Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

SMO Control

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

SINEAX P530 / Q531

Transducer for Active or Reactive Power

Carrying housing P13/70 resp. P18/105

Application
The transducer SINEAX P530/Q531 (Fig. 1) converts to active or
reactive power of a single-phase AC or three-phase system with
balanced or unbalanced loads.
The output signal is proportional to the measured value of the
active or reactive power and is either a load-independent DC
current or a load-independent DC voltage.
The transducer fulfils all the important requirements and regulati-
ons concerning electromagnetic compatibility EMC and Safety
(IEC 1010 resp. EN 61 010). It was developed and is manufac-
tured and tested in strict accordance with the quality assurance
Fig. 1. Transducer SINEAX P530 in housing P18/105
standard ISO 9001.
clipped onto a top-hat rail.

Features / Benefits Nominal input current IN: 1 to 6 A


● Measuring inputs: Sine wave forms of nominal input currents and Calibration factor c: 0.75 to 1.3 with active power
nominal input voltages 0.5 to 1.0 with reactive power
Measured Nominal Nominal Admissible measuring range
variables input current input voltage and values (calibration
factor c): Acc. to table 2, feature 6
Active or
1 to 6 A 100 to 690 V
reactive power Own consumption: ≤ I2 · 0.01 Ω per current path
U2 / 400 kΩ per voltage path
● Measuring output: Unipolar, bipolar or live zero output variables
Overload capacity:
● Measuring principle / TDM system
Interval
● DC-, AC-power pack with wide power supply tolerance / Universal Measured Duration of
Number of between two
quantities one
● Standard as marine version per Lloyd’s Register of Shipping applications successive
IN, UN application
applications
1.2 x IN ––– continuous –––
20 x IN 10 1s 100 s
Technical data 1.2 x U 1
––– continuous –––
N

General 2 xU N
1
10 1s 10 s
Measured quantity: Active or reactive power, unipolar or 1
But max. 264 V with power supply from voltage measuring
bipolar (in 4 quadrants) input
Measuring principle: Pulse duration modulation (Time-
Division-Multiplikation, TDM) Measuring output
Load independent
Measuring input
DC current: 0 … 1.0 to 0 … 20 mA
Nominal frequency fN: 50 or 60 Hz, sine resp. live-zero 0.2 … 1 to
Nominal input voltage UN: 100 … 690 V 4… 20 mA
(85 … 230 V with power supply from ± 1.0 to ± 20 mA
voltage measuring input) Burden voltage: ± 15 V

Camille Bauer Data Sheet P530/Q531 Le – 03.09 1


SINEAX P530 / Q531
Transducer for Active or Reactive Power
Load independent Power supply
DC voltage: 0 … 1 to 0 … 10 V resp.
live-zero 0.2 … 1 to 2 … 10 V DC-, AC-power pack (DC or 40 … 400 Hz)
± 1 V to ± 10 V Table 1: Rated voltages and permissible variations
Load capacity: 4 mA
Rated voltage Tolerance
Voltage limit under 85 … 230 V DC, AC DC – 15 … + 33%
Rext = ∞: ≤ 40 V AC ± 15%
24 … 60 V DC, AC
Current limit under
overload: Approx. 1.3 x IAN at current output Power consumption: Approx. 2.5 W resp. 4.5 VA
Approx. 30 mA at voltage output
Options
Residual ripple in
output current: < 1% p.p. Power supply from
voltage measuring input: ≥ 85 to 230 V AC
Response time: < 300 ms (Nominal input voltage range =
internal power supply range)
Accuracy (acc. to EN 60 688)
Connected to the
Reference value: Output end value low tension: 24 V AC or 24 … 60 V DC
Basic accuracy: Class 0.5
Reference conditions: Installation data
Ambient temperature 15 … 30 °C Mechanical design: Housing P13/70 resp. P18/105

Input current IN · c Material of housing: Lexan 940 (polycarbonate)


flammability Class V-0 acc. to UL
Input voltage UN 94, self-extinguishing, non-dripping,
Power factor cosϕ = 0.8 … 1.0 … 0.8 free of halogen
with active power Mounting: For rail mounting
cosϕ = 0.8 … 1.0 … 0.8
Mounting position: Any
with reactive power
Weight: Housing P13/70 approx. 0.3 kg
Frequency 50 or 60 Hz
Housing P18/105 approx. 0.7 kg
Wave form Sine, distortion factor < 1%
Power supply At nominal range Connecting terminals
Output burden Current: 0.5 · Rext max. Connection element: Screw-type terminals with indirect
Voltage: 2 · Rext min. wire pressure

Safety Permissible cross section


of the connection leads: ≤ 4.0 mm2 single wire or
Protection class: II (protection isolated, EN 61 010) 2 x 2.5 mm2 fine wire
Protection: IP 40, housing
(test wire, EN 60 529) Environmental conditions
IP 20, terminals
(test finger, EN 60 529) Operating temperature: – 10 to + 55 °C

Pollution degree: 2 Storage temperature: – 40 to + 70 °C


Installation category: III Relative humidity of
annual mean: ≤ 75%
Rated insulation voltage
(against earth): 400 V, inputs Altitude: 2000 m max.
230 V, power supply
40 V, output Indoor use statement!

Test voltage: 50 Hz, 1 min. acc. to EN 61 010-1


Ambient tests
5550 V, inputs versus all other circuits
as well as outer surface EN 60 068-2-6: Vibration
3250 V, input circuits versus each Acceleration: ±2g
other
3700 V, power supply versus output Frequency range: 10 … 150 … 10 Hz, rate of frequency
as well as outer surface sweep: 1 octave/minute
490 V, output versus outer surface Number of cycles: 10, in each of the three axes

2 Data Sheet P530/Q531 Le – 03.09 Camille Bauer


SINEAX P530 / Q531
Transducer for Active or Reactive Power

EN 60 068-2-27: Shock Germanischer Lloyd


Acceleration: 3 x 50 g Type approval certificate: No. 12 260-98 HH
3 shocks each in 6 directions
Ambient category: C
EN 60 068-2-1/-2/-3: Cold, dry heat, damp heat
Vibration: 0.7 g
IEC 1000-4-2/-3/-4/-5/-6
EN 55 011: Electromagnetic compatibility

Table 2: Specification and ordering information


*Blocking No-go with Article No./
Description
code blocking code Feature
Order Code xxx - xxxx xxxx xx
Features, Selection
SINEAX P530, Transducer for active power 530 –
SINEAX Q531, Transducer for reactive power 531 –
1. Mechanical design
Housing type P for rail mounting 4
2. Measuring mode / Application
3-wire 3-phase balanced load, housing P18/105 1
Type 530 (active power) available also for 4-wire 3-phase balanced load
3-wire 3-phase unbalanced load, housing P18/105 2
4-wire 3-phase unbalanced load, housing P18/105 3
Single-phase AC, housing P13/70 E 4
3. Nominal input frequency
50 Hz 1
60 Hz 2
4. Nominal input voltage (measuring input)
100 … 115 V [V] 1
200 … 230 V [V] 2
380 … 440 V
A 3
Single-phase AC max. 400 V [V]
600 … 690 V
A E 4
Not possible with single-phase AC [V]
Non-standard UN
Non-standard [V]: ≥ 115.00 to < 600 with 3-phase system,
9
≥ 57.73 to ≤ 400 with single-phase AC;
With power supply from measuring input max. 230 V [V]
Lines 1 to 9:
Without PT: Specify effective nominal voltage
With PT: Specify primary/secondary voltage in V,
e.g. 16000/100
Input voltage UN:
– line-to-line voltage with 3-phase system
– line-to-neutral voltage with single-phase AC
5. Nominal input current (measuring input)
1A [A] 1
5A [A] 2
Non-standard IN [A] > 1 to ≤ 6 A [A] 9
With CT: Specify primary/secondary current in A

Camille Bauer Data Sheet P530/Q531 Le – 03.09 3


SINEAX P530 / Q531
Transducer for Active or Reactive Power

*Blocking No-go with Article No./


Description
code blocking code Feature
Order Code xxx - xxxx xxxx xx
Features, Selection
SINEAX P530, Transducer for active power 530 –
SINEAX Q531, Transducer for reactive power 531 –
6. Measuring range W or Var
Measuring range bipolar [W] or [Var] 1
Measuring range unipolar [W] or [Var] B 2
Specify measuring range in W or Var,
e.g. 500 at measuring range bipolar – 500 … + 500
1000 at measuring range unipolar 0 … 1000
Admissible measuring range end values (calibration factor c)
With single-phase AC active power ≥ 0.75 ti 1.3 · UN · IN
With single-phase AC reactive power ≥ 0.5 to 1.0 · UN · IN
With 3-phase system active power ≥ 0.75 to 1.3 · 3 · UN · IN
With 3-phase system reactive power ≥ 0.5 to 1.0 · 3 · UN · IN
7. Output signal, start value
Output bipolar, start value – 100% final value B 1
Not possible with unipolar measuring range
Output unipolar, start value 0 2
Output live-zero, start value 20% final value 3
8. Output signal, final value
Output final value 20 mA 1
Output final value 10 mA 2
Output final value 5 mA 3
Output final value 2.5 mA 4
Output final value 1 mA 5
Non-standard (> 1.00 to < 20) [mA] 9
Output final value 10 V A
Non-standard (1.00 to < 10) [V] Z
9. Power supply
85 … 230 V DC, AC 1
24 … 60 V DC, AC 2
From measuring input (≥ 85 to 230 V AC) A 4
Connected to the low tension side
5
24 V AC / 24 … 60 V DC
10. Additional lettering on type label
Without additional lettering on type label 0
With additional lettering on type label
9
1 line with max. 40 letters, e.g. measuring location
11. Test records
Without test records 0
Test records in German D
Test records in English E

*Lines with letter(s) under “no-go” cannot be combined with preceding lines having the same letter under “SCODE”.

4 Data Sheet P530/Q531 Le – 03.09 Camille Bauer


SINEAX P530 / Q531
Transducer for Active or Reactive Power

Electrical connections
Terminal allocation housing P13/70

– + – + – +

10 11 12 13
10 11 12 13 10 11 12 13

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9


IL1 IL1 Measuring input
UL1 N
Measuring output
Measuring input Power supply

Fig. 2. Power supply connected Fig. 3. Power supply internal from measuring Fig. 4. Power supply connected to the low
to terminals 8 and 9. input, without separated power supply. tension terminal side 12 and 13.

Terminal allocation housing P18/105

– + – + – +

15 16 17 18 15 16 17 18 15 16 17 18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 2 3 4 5 6 7 8 9 10 11 12 13 14


IL1 IL1 IL3 IL3
IL2 IL2
UL1 UL2 UL3 N

Measuring inputs,
acc. to measuring mode

Fig. 5. Power supply connected Fig. 6. Power supply internal from measuring Fig. 7. Power supply connected to the low
to terminals 13 and 14. input, without separated power supply. tension terminal side 17 and 18.

Camille Bauer Data Sheet P530/Q531 Le – 03.09 5


SINEAX P530 / Q531
Transducer for Active or Reactive Power

Measuring inputs
Meas. mode/
Terminal allocation
Application

2 5 1 3 2 5 1 3 2 5 1 3
Active or
reactive power
u v
measurement in
single-phase k l k l
U V
AC network L1 L1 L1
K L K L
N N N

2 5 8 1 3 2 5 8 1 3 2 5 8 1 3
Active or
reactive power
u v u v
measurement in
3-wire 3-phase k l k l
U V U V
network L1 L1 L1
K L K L
balanced load L2 L2 L2
L3 L3 L3

2 5 8 1 3 7 9 2 5 8 1 3 7 9 2 5 8 1 3 7 9
Active or
reactive power u v u v
measurement in
k l k l
3-wire 3-phase U V U V
network L1 L1 L1
K L k l K L k l
unbalanced load L2 L2 L2
L3 L3 L3
K L K L

2 5 8 1 3 2 5 8 1 3 2 5 8 1 3

Active power
u v u v
measurement in
k l k l
4-wire 3-phase U V U V
network L1 L1 L1
K L K L
balanced load L2 L2 L2
L3 L3 L3
N N N

6 Data Sheet P530/Q531 Le – 03.09 Camille Bauer


SINEAX P530 / Q531
Transducer for Active or Reactive Power

Measuring inputs
Meas. mode/
Terminal allocation
Application

2 5 8 11 1 3 4 6 7 9 2 5 8 11 1 3 4 6 7 9

k l
k l
L1 L1
K L k l
L2 L2
K L
Active or L3 L3
K L
reactive power N N
measurement in
4-wire 3-phase
2 5 8 11 1 3 4 6 7 9
network
u u u
unbalanced load
x x x
X
X X
k l
U U U k l
L1
K L k l
L2
K L
L3 3 single-pole insulated voltage transformer in the
K L
N high-voltage system

Dimensional drawings Standard accessories


112.5 1 Operating Instructions in three languages: German, French and
English
10 11 12 13
69.1

1 2 3 4 5 6 7 8 9

114.1 70

Fig. 8.SINEAX P530/Q531 in housing P13/70 clipped onto a top-hat rail


(35 x 15 mm or 35 x 7.5 mm, acc. to EN 50 022).

112.5

15 16 17 18
69.1

1 2 3 4 5 6 7 8 9 10 11 12 13 14

Rely on us.
114.1 105

Fig. 9.SINEAX P530/Q531 in housing P18/105 clipped onto a top-hat


rail (35 x 15 mm or 35 x 7.5 mm, acc. to EN 50 022).
Camille Bauer Ltd
Aargauerstrasse 7
CH-5610 Wohlen / Switzerland
Phone: +41 56 618 21 11
Fax: +41 56 618 35 35
e-Mail: info@camillebauer.com
www.camillebauer.com

Subject to change without notice • Edition 03.09 • Data Sheet P530/Q531 Le

You might also like