 V. The unit can
be configured to either alarm or shut down upon detection of a supply voltage
fault.
4 Woodward
L-Series Position Control Functional Overview
TPS TPS
Act’l Position Ouput
(0.75-4.25 V for CW-CCW) De-code
Linearization
Scaling &
Fault
Detection
Woodward
Calibration Settings
Configuration
Manual 26635
Aux 1
Run Enable
(optional)
L-Series Position Controller w/ CAN Capability
5
L-Series Position Controller w/ CAN Capability Manual 26635
Demand
Failed
The input failure levels are below 3% and above 97% duty cycle. The unit can be
configured to either alarm or shut down on detection of a position command
failure. The shutdown failsafe position is also user-configurable and can be set to
any point between 0% and 100%.
6 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
90 failsafe position
80
70
60
50
40
30
20
user-defined points
10
0
0 10 20 30 40 50 60 70 80 90 100
The input failure levels are below 0.2 V and above 4.8 V. The units can be
configured to alarm or shut down on detection of a position command failure
(loss of all position command inputs). The shutdown failsafe position is also user-
configurable and can be set to any point between 0% and 100%.
Woodward 7
L-Series Position Controller w/ CAN Capability Manual 26635
90 failsafe position
80
70
60
50
40
30
20 user-defined points
10
0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
8 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Discrete Output
A discrete output is provided to serve as a status indicator. This switchable
discrete output is a closure to ground capable of sinking 250 mA with an output
voltage rise of less than 1.5 V, and it is available to power external relays for
devices such as alarms or fuel shutoff solenoids. The circuit is protected
internally against overcurrent and inductive spikes, so external clamping is not
necessary.
There are two conditions that will prevent the discrete output from operating
correctly:
If battery positive is accidentally connected to the discrete output;
If the discrete output is shorted to ground.
The circuit will protect itself in the event of a miswire, but it will hold the output
open (floating) until the fault is removed.
Additional Inputs/Outputs
Auxiliary Inputs—There are four auxiliary inputs on the L-Series controller, all of
which are capable of both analog and discrete functions. They can all be
functionally defined for purpose in the software application. Although they are
very flexible, two of them are shared with the serial and CAN communications, so
will be unavailable if the L-Series is connected to the Service Tool or when CAN
is used. More detail concerning the auxiliary inputs is provided in Chapter 3
(Installation).
Woodward 9
L-Series Position Controller w/ CAN Capability Manual 26635
Temperature Sensing
The L-Series has an on-board temperature sensor to monitor board temperatures
and protect the unit from overtemperature. This temperature is monitored and a
fault is annunciated if the set point is exceeded.
Current limiting based on temperature begins when the combined current and
temperature environment causes board temperatures greater than 117 °C. The
limit curve is a linear derate from full current at 117 °C down to zero current at
125 °C. At 117 °C, an Over Temperature fault is annunciated. Depending on the
current (actuator torque) and ambient operating temperatures, the unit may never
reach a reduced level.
RS-232 Communications
RS-232 communications are available on the L-Series when used with an
external transceiver connected to pins 4 and 6. Serial communications allow for
the use of a service and configuration tool with the L-Series actuator. The
simplest way to establish this interface is to use Woodward kit # 8923-1061.
Functions available through this port include tuning, monitoring, and configuration
of the position controller. Detailed driver status information is also available.
Any RS-232 wiring must meet the requirements in the EIA RS-232 Standard
document. The RS-232 standard states that the length of the RS-232 cable
between the driver and the PC must be less than 50 ft (15 m) with a total
capacitance less than 2500 pF. The RS-232 data rate is fixed at 19.2 kbps. The
communication port is non-isolated and susceptible to both EMI noise and
ground loops related to PC connections and typical industrial environments.
The service port is not isolated and is not intended to function while
the prime mover is in normal operation. The service port is provided
for configuration and setup only.
CAN Communications
To use CAN (Controller Area Network), the L-Series version that supports CAN
must be purchased. The L-Series Position Control can provide either J1939 or
CANopen, based on the CAN Protocol setting in the Service Tool. AUX3 and
AUX4 inputs are not available for other I/O options since they are used for CAN
communications.
10 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Parameter Format
The L-Series uses a little-endian format when handling multiple-byte parameters
(i.e. a position demand of 50% is $FF0F, not $0FFF). All parameters must use
this format unless otherwise specified.
J1939
This section describes the communication that will take place over the J1939
Data Link when the optional CAN communication link is used and configured for
J1939. For details, see SAE J1939/11. The L-Series uses CAN 2B with 29-bit
identifiers.
Device Identifier
The device source address is a Service Tool configurable parameter (CAN
Device Identifier). The L-Series has an allowed range of 18 to 21 (12 to 15 hex),
allowing multiple L-Series controllers on a single CAN link. The configured
Device Identifier affects the PDU Specific portion of the incoming position
demand message.
Woodward 11
L-Series Position Controller w/ CAN Capability Manual 26635
The L-Series Position Controller optionally receives the following information over
CAN:
Position Demand
DM13
Message
Update rate: on startup. on request, response to Address Claimed
Data length: 8 bytes
Data page: 0
PDU format: 238
PDU specific: 0
Priority: 6
PGN: 60928 (0xEE00)
Data
Bytes 1.1 - 3.5: (21 bits) Identity Number, SPN 2837
Bytes 3.6 - 4.8: (11 bits) Manufacturer Code, SPN 2838
Byte 5.1: (3 bits) ECU Instance, SPN 2840
Byte 5.4: (5 bits) Function Instance, SPN 2839
Byte 6.1: (8 bits) Function, SPN 2841
Byte 7.1: (1 bit) Reserved
Byte 7.2: (7 bits) Vehicle System, SPN 2842
Byte 8.1: (4 bits) Vehicle System Instance, SPN 2843
Byte 8.5: (3 bits) Industry Group, SPN 2846
Byte 8.8: (1 bit) Arbitrary Address Capable, SPN 2844
The Address Claimed message will be sent out shortly after power has been
applied to the L-Series. The Address Claimed message will also be sent out in
response to a Request for Address Claimed. The Request for Address Claimed
can be sent to a specific Address or to the Global Destination Address, 255. The
L-Series will respond to a specific query, or one to the Global Destination
Address, 255.
The Source Address for the L-Series is configurable uniquely using the service
tool. Since Dynamic Addressing is not supported, the L-Series will only try to
claim the configured address. If a higher priority device claims the configured
address, the L-Series will stop communicating as defined per SAE J1939.
The Address Claimed Message will also be sent out if the L-Series receives an
Address Claimed message from the same Address as the receiving node and a
lower priority (higher value) NAME. The entire 8-byte value of the NAME is used
for arbitration with the Arbitrary Address Capable Field as the Most Significant
Bit.
12 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
The Cannot Claim Address message will be sent out if the L-Series receives an
Address Claimed message with the same Source Address as the receiving node
and with a higher priority (lower value) NAME. The entire 8-byte value of the
NAME is used for arbitration with the Arbitrary Address Capable Field as the
Most Significant Bit.
The Cannot Claim Address will also be sent out in response to a Request for
Address Claimed if the address was unsuccessfully claimed. The Cannot Claim
Address message is identical to the Address Claimed message in all aspects
except that the Source Address of the L-Series is replaced with 254.
If the L-Series cannot claim an Address, a status bit will be set and any position
demand value from CAN will be forced to zero (this may cause a shutdown
depending on demand source settings).
Message
Update rate: 0.1 sec
Data length: 8 bytes
Data page: 0
PDU format: 255
PDU specific: 252
Priority: 7
PGN: 65532 (0xFFFC)
Data
Byte: 1 Actual valve position (8 bits)
2 Desired valve position (8 bits)
3 Electronics Temperature
4 Reserved
5...6 Actual valve position (2 bytes)
7...8 Desired valve position (2 bytes)
Woodward 13
L-Series Position Controller w/ CAN Capability Manual 26635
Desired valve position—Desired position. A value of 0% represents min and a
value of 100% represents max.
Data length: 1 byte
Resolution: 1/2.56 % / bit, 0 offset
Range: 0 to 100% (scaled from 0 to FF hex)
Error Indicator set if: None
Bytes 1-4 of the diagnostic message are set to indicate their current status and
bytes 5-6 indicate historical (logged) value status. The logged diagnostics are
retained in non-volatile memory. They provide an indication of the events that
occurred since the last time they were cleared/reset.
Message
Update rate: 0.1 sec
Data length: 8 bytes
Data page: 0
PDU format: 255
PDU specific: 253
Priority: 6
PGN: 65533 (0xFFFD)
Data
Byte: 1..4 Diagnostics (current)
5..8 Diagnostics (logged)
14 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Bit code legend
The following diagnostics and events status will be sent by the L-Series actuator
in a sequence.
Diagnostic codes
The following diagnostics will be sent by the L-Series actuator.
Message
Update rate: between 5 and 100 ms
Data length: 2 bytes
Data page: 0
PDU format: 255
PDU specific: DA (L-Series Source Address*)
Priority: 1
Supported PGNs: 65298-65301 (0xFF12 … 0xFF15)
Data
Byte: 1...2 Valve Position Demand
3 Command Bits (only supported in 5418-6638 firmware)
4...8 Reserved/Not Used
Woodward 15
L-Series Position Controller w/ CAN Capability Manual 26635
Valve position demand — CAN commanded position setpoint.
Data length: 2 bytes
Resolution: 1/81.92 % / bit, 0 offset
Range: 0 to 100% (scaled from 0 to 1FFF hex)
* A reset action must be preceded by a no action command or the device will not
perform the requested action—the bits cannot remain in a ‘01’ state. The reset
action occurs only upon the transition from 00 to 01.
Only the Reset Action bit pattern (01) will activate a reset. All other commands
are interpreted as no action. The reset action requires a rising edge, meaning the
signal must go to another value and then back to 01 before another reset will be
performed.
Only the Reset Action bit pattern (01) will activate a reset. All other commands
are interpreted as no action. The reset action requires a rising edge, meaning the
signal must go to another value and then back to 01 before another reset will be
performed.
16 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Only the Shutdown bit pattern (01) will activate the CAN Stop Command. All
other commands will be interpreted as 'Run'.
Message
Update rate: on request
Data length: 3 bytes
Data page: 0
PDU format: 234
PDU specific: DA
Priority: 6
PGN: 59904 (0xEA00)
Data:
Byte: 1..3 requested data PGN* (byte 3 is msb)
4..8 reserved
*Supported PGNs: 60928, 65242, 65259, and 65496.
Message
Update rate: on request
Data length: 8 bytes
Data page: 0
PDU format: 254
PDU specific: 218
Priority: 6
PGN: 65242 (0xFEDA)
Data:
Byte 1: Number of Software Identification Fields, SPN 965
Data length: 1 byte
Resolution: 1 /bit, 0 offset
Range: 0 to 250 (0x00 to 0xFA)
Actual value: 1 (will always report 1)
Bytes 2-7: Software Identification, SPN 234
Data length: 6 bytes
Resolution: ASCII, 0 offset
Range: 0 to 255 per byte
Actual value: varies**
Byte 8: Delimiter, SPN 234
Data length: 1 byte
Resolution: ASCII, 0 offset
Range: 0 to 255
Actual value: 42 (0x2A)
Character: *
**Data actual value for firmware 5418-6084 NEW is ‘020000’ (for major rev ‘2’)
Data actual value for firmware 5418-6638 NEW is ‘020100’ (minor rev ‘1’)
Data actual value for firmware 5418-7022 NEW is ‘030000’ (for major rev ‘3’)
Woodward 17
L-Series Position Controller w/ CAN Capability Manual 26635
Message
Update rate: on request
Data length: Variable
Data page: 0
PDU format: 255
PDU specific: 235
Priority: 6
PGN: 65259 (0xFEEB)
Data:
Byte 1-2: Delimiter, SPN 234
Data length: 1 byte
Resolution: ASCII, 0 offset
Range: 0 to 255
Actual value: 42 42 (0x2A 0x2A)
Character: **
Byte 3-10: Serial Number field, SPN 588
Data length: 1 byte
Resolution: 1 /bit, 0 offset
Range: 0 to 250 (0x00 to 0xFA)
Actual value: varies
Byte 11-12: Delimiter, SPN 234
Data length: 1 byte
Resolution: ASCII, 0 offset
Range: 0 to 255
Actual value: 42 42 (0x2A 0x2A)
Character: **
Note: data is basically **cccccccc** sent in 2 messages, where c is the 8-byte
serial number representation.
Data1: 01 2A 2A (first 5 bytes of serial number)
Data2: 02 (last 3 bytes of serial number) 2A 2A FF FF
Specific Request
Action Message Actual (hex)
ECM-to-L-Series request RQST SOFT, 65259 EA1200 (EB FE 00)
L-Series-to-ECM RTS TP.CM_RTS, 16,14,0,2,2,65259 EC0012 (10 OE 00 02 02 EB FE 00)
ECM-to-L-Series CTS TP.CM_CTS,17,2,2,0,0,65259 EC1200 (11 02 02 00 00 EB FE 00)
L-Series-to-ECM data1 TP.DT, 1, data 1-7 EB0012 (01 2A 2A 31 31 31 31 31)
L-Series-to-ECM data2 TP.DT, 2, data 8-14 EB0012 (02 31 31 31 2A 2A FF FF)
ECM-to-L-Series EndOfMsg TP.ACK, 19,14,2,2,0,65259 EC1200 (13 FF 00 02 00 EB FE 00)
Global Request
Action Message Actual (hex)
ECM-to-L-Series request RQST SOFT, 65259 EAFF00 (EB FE 00)
L-Series-to-ECM BAM TP.CM_BAM, 16,14,0,2,2,65259 ECFF12 (20 OE 00 02 FF EB FE 00)
L-Series-to-ECM data1 TP.DT, 1, data 1-7 EBFF12 (01 2A 2A 31 31 31 31 31)
L-Series-to-ECM data2 TP.DT, 2, data 8-14 EBFF12 (02 31 31 31 2A 2A FF FF)
18 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Message
Update rate: on request
Data length: 8 bytes
Data page: 0
PDU format: 255
PDU specific: 216
Priority: 6
PGN: 65496 (0xFFD8)
Data:
Byte: 1...8 Parameter file identifier. 8-bytes, 1 character/byte.
Start/Stop
The L-Series will respond to the Start and Stop Broadcast commands for the
‘Current Data Link’ and supports the Hold Signal to maintain the Stop state for
another 6 seconds. In addition to ceasing message broadcasts, the L-Series
suspends loss of communications diagnostics during a DM13 Stop state.
Suspend/Resume
The suspend function turns off the loss of communication diagnostics in the L-
Series. An example usage would be when an ECM reflash is initiated. Loss of
communication diagnostics will resume upon receipt of a DM13 resume signal,
upon receipt of a position command (normal ECM communication resumes) or a
device power cycle. Indefinite suspension is supported, temporary suspension is
not supported.
Message
Data length: 8 bytes
Data page: 0
PDU format: 223
PDU specific: DA
Priority: 6
PGN: 57088 (0xDF00)
Data
Byte: 1 bits 8-7 Current Data Link (Start/Stop)
bits 6-1 (not supported)
Byte: 2-3 (not supported)
Byte: 4 bits 8-5 Hold Signal
bits 4-1 Suspend Signal (Suspend/Resume)
Byte: 5-6 Suspend Duration (not supported)
Byte: 7-8 SAE Reserved
Woodward 19
L-Series Position Controller w/ CAN Capability Manual 26635
Start/Stop bit interpretation (SPN1230)
Bit Code Description
00 Stop Broadcast
01 Start Broadcast
10 Reserved
11 Don’t Care/take no action (leave as is)
Suspend Signal bit interpretation (SPN 2618)
Bit Code Description
0000 Indefinite suspension of all broadcasts
0001 Indefinite suspension of some messages
0010 Temporary suspension of all broadcasts (not supported)
0011 Temporary suspension of some messages (not supported)
0100-1101 SAE Reserved
1110 Resuming normal broadcast pattern
1111 Not Available
Hold Signal bit interpretation (SPN 1236)
Bit Code Description
0000 All Devices
0001 Devices whose broadcast state has been modified
0010-1110 SAE Reserved
1111 Not Available
CANopen
Overview
CANopen is a networking system based on the CAN serial bus. CANopen
assumes that the device’s hardware has a CAN transceiver and CAN controller
as specified in ISO 11898. The CANopen specification covers both application
layer and communication profile. The CANopen profile family specifies
standardized communication mechanisms and device functionality. It is
maintained by an international users’ and manufacturers’ group called CAN in
Automation (CiA).
The L-Series CANopen Data Link is functional when the optional CAN
communication link is used and the CAN Protocol is configured for CANopen. For
details on the CANopen protocol, refer to CiA DS301 Version 4.02.
Initially only one L-Series was going to be on a single CAN link. This requirement
has recently changed and some areas of this document will also change as a
result.
20 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Device Identifier
The Device Identifier is a Service Tool configurable parameter, allowing multiple
L-Series controllers on a single CAN link. Allowed values for the Device Identifier
are from 1 to 127.
The configured Device Identifier affects the COB-ID of the incoming message.
COB-IDs follow the predefined connection set as defined on page 78 of DS301.
Heartbeat
The L-Series heartbeat message is transmitted at the user-defined Heartbeat
Producer Time set using the Service Tool.
Woodward 21
L-Series Position Controller w/ CAN Capability Manual 26635
Requested Messages
The software version number, parameter filename, and serial number messages
can be obtained using a request of the Identity Object. The Identity Object is
accessed via SDO upload at OD Index 0x1018.
Received Messages
The L-Series receives only one input command from CAN, the position demand
setting. To use this input, either the primary or backup position command signal
must be set for ‘CAN’. The maximum message receive frequency that the L-
Series can respond to is 9 ms. The minimum receive rate, prior to an
annunciated fault, is determined by the CAN Fault Timeout setting in the Service
Tool.
22 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Transmitted Messages
The transmitted parameters are shown in Table 1. These parameters are
transmitted at a frequency of one per second.
Faults
Faults are separated into two categories: Logged Faults and Current Faults. The
Current Faults are volatile and reset every time power is applied. Current Faults
are detected faults that are presently active; they may latch or not latch
depending on the fault. All latching Current Faults are reset by a power cycle or
Service Tool reset. All logged faults are latched and written to the EEPROM.
They must be cleared through the Service Tool.
Watchdog Reset
Watchdog Reset is true if a watchdog timer timeout occurred which resulted in a
reset of the microprocessor. This is a hard-coded alarm. If detected, the control
will attempt to continue normal operation.
Brownout Reset
Brownout Reset is true if CPU Voltage drops below 4.2 V but not below 1 V. The
brownout detect circuit will reset the CPU. This is a hard-coded alarm. If
detected, the control will attempt to continue normal operation.
EEPROM Fail
EEPROM Fail indicates failure or corruption of the internal non-volatile memory.
If the CRC is not correct for the EEPROM data, this fault will be set true. This is a
hard-coded internal shutdown. If detected, the control output will go limp. A
power cycle is required to clear this fault.
OverTemp
If the on-board temperature sensor reads above 117 °C, this error will be set,
which is the temperature at which current limiting begins. At 125 °C, the
temperature-based current limiting will effectively make the output "limp" by
reducing the drive current to zero.
Position Error
Position Error detection logic will indicate a difference between commanded
position and actual position exceeded for longer than the set delay. The error
magnitude and duration are customer-configurable parameters.
Woodward 25
L-Series Position Controller w/ CAN Capability Manual 26635
Can be configured as an alarm or shutdown. If configured as a shutdown, the
control will drive to Shutdown Position (using position control) if this fault is
detected. If configured as an alarm, the control will attempt to continue normal
operation.
CAN Fault
Indicates the address was not successfully claimed (J1939) or the position
command over CAN is stopped or the detected CAN position command updates
are too slow. The command failed detection is only active when the position
demand is configured for 'CAN'. If new position updates from CAN are not
received within the configured CAN Fail Timeout a CAN Fault is annunciated.
26 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Tamper Fault
CAN command failed is only active when the backup position demand is
configured for 'CAN' and Tamper Fault is enabled.
Indication that the primary position command does not match the CAN position
command. When this condition is detected the primary command will be “faulted”
and the backup (CAN) command will be used.
Failure levels: Set by customer variable, |Error| > CAN Tracking Error Max
Persistence: Set by customer variable, CAN Tracking Error Delay
Override: Fault is disabled for CAN Fault
Woodward 27
L-Series Position Controller w/ CAN Capability Manual 26635
Chapter 3.
Installation
Introduction
This chapter provides instructions on how to mount and connect the L-Series
controller into a system. Hardware dimensions are provided for mounting the
device to a specific application.
The surface of this product can become hot enough or cold enough
to be a hazard. Use protective gear for product handling in these
circumstances. Temperature ratings are included in the specification
section of this manual.
28 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Unpacking
Be careful when unpacking the actuator. Check the unit for signs of damage,
such as bent or dented panels, scratches, and loose or broken parts. Notify the
shipper and Woodward if damage is found.
Mechanical Installation
Mounting Location
Locate the L-Series control a distance from sources of extreme radiant heat,
such as exhaust manifolds or turbochargers. The operating temperature range of
the control is –40 to +105 °C (–40 to +221 °F). In spark-ignited applications,
make sure the L-Series is located away from the ignition coil, and that harness
wires are not routed next to the spark plug wires.
Mounting Orientation
While it is not a requirement, it is good practice to orient the connector feature on
the control in a horizontal or downward orientation to minimize fluid accumulation
between the enclosure and the mating connector’s gasket.
Actuator Configuration
The L-Series actuator utilizes a 2-inch (50.8 mm) square mounting bolt pattern
and is intended to fit within an envelope of 2.618 x 2.618 x 2.540 (66.50 x 66.50 x
64.52 mm) with the short dimension along the shaft axis. Two shaft seal
configurations are available, an internal lip seal and an external lip seal with
spring backup (Figure 3-2). In addition, six independent output shaft
configurations are available (Figure 3-3). Consult Woodward Applications
Engineering for the application appropriate seal and shaft configuration.
Mounting Hardware
Use #10 or M5 fasteners to attach the L-Series control to the mounting bracket.
The bracket and attaching hardware must be designed to hold the weight and to
withstand the vibration associated with prime mover mounting. Use the
appropriate fasteners for securing the mounting bracket to the engine.
Woodward 29
L-Series Position Controller w/ CAN Capability Manual 26635
30 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward 31
L-Series Position Controller w/ CAN Capability Manual 26635
32 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward 33
L-Series Position Controller w/ CAN Capability Manual 26635
Electrical Installation
Figure 3-4 shows a wiring pin-out of the L-Series control, as viewed by looking
into the control’s connector feature. Typical connections to external devices are
also shown.
The L-Series has an operating voltage range of 8 to 32 Vdc with nominal
voltages of 12 or 24 Vdc. The power supply is reverse polarity protected, and
consumes 32 W maximum power at a peak current of 1 A (32 V) assuming 4 Ω
stator resistance at 25 °C. These assumptions are based on the fact that the
software limits the power to the rotary actuator to 25 W at any given time and
input voltage (in the valid range). The control system should be protected with a
6 A slow-blow fuse in the voltage supply lines. Typical max average current is 2.1
A, or max 25 W at 12 V. The application should be configured to turn on power to
the actuator when the engine is first cranked.
34 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Electrical Connections
Prior to installation, refer to the wiring diagrams and the representative I/O
interfaces schematic in this chapter. Also, review the hardware I/O specifications
in Appendix B.
The control will only meet ingress protection specifications while the
Deutsch connector is installed in the unit. As such, the unit should
not be exposed to operating environments unless the mating
connector is installed. In addition, if a wire is not used for each of the
12 pins on the control, a Deutsch 114017 plug must be used in place
of each missing wire. Failure to adhere to these guidelines may
result in product failure or decreased life.
Use 16 to 18 AWG (1 to 1.5 mm²) stranded copper wire with insulation that
meets temperature requirements in the harness design. A wiring harness stress
relief within 16” (406 mm) of the control’s connector is recommended. Limit all I/O
and signal lines to less than 30 m (98 ft). Also limit input power (B+/B–)
connections to an earth grounded battery or conditioned power interface to less
than 10 m (33 ft) from the L-Series product.
Dress the harness with wire loom to contain it in a single bundle. Use grommets
when passing the harness through metal panels.
Woodward 35
L-Series Position Controller w/ CAN Capability Manual 26635
Connector
The following Deutsch connector components are recommended for harness
designs:
Recommended Optional
Mating Connector DT06-12SA-P012
Secondary Lock W12S-P012
Sockets 0462-201-16141 1062-16-0122
Crimp Tool HDT-48-00 DTT-16-00
Sealing Plug 114017
For convenience, Woodward part number 8928-396 is a kit that provides all the necessary
Deutsch components (crimp tool not included).
6A FUSE
+
12/24 Vdc
connector POWER INPUT + 1 -
key
TPS OUTPUT 2 THROTTLE POSITION
12 1 V (0.75 VDC TO 4.25 Vdc )
PWM -/AUX -
3
(SIG. GND)
11 2
AUX3+/RS232 TX 4
10 3 SERIAL COMMUNICATIONS (USE
INPUT POWER GND 5 WOODWARD 8923-1061 TO
9 4 CONNECT TO COMPUTER)
AUX4+/RS232 RX 6
8 5
+5V OUT 7 12 V/24 V OPTIONAL RUN ENABLE DISCRETE
7 6 INPUT (CLOSED TO RUN)
AUX1+ 8
connector 5 Vdc - 32 Vdc, 500 mA max.
key RELAY DRIVER 9
RELAY COIL
CUSTOMER CONTROL
Connector Pinout as Viewed 0.5-4.5 +
AUX2+ 10
Looking Into PWM OR 0.5-4.5 V
L-Series Control PWM + POSITION COMMAND
PWM+ 11
-
POS. CMD COMMON
IGN 12
VIS-168
08/3/4
Connector
Description Comment
Pin #
+12 V/24 Vdc Input
1 Supply power
Power
2 TPS Signal Output Direct position feedback output indication
3 PWM – / AUX – Ground for the PWM or AUX command signal common
RS-232 transmit / CAN
4 For use with the service tool and CAN
H
5 Input Power Ground Ground for the 12 V/24 V input power
6 RS-232 receive / CAN L For use with the service tool and CAN
7 5 V Out Power for external sensors (10 mA max)
8 Aux Input 1 Optional Run Enable or CAN ID discrete input
9 Relay Driver Output Status / fault detection output
10 Aux Input 2 Optional 0–5 V command input or CAN ID selector
11 PWM + / Aux Input 5 Optional PWM command input or CAN ID discrete input
12 Ignition Input Not used—Leave open
36 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Power Supply Input (+12 Vdc/24 Vdc at pin 1, ground at pin 5)—The L-Series is
configured for 12 or 24 V nominal operation, although it will handle 8–32 V. The
power supply terminals are reverse polarity protected, and in the case that a
reverse polarity condition exists, the L-Series actuator will not power-up and will
remain at the minimum stop if attached to a throttle body with an internal return
spring.
The input power must be fused. Failure to fuse the L-Series could,
under exceptional circumstances, lead to explosion, personal injury,
or damage to the control valve.
PWM Command Input (+PWM at pin 11, PWM ground at pin 3)—This actuator
can be configured to handle a PWM signal from a high-side or low-side open-
collector or open-drain source, as well as from a push-pull (customer pull-up)
source. The necessary pull-up and pull-down voltages to accommodate the
open-collector sources are handled within the L-Series actuator. Nominally, the
frequency of PWM is 1 kHz, but it will handle the full range of 300 to 1500 Hz.
See Figure 3-5 below, which describes the possible input types and
configurations for the PWM input.
This input (pin 11) can also be used as a CAN ID HIGH discrete input, referred to
as Aux5. This feature only applies to J1939 and is not available in firmware
5418-6084.
TPS Output (pin 2, referenced to either pin 3 or pin 5)—This pin feeds the output
of the Hall effect position sensor to the terminal wiring. The output range of this
pin should be approximately 0.75 Vdc when the actuator is full counterclockwise
(when viewed at the end of the shaft), and approximately 4.25 Vdc when the
actuator is at full clockwise. This gives the end user an indication of throttle
position.
Woodward 37
L-Series Position Controller w/ CAN Capability Manual 26635
For this type of PWM Source... ...the L-Series PWM Input looks like...
5 - 32 VDC
L-Series
Pin 11
To
PNP (or P-Channel FET) 4 kW 9.5 kW Processor
Internal Clamped to 5V, then
12 kW
Command compared with 2.5V reference.
L-Series 12 kW
NPN (or N-Channel FET) Pin 11
To
Internal 4 kW 9.5 kW Processor
Command
Compared with 2.5V
reference.
L-Series
Pin 11
To
Internal 5 - 32 VDC
Processor
Command OR 13.5 kW
Internal
Command
5 - 32 VDC
OR
Internal
Command
38 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
RS-232 Connections (pin 4 and pin 6)—These pins are for serial communication
with the L-Series actuator. An external RS-232 transceiver is necessary to make
communications possible with the Woodward L-Series Service Tool. A
connectivity kit can be purchased from Woodward to accomplish this. Further
instructions for using this connectivity kit are provided in Chapter 4. See also the
description below on Auxiliary Inputs.
Relay Driver Output (pin 9)—This pin provides the end user with a means for
detecting a fault or shutdown condition that is experienced by the L-Series
actuator. It is a low-side driver capable of sinking 250 mA (not to exceed 500 mA)
through an external load such as a lamp or relay. This circuit is internally
protected against over-current conditions and inductive flyback, such as from a
relay coil. By default, this circuit will be configured in a failsafe manner, meaning
it will be active (conducting) when no fault exists, but if power is lost or a fault is
detected by the L-Series actuator, the circuit will open. See Figure 3-6 below for
typical usage of this feature.
5-32 VDC,
500mA maximum
Lamp Relay
Indicator Coil
OR Relay Driver
Status back
L-Series
to Processor
Pin 9
Self-Protecting From
.01mF FET Processor
Woodward 39
L-Series Position Controller w/ CAN Capability Manual 26635
Auxiliary Inputs (pins 4, 6, 8, and 10)—The L-Series has three dedicated digital
inputs (AUX2, AUX3, and AUX4) used to activate various features of the control.
Shorting an auxiliary input pin to battery voltage activates it. Removing battery
voltage from an input pin or shorting the pin to ground deactivates the input. If it
is decided not to use battery voltage with the auxiliary digital inputs, Woodward
recommends that at least 3 V be present on an input pin in order to change its
state from inactive to active. All discrete inputs will be the same voltage as the
system power supply and will be active only while the input is in a high state. For
AUX2, AUX3, and AUX4, greater than 2.5 Vdc is considered high, and less than
0.8 Vdc is considered low. For the AUX1 discrete input only, the input must
exceed 3 V to activate the discrete state. AUX3 and AUX4 are also used for
digital communications such as RS-232 (service tool) or CAN (If the CAN option
was purchased). RS-232 and CAN will NOT run simultaneously.
An additional CAN ID HIGH discrete input (AUX5, pin 11) can be configured to
support up to four J1939 devices on a single bus.
AUX1 can be configured as a run enable or CAN ID LOW discrete input (J1939
mode only). This configuration must be specified in the configuration of the
device using the Service Tool. If AUX1 is selected to perform the run enable
function, then 5 V (5–32 V) applied to pin 8 will allow the control to run normally.
When this input is opened, the actuator will be in stand-by mode. When in stand-
by, the actuator driver will be disabled, and the shaft will be limp.
See Figure 3-7 below for typical usage of AUX1 and AUX2 when the L-Series is
configured as an analog position control.
This actuator can also be commanded using a PWM signal. See the
description above in the PWM Command Input section. The PWM and
AUX2 input pins should not be tied together.
40 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
L-Series
Aux.2 Input
(Pin 10) Clamp to 5V Analog
Command
0.5V to 4.5VDC 10k Signal to
Command Signal Processor
1000pF 499k
** if optional external Run Enable is chosen during L-Series configuration, Aux. 1 can be used to enable or
disable the actuator output shaft torque.
Communications
The L-Series can communicate using CANbus protocol or serially using RS-232.
CAN is an optional feature that requires additional hardware and a CAN-capable
processor. For protocol details, refer to the CAN section in chapter 4 of this
manual.
On CAN-capable units, both CAN and RS-232 share the same I/O pins. The L-
Series performs a check on these pins in power-up to determine if the Service
Tool is attempting to communicate with the unit. If not, CAN is initialized and
used. When finished with the Service Tool functions, disconnecting the RS-232
communications and cycling the input power will re-establish CAN
communications.
Woodward 41
L-Series Position Controller w/ CAN Capability Manual 26635
RS-232/Service Tool Connections (pin 4 and pin 6)
These pins are for serial communication with the L-Series actuator. An external
RS-232 transceiver is necessary to make communications possible with the
Woodward L-Series Service Tool. A connectivity kit can be purchased from
Woodward to accomplish this. Further instructions for using this connectivity kit
are provided in Chapter 4.
Woodward recommends that the OEM or packager provide a breakout cable that
is connected to the L-Series service port and run to an easily accessible area on
the engine. The service port is absolutely necessary to set up and troubleshoot
the L-Series.
Any RS-232 wiring must meet the requirements in the EIA RS-232 Standard
document. The RS-232 standard states that the length of the RS-232 cable
between the driver and the PC must be less than 50 ft (15 m) with a total
capacitance less than 2500 pF. The RS-232 data rate is fixed at 19.2 kbps. The
communication port is non-isolated and susceptible to both EMI noise and
ground loops related to PC connections and typical industrial environments.
Functions available through the Service Tool include tuning, monitoring, and
configuration of the position controller. Detailed driver status information is also
available. For details, refer to the Service Tool chapters of this manual.
The service port is not isolated and is not intended to function while
the prime mover is in normal operation. The service port is provided
for configuration and setup only.
The limits below are the maximum allowed by the CAN standard, when isolated.
Shorter lengths in practice are highly recommended in order to maintain a high
level of reliability.
42 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
CAN Network Termination
CAN networks must be terminated with a 121 1% differential resistance at
each end of the network. It is necessary to terminate the network to prevent
interference caused by signal reflections. Depending on length, many CAN
networks will not operate at all without the proper termination. Generally it is a
good idea not to build the termination into a node since CAN is intended to be a
plug-and-play type network with RIUP (remove and insert under power).
However, no specific restrictions are placed on the inclusion of termination
resistors in a node.
Termination resistors must be installed only at the physical ends of the network.
Terminating other midpoint units can overload the network and stop all
communications. As a rule, no matter how many units are on a network, there
should never be more than two terminations installed.
If termination resistors are provided within a node, the EMC test should be
conducted both using and not using the termination network to validate that both
wiring versions provide acceptable results. This assumes the termination network
can be disabled which is generally true.
In most applications, a ground wire is needed between all units on the network.
The preferred method for isolated ports is to include a separate wire in the CAN
cable. This keeps the communications and ground reference at the same
potential at all times. For this reason the recommended cable types below are
DeviceNet cables, which include an extra wiring pair.
Non-isolated nodes may not have a signal ground available for connection. If a
signal ground is not available, use the alternate wiring scheme of connecting the
CAN ground wire from the isolated nodes to the B- terminal at a non-isolated
node (this is typically the signal reference for CAN if isolation is not provided).
Woodward 43
L-Series Position Controller w/ CAN Capability Manual 26635
Here are the cable specifications from the DeviceNet standard, a good source for
CAN requirements.
“DeviceNet” cable is a good example of CAN cable, but use caution as most
DeviceNet cables are not rated for on-engine temperatures.
When using DeviceNet cables, only use the “Thick” or “Trunk” cable. The
advantage of “Thick” cables is the conductor size. Larger gauge conductors fare
much better in high vibration environments.
44 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Below are two example DeviceNet CAN cables that are suitable for on-engine
use if the wiring area stays below 75 °C. Other cables may exist.
CAN Shielding
Shielded cable is required for industrial applications. Only very cost sensitive
automotive applications attempt to use unshielded cable for communications.
Unshielded cables and improperly shielded cables are likely to cause
communication problems and unreliable control operation. The standard for CAN
networks is that each device will have an ac-coupled (connected through a
0.01 µF coupling capacitor) shield connection and a single shield ground location
will be provided. The ground location does not have to be at a unit connector, it
can be any convenient place in the system but should be the same ground as
used for the system power.
YES !!
Other CAN HI CAN HI
Units On
CAN Bus Shielded Twisted-Pair (STP)
CAN LO CAN LO
Shield Shield
YES !!
Other CAN HI CAN HI
Units On
CAN Bus Shielded Twisted-Pair (STP)
CAN LO CAN LO
Shield Shield
NO !!
Other CAN HI CAN HI
Units On
Shielded Twisted-Pair (STP)
CAN Bus CAN LO CAN LO
Shield Shield
NO !!
Other CAN HI CAN HI
Units On
CAN Bus Shielded Twisted-Pair (STP)
CAN LO CAN LO
Shield Shield
Woodward 45
L-Series Position Controller w/ CAN Capability Manual 26635
Ground Junction (see Figure 3-10)—This grounding junction is provided for
joining external ground wires. THERE IS NOT AN INTERNAL CONNECTION TO
CIRCUIT GROUND. Terminal pins 3 and 5 must be used for access to the circuit
ground. This junction point is completely electrically isolated from the L-Series
actuator’s electronics, and is solely for convenience during installation.
GROUND
Ground
Junction
JUNCTION
46 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Chapter 4.
Service Tool
Introduction
This chapter covers tuning, configuring, calibrating, and servicing the control via
the L-Series Service Tool. The control should already be installed on the engine.
Description
The Service Tool software is used to configure, tune, and troubleshoot the
L-Series controller. This chapter identifies the parameters available that can be
viewed and provides detailed information on configuring and setting up the
L-Series to the customer-specific field application.
Woodward 47
L-Series Position Controller w/ CAN Capability Manual 26635
The following hardware is required to work with the L-Series control:
PC-compatible laptop or desktop computer with at least one available serial
communications port, and Windows 2000, XP, NT 4.0, Vista, Win 7 (32- and
64-bit) as the operating system.
Programming/datalink harness as shown in Figure 4-2.
In addition to the hardware, the following are the distributions of tool software
needed to communicate with the control:
Woodward part number 9927-1222, L-Series Service Tool
Getting Started
Installation Procedure
The Service Tool software can be downloaded and installed from the Woodward
internet site (www.woodward.com/software).
What to do next
After the software is installed, connect a serial communications cable between
the RS-232 connections on the L-Series control and an unused serial port on
48 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
your computer. Run the Service Tool program and select the appropriate comm
port. Once connected to the control, the status bar will display ‘connected’ and
the Service Tool screen will populate with monitor parameters.
Configuration Password
If a password has been saved in the configuration file, the file cannot be opened
without first entering the password. Once a configuration with a password has
been loaded into the L-Series driver, the control configuration cannot be opened
without the password. All other service tool functions do not require a password
including: writing over a password protected file configuration, writing over a
password protected control configuration, using the Position Calibration Tool, and
using the Edit Position PID.
L-Series Configuration
The L-Series can be configured either on-line or off-line. On-line configuration
can only be performed when the Service Tool is connected to and
communicating with the L-Series control. Off-line configuration can be done at
any time; however, settings will not take effect until they are loaded into the
control.
Woodward 49
L-Series Position Controller w/ CAN Capability Manual 26635
The current L-Series control configuration settings can be viewed at any time
when connected to the control by opening the Configuration Editor (File/Open
Control Configuration). See Figure 4-3.
50 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Configuration Parameters
There are five tab sheets that contain all the configuration settings: Overview,
Setup, Discrete Output, Alarm/Shutdown and Security.
Note: If the Shutdown/Fail Position is not set to ‘0.0’, the ‘Actuator fails to a non-
zero position.’ indication is activated. This is to alert the user of a potential unsafe
condition.
Friction/Dither Setting
Sets the position controller’s friction and dither values. This parameter should be
set to zero (no effect) while tuning the PID and then increased for optimum
response. If unsure, a typical value would be 25. Allowed values: 0–100.
Proportional Gain
Sets the position controller PID’s proportional gain. Increased gain corresponds
to increased PID output (higher proportional = faster response). This setting can
also be dynamically adjusted using the PID Tuning screen. Allowed values: 0–
100%.
Integral Gain
Sets the position controller PID’s integral gain. Increased gain corresponds to
increased PID output (higher integral = faster response). This setting can also be
dynamically adjusted using the PID Tuning screen. Allowed values: 0–100%.
Derivative Gain
Sets the position controller PID’s derivative gain. Increased gain corresponds to
increased PID output (higher derivative = faster response). This setting can also
be dynamically adjusted using the PID Tuning screen. Allowed values: 0–100%.
52 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Backup Position Demand Input- (only displayed if configured for Redundant
Demand Inputs)
The Backup Position Demand source can be set to one of the following:
PWM Selects a PWM position demand input.
Analog Selects an analog (0–5 V) position demand input.
CAN Selects a CAN position demand input.
Note: The Primary and Backup Position Demand input cannot be set to the same
source.
Woodward 53
L-Series Position Controller w/ CAN Capability Manual 26635
PWM Settings - (only displayed if PWM is selected as a Demand Input)
Two additional configuration parameters appear when the position demand
is set to PWM (see Figure 4-6).
PWM Offset
Sets the PWM Duty cycle offset. This setting is provided to compensate for
duty cycle variations in PWM input frequencies, voltages, and types.
Allowed values: –5.01 to +5.01%
CAN Settings
CAN ID Discrete Input (only displayed for J1939 with firmware 5418-6084)
Determines if the CAN ID selector is used. When used, allows two to four
different device identifiers, determined by the discrete input state on device
power-up. Allowed values: Not Used or Aux 2.
CAN ID LOW Discrete Input (only displayed for J1939 with firmware 5418-6638)
Determines if the CAN ID selector is used. When used, allows two to four
different device identifiers, determined by the discrete input state on device
power-up. Allowed values: Not Used or Aux 2.
CAN ID HIGH Discrete Input (only displayed for J1939 with firmware 5418-6638)
Determines if the CAN ID selector is used. When used, allows two to four
different device identifiers, determined by the discrete input state on device
power-up. Allowed values: Not Used, Aux 1 or Aux5.
CAN Device Identifier 2 (only displayed for J1939 when using CAN ID LOW
discrete input)
Sets the device source address when the CAN ID discrete inputs select unit
2. Allowed values: 18–21
CAN Device Identifier 3 (only displayed for J1939 when using CAN ID HIGH
discrete input)
Sets the device source address when the CAN ID discrete inputs select unit
3. Allowed values: 18–21
54 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
CAN Device Identifier 4 (only displayed for J1939 when using both CAN ID
HIGH and LOW discrete inputs)
Sets the device source address when the CAN ID discrete inputs select unit
4. Allowed values: 18–21
Non-linear Actuator
Selects either a Linear position command, when unchecked, or a Nonlinear
5-point curve command. Linear/Nonlinear refers to the relationship between
the position requested and the position commanded to the position PID.
When this box is checked, additional parameters appear to set up the
5-point demand curve.
Woodward 55
L-Series Position Controller w/ CAN Capability Manual 26635
Relay Output Configuration
The relay output can be configured to one of the following:
Normally On Sets the relay driver to a normally on mode that turns off
for any of the faults selected. This is the preferred,
failsafe output configuration.
Normally Off Sets the relay driver to a normally off mode that turns on
for any of the faults selected.
56 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Enable CAN Fault Latching – (only displayed on CAN units if Enable Fault
Latching is false)
This setting determines whether the CAN fault is latching or non-latching. This
option is provided to latch-in the CAN fault even though all other faults are set to
non-latching.
CAN Tracking Error Maximum (%) – (only displayed if Position Tamper Fault is
used)
Maximum deviation between the primary position demand and the CAN position
demand. If the Error is exceeded for longer than the CAN Tracking Error Delay,
then the Position Tamper Fault is annunciated.
Allowed values: 0–100% but must be greater than the Max Demand Difference
setting.
Woodward 57
L-Series Position Controller w/ CAN Capability Manual 26635
58 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Security Configurations
All checked features will have the security password enforced prior to allowing
the function. Unchecked features will not be prompted with a password.
Read Configuration
When checked, requires a password before the configuration can be read
from the L-Series control (protects Open From Control execution).
This is the minimum level of protection and is required in order to use any
other security option.
Configuration Load
When checked, requires a password before a configuration can be loaded
into the L-Series control (protects Load to Control execution).
Position Calibration
When checked, requires a password before the position calibration mode
can be entered (protects Manual and Automatic Position Calibration menu
options).
Select the File/’Load to Control’ option from the menu or Blue Arrow icon on the
Configuration Editor to load the changes into the control. The L-Series process
must be zero prior to allowing a ‘Load’ command. This feature can be optionally
password protected.
Woodward 59
L-Series Position Controller w/ CAN Capability Manual 26635
Each screen displays the position setpoint and actual position values.
Position Setpoint
Displayed value of the position demand, in percent.
Actual Position
Displayed value of the actual position, in percent.
Communication Status
This section of the status bar shows the status of communication between the
service tool and the L-Series Driver. For more information, see Establishing
Communication.
Connected—The Service Tool is connected to and communicating with the
driver.
Not Connected—The Service Tool is not connected to the driver.
Connecting—The Service Tool is attempting to connect to the driver. This
message is displayed when Connect is selected from the Communications
menu or when attempting to re-establish communication to the driver. If the
connection is lost it will continuously attempt to re-connect.
Alarm Status
Indicates that one or more alarms on the Alarms screen are active.
Shutdown Status
Indicates that one or more shutdowns on the Shutdowns or Internal Shutdowns
screen are active.
60 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Supply Voltage
Displayed value of the input power, in volts, as read by the processor.
Power Demand
Displayed value of the power demanded, in watts, as read by the processor. This
is an indication of the work output.
Electronics Temperature
Displayed value of the electronics temperature sensor, in degrees Celsius, as
read by the processor. The temperature sensor is physically located between the
electronics module and the LAT motor.
AUX2 Input
Displayed value of the analog 0–5 V input, in volts. This indication is displayed
only when the position demand is set to ‘0.5 V’.
Discrete Output
On/Off status of the discrete output command. The indicator is illuminated when the
channel is commanded to ON and grayed-out when the command signal is OFF.
Run Enabled
Open (off) / Closed (on) indication of the Run Enable discrete input.
Woodward 61
L-Series Position Controller w/ CAN Capability Manual 26635
Full Travel Position Setpoint
Indication of the position setpoint in terms of total overall unit travel. Useful if a
less than full-travel user-calibrated range is used.
An active fault is one that is currently active or latched in the control. The
latching/non-latching faults configuration setting factors into this indication. If the
fault is latching, then an active fault could either be one that is still present or one
that occurred but has not been reset. Latched faults can be cleared by cycling
power on the L-Series control or by selecting the ‘Reset Alarms and Shutdowns’
button on any of the Alarm or Shutdown screens.
A logged fault is one that occurred but is no longer currently active or latched in
the control. Logged faults are permanently cleared by selecting the ‘Reset
Logged Alarms and Shutdowns’ button on any of the Alarm or Shutdown
screens.
62 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Alarms Screen
To monitor the alarm conditions, go to the Alarms page on the main window. The
values displayed on this screen dynamically change with the fault configuration.
Refer to chapter 2 for a complete listing and details of all the faults.
Woodward 63
L-Series Position Controller w/ CAN Capability Manual 26635
64 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Identification Screen
To monitor the L-Series product identification, go to the Identification (Figure 4-
15) page on the main window.*
Woodward 65
L-Series Position Controller w/ CAN Capability Manual 26635
The L-Series controller can be put into a manual control mode from this screen
by selecting the “Enable Manual Position Tuning’ checkbox (Figure 4-16). Once
in manual mode, the position setpoint box is highlighted and the value displayed
is actively positioning the output. Use this command to create step changes for
the PID and monitor the response using the displayed trend.
Pressing the Properties button pops open the Properties Window (Figure 4-17).
From this window the user can adjust the trending window properties including
the update rate and display range.
66 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
The Service Tool can be used to calibrate the control to end user stops (physical
or soft) or to verify the position calibration. To get to the Position Calibration
screens select the desired function from Position Calibration under the Tools
menu selection.
Position Calibration is only used when the full travel of the actuator
is constrained or limited such that 0 to 60 degrees of travel is not
used.
Woodward 67
L-Series Position Controller w/ CAN Capability Manual 26635
Automatic Mode
1. Select Automatic Position Calibration Mode.
2. Select CW or CCW Direction.
3. L-Series automatically rotates in both CW and CCW directions until the stops
are detected. The values are then captured and stored.
4. When completed, cycle the power on the L-Series.
5. Woodward recommends that a Position Verification be performed to confirm
the calibration is correct. See Position Verification below.
Manual
1. Determine to rotational travel limits. This can be done by positioning the unit
to the minimum and maximum positions and recording the position settings.
2. Select Manual Position Calibration Mode.
3. Select Direction.
4. Enter the pre-determined rotational travel limits values.
5. When completed, cycle the power on the L-Series.
6. Woodward recommends that a Position Verification be performed to confirm
the calibration is correct. See Position Verification below.
Position Verification
When the Verify Position screen is entered, the control is put into position control
and the position is set to the position the control was at when the screen was
entered. The screen displays the “User” Requested Position, Actual Position,
Minimum Position, and Maximum Position (see Figure 4-18). These User
Positions are calculated from the user-calibrated stops.
The Full Travel Actual Position is the full stroke factory position without user
stops after software linearization. The Full Travel Sensor Position is the full
stroke factory position without user stops before software linearization. The Full
Travel Sensor Position will match the TPS Output Signal.
The Verify Position screen can be used to check the calibration or to get the
minimum and maximum position values for the manual calibration. If the Enable
Requested Position Tuning box is checked the valve can be positioned anywhere
from 0 to 100% of the user minimum and maximum stops by entering a value into
the Requested Position. If the Enable Requested Position Tuning box is
unchecked the valve will go limp and can be physical positioned by hand.
If the full factory position calibration range is not being used (the
Manual or Automatic Calibration has been performed) and the
minimum position direction is changed, the calibration must be run
again for the Verify Position mode to work correctly.
68 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Manual
The manual calibration mode is used to set the minimum position and fail
direction and to calibrate the valve to user soft stops (inside of any physical
stops). The first screen to appear when entering the manual mode is used to set
the minimum position and fail direction. This setting must be correct before
manually calibrating the valve.
Woodward 69
L-Series Position Controller w/ CAN Capability Manual 26635
The next screen is used to set the minimum and maximum positions for the user
soft stops. To find the minimum and maximum soft stops use the verify position
mode described above to position the valve and use the Full Travel Actual
Position reading for minimum and maximum position values.
After leaving this mode, power must be cycled for the new settings to
take effect.
70 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Automatic
The automatic calibration mode is used to set the minimum position and fail
direction and to calibrate the valve to user physical stops (mechanical hard
stops). Like the manual mode, the first screen to appear is used to set the
minimum position and fail direction. This setting must be correct before automatic
calibration is performed.
After setting minimum position and fail direction the screen below will appear.
The control is now moving first to the CCW stop and then to the CW stop to get
the physical minimum and maximum positions.
After leaving this mode, power must be cycled for the new settings to
take effect.
Woodward 71
L-Series Position Controller w/ CAN Capability Manual 26635
Chapter 5.
Troubleshooting
Introduction
This chapter presents several broad categories of application failures typically
experienced in the field, possible causes, and some tests used to verify the
causes. Because the exact failure experienced in the field is the product of the
mechanical/electrical failure combined with the configuration file resident in the
control, it is left as the OEM’s responsibility to create a more detailed
troubleshooting chart for the end user. Ideally, this end-user troubleshooting
chart will contain information about mechanical, electrical, engine, and load
failures in addition to the possible governor failures. For more detailed
information about governor system failure modes and effects, contact Woodward
for a copy of the system DFMEA.
The troubleshooting scenarios listed below assume that the end user has a
digital multi-meter at his disposal for testing voltages and checking continuity,
and assume that the application has been engineered and tested thoroughly.
72 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Engine/Generator Troubleshooting
Problem Possible Cause Suggested Test/Correction
Move throttle by hand. Assess
Stuck throttle/frozen shaft smoothness, friction, and return
spring force.
Disconnect starter motor solenoid.
Disconnect harness from governor.
Power not applied to control Activate application. Test for +12/24
V between +12/24 V pin and ground
pin.
Verify status of input. Measure input.
Run Enable not closed Verify input and configuration using
Service Tool.
No configuration or Using Service Tool, read
incorrect configuration in configuration from controller and
Engine does not controller. evaluate parameters for correction.
start Using Service Tool, read faults from
Fault detected in controller. controller. Verify/correct any
shutdown conditions.
Do a power cycle and reflash
L-Series again. L-Series will use
communication settings from last
reflashing event. If L-Series will fail
to read non-volatile memory
Unsuccessful reflashing* correctly it will use default
communication settings:
CAN baud rate 250k, Device
Address 0x15, ECU_Part_Number
4385563 and Device_Name
‘flcntvlv’.
Using Service Tool, tune the position
Improperly tuned dynamics.
dynamics.
Intermittent position Using Service Tool, verify fault
Engine unstable command input signal. indications.
Device sending position
Measure input signal. Verify signal
command is sending
using Service Tool.
oscillating signal.
Using Service Tool, tune the position
Improperly tuned dynamics.
Poor frequency dynamics.
control Friction/dither improperly Using Service Tool, adjust the
set. Friction/Dither setting.
Non-indexed linkage Manually verify full travel of throttle
slipped on shaft. plate.
Unable to develop
Using Service Tool, view status of
full power
Fault detected in controller. fault codes. Take appropriate action
for active faults.
Woodward 73
L-Series Position Controller w/ CAN Capability Manual 26635
74 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward 75
L-Series Position Controller w/ CAN Capability Manual 26635
76 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
PWM Input
If the PWM input is not functioning properly, verify the following:
Measure the input voltage, frequency, and duty cycle.
Check the values seen by the L-Series driver using the Service Tool and
verify that is matches the input signal.
Check the wiring. Look for loose connections and disconnected /
misconnected cables/connections.
Check the software configuration to ensure that the input is configured
properly as the demand source.
CAN Input
If the CAN connection is not functioning properly, verify the following:
Check the values seen by the L-Series driver, if any, using the Service Tool
and verify that is matches the sent signal and/or received signal.
Check the wiring. Look for loose connections and disconnected /
misconnected cables/connections. Verify 120 Ohm resistor at ends of
transmission lines.
Check the software configuration to ensure that the signal is configured
properly (Device ID, fail timeout, protocol, etc).
Discrete Output
If the discrete output is not functioning properly, verify the following:
Measure the output voltage on the terminal block. It should be in the range
of 10–28 Vdc when the output is off/false. The voltage will be in this range
only if all shutdowns are false. This can be verified through the Service Tool.
Check the wiring, looking for loose connections or disconnected /
misconnected cables.
Verify the configuration of the output.
Service Tool
If the service tool is not functioning properly, review the installation information in
Chapter 4. Verify the following:
Check the wiring, looking for loose connections or disconnected /
misconnected cables.
Check that Service Tool is running. Verify the Port setting is correct.
Follow on-screen error messages. Re-install software as needed. The latest
version of software is available for download from the Woodward web site
(www.woodward.com).
Service Tool will not communicate if reflashing has been unsuccessful (this
is available only in firmware version 5418-7022). See ‘Unsuccessful reflash’
section for more details.
Unsuccessful Reflash
The ability to reflash is only provided in firmware version 5418-7022 using J1939
PGN 55808. On an unsuccessful reflash the device will not function and will
remain in boot mode. The output shaft will be limp (no drive current). To recover
do a power cycle and repeat reflashing sequence. Communication settings (CAN
baud rate, Device Address, Identification) will remain inherited from previously
installed firmware. Nevertheless in rare occasion when L-Series was unable to
read EEPROM, communication settings and identity may be defaulted:
CAN baud rate set to 250kbps,
Device Address set to 0x15.
Serial Number set to 12345678
When device is in a boot mode, following NAME is used in J1939 Address Claim:
78 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Chapter 6.
Product Support and Service Options
OEM or Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the best
source for product service and support. Warranty service for Woodward products
shipped with an equipment system should also be handled through the OEM or
Packager. Please review your equipment system documentation for details.
Woodward 79
L-Series Position Controller w/ CAN Capability Manual 26635
Replacement/Exchange: Replacement/Exchange is a premium program
designed for the user who is in need of immediate service. It allows you to
request and receive a like-new replacement unit in minimum time (usually within
24 hours of the request), providing a suitable unit is available at the time of the
request, thereby minimizing costly downtime.
This option allows you to call your Full-Service Distributor in the event of an
unexpected outage, or in advance of a scheduled outage, to request a
replacement control unit. If the unit is available at the time of the call, it can
usually be shipped out within 24 hours. You replace your field control unit with
the like-new replacement and return the field unit to the Full-Service Distributor.
Flat Rate Repair: Flat Rate Repair is available for many of the standard
mechanical products and some of the electronic products in the field. This
program offers you repair service for your products with the advantage of
knowing in advance what the cost will be.
Flat Rate Remanufacture: Flat Rate Remanufacture is very similar to the Flat
Rate Repair option, with the exception that the unit will be returned to you in “like-
new” condition. This option is applicable to mechanical products only.
When shipping the item(s), attach a tag with the following information:
return number;
name and location where the control is installed;
name and phone number of contact person;
complete Woodward part number(s) and serial number(s);
description of the problem;
instructions describing the desired type of repair.
Packing a Control
Use the following materials when returning a complete control:
protective caps on any connectors;
antistatic protective bags on all electronic modules;
packing materials that will not damage the surface of the unit;
at least 100 mm (4 inches) of tightly packed, industry-approved packing
material;
a packing carton with double walls;
a strong tape around the outside of the carton for increased strength.
Replacement Parts
When ordering replacement parts for controls, include the following information:
the part number(s) (XXXX-XXXX) that is on the enclosure nameplate;
the unit serial number, which is also on the nameplate.
80 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Engineering Services
Woodward’s Full-Service Distributors offer various Engineering Services for our
products. For these services, you can contact the Distributor by telephone or by
email.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodward’s worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact.
You can also contact the Woodward Customer Service Department at one of the
following Woodward facilities to obtain the address and phone number of the
nearest facility at which you can obtain information and service.
For the most current product support and contact information, please visit our
website directory at www.woodward.com/directory.
Woodward 81
L-Series Position Controller w/ CAN Capability Manual 26635
Technical Assistance
If you need to contact technical assistance, you will need to provide the following information.
Please write it down here before contacting the Engine OEM, the Packager, a Woodward
Business Partner, or the Woodward factory:
General
Your Name
Site Location
Phone Number
Fax Number
Number of Cylinders
Type of Fuel (gas, gaseous, diesel,
dual-fuel, etc.)
Power Output Rating
Application (power generation, marine,
etc.)
Control/Governor Information
Control/Governor #1
Serial Number
Control/Governor #2
Serial Number
Control/Governor #3
Serial Number
Symptoms
Description
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
82 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Appendix A.
L-Series Configuration Summary
APPLICATION ________________________________________________
Setup
Single or Redundant/Backup Selection Single ____ Redundant ____
Primary Position Demand Selection PWM ____ Analog ____ CAN ____
Backup Position Demand Selection PWM ____ Analog ____ CAN ____
Maximum Demand Difference (%) = ______________
PWM Input
PWM Drive Select Push-Pull ____ High Side ____ Low Side ____
PWM Offset (%) = ______________
CAN
CAN Fail Timeout (sec) = ______________
Protocol J1939 ____ CANopen ____
CAN ID LOW Discrete Input Not Used ____ Aux 2 ____
CAN ID HIGH Discrete Input Not Used ____ Aux 1 ____ Aux 5 ____
Device Identifier = ______________
Device Identifier 2 = ______________
Device Identifier 3 = ______________
Device Identifier 4 = ______________
Data Rate 250 K ____ 500 K ____
Heartbeat Producer Time (sec) = ______________
Enable Position Tamper Fault? Yes ____ No ____
Woodward 83
L-Series Position Controller w/ CAN Capability Manual 26635
Discrete Out
Discrete Out Normally On? Yes ____ No ____
Indicates Watchdog Reset? Yes ____ No ____
Indicates Brownout Reset? Yes ____ No ____
Indicates EE Prom Failure? Yes ____ No ____
Indicates Position Sensor Failure? Yes ____ No ____
Indicates Temperature Sensor Failure? Yes ____ No ____
Indicates Supply Voltage Fault? Yes ____ No ____
Indicates Relay Fault? Yes ____ No ____
Indicates Position Demand Failure? Yes ____ No ____
Indicates Overtemperature? Yes ____ No ____
Indicates Position Error? Yes ____ No ____
Indicates Run Enable Shutdown? Yes ____ No ____
Indicates Analog Demand Failed? Yes ____ No ____
Indicates PWM Demand Failed? Yes ____ No ____
Indicates CAN Demand Failed? Yes ____ No ____
Indicates Position Tamper Fault? Yes ____ No ____
Indicates CAN Stop Command? Yes ____ No ____
Faults (Shutdown/Alarms)
Temp Sensor Failure Action Shutdown ____ Alarm ____
Supply Voltage Fault Action Shutdown ____ Alarm ____
Relay Fault Action Shutdown ____ Alarm ____
Position Demand Failure Action Shutdown ____ Alarm ____
Overtemperature Action Shutdown ____ Alarm ____
Position Error Action Shutdown ____ Alarm ____
Position Tamper Fault Shutdown ____ Alarm ____
Security
Apply security to Configuration Reading? Yes ____ No ____
Apply security to Configuration Loading? Yes ____ No ____
Apply security to Position PID Edit? Yes ____ No ____
Apply security to Position Calibration? Yes ____ No ____
Password = ______________
84 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Appendix B.
L-Series Control Specifications
Specifications
Power Supply 12/24 V systems (10–32 Vdc) reverse polarity
protection, 2.5 A max
Power Consumption 32 W maximum
Torque Nominal: 0.34 N·m (0.25 lb-ft) at 25 °C
Maximum Transient (at 105 °C): 0.20 N·m (0.15 lb-ft)
Minimum Continuous (at 105 °C): 0.14 N·m (0.10 lb-ft)
Mass/Weight 425 g (15 oz)
Power-Up to Operation Time <250 ms (< 1 s CAN versions)
Performance
Positioning Accuracy ±2% at 25 °C
±4% (analog), ±3.6% (PWM), ±3% (CAN)–over temp
range
Slew Time 10%–90% 33 ms
Overshoot 1%
Settling Time 10 ms
–6 db Roll-off at ±0.5% Input 32 Hz
–3 db Roll-off at ±2% Input 8 Hz
Environment
Ambient Operating Temperature –40 to +105 °C (–40 to +221 °F)
Storage Temperature –40 to +125 °C (–40 to +257 °F)
EMI/RFI EN61000-6-2 : Immunity for Industrial Environments
EN61000-6-4 : Emissions for Industrial Environments
SAE J1113-21: Radiated Immunity (100 V/m)
SAE J1113-11: Conducted Transient Immunity –
Pulse 5b
Suppressed Load Dump (45 V)
Humidity US MIL-STD 810E, Method 507.3, Procedure III
Salt Spray US MIL-STD 810E, Method 509.3, Procedure I
Shock MS1-40G 11 ms sawtooth
Random Vibration Random: 0.3 G²/Hz, 10–2000 Hz (22.1 Grms) 3 h/axis
Sine: 5 G 2.5 mm peak-to-peak, 5–2000 Hz, 3 h/axis,
90 min dwells, 1 octave/min
Drop SAE J1211, Paragraph 4.8.3 (modified)
Thermal Shock SAE J1455, Paragraph 4.1.3.2
Ingress Protection IP56 per EN60529
Woodward 85
L-Series Position Controller w/ CAN Capability Manual 26635
PWM Command Input
Parameter Value
Input Magnitude 5–32 V p-p
Frequency Range 300–1500 Hz
Duty Cycle Scaling 10% = fully closed and 90% = fully open
Isolation None
Input Impedance Push-Pull Mode 44 kΩ–113 k
Input Impedance Open Collector Mode,
15 k
High Side or Low Side.
Resolution 16 bits at 300 Hz, 14 bits at 1.5 kHz
±1% of full scale (duty cycle), over the
Accuracy temperature range of –40 to +125 °C,
including drift
I/O Latency 8.2 ms
Duty cycle offset adjustment is available
Calibration in Service Tool. This will tailor the input to
the signal source
Out of Range Frequency None
Out of Range Duty Cycle < 3% or > 97%
Discrete Input
Parameter Value
Input Current 0.5 mA @ 5 Vdc
Input Type Ground referenced discrete input
Delay Time for Shutdown < 200 ms for system to recognize shutdown
Delay Time for Reset
< 1 s for valves to move to minimum position
Detection
Max Voltage from +
32 V (power input voltage)
Connection
None, Intended for use with external relay or other dry
Isolation
contact
Input Thresholds > 3.1 Vdc = “ON” < 0.8 Vdc = “OFF”
Input Current 0.5 mA @ 5 Vdc
Discrete Output
Parameter Value
Output Type Low-side output driver
Max Contact Voltage (Open) 32 V
Max Current 0.5 A
Max Contact Voltage at 0.5 A
1.5 V
(Closed)
Max Delay Time for Opening
8.2 ms
Contact
Default at Power Up Configurable in software
Error Condition Configurable in software
OK Condition Configurable in software
Driving Inductive Loads Yes, internally protected low-side switch
Utilizes circuitry that will open the contact when
Protection output contacts are short-circuited. Self-resetting
when fault is removed
86 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
TPS Output
Parameter Value
Output Type 0–5 V, single-ended
0.75 V = full CCW position and 4.25 V = full CW
Output Scaling
position
Isolation None
3 db Circuit Bandwidth 350 Hz
Transient Protection According to EMC norm
Output Impedance 2.8 k (±1%)
Accuracy ±10% of full scale, @ 25 °C
Temperature Drift ±0.4% over the full temperature range
I/O Latency n/a – direct from position sensor
Calibration Method Sensor-in-place factory calibration. 2-point linear
Out of Range Signal < 0.25 V or > 4.75 V
Output protected against 32 Vdc, steady-state; if
Overvoltage Protection >28 V is applied to pin 2, a position-related error will
be annunciated
If an isolator is used:
Line Limitations
Trunk Length: 250 m (820 ft)
Maximum Drop: 6 m (20 ft)
Cumulative Drop: 78 m (256 ft)
Fault Detection Service Tool setting
Woodward 87
L-Series Position Controller w/ CAN Capability Manual 26635
Software Execution Rates
Software Routine Nominal Software Execution Rate
Position Control Algorithms 1.6 ms
Position Demand Algorithms 8.2 ms
Analog Input Logic 8.2 ms
PWM Input Logic 8.2 ms
Serial Port background task
CAN communications 8.2 ms
Run Enable Discrete Input 8.2 ms
Discrete Output 8.2 ms
Diagnostics 8.2 ms
88 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Revision History
Changes in Revision C—
Added information for new part number 5418-7022
Updated Declarations
Changes in Revision B—
Improvements to clarity and wording
Changes in Revision A—
Added information for new part number 5418-6638
Woodward 89
L-Series Position Controller w/ CAN Capability Manual 26635
Declarations
90 Woodward
Manual 26635 L-Series Position Controller w/ CAN Capability
Woodward 91
We appreciate your comments about the content of our publications.
Send comments to: icinfo@woodward.com