Cms Architecture
Cms Architecture
Cms Architecture
POWER PROJECT
Owner:
NTPC LIMITED
(A GOVERNMENT OF INDIA ENTERPRISE)
EPC Contractor:
Architect Engineer:
Vendor:
GE T&D India Limited
(formerly ALSTOM T&D India Limited)
Stamp:
Rev
Details / Description Date
No.
00 Original issue 08/08/2017
3 Page 6 100% redundant Hot standby As discussed during meeting, comment closed.
4 Page 6 armored cable Noted, Incorporated
5 Page 7 Ethernet switch Noted, Incorporated
Noted, Incorporated. mentioned comment will be Incorporated in Panel Schemes at the earliest
9 Page 36 all supplies including 240/110V AC, 24V DC as applicable shall be redundant. Kindly confirm
after approval of this Architecture.
In Technical Catalogue, its the methods of Current masurement techniques. Change the Heading
10 Page 40 Kindly ensure in actual scheme as commented on architecture drawing.
in revise document in Part - 3. As discussed during meeting, this comment closed.
11 Page 47 Check & correct Noted, Incorporated in Part - 3.
1 2 3 4 5 6 7 8
A A
or used to furnish information to others, without the prior written permission of GE Grid.
B
Architecture – Drawing & B
MS 3000 – Philosophy
C C
Content:
MS 3000 – Cover sheet Page 1
MS 3000 – Communication Overview Page 2
D MS 3000 – Detailed Communication Overview Page 3 D
MS 3000 – Included Signals Page 4
MS 3000 – Included Functionality Page 5
MS 3000 – Cooling Control Logic Page 6-12
MS 3000 – Philosophy Page 13-14
E E
F F
RJ45
B CMS Processor CMS Processor B
LEGEND:
Panel Panel
IEC 61850 Protocol***
GT – Bank 1 GT – Bank 2
MODBUS/TCP**
Including redundant processors Including redundant processors PROFIBUS/ Fiber Optic (Armored)**
Analog and Digital interface signals**
CONTROL ROOM
C C
SUBSTATION GT – SPARE
GT - R GT - Y GT - B
D D
CMB 2 CMB 1
(GT-Bank 1) (GT-Bank 1)
GT - R GT - Y GT - B
E NOTES:
E
DGA 500 DGA 500 DGA 500
* MS 3000 Master: 19-inch rack mount for installation
GE En erg y GE En erg y GE En erg y
in available cubicle in control room. Supply or
TR AN SFI X TR AN SFI X TR AN SFI X engineering of cubicle is not included in GE M&D Scope
! ! !
CMB-2
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
MS 3000 MS 3000
(100% processor main) (100% processor hot stand-by)
or used to furnish information to others, without the prior written permission of GE Grid.
Converter
GE E nergy
DGA
DI DI DI AI AI DO DO T RANSFIX
E/S*
Data concentrator
IEC 61850**
Converter
C DGA
C
GE E nergy
DI DI DI AI AI DO DO T RANSFIX
E/S*
IEC 61850**
Processor task GT-Y Processor task GT-Y Redundant FO BK !
IEC 61850**
Converter
GE E nergy
DGA
DI DI DI AI AI DO DO T RANSFIX
BK !
E Redundant DC E
Supply, Changeover
in CMS Processor
Panel
Redundant DC
Supply, Changeover
in CMB – 2
Notes: (CMS I/O Panel)
This is a functional architecture for illustration purpose. The detailed design may vary slightly, respectily consider further components or connections as per NTPC specification.
DC supply with Changeover scheme and MCB will be part of CMB-2 Panel and CMS Processor Panel schemes drawings.
F *The CMS Processor panel will have 3 Ethernet Switches (E/S*). The Detail connection with switch will be available in CMS Processor Panel schemes drawings. F
** Only one protocol IEC 61850 will be available for communication with SCADA/ DCS/ Data Concentrator. GE will provide the ICD Files to respective SCADA/ DCS/ Data
Concentrator OEM.
09 - 27.07.18 Schneider Date 04.05.2017
08 - 18.05.18 Schneider Drawn by Schneider MS 3000 for Khargone 09 3 of 14
07 - 16.05.18 Schneider Checked - S9723277
Revision Modification Date Name
PTR/L&T/NTPC Revision Page
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
FO-ST (multimode).
Alarm Signals (Digital): Analog Signals (4-20mA): Other signals:
1) SUPPLY-A FAIL 1) FOR TRANSFORMER OIL TEMPERATURE 1) UNIT COOLER -1 ON
2) SUPPLY –B FAIL 2) WINDING TEMPERATURE – HV 2) UNIT COOLER -2 ON
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
F F
Overload capacity
or used to furnish information to others, without the prior written permission of GE Grid.
F F
or used to furnish information to others, without the prior written permission of GE Grid.
B B
C C
D D
E E
Note:
0" means Low and 1" means High.
In case of CMS FAIL (BO 25=0), all running coolers will maintain their status quo (continue running) and also stand-by cooler will start
In case of Coolers are not running or to be started in CMS fail condition then following steps shall be followed:
1) initially put all coolers individual selector switch in Off position
2) Then start (put selector switch in Service position) each cooler one by one with manual time delay of 10 seconds between each other.
F ->For "EHV CB closed"/"Generator FB closed"/"Generator voltage greater than or equal to 20% of rated voltage" to give command for cooler "ON" (conditional). F
-> For "EHV CB opened" & "Generator FB opened" & "Generator voltage less than 20% of rated voltage" to give command for cooler "OFF" (conditional).
or used to furnish information to others, without the prior written permission of GE Grid.
B B
C C
D D
E E
F F
or used to furnish information to others, without the prior written permission of GE Grid.
B B
C C
D D
E E
Note:
** The cooling unitis controlled by the MS 3000 Monitoring System according to NTPC philosophy. The
user can define a time in the MS 3000 visualization to which the stand-by cooling unit shall be started.
Counting from that programmable time the stand-by cooling unit will run for a programmable time.
The starting time can be changed at any time in the MS 3000 visualization.
F F
E
C
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
07
08
09
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
Revision
or used to furnish information to others, without the prior written permission of GE Grid.
1
1
-
-
-
Modification
Date
16.05.18
18.05.18
27.07.18
Name
Schneider
Schneider
Schneider
2
2
Date
Checked
Drawn by
-
Schneider
04.05.2017
3
3
PTR/L&T/NTPC
MS 3000 for Khargone
4
4
5
5
6
6
S9723277
7
7
09
Revision
8
8
Page
9 of 14
F
A
E
C
F
A
E
C
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
07
08
09
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
Revision
or used to furnish information to others, without the prior written permission of GE Grid.
1
1
-
-
-
Modification
Date
16.05.18
18.05.18
27.07.18
Name
Schneider
Schneider
Schneider
2
2
Date
Checked
Drawn by
-
Schneider
04.05.2017
LOGIC FOR TRANSFORMER TROUBLE:
3
3
PTR/L&T/NTPC
MS 3000 for Khargone
4
4
5
5
6
6
S9723277
7
7
09
Revision
8
8
Page
10 of 14
F
A
E
C
1 2 3 4 5 6 7 8
or used to furnish information to others, without the prior written permission of GE Grid.
B B
C C
D D
E E
F F
or used to furnish information to others, without the prior written permission of GE Grid.
B B
C C
D D
E E
Note:
CMS cooler input I/O fail signal would be generated in DCS / OWS and communicated.
F F
MS 3000 – Philosophy:
A I) Architecture Philosophy A
1) DATA Transfer from MS 3000 I/O Card to Processors :
Communication is via two redundant FO cables (ring architecture) laid through different route for each 1-ph GT.
2) Fiber Optic Main/Stand-By Cable:
If one of the FO cables is cut, the MS 3000 system will keep working as long as all modules are still connected to the processors by either way through the partial FO
ring.
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
If any I/O cards fails or de-energized, the fail-safe logic would be operational and all unit coolers including stand-by would start. If it is already running, it will keep on
B B
running.
If a single FO cable of an I/O device is cut/damage, same inputs will also be available with bump less transfer through stand-by FO cable to processors.
If both fiber optic cables are disconnected, the fail-safe logic would be operational and all unit coolers including standby would start. If it is already running, it will keep
on running.
4) I/O device fail communication:
If any I/O device fails, the fail-safe logic would be operational and all unit coolers including standby would start. If it is already running, it will keep on running. The
information shall be communicated to SCADA. I/O device shall be checked every 2 mins.
C C
5) Failure Communication:
Communication failure between I/O device and processors will be treated as fail-safe condition and all the unit coolers including stand-by will start functioning.
6) Failure of Main Processor / Power Supply of Processor inside Panel:
The Watchdog of the Main MS 3000 Processors will automatically activate the switch of the hot stand-by processors to access the stand-by system and starts functions
with bump less transfer. The access browser on DDCIMS might need to be refreshed for updated data.
7) Failure of Stand-by MS 3000 Processor / Supply:
In case stand-by MS 3000 processors/supply fails and as the main MS 3000 is healthy, all the data would be available on main MS 3000 processors.
D D
8) Changeover Procedure:
During normal operation both (Main and Stand-by) processor having same data via redundant fiber optics but only one Processor (either main or stand-by) is connect
with customer network/ OWS to display the current data. If Main processor fail, Another processor(Hot stand-by) will be bump less transfer and manage the GT
operation immediately. But during that event, when main processor fail, it will give fail command to customer on OWS Screen via watchdog (Relay) to communicate its
failure status and disconnect from customer network without any disturbing GT operation. Here, watchdog failure command will be accepted by Hot Stand-by
processor, which will be connected to customer network and OWS in place of (in absence of) Main Processor.
9) Communication details between MS 3000 and SCADA/ DDCIMS:
E E
MS 3000 will be communicating to SCADA/DDCIMS via IEC-61850. IEC 61850 protocols can be connected via copper cables (RJ-45-connectors) or fiber-optic-cable (ST-
connectors) as per customer requirement.
MS 3000 visualization can be accessed from CMS OWS through a web browser via Ethernet TCP/IP (RJ-45-connectors or FO-ST-connectors).
10) Communication Main/Stand-By status:
Status as well as control would be made via main processor. When main processor fails, it would be made using stand-by processor.
11) CMS port detailes & their IP address status:
Communication port would be RJ-45 with a single IP address. Only the active processor will be accessable.
12) Communication hardware & software:
F Hardware: Ethernet switch with RJ-45 ports will be provided for communication with SCADA/ DDCIMS. F
Software: All MS 3000 data can be accessed through the MS 3000 visualization by entering user id and password on dedicated IP address in browser .
09 - 27.07.18 Schneider Date 04.05.2017
08 - 18.05.18 Schneider Drawn by Schneider MS 3000 for Khargone 09 13 of 14
07 - 16.05.18 Schneider Checked - S9723277
Revision Modification Date Name
PTR/L&T/NTPC Revision Page
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
MS 3000 – Philosophy:
A A
I) Architecture Philosophy
13) SCADA connection port at MS 3000 failure:
In case of failure of connection between CMS and switchgear SCADA, the data would remain with CMS.
14) Cooling Control Status during CMS Fail:
In CMS fail condition all the unit coolers would start running irrespective of any logics.
15) Open Cable connection between MS 3000 and SCADA/ MS 3000 Status Fail:
property of GE Grid and may not be reproduced, transmitted, stored, or copied in whole or in part,
© 2016 GE Grid propritary and confidential information. All rights reserved. This document is the
Open cable connection is treated as connection cutoff and the CMS fail safe function will be activated and all unit coolers including stand-by would start.
or used to furnish information to others, without the prior written permission of GE Grid.
Along with the concept of MS 3000, different measurement and analysing quantities can be combined for a tailor
made solution, depending on transformer design and/or required monitoring comprehension.
The architecture is based on field bus technology. The sensors are wired to a monitoring module installed at the
transformer (slave modules). The connection from the monitoring module(s) to the MS 3000 IED (Intelligent
Electronic Device) is carried out via the field bus. The MS 3000 IED has the capability to acquire on-line data,
perform processing and control. It is working self-sufficient and has the facility to store data. Communication can be
performed in various ways using network access, modem or protocols (optional).
STANDARD CHARACTERISTICS
Sampling Rate 20 ms for voltages and currents measurements.
10µs for phase shifting measurement.
1 to 5 minutes for all remaining measurements.
(except gas-in-oil measurement (depends on used sensor)).
Baud rate 1.5 Mbit/s.
Field bus specification Total maximum length for the fibre optic cable ring connecting the slave modules is up to
2000m.
SOFTWARE TOOLS
Password protection The password protection restricts data access in two levels: user and supervisor
(Further password levels on special request).
Online Online data is presented in user-friendly structured web pages (status overview,
warning/alarms*, active part, overload calculation, bushings, tap changer, cooling unit,
conservator, simulator, name plate)
Application examples
of Web-Visualisation
COMMUNICATION (optional)
Standard protocols IEC 60870-5-104 TCP/IP Master/Slave
(others on request) Modbus TCP/IP Master/Slave
IEC 61850 (reports) TCP/IP Client
Profibus Profibus (d-sub 9-pol) Master
MS 3000
Detailed Technical Catalogue
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 1 of 151
Contents
Topic Page
1 Introduction ................................................................................................5
1.1 Product Overview......................................................................................................... 5
1.2 Versatile Architecture Support .................................................................................... 6
1.3 Analysis, Diagnostics, Prognostics and Lifetime Data Management tool .................... 7
2 Safety ..........................................................................................................8
2.1 Symbols ........................................................................................................................ 8
2.2 Warnings ...................................................................................................................... 8
3 Requirements ..............................................................................................9
3.1 Pre-installation ............................................................................................................. 9
3.2 Handling & Storage ...................................................................................................... 9
4 Hardware .................................................................................................. 11
4.1 General information ................................................................................................... 12
4.1.1 Mechanical configuration............................................................................... 12
4.1.2 Electrical configuration and Parameters Monitoring..................................... 14
4.2 Type of Sensors used in MS 3000 .............................................................................. 15
4.3 Voltage and Current Measurement ........................................................................... 16
4.3.1 Voltages .......................................................................................................... 16
4.3.2 Load current ................................................................................................... 16
4.4 Temperatures ............................................................................................................. 19
4.4.1 Ambient temperature .................................................................................... 19
4.4.2 Oil temperature .............................................................................................. 20
4.5 Cooling unit ................................................................................................................ 21
4.5.1 Operating states of pumps and fans .............................................................. 21
4.5.2 Controller of the cooling unit ......................................................................... 22
4.6 Oil analysis.................................................................................................................. 23
4.6.1 Online DGA 500 .............................................................................................. 24
4.7 Bus modules ............................................................................................................... 26
5 Software ................................................................................................... 27
5.1 Software and database configuration........................................................................ 27
5.2 Process variables (PV) ................................................................................................ 27
5.3 Data acquisition/ Measurement Philosophy ............................................................. 27
5.3.1 Event-driven data acquisition ........................................................................ 27
5.3.1.1 Switch states of the fans and pumps ............................................... 27
5.3.1.2 Switching on the transformer .......................................................... 27
5.3.1.3 Switching off the transformer .......................................................... 27
5.3.1.4 Limit value overshoots and alarms .................................................. 27
5.3.2 Interval driven data acquisition ..................................................................... 28
5.4 Saving the measured data.......................................................................................... 28
5.5 Real-time Database .................................................................................................... 29
5.6 Historical Database .................................................................................................... 29
5.7 Functions and Analysis ............................................................................................... 30
5.7.1 Active part ...................................................................................................... 30
5.8 Cooling unit ................................................................................................................ 41
5.9 Overload calculation .................................................................................................. 42
6 Web Visualisation ..................................................................................... 45
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 2 of 151
6.1 System access via Web Visualization ......................................................................... 45
6.2 Overview .................................................................................................................... 46
6.3 Login ........................................................................................................................... 47
6.4 Presentation of data .................................................................................................. 48
6.4.1 Status overview .............................................................................................. 48
6.4.2 Alarms............................................................................................................. 59
Alarm configuration ......................................................................... 60
6.4.3 Transformer Online Data................................................................................ 63
6.4.3.1 Active part ........................................................................................ 63
6.4.3.2 Overload Calculation ........................................................................ 75
6.4.3.4 Cooling unit ...................................................................................... 77
6.4.3.5 Conservator ...................................................................................... 83
6.4.3.6 Simulator .......................................................................................... 85
6.4.3.7 Nameplate ........................................................................................ 91
6.4.4 Historical data ................................................................................................ 92
6.4.4.1 Graph 92
Historic Alarms ............................................................................... 104
6.4.4.3 Historical list ................................................................................... 108
6.4.4.4 Download ....................................................................................... 112
6.4.5 Tools ............................................................................................................. 115
6.4.6 System data .................................................................................................. 121
6.4.6.1 System data .................................................................................... 121
6.4.6.2 PV Table .......................................................................................... 126
6.4.6.3 Multimonitor .................................................................................. 129
6.4.6.4 User administration ....................................................................... 130
7 Troubleshooting ...................................................................................... 131
8 Maintenance schedule ............................................................................ 144
8.1 Changing the filter .................................................................................................... 145
8.2 Exchange the Battery ............................................................................................... 147
8.3 Visual inspection ...................................................................................................... 149
8.4 Gas-in-oil content – verification of the measurement ............................................ 150
8.5 Moisture in oil – verification of the measurement .................................................. 150
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 3 of 151
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 4 of 151
1 INTRODUCTION
1.1 Product Overview
What is MS 3000 ?
• A holistic transformer monitoring solution that combines the outputs from all available
transformer sensing devices
• It correlates and analyses this data, to provides not only an aggregated view of the
transformer’s health (to minimize the risk of outage) but also to help you optimize its
operation and maintenance
• An “all-in-one expert system” to help you manage your valuable transformers
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 5 of 151
1.2 Versatile Architecture Support
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 6 of 151
1.3 Analysis, Diagnostics, Prognostics and Lifetime Data
Management tool
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 7 of 151
2 SAFETY
2.1 Symbols
2.2 Warnings
The minimum ambient temperature for installation and service activities is −10 C.
If the equipment is installed or used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
If working at height, third parties must have received appropriate training for working at
height prior to work commencing. This includes, but is not limited to "Working at height
training".
If working at a height greater than 4 feet or at a height greater than that stipulated by
national or site regulatory requirements, it is the responsibility of the installer to ensure
that planned work complies with those requirements.
The installer shall also ensure that any third-party equipment, such as an approved
platform, scaffold or lift is suitable and safe before commencing work. Ladders or
improvised platforms do not meet GE service engineer requirements.
Once installed, the product may have more than one source of supply. Disconnect all
supplies at their source before accessing the cabinet for servicing. Follow the site lockout-
tagout (LOTO) procedure.
Only GE-trained and certified personnel may commission GE products. Commissioning tasks
include making any connections and/or performing any work within the enclosure, or
performing tasks such as all first start-up procedures relating to equipment or
firmware/software.
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 8 of 151
3 REQUIREMENTS
3.1 Pre-installation
Ensure that the mains selection switch in the product is set to the relevant voltage range.
The product can be safely connected to an energised or non-energised transformer.
However, if installation personnel are required to work in an energised environment they
must be made aware of this prior to work commencing and must observe all health and
safety practices, especially when working with conductive materials such as stainless steel
installation tubing. If either of the oil supply or return valves to be utilised brings personnel
within restricted approach boundaries then the transformer must be de-energised and
isolated before such work is performed.
To ensure success, careful planning and proper execution of the tasks outlined in this manual
are essential. In addition, the GE Customer Service Centre representative will need specific
information in order to provide recommendations for a trouble-free installation. If GE is to
perform the installation, the installation will not be scheduled until all pre-installation tasks
outlined in this manual are complete (as performed by the customer and GE).
The appendices to this manual contain additional information, such as drawings, forms and
checklists that need to be reviewed and completed prior to the installation. This relates to
materials and facilities that need to be ordered, acquired and in place well in advance of the
scheduled installation date. Confirmation of this needs to reach GE as soon as possible, at a
minimum four weeks prior to the installation date, unless prior arrangements have been
made with the installation group. This aids in planning and supporting the installation
thereby ensuring a trouble-free commissioning process.
Note: Customers/ Buyers are fully responsible for ensuring that stacked pallets are stable and, if necessary,
providing additional external support. Damage incurred as a result of poor customer handling or storage will
not be covered under the GE warranty.
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 9 of 151
2.3 Hot Surface
Hot Surface! If the RXi Box IPC-EP operates by an enhanced ambient temperature
up to 55° C the surface of the housing, specially the heat sink, can reach a
temperature of 70° C and above. Therefore be careful and do not touch the RXi Box
IPC-EP with bare fingers. Install the RXi Box IPC-EP only in rooms with restricted
access.
The Heating in sight the cubical could be hot. The upper grated surface (air outlet
grating) is hot, max 185° C (365° F). Please pay attention to the safety messages.
The max. air outlet temperature is 145° C (293° F) at a height of 55mm above the
grating surface. The surface temperature (on the barrel casing) is max. 80° C (176°
F).
MS-001 – MS 3000 Detail Technical Catalogue – Rev 3.0 9-Oct-18 Page 10 of 151
4 HARDWARE
Essentially the system consists of the following components:
- The Intelligent Electronic Device (IED), which is used as server for the bus
technology, data recording and visualisation.
- The field bus technology that constitutes the I/O interface to the sensors and the
digital signals.
- The sensors and transducers described below.
Depending on the architecture and number of transformers monitored by the MS 3000 the
system can consists of several modules, which are:
Control room module: The control room module is installed indoor and is mounted in
a 19”-Rack. It consists of the IED, network components and
protocol devices. In addition, auxiliary devices (e.g. Power
supply, MCB). I/O-Terminals can be installed within the control
room module, too.
Master module: MS 3000 enclosure, which contains the IED and is installed
outdoor at the transformer or near it, is called Master module.
The master module collects and processes the data of the
whole system.
Slave module: MS 3000 enclosure, which contains no IED. Slave modules are
installed at transformers, to collect the data from numerous
sensors and provide the data of one transformer via Profibus
to the IED in the Master module, where the data is processed.
MS-001 – MS 3000 Detail Technical Catalogue – Rev 2.0 9-Oct-18 Page 11 of 151
4.1 General information
4.1.1 Mechanical configuration
Different housings are used for different modules. For the control room module a 19”-
Housing with 6 HU is used. All other modules mentioned are using a metal enclosure as
housing. The complexity of the MS 3000 can vary in a wide range; enclosures with different
dimensions and degrees of protection (IP code) are available. Dimensions of the enclosures
and information regarding material, painting and IP-code are included in the circuit diagram.
Technical data
Dimensions: 480 mm x 266 mm x 376 mm (w x h x d)
Weight: Approx. 7.0 kg
Degree of protection: IP20 (indoor use only)
Operating temperature: +0 °C to +45 °C
Storage temperature: +0 °C to +45 °C
Relative humidity: 95% non-condensing
System control: 1 x on/off switch
MS-001 – MS 3000 Detail Technical Catalogue – Rev 2.0 9-Oct-18 Page 12 of 151
MS 3000 Master Module
MS-001 – MS 3000 Detail Technical Catalogue – Rev 2.0 9-Oct-18 Page 13 of 151
4.1.2 Electrical configuration and Parameters Monitoring
The power supply, fusing, wiring and installation are executed in accordance with the DIN
VDE1000, TLV, and BGVA standards. The 24 V auxiliary voltages for bus modules, measured
value converters are provided via switching power supply. MS 3000 enclosures are equipped
with a thermostat-controlled heater and with lighting. The control room module is equipped
with a thermostat controlled fan.
The connection between the MS 3000 server and client modules can be carried out with
fibre optic cable with rodent protection or Profibus cable, depending on the distance
between the different modules and the system architecture.
To connect external sensors (e.g. PT100, Gas-in-oil-sensor) with the MS 3000 cubicle only
shielded, oil-resistant and UV-resistant cables may be used. The shield of the cables must be
connected on one side only. They should be connected to the earthing bar in the MS 3000
cubicle.
The exception is the connection to the capacitive bushing measurement connections for
voltage measurement; in this case the shield is connected to earth on the capacitive voltage
sensor, installed on the bushing. If the MS 3000 contains electrical PD measurement, the
shield has to be connected to earth via a capacitor and the wires have to be connected
directly to the Signal Matching Unit (SMU). For details refer to the circuit diagram.
For the mains power supply a non-shielded cable may be used. The internal power supply
unit (PSU) is fitted according to the mains power supplied onsite, as state in the technical
clarification. For details of the power supply please refer to the circuit diagram.
If the MS 3000 is equipped with a socket refer to the circuit diagram to determine
voltage and maximum current rating.
MS-001 – MS 3000 Detail Technical Catalogue – Rev 2.0 9-Oct-18 Page 14 of 151
4.2 Type of Sensors used in MS 3000
Load Current
Bushing CT
PT100
Top Oil Temperature
Dry Contacts
Cooling Control
4.3.1 Voltages
The measured voltage is the voltage between conductor and earth (phase to ground
voltage). The overvoltages are displayed as peak value of the phase-to-ground voltages,
which is the physically correct value. With knowledge of the overvoltages with which the
transformer is stressed, in conjunction with the quantity of harmful gases dissolved in the
oil, statements can be made concerning possible damage to the insulation of the active
part due to overvoltages.
• Load factor
• Apparent power
• Hot-spot temperature
• Ageing rate
• Thermal modelling
Sensor
Bushing built in CT
The operating currents and over currents of the transformer are measured with the aid of
the current transformers (CT) in the bushings. Detection of the over current is only possible
if transformer sides a proper current transformer is used.
Typically the CT in the bushing provides an output signal of 0 to 1 A, 0 to 2 A or 0 to 5 A. This
signal is converted to a 0 to 20 mA signal by a transducer for sinusoidal current. It is located
in the MS 3000 enclosure. The 0 to 20 mA signal is read in by an analogue input terminal
(e.g. KL3042, KL3044).
Current transformer
To use a split core CT an active current loop from a bushing CT is necessary. The split core CT
is clamped on to this loop. Therefore it has to be installed in an enclosure, where the active
current loop is available and not in the MS 3000 enclosure.
The split core CT provides a 4 to 20 mA signal and is loop powered. Thus, only two wires are
necessary to connect it to the MS 3000 enclosure.
The load current can be integrated through a 0/4 to 20 mA direct current signal from SCADA
or from a station CT. Usually station CT consist of a built in measuring transformer, which
converts an alternating current to a 0/4 to 20 mA signal. By integrating the current signal
from SCADA or a station CT it cannot be guaranteed, that over currents can be acquired.
The 0/4 to 20 mA signal is read in by an analogue input terminal in the MS 3000 enclosure
Function
Sensor
The temperature of the upper and lower oil layer is detected via PT100 sensors that are
screwed into provided thermometer pockets in the cover and in the floor of the
transformer. The receptacle and type of the thermometer pocket can vary.
Alternatively a 0/4 to 20 mA signal, provided by a temperature transmitter, can be read in
by an analogue input terminal.
Dry Contacts used to operate the individual fan and pumps for
Cooling Control
Function
An intelligent cooling unit controller can be integrated in the MS 3000. In this regard there
are several possibilities for controlling the cooling unit; as a function of the actual load,
and/or as a function of the actual oil temperature. The chapter, Web Visualisation, describes
how to set the appropriate limit values and other parameters.
Actuators
Relays are integrated in the MS 3000 enclosure parallel to the conventional controller in the
cooling control cabinet to activate the cooling unit. To prevent overlap of the two
controllers, the conventional controller must be reconfigured in such a manner (usually via
dial-indicator thermometers), that it only takes over emergency cooling.
Depending on the technical solution, the switching relays in the cooling control cabinet are
activated either via digital output terminals (e.g. KL2134), or via relay output terminals (e.g.
KL2652) that make floating contacts available.
With knowledge of the moisture in oil, statements can be enabled concerning the moisture
absorption of the oil through oil respiration and formation of moisture due to
decomposition of the paper insulation. Moreover moisture content is an indicator of the
electrical resistance of the insulating oil. In oil analysis will be
• HYDROGEN (H2)
• METHANE (CH4)
• ETHYLENE (C2H4)
• ACETYLENE (ETHINE) (C2H2)
• CARBON MONOXIDE (CO)
• MOISTURE (H2O)
Communication between the gas sensor and the MS 3000 Monitoring System is established
via different protocols and connection types.
For example, this can be an RS485 or TCP connection with a Modbus protocol. (See the
circuit diagram and highlighted circle for illustration).
Example : In MS 3000 following combination of Bus Modules and be customised as per the project
specific requirement.
Changes in fan and pump operating condition and runtimes are saved in the historical
database.
When the transformer is switched on the voltage and the current are recorded for a period
of 10 seconds.
Switch-off can be caused by the tripping of a protective element. In this case, a switch-off log
is generated to obtain precise information concerning the course of events of the switch-off
and thus the cause.
All overshoots of measurement ranges and limit values are logged in the historical database.
Data acquisition
Profibus / Modbus /
Several
communications
protocols
Real-time database
RAM, high temporal
Visualisation
resolution
Historical database
Flash memory,
optimised data rate
MS 3000 IED
The processed real-time data is saved in a fast, special long-term database. In this process
the data is stored per its physical characteristic. This means either event-oriented storage of
stochastic processes (e.g. switch processes), or cyclical storage of continuous operating data,
where the storage rate of the time constants is adapted to the respective characteristic
value.
Apparent power
Input variables
Actual voltages
Actual current
Calculation of
apparent power
Output variables
Actual apparent
power
Input variables
Actual Voltage
Actual current
cosφ
Calculation of active
power & reactive power
Output variables
Active Power
Reactive Power
Input variables
Actual power
Normal power
Calculation of load
factor
Output variables
Actual load factor
Input variables:
Actual hot spot temperature
Paper type
Output variables:
Aging rate
Input variables
Ageing rate per day (daily
update)
Calculation of lifetime
consumption
Output variables
Lifetime consumption
Input variables
Actual load current
Oil temperature
Actual voltage
P0 & Pk (nominal values)
Average winding to average oil temperature at rated current
Output variables
Ageing losses
Input variables
Actual load current
Oil & air/water temperature
Transformar specific data(winding gradient, Hot-
Spot factor)
Output variables
Hot-spot temperature in accordance with IEC
60354/60076
Input variables
Condition - pumps & fans
Cth (nominal value)
P0 & Pk (nominal values)
Cooling method
(ON, OF, OD)
Output variables
Hot-spot temperature in accordance with the
thermal model
Input variables
Moisture in oil
(Oil temperature)
Output variables
Moisture in paper
Input variables
Actual gas-in-oil
content
Calculation of gas-in-
oil gradient
Output variables
Gas-in-oil gradient
Input variables
Actual current
Output variables
Number of overcurrents
Log of high-resolution data of the current for max. 10s
Recording of the overcurrent events
Input variables
Oil temperatures
Calculation of the
characteristic data of
the cooling unit
Output variables
Temperature differences
Power of cooling unit
Thermal resistance
Input variables
Status of fans and pumps
Actual load current
Oil, water and air temperatures
Pk and P0
Output variables
Thermal resistance (Rth)
Input variables
Status of fans and pumps
Actual load current
Oil, water and air temperatures
Cth, Pk and P0
Output variables
Duration of emergency operation
at overload
Duration of emergency operation
if the cooling unit fails
Input variables
Status of fans and pumps
Actual load current
Oil, water and air temperatures
Cth, Pk and P0
Output variables
Duration of emergency operation
at overload
Duration of emergency operation
if the cooling unit fails
A) Direct connection
To establish a direct connection, the PC must be connected directly to the Monitoring Server
via a network cable. The PC must be configured for the direct connection, i.e. a fixed IP
address that is compatible with the MS 3000 server must be assigned to the PC.
At delivery the server has the default IP address 10.53.54.185. The subnet mask is
255.255.255.0. The PC must have a fixed IP address, type 10.53.54.x (x = 0-255 except 185,
which is reserved for the server).
The advantage of the direct connection is the extremely high-speed of data transmission.
C) Modem connection
To establish a modem connection, a dial-up connection must be set-up to the server. This is
done in precisely the same manner required for a dial-up connection to the Internet. The
following identification data is set:
• Password: ppp.
The dial-up modem connection is always significantly slower than a LAN connection.
Moreover the speed depends on the quality of the telephone network. A LAN connection or
direct connection are possible concurrently with an established modem connection.
Regardless of whether a direct, LAN, or modem connection is established, the following
preparations must be made:
• A connection to the MS 3000 server must be established.
• The web browser of the client PC, e. g. Internet Explorer, must be open and the IP
address of the MS 3000 server (e.g. http://10.53.54.185) must be entered.
6.2 Overview
You can access the server from client PCs through the connection of the Monitoring Server
to the intranet, or the local area network via the TCP/IP protocol. Data access is password
protected and is user-group specific.
Web visualization offers the following functionalities:
Visualization is started by entering the IP address of the monitoring system in a web browser
For repeated access to the server we recommend setting a bookmark in the browser.
6.3 Login
Login screen
The websites are protected through Apache Web Server Authentication. After selecting a
user group on the homepage, you must enter a user name and the appropriate password.
To log in as Supervisor the following identification data must be entered:
Information field:
• System time
• Logged-in user
• Logout Button
Main navigation:
• Status overview
• Alarms
• Transformer 1... x
• Historical data
• Tools
• System data
Visualization is explained here for users on the supervisor level, as an example. The
functionality in the User-level is the same, however it is restricted in some points.
Active part:
If there is no active part malfunction, this field is white and contains the phrase Active part
no fault. When the system detects a warning or alarm condition, this is displayed by the
associated flashing, thick border phrase, e.g. Oil temperature warning. Additional
information is provided on the page Active Part and under the menu item Transformer, as
well as under the menu items Alarms or Historical Data. Click the flashing fault text to open
a new page with the recommendation texts for the fault (see Table 2:)
This warning appears when the gas-in-oil gradient is higher than the warning limit.
• Water content in oil
The water content in the oil has exceeded the warning limit. Possible reasons are,
respiration of the transformer or disintegration of the paper insulation.
• Buchholz gas
Released gas is collected in the Buchholz gas sensor. When reaching a defined gas quantity a
warning will be generated. The gas volume can continuously increase over a longer period of
time, or it can also spontaneously increase.
• Humidity
The humidity has exceeded the warning limit. The cause can be a leak in the pipeline or the
desiccant is used up.
• Moisture in paper
This value is calculated from the top oil temperature and moisture in oil. A warning is output
when the permissible value is exceeded.
• Oil level – tank
Monitoring of the upper and lower oil level in the tap changer.
• Malfunction gas sensor
Warning – humidity Depending on the oil Check desiccant (silica gel), check desiccant
The humidity is too high. Humidity should be as low temperature breather circuit or line
as possible to reduce water absorption in the active
part.
Warning – moisture in paper Check the measured value Make an off-line water content
Moisture in paper exceeds the warning threshold. measurement, or check moisture in oil
Moisture in paper is a calculated value and is based sensor and PT100 sensor and associated
on water content in the oil and oil temperature. bus terminals
Since most of the water in the transformer is located
in the insulation paper, and the solubility of water in
oil is temperature-dependent, water content in the
oil depends on the equilibrium condition in the
transformer.
Warning – oil level in the conservator Unusually low oil temperature Refer to chapter Service/maintenance in
The oil level in the conservator underranges the the transformer manual (fill quantity)
warning threshold. The oil level in the tank depends Unusually high oil temperatures Reduction of load
on the oil temperature in normal operation. Oil level drops without reason Check for leaks
Oil level increases without Refer to chapter Service/maintenance in
reason the tap changer manual
Warning – oil level, tap changer Unusually low oil temperature Refer to chapter Service/maintenance in
The oil level in the tap changer exceeds the warning the transformer manual (fill quantity)
threshold. The oil level in the tap changer depends Unusually high oil temperatures Reduction of load
on the oil temperature in normal operation. Oil level drops without reason Check for leaks
Oil level increases without Refer to chapter Service/maintenance in
reason the tap changer manual
If the bushing is in proper condition this field is white and contains the phrase, Bushing – no
fault. When the system detects a warning or alarm condition, this is displayed by the
associated flashing, thick border phrase, e.g. Warning – overvoltage. Additional information
is provided on the page Bushing under the menu item Transformer, as well as under the
menu items Alarms or Historical Data. Additional information is provided on the page Active
Part and under the menu item Transformer, as well as under the menu items Alarms or
Historical Data. Click the flashing fault text to open a new page with the recommendation
texts for the fault (see Table 3:)
Deviation of the bushing capacity of a phase is greater than the configured warning limit.
The cause can be damage to the capacitance layers in the bushing. If necessary, additional
off-line measurements are advisable.
• Overcurrent
The measured value of the load current exceeds the warning limit.
• Overcurrent counter
At high ambient temperatures oil pressure in the bushings significantly increases. There is
danger that the bushings will be damaged or even explode.
• Network unbalance
Network unbalance is normally caused by external faults or unbalanced load in the network.
Warning – overvoltage Inner overvoltages or switching Check overvoltage counter of the surge
An overvoltage was detected. The operations in the network, or external voltage protector.
overvoltage counter has been increased. overvoltages or direct lightning strikes.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 52 of 151
Pulse-shaped overvoltages can occur due to
switching operations in the network, e.g.
through interruption of currents in inductive
current circuits of the network, or through
direct lightning strikes on energy-supply
equipment.
Warning – overvoltage counter Inner overvoltages or switching Check overvoltage counter of the surge
The overvoltage counter has exceeded the operations in the network, or external voltage protector. Check the bushings
warning threshold. If the event occurs overvoltages or direct lightning strikes. through off-line measurement.
frequently it can also indicate partial Contact the GE Monitoring Team.
breakdown of the layers of the bushing.
Warning – bushing capacitance Erratic increase of a phase voltage Trend analysis of bushing capacitance, or
A possible change in bushing capacitance has contact the GE Monitoring Team.
been detected. The bushing capacitance is Wrong bushing capacitance values Check the bushing capacitance values in the
determined through comparison of the entered monitoring system
phase voltage. Through the monitoring In all cases Off-line measurement of the bushings
function, partial breakdowns and arcing of
the capacitive layers of the bushing can be
detected early on. The implemented
algorithm distinguishes between normal
voltage fluctuations in the networks and
faults in the insulation of the bushing.
Typical erratic increases of a phase voltage
are observed for this.
Partial failure of the insulation of the
bushing can be related to a preceding
overvoltage.
Comment: If there is a dry bushing,
appropriate control measurements must be
initiated as quickly as possible.
Warning – overcurrent In all cases Refer to the device manuals for rating and
An overcurrent was detected. The overload.
overcurrent counter has been increased.
The load capacity and overload capacity of
oil-filled transformers is specified in IEC
standards relative to level and duration.
Ambient temperature and the type of
cooling must be taken into account. The
duration of the overload phase
proportionally reduces the service life of the
transformer. You must consider whether the
overcurrents occurred briefly or long-term.
Warning – overcurrent counter In all cases Refer to the device manuals for rating and
The overcurrent counter has exceeded the overload.
warning threshold.
Warning – current without voltage In all cases If possible check the voltage sensor, wiring,
The monitoring system has detected a or peak sampler and associated bus terminal,
current without voltage. This can only occur or contact the GE Monitoring Team.
if the voltage monitor or the measurement
chain has been interrupted or has not been
connected.
Warning – oil pressure of the bushing Change in oil pressure Check for visible leak points
The deviation in oil pressure of one bushing
relative to others has been detected.
Warning – network unbalance A network unbalance can make Trend analysis of bushing capacitance, or
Network unbalance has been detected. detection of faults on the bushing contact the GE Monitoring Team.
Deviation in amplitude of the three voltages difficult
of a three-phase current system can occur,
e.g. in networks with a low network voltage
level.
If the cooling unit is in proper condition this field is white and contains the phrase, Cooling
unit- no fault. When the system detects a warning or alarm condition, this is displayed by the
associated flashing, thick border phrase, e.g. Pump fault. Additional information is provided
on the page Cooling System under the menu item Transformer, as well as under the menu
items Alarms or Historical Data. Click the flashing fault text to open a new page with the
recommendation texts for the fault (see Table 4:)
One or more pumps are not running, although they are switched on.
• Efficiency – cooling unit
The difference between the inlet and outlet temperature is below a specified limit value. The
cause can be a fouled cooler or fan failure.
• Fan controller: Cooler faulty
A fan cannot be switched on or off although the fan controller software has changed the
number of switched-on fans.
Pump fault Depending on the signal used, the Check the appropriate assemblies
A non-functioning pump has been detected. motor protection contact used, or
The diagram can be used for more detailed analysis. the corresponding flow detector
can be defective, or the pump is
defective.
Efficiency – cooling unit Reduced cooling capacity due to If possible reduce the load on the
The monitoring system has detected that the cooling fouling, reduced oil throughput transformer until the cause has been
capacity is too low for current ambient conditions. due to fouling, pump fault, eliminated, check the appropriate
The diagram can be used for more detailed analysis. defective fan motor or assemblies, check whether the
temperature of the cooling valves are completely open.
medium is close to the nominal
temperature
If the tap changer is in proper condition this field is white and contains the phrase, Tap
changer – no fault. When the system detects a warning or alarm condition, this is displayed
by the associated flashing thick border phrase, e.g. Duration of inrush current. Additional
information is provided on the page Tap Changer under the menu item Transformer, as well
as under the menu items Alarms or Historical Data. Click the flashing fault text to open a
new page with the recommendation texts for the fault (see Table 5:)
Duration of the total tap change operation exceeds the warning limit.
• Power consumption index
The tap change duration was too short. The tap change operation may not have been
concluded.
• Motor operation without new tap change setting
The tap change operation may not have been concluded. The tap changer may have
jammed.
• Tap change without motor operation
The duration of the tap change over multiple taps is too long.
• Inspection of the tap changer is recommended
The number of switching operations or the switched summated current exceeds the
recommended maintenance intervals.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 56 of 151
• Oil filter is fouled
The oil filter is fouled. To prevent more extensive damage, check the oil filter.
Duration of inrush current Sluggishness for all taps Sluggishness of outer components of
Duration of inrush current of the motor drive the tap changer (all taps are affected) –
was too long. The duration of the inrush check gear unit and mechanical
current peaks is influenced by the mechanical elements.
condition of the motor drive. If the inrush Sluggishness for one tap Sluggishness in the tap changer tank
current peak is too long, this is attributed to (one tap affected) – contact the GE
excessive starting torque due to sluggishness in Monitoring Team.
the mechanism of the tap changer. This effect Sluggishness due to low oil viscosity Sluggishness due to temperature-
can only occur selectively for certain taps or it or mechanical warping due to low related tensions – contact the GE
can occur consistently for all taps. Likewise a temperature. Monitoring Team.
low oil temperature in the tap changer tank can
negatively influence mechanical behaviour.
Duration of tap change operation Sluggishness for all taps Sluggishness of outer components of
Motor runtime was too long. the tap changer (all taps are affected) –
Duration of tap change operation is influenced check gear unit and mechanical
by the mechanical condition of the motor drive. elements.
If the inrush current is too long, this can be due
to sluggishness in the tap changer. This effect Sluggishness for one tap Sluggishness in the tap changer tank
can only occur selectively for certain taps, or it (one tap affected) – contact the GE
can occur consistently for all taps. Likewise a Monitoring Team.
low oil temperature in the tap changer tank can Sluggishness due to low oil viscosity Sluggishness due to temperature-
negatively influence mechanical behaviour. or mechanical warping due to low related tensions – contact the GE
temperature. Monitoring Team.
Power consumption index Sluggishness for all taps Sluggishness of outer components of
The power consumption of the motor was too the tap changer (all taps are affected) –
high. The power consumption of the tap check gear unit and mechanical
changer drive reflects the mechanical condition elements.
of the tap changer. With increasing wear or due
to mechanical warping or low oil viscosity Sluggishness for one tap Sluggishness in the tap changer tank
related to low temperatures, a certain (one tap affected) – contact the GE
sluggishness can occur over the entire tap Monitoring Team.
change operation. Through integral detection Sluggishness due to low oil viscosity Sluggishness due to temperature-
of power consumption, mechanical problems or mechanical warping due to low related tensions – contact the GE
can be detected early on. temperature. Monitoring Team.
Fault – maximum sector 1 Sector value increased for all taps Sluggishness in the tap changer tank (all
The maximum energy consumption in sector 1 taps affected) – contact the GE
exceeds the warning threshold. Motor monitoring team.
operation is divided into 3 sectors for better Sector value increased for one tap Sluggishness in the tap changer tank
monitoring of the different tap change phases. (one tap affected) – contact the GE
Over-proportional power consumption in one Monitoring Team.
sector indicates internal mechanical problems Sector value increased, temperature- Sluggishness due to temperature-
of the tap changer. dependent related tensions – contact the GE
Monitoring Team.
Fault – maximum sector 2 Sector value increased for all taps Sluggishness in the tap changer tank (all
The maximum energy consumption in sector 2 taps affected) – contact the GE
exceeds the warning threshold. Motor monitoring team.
operation is divided into 3 sectors for better Sector value increased for one tap Sluggishness in the tap changer tank
monitoring of the different tap change phases. (one tap affected) – contact the GE
Over-proportional power consumption in one Monitoring Team.
sector indicates internal mechanical problems Sector value increased, temperature- Sluggishness due to temperature-
of the tap changer. dependent related tensions – contact the GE
Monitoring Team.
Fault – maximum sector 3 Sector value increased for all taps Sluggishness in the tap changer tank (all
The maximum energy consumption in sector 3 taps affected) – contact the GE
exceeds the warning threshold. Motor monitoring team.
operation is divided into 3 sectors for better Sector value increased for one tap Sluggishness in the tap changer tank
monitoring of the different tap change phases. (one tap affected) – contact the GE
Over-proportional power consumption in one Monitoring Team.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 57 of 151
sector indicates internal mechanical problems Sector value increased, temperature- Sluggishness due to temperature-
of the tap changer. dependent related tensions – contact the GE
Monitoring Team.
Tap change duration too short Interruption observed Check wiring (loose terminal point –
The detected tap change duration was too loose connection).
short. The cause can be a brief interruption of
the motor operation, triggered by loss of
contact.
Motor operation without new tap change Typical performance curve recorded, Check resistor wheel (possibly BCD
setting however certain tap changer code).
Tap change did not follow the last motor positions are not detected.
operation. The cause can be malfunction of the Typical performance curve recorded, Wiring fault or defect of the bus
motor monitor. however no tap change is detected. terminal, mechanical connection –
drive/tap changer – disconnected.
Performance curve shows only a short Interference pulse, trigger threshold
pulse must be adapted – contact the GE
Monitoring Team.
Tap change without motor operation Motor power not detected Check wiring and Adamczewski relay,
New tap changer position without motor check associated bus terminal.
operation. The cause can be malfunction of the Detection of motor power Check for manual tap change, check the
motor monitor. sporadically drops out electrical connections for loose
terminal points.
Total tap change duration was too long Sluggishness for all taps Sluggishness of outer components of
The total duration of tap change/motor the tap changer (all taps are affected) –
operation was too long. Power consumption of check gear unit and mechanical
the tap changer motor drive has been detected elements.
over a period of time that is longer than the tap Sluggishness for one tap Sluggishness in the tap changer tank
change process from the lowest to the highest (one tap affected) – contact the GE
tap would last. Monitoring Team.
Sluggishness due to low oil viscosity Sluggishness due to temperature-
or mechanical warping due to low related tensions – contact the GE
temperature. Monitoring Team.
Defect on the Adamczewski relay Check signal output or contact the GE
Monitoring Team.
Inspection of the tap changer is recommended The number of tap changes has See the tap changer manual for the
reached the warning threshold. subsequent procedure.
Oil filter is fouled The measured oil pressure in the filter The condition of the filter should be
of the tap changer was too high. It is checked.
possible that the filter in the oil circuit
is fouled.
Actual alarms
Click this button in the navigation menu to display the current alarms.
The alarm overview shows all currently pending warning and alarm messages generated by
MS 3000. Warnings are marked with a yellow and alarms with a red colour change.
The alarm list updates automatically every 10 seconds. Manual updating can be initiated by
the button Update.
A warning or alarm can be acknowledged by the user. For this, the corresponding table entry
must be selected by mouse click and then the button Acknowledge must be pushed. Enter
the user name and the password in the resulting dialogue. Optionally, a comment can be
entered. This is saved in the alarm database and displayed together with the corresponding
event when calling historical alarms (see Historic data). Acknowledged messages are
displayed with a white colour change. The button "Acknowledge all" acknowledges all active
warnings and alarms.
Alarm configuration
Click the Alarm Configuration menu item to set the warning and alarm thresholds.
The alarm thresholds pre-configured in the MS 3000 can be adjusted on demand. To change
the threshold values for a process variable, the corresponding process variable must be
selected first. For this, push the button Selection and select the process variable in the
dialogue that appears.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 60 of 151
Configuring the alarms
After loading is complete and the current thresholds have been loaded, they can be
changed. To change a value, click the corresponding table entry and enter the new value in
the appearing dialogue.
The modification is saved by clicking the button Set. Before the button Set has been clicked,
the active thresholds can be loaded again with the button Update.
Loading + Current
Status of transformer:
This field indicates whether the transformer is switched on or off.
Apparent power:
This is where the apparent power absorbed by the transformer is displayed. The measured
value is saved in the historical database as 15-minute mean value.
Active power:
Display of the active power of the transformer. The measured value is saved in the historical
database as 15-minute mean value.
Reactive power:
Display of the reactive power of the transformer. The measured value is saved in the
historical database as 15-minute mean value.
Actual losses:
The momentary transformer losses are the sum of no-load losses and short-circuit losses at
actual load current. The measured value is saved in the historical database as 15-minute
mean value.
Number of overcurrents:
The number of detected overcurrents since the system was commissioned is shown here.
Graphics button
After activating the Graphics button the historical trend of the corresponding value is
displayed in a popup window (popup windows must be enabled). Functionality of the
graphic visualisation is described in section 6.4.4.1 Graph. This button is available on
different pages of the Web Visualisation.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 64 of 151
Graphics button
Ageing rate:
The aging rate is a relative value that describes the deterioration process of a transformer.
The hot-spot temperature of the transformer can be calculated via load current and
temperature of the top oil layer.
E.g. for a hot-spot temperature of 98 °C the ageing rate is 1.0. The ageing rate doubles for
each 6 °C of temperature increase, inversely the ageing rate is halved for each 6 °C of
temperature decrease.
The measured value is saved as an hourly mean value in the historical database.
This is where the gas concentrations analyzed with the online DGA sensor are displayed. The
measured values are saved in the historical database as 15-minute mean values.
All detected gases are shown in this part of the window with the actual value in ppm. In
addition, the total gas volume (total dissolved combustible gas) TDCG is also shown.
The following 4 different hazard levels as specified in IEEE C57.104-2008 can be signalled by
the colour coding of the fields.
Level 1:
A TDCG value assigned to this level indicates that the transformer is functioning without
problems.
Level 2:
A TDCG value in this area indicates a quantity of combustible gases that is greater than
normal. If one of these gases exceeds the limit value, observation is required (monthly
inspection).
Level 4:
A TDCG value in this area indicates an extremely serious decomposition of the oil. A failure
can occur if the transformer continues to be operated (daily inspection).
Example
Levels H2 CH4 C2H2 C2H4 C2H6 CO CO2 TDCG
Level 2 101 - 700 121 - 400 2–9 51 - 100 66 - 100 351 - 570 2501 - 4000 721 - 1920
Level 3 701 - 1800 401 - 1000 10 – 35 101 - 200 101 - 150 571 - 1400 4001-10000 1921 - 4630
In this part of the window the daily rates of the different gases are displayed in ppm/day.
The measured values are saved in the historical database as hourly mean values.
The consequences of a system fault range from minor (e.g. replacement of the battery) to
major (e.g. replacement of the sensor). The operator must react to such an alarm by
gathering information about its origin and degree of severity and informing maintenance
personnel without delay. Maintenance personnel must identify and eliminate the cause of
the system fault to ensure trouble-free operation of the gas sensor and to maintain the
protection of the transformer. For additional information see the gas sensor system manual.
Breakdown voltage:
Breakdown voltage can be calculated from the knowledge of the moisture in oil. This value is
a measure for the quality of the insulating oil. The measured value is saved in the historical
database as 15-minute mean value.
Thermal resistance:
This is where the thermal resistance is displayed. The measured value is saved in the
historical database as 15-minute mean value.
Bubbling temperature:
This is where the calculated bubble formation temperature is displayed. The bubbling
temperature is the oil temperature at which the bubble formation of the oil/paper system is
recorded. The value is saved in the historical database as 15-minute mean value.
The condition of different devices can be checked on the Digital Values page. For example,
the system shows whether a device is switched on (ON/OFF) and whether it is functioning
properly (no fault/warning). The detected values are system-dependent.
Maximum overload:
If there is a critical operating condition of the network, it may be necessary to overload the
transformer. There are two fundamental types of overload. Overload with increased
conductor temperature and thus related accelerated deterioration. This should only be
permitted in emergency cases, such as a threatening power outage. On the other hand,
conditions are conceivable under which the current flow is greater than the nominal current,
however the ambient conditions prevent a temperature rise of the conductors beyond the
operating limits. Both overload cases are procedures that reduce the safety margin and
consequently demand conscientious checking and monitoring.
With the aid of the thermal model implemented in the MS 3000, the actual permissible
continuous load depending on actual ambient temperature is calculated in accordance with
the IEC 60076-7 standard and shown in the Max. Overload field.
Pumps + Fans
The status (ON/OFF) of the pumps and fans is displayed in the left column Condition of the
respective function group. The operating hours of the pumps and the fans are shown in the
right column Operating time. The measured values are recorded in the historical database,
event-driven or after 24-hours.
The difference between the inlet and outlet temperature of the cooling unit in operation is
too low. The cause can be a fouled cooler or fan failure.
• Fan controller: Fan is defective
A fan cannot be switched on or off although the fan controller software has changed the
number of switched-on fans.
The switching status of the fan group prescribed by the fan controller routine is displayed.
• Operating hours
The cooling controller is structured in two levels. In one level, fans are switched on or off
individually depending on the actual oil temperature. In this process the number of required
fans is determined by the software, and the fans with the lowest duration of operation are
switched on, or the fans with the longest duration of operation are switched off. With the
appropriate configuration, the positions of the fan groups on the transformer are also taken
into account (if mounted on the facing sides), so that if possible, the fans go into operation
alternately by groups, to avoid cooling on one side.
In an overlaid second level, the cooling controller can activate the entire cooling capacity
load-dependently (see Load-dependent control).
Load factor:
The load factor indicates the actual capacity utilisation of the transformer.
Temperature increment:
Shows the set interval for switching in the next fan. By entering a new value in the input field
and activating the Set Value button you can change the interval.
Temperature hysteresis:
If a fan is switched on through reaching the appropriate temperature threshold, (start
temperature + x-times temperature increment), then the temperature must drop by the
value set here (in Kelvin), so that the fan can be switched off again.
With this hysteresis you avoid the situation, that at temperatures around a switch point a
high number of switching operations are executed.
By entering a new value in the input field and activating the Set Value button you can change
the hysteresis.
The min. or max. warning threshold of the oil level in the case has been exceeded.
The min. or max. warning threshold of the oil level in the tap changer has been exceeded.
The simulator pages of the Web Visualization have been developed for determination of the
theoretical behavior of a transformer in specified operating scenarios.
Load factor
In the ONLINE area the momentary values of the detected transformer parameters are
displayed. In the SIMULATOR area the values can be entered and subsequently a theoretical
calculation of dependent values can be executed.
By activating the Load Online Data button, the data from the ONLINE area will be copied to
the entry fields of the simulator. These values can be changed here.
Use the Simulate button to start the calculation for the prescribed scenario.
Rated Power:
This is where the calculated (ONLINE) or entered (SIMULATOR) nominal power of the
transformer is displayed.
Apparent power:
This is where the apparent power calculated from the line-to-line voltage and the load
current is displayed.
Load factor:
This is where the load factor calculated from the line-to-line voltage and the load current is
displayed.
.
Hot-spot simulator
Hot-spot temperature:
This is where the calculated (ONLINE) or entered (SIMULATOR) hot point temperature is
displayed.
Ageing rate:
This is where the ageing rate calculated from the hot-spot temperature is displayed.
Actual losses:
This is where the calculated actual losses are displayed.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 89 of 151
Moisture of Insulation Paper
Historically saved data can be displayed graphically. The user may generate charts for
different process variables and periods here.
Select
PV - Select
Profiles can be set up to avoid repeated manual selection of the same values. The currently
selected process variables are saved in a profile, so that the entire selection can be loaded
again at a later time.
To save a profile, select the process variable and then enter the profile name into the
corresponding field, and push the button Save.
Save Profile
To load a saved profile, the corresponding entry in the profile list must be selected and the
button Load must be pushed.
Load Profile
To rename a profile, the corresponding entry in the profile list must be selected and the new
name entered in the input field; then the button Rename must be pushed.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 93 of 151
Rename Profile
To remove a profile from the list, the corresponding entry in the profile list must be selected
and the button Remove must be pushed.
Delete Profile
After the process variables have been selected, the time range for which the data are to be
displayed must be selected in the dialogue that appears. The starting and end times can be
entered manually or using the calendar functions.
Calendar
After selection of the time range has been completed, the historical data are loaded and
displayed in the chart.
The time at the root of the X-axis is displayed in the corresponding field.
To facilitate legibility in the chart, the time stamp corresponding to the current cursor
position is displayed in the lower right corner of the chart and the respective Y-values in the
key next to the process variable name.
Value
Zoom
Zoom
The two zoom buttons can be used for linear zooming into and out of the chart. The zoom
focus is on the chart centre.
The last zoom step can be reversed with the button Zoom Back.
Back
To reverse all zoom steps and to return to the initial view, push the Zoom Back button.
Scaling
Pushing the button Scaling menu opens a menu that offers options to adjust scaling of
displayed curves.
Expanded settings
Observe that the adjustments made here affect all process variables selected in the key of
the chart.
Curve selection
Alternatively, a specific process variable can be selected by clicking the corresponding Y-axis.
There are three options for each process variable.
- The display range is scaled so that the chart is best used in the X as well as the
Y directions for displaying the respective curve.
- The display range is scaled so that the chart is best used in the X direction for
displaying the respective curve.
The menus Setting X-scale and Setting Y-scale can be used to enter the respective display
areas manually. After clicking one of the options, the corresponding input dialogue appears.
Alternatively, scaling can be adjusted with the scroll wheel of the mouse and the shift and
control keys.
- Turning the scroll wheel: Scaling the X- and Y-axes
- Pushing the control key and turning the scroll wheel: Scaling the X-axis
- Pushing the shift key and turning the scroll wheel: Scaling the Y-axis
The options Zoom X-adjustment and Zoom Y-adjustment permit scaling the display range so
that the chart is best utilised in the X- and Y-directions for displaying each curve.
Switching pulling/selection
The shift button can be used to change the mouse button function. If the button is activated,
the left mouse button is used to grip and pull the chart with the mouse. If the button is
deactivated, the left mouse button can be used to freely select a zoom area.
Crosshatch
Crosshatch
Pop-up Information
When moving over the data points of a curve with the mouse, a pop-up field next to the
cursor can be displayed to show the current time stamp and the value. For this, the button
Display pop-up information must be activated.
Comments
Comments
The historical figure enables the user to assign comments to any displayed data points.
Entered comments are saved in the system and can be displayed for future evaluations.
To activate the comment function, push the button Display comments.
After clicking a data point, the option Add comment appears and can be pushed to open the
comment input dialogue.
Add comment
Enter comment
The data points that have been assigned a comment are marked accordingly.
Comment display
To open, edit or delete a comment that has already been generated, click the pen symbol in
the comment mark.
Edit comment
Curve display
Curve display
The standard display of the curves by interpolation can be changed as follows with the three
respective buttons:
- Marking individual data points
Area view
- Marking the individual data points and display in the form of a step function
Chart enlargement
Multiple scaling
The button Display all axes activates the display for the X-axis for each chosen process
variable. When deactivating the button, a Y-axis applicable for all curves is displayed. In the
latter case, the display of the curves automatically adjusts to the Y-scale, so that the chart is
used in the best way in the Y-direction for display of all curves.
Download
Download
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 102 of 151
The data presented in the chart can be downloaded in the form of an ASCII file. For this,
push the button Download. The user has download options in the resulting dialogue.
The currently displayed time area can be adjusted with the fields From and To.
The entire time range can be structured in intervals. The interval option must be activated
for this. An interval is specified in the form Days:Hours:Minutes:Seconds in the field Interval.
If an interval is defined, one value per interval is assumed in the result (interpolated if
necessary) when downloading the data for each process variable across the time range. The
function applied here can be specified for each process variable via the option Function (see
below).
If the interval option is deactivated, the data available in the historical database for the
specified time range are directly assumed into the result.
If an interval is defined, the button Evaluation can be used to calculate the number of
expected entries (lines) depending on the entire time range and the interval.
If an interval is defined, the option Function can be used to specify the values to be used for
each process variable for generation of the values. Possible functions for this are:
Last: The last value per interval is considered.
First: The first value per interval is considered.
Minimum: The lowest value per interval is considered.
Maximum: The highest value per interval is considered.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 103 of 151
Average: The arithmetic average of all values available in an interval is formed.
After pushing the button Download, the data are called and displayed in the web browser in
a new window. The user can save the file locally with the corresponding function of the web
browser.
The generated text file is compatible with common spread sheet programmes and can be
imported into them for further processing. The tabs sign is used as a separator.
Historic Alarms
All alarm messages generated automatically by the MS 3000, information on the alarm
acknowledgements by the users and the ended alarms are saved historically and can be
called on demand.
The comments entered by the users for the alarm acknowledgements and the comments
automatically generated by the system (such as exceeded alarm thresholds) are displayed in
the comment column.
Alarms
Select
The button Selection can be used to select process variables (PV). After clicking the button, a
selection dialogue appears. In the PV tree, the interesting values can be added to the
selection or removed from it.
Profiles can be set up to avoid repeated manual selection of the same values. The currently
selected process variables are saved in a profile, so that the entire selection can be loaded
again at a later time.
To save a profile, select the process variable and then enter the profile name into the
corresponding field, and push the button Save.
Save profile
To load a saved profile, the corresponding entry in the profile list must be selected and the
button Load must be pushed.
Load profile
To rename a profile, the corresponding entry in the profile list must be selected and the new
name entered in the input field; then the button Rename must be pushed.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 105 of 151
Edit profile
To remove a profile from the list, the corresponding entry in the profile list must be selected
and the button Remove must be pushed.
Remove profile
Load
The button Load can be used to select a time range for display of the historical data.
The starting and end times can be entered in the appearing dialogue manually or using the
calendar function.
Calendar
After selection of the time range has been completed, the historic alarms are loaded and
displayed.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 106 of 151
Last entries
The button Last can be used to load the last available entries for all process variables.
Preview
The button preview can be used to display the currently loaded entries in a new window of
the web browser in the form of an HTML table. The corresponding browser function can be
used to print out the table.
Preview
Historical list
Select
The button Selection can be used to select process variables (PV). After clicking the button, a
selection dialogue appears. In the PV tree, the interesting values can be added to the
selection or removed from it.
Profiles can be set up to avoid repeated manual selection of the same values. The currently
selected process variables are saved in a profile, so that the entire selection can be loaded
again at a later time.
To save a profile, select the process variable and then enter the profile name into the
corresponding field, and push the button Save.
Save profile
To load a saved profile, the corresponding entry in the profile list must be selected and the
button Load must be pushed.
Load profile
To rename a profile, the corresponding entry in the profile list must be selected and the new
name entered in the input field; then the button Rename must be pushed.
Edit profile
Remove profile
Load
The button Load can be used to select a time range for display of the historical data.
The starting and end times can be entered in the appearing dialogue manually or using the
calendar function.
Calendar
After selection of the time range has been completed, the historic alarms are loaded and
displayed.
Preview
The button preview can be used to display the currently loaded entries in a new window of
the web browser in the form of an HTML table. The corresponding browser function can be
used to print out the table.
Historically saved data can be downloaded as an ASCII file. The generated text file is
compatible with common spread sheet programmes and can be imported into them for
further processing. The tabs sign is used as a separator.
Data download
In the PV tree, the interesting values can be added to the selection or removed from it.
Profiles can be set up to avoid repeated manual selection of the same values. The currently
selected process variables are saved in a profile, so that the entire selection can be loaded
again at a later time.
To save a profile, select the process variable and then enter the profile name into the
corresponding field, and push the button Save.
Save profile
To load a saved profile, the corresponding entry in the profile list must be selected and the
button Load must be pushed.
Load profile
Edit profile
To remove a profile from the list, the corresponding entry in the profile list must be selected
and the button Remove must be pushed.
Remove profile
After pushing the button Download, the data are called and the generated text file is offered
for saving or opening in the resulting dialogue.
DGA Tool
DGA Tool
Use the DGA tools to enter the values obtained from a conventional analysis of harmful
gases in the appropriate fields.
If the MS 3000 is equipped with a gas sensor, the online harmful gas values are loaded by
activating the Load Online Data button. The displayed values can be saved via the Save DGA
button. In the display dialogue window, a name for the current measurement can be
specified; however we recommend that you specify the time stamp of the measurement.
By activating the Save button the data from the analysis of harmful gases will be saved with
a specified designation.
To load a saved measurement, in the DGA Tool window, you must click the Load button. This
will open the following dialogue:
Load a DGA
Comment: When a DGA is saved, the website must be updated so that the appropriate
time span or the designation can be displayed the next time the Load window is opened.
Activate the Results button in the DGA Tool window to display the results of the following
gas-in-oil diagnostic methods:
• MSS method
• Doernenburg method
• Rogers method
• Duval method
• Duval triangle
The Duval triangle shows the last saved DGA values. The position of the point that describes
the gas condition is shown by three white lines. Use the dropdown menu in the upper right
corner to go to the historical view, to see the trend of the values. Here the recorded points
are connected by a black line.
Detailed information about the resources and the software condition of the MS 3000
Monitoring System is displayed in this window.
System resources
System resources
Commissioning:
This is where the date when the monitoring system was commissioned is entered.
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 121 of 151
I/O modules:
The system shows which type of I/O module (Profibus DP) is used here.
Operating system:
The system shows which operating system (QNX 6.3) is used here.
Processor:
The system shows which processor (Intel ® Atom N270 1.6 GHz) is used here
Network:
Information concerning the network used is displayed here.
System status
System time:
The actual time and date of the system are displayed here. This information is used for the
time stamp of the alarm and warning messages.
A fault has been detected in the calculation server. This server is responsible for all
calculations executed by the MS 3000. The calculation server has stopped. Currently no
calculations are being executed.
• Fault (damaged historical file has been found)
The fault has been detected in the data memory. A new database will be created; data will
be saved in the new database from this point in time. Data access is only possible for data in
the new database.
• Fault (HDD storage space rate)
The hard disk storage space is being reduced at an unusual speed. The cause could be an
increased number of recorded events, such as a fan switching on and off due to defective or
bouncing contacts.
• Profibus error (time)
A Profibus error has been detected. The Profibus communication has been interrupted. New
time stamps and actual values are not displayed.
• Profibus error (value)
A Profibus error has been detected. New time stamps are displayed, but no actual values are
displayed.
Communication status
The process variables configured in the MS 3000 and their alarm thresholds can be displayed
as a table.
PV Table
Update
The button Update can be used to update the view.
Selection
The button Selection can be used to select process variables (PV). After clicking the button, a
selection dialogue appears. In the PV tree, the interesting values can be added to the
selection or removed from it.
Profiles can be set up to avoid repeated manual selection of the same values. The currently
selected process variables are saved in a profile, so that the entire selection can be loaded
again later.
To save a profile, select the process variable and then enter the profile name into the
corresponding field, and push the button Save.
Save profile
To load a saved profile, the corresponding entry in the profile list must be selected and the
button Load must be pushed.
Load profile
To rename a profile, the corresponding entry in the profile list must be selected and the new
name entered in the input field; then the button Rename must be pushed.
Edit profile
Delete Profile
The current values of the process variables configured in the MS 3000 can be displayed as a
table.
Multimonitor
Browse
The button Page up / page down moves the view by one table page in the respective
direction.
Setting cursor
The button Setting cursor can be used to specify the first process variable to be displayed.
The number of the process variable is to be entered in the appearing dialogue for this.
Search
The button Search can be used to specify the short designation or part of the short
designation of the interesting process variables. The designation of the process variable is to
be entered in the appearing dialogue. All process variables that this input applies to are
displayed in the table.
The *-operator can be used to show any character sequence and combine it with other
characters (e.g. < Ambient_Temp* > to display all recorded ambient temperature values).
The members of the supervisor group (group 1) have the right to set up further users,
remove them or specify the access password.
User administration
To set up a new user, the user name must be entered in the respective field, the group
assignment chosen with the corresponding group assignment menu and the button New
User must be pushed. The added user name appears in the user list.
After all new users have been set up, the configuration must be transferred with the button
Save.
To assign a password to a user, the respective user name must be chosen in the user list, the
password entered in the corresponding field and the button Set password must be pushed.
A user can be removed from the user list again. For this, select the corresponding user name
and push the button Delete. Then the configuration must be accepted by pushing the button
Save.
If users are added to the user list or removed from it, and the new configuration has not
been saved yet, the currently active configuration in the system can be displayed with the
button Load in the current user list.
Software
Fault Cause Solution
Ensure that the address in the browser is correct. It must agree
Wrong IP address with the IP address of the MS 3000 server.
(e.g. http://10.53.54.185)
Check the connection to the server
Click on: Start --> run
Enter cmd and click OK
Enter "ping [server IP address]“ and confirm with ENTER (e.g.
"ping 10.53.54.185" [ENTER])
If the connection is in order, this output will be displayed:
Visualisation is
not displayed If the connection is not in order, the following will be displayed:
Network fault
If the time stamp of the unrealistic value is current, the value may
either have been falsified by a sensor fault, or if a calculated value
is involved, the calculation can be falsified due to defective input
values, which in turn are attributed to sensor faults.
In this case check the appropriate hardware (see Hardware or
Sensor Part in this table).
For a more extensive analysis it is quite helpful to have
screenshots of all available pages of the tool "MultiMonitor" in
the visualisation under the "System Data" header.
Bus error
If there are bus errors the coupler should signal this fact via a flash code on
the LEDs, "BF", "DIA" or "I/O ERROR". As a rule the flash codes consist of 2
parts that are separated by a pause in the flash sequence. The coupler
characterises the beginning or the end of a complete sequence by a "high
frequency flashing phase" that lasts 1-2 seconds. On the other hand, the
actual sequence is output with flashes at approx. one second intervals. These
flash codes are required to analyze the type of error, and they must be
reported to the GE - Monitoring Systems Competence Center. For short-term
correction of the problem you can attempt to restart the coupler through
reinitialisation (briefly switching off the supply voltage by activating the fuse
in the cabinet for approx. 10s). If the IED is installed in the same cabinet, the
coupler should be reset by briefly disconnecting the 24V feed!
Digital inputs are read in via appropriate terminals and in most cases are wired
Digital input
with floating contacts (KL1104, KL1408)
Current signals
(4-20mA or 0-20mA)
In either case the ERROR LED is only illuminated if a signal greater than 20mA
is applied on the input.
To measure the effective value of the load currents, type MU-J1/s current converters
are used.
Current
measurement
The converter converts the input signal into a current of 0 to 20 mA, which in turn is
detected via analogue input terminals (KL3042, KL3044).
Note:
This information applies for troubleshooting on the input (terminal 1 and 3) of the current
transformer! For the output side (terminal 13 and 14 0 to 20 mA) proceed as described under
troubleshooting for mA signals in the hardware portion of this table.
To protect the CTs, frequently short-circuit bridges are used
in the current circuit in the control cabinets. Usually these are
Short-circuit bridges located in the transformer cabinet and in the monitoring
cabinet. If one of these bridges is still closed, the
No current measurement signal is dissipated via this bridge.
If all short-circuit bridges are removed and there is still no
Cable break or wiring signal, we recommend measuring the current on the input
problem side with a clip-on ammeter.
Voltage The voltage is measured on the measurement connections of the bushings. A peak
measurement sampler is used as a measuring transducer
that converts the input voltage from approx. 20-57V AC into a current signal. See the
appropriate sections of this manual for more detailed information.
Alternatively 0/4 to 20 mA signal
Wrong display Scaling Due to incorrect scaling of the input signal in the software, a
(stable value) faulty display can occur in the system.
No display No supply voltage on Measure the 24V supply of the peak sampler between the 0V
the peak sampler and 24V connections. If it is not present establish the voltage.
Scaling Due to incorrect scaling of the input signal of the software, it
may be the case that the scaled value is under 50% of the rated
voltage and thus is hidden.
Wire break Check the output side of the peak sampler as described in the
instructions "mA signals" in the hardware portion of this table.
(PV 180 181 182 in the monitor)
1. Resistor wheel
Here a resistor wheel is used that is placed on the shaft of the tap changer. This signal
is recorded by a specially configured PT100 terminal (KL3202). The corresponding
channel of the terminal is marked with a black box in this process.
Since the resistor wheel involves a two-conductor circuit the two + contacts of the
Beckhoff terminal are directly bridged.
See the Temperatures section in the hardware portion of this table for the further
procedure.
2. BCD code
Here the tap changer position is transferred from the tap changer via a BCD signal and
it is detected in the monitoring system via a digital input terminal (KL1408). In this
process 6 digital inputs are used (1, 2, 4, 8, 10, 20) to show the position in BCD code.
(See digital input in the hardware portion of this table)
3. mA signal
From the tap changer, or the control and protection technology, a current signal (e.g.4
to 20mA) is made available that depicts the position of the tap changer (e.g. tap 1-29).
(See mA signals in the hardware portion of this table)
Tap changer The power consumption of the motor is measured via a power converter
power (Adamczewski AD-LU 410 GA), which converts the power consumption of the motor
consumption into a linear current signal (0 to 2kW -> 0 to 20 mA). This signal is then read in via an
analogue input terminal (KL3042, KL3044) and digitalized. The power converter is
mounted in the tap changer cabinet.
Wrong values Scaling Check the output and range information on the power
converter.
Normally the following are assumed as standard values:
Output: 0-20mA
Range: 0-2 kW
No display Wire break Check wiring and lines
No supply voltage on Measure the supply voltage of the converter between 14 and
the power converter 15. If it is not present, establish the supply voltage.
Error on the output The signal is transferred through a current from connections 1
and 2.
(See mA signals in the hardware portion of this table)
Fan controller The fan controller switches the available fans (groups) in or out depending on
temperature. For configuration of the controller, a start temperature for switching-in
MS-001 – MS 3000 Manual – Rev X.0 9-Oct-18 Page 141 of 151
the 1st fan as well as a temperature increment, according to which an additional fan
will be switched in, can be specified. Fans are switched in or out with due consideration
of the operating hours of the individual fans. Overlaid temperature regulation means
that the fan controller still has load-dependent regulation; and the entire cooling
capacity is switched in when reaching a specifiable load on the transformer, in order
to slow the heating of the transformer and thus create possibly required time reserves.
Fan always on or Overlap of the If a conventional controller is still present on the transformer
always off conventional and is not deactivated, under certain circumstances
controller influencing can occur, if the conventional controller executes
switch operations and thus disturbs the fan controller. In this
case a message is generated for the affected fan that states
that this fan cannot be switched in or out. Digital inputs of the
fans are active, although the associated controller output is
inactive!
Manual control If there is a discrepancy between the digital output signal of
the controller and the associated fan, it may be the case that
manual control is active and the fans cannot be controlled by
the MS 3000.
Wire break in the If there is a discrepancy between the digital output signal of
controller or the controller and the associated fan, the wiring must be
defective contactor checked. If no error can be found there, it may be the case that
the contactor is defective.
Wrong limit value set The parameters cited in the general function description of the
controller must correspond to the real temperature level of
the transformer and the performance capacity of the cooling
unit, if this is not the case the result will be either continuous
operation of all fans or the fans will remain completely
switched off.
Switch through of Wire break in the For example, if the feedback of the switch states of the fans to
the fans feedback the controller is disturbed through cable break, the controller
tries to find a functioning fan cyclically at 2 minute intervals
through switching in. This is perceived from outside as cyclic
switch of the fans. In this case, the digital outputs are
completely inactive, although control outputs are activated.
PD measurement A SPECmonitor is used for the PD measurement. The PD signals are uncoupled in the
voltage sensor and supplied to the device via a signal adaptation unit. In the signal
adaptation unit the signals are processed and relayed to the MS 3000 via an RS232
interface.
No Wrong wiring Only 2 data lines and GND are used, this means there is a 50/50
communication chance.
Error in the driver When calling the driver the correct device code must be
(call) entered in the FC46icmMon.ini. The file is located in the driver
directory.
No display / only Incorrect setting on There are different settings on the SPECmonitor to adjust the
noise the SPECmonitor level of the display. If, for example, amplification is selected
too low only the background noise will be displayed.
Additional setting possibilities are described in the sensor
manual
Unrealistic values PD activity in the Values that are higher than usual can be an indication of
transformer beginning PD activity in the transformer. Here primarily the
phase-resolved PD pattern and the long-term trend must be
referenced for the evaluation.
Risk of injury! Only change the filter mat while the fan rotor is stationary.
Never insert your fingers into the fan rotor.
To insert or replace the filter, proceed as follows (direction of airflow: drawing from outside
and blowing into the enclosure):
• First press the catch of the louvred grill (Logo) up slightly with one finger (see figure)
• Once it is released, the louvred grille can be dropped open by approx. 70° or 90°
• If necessary, first place the fine filter mat into the housing
• Ensure that the open (roughened) side faces towards the louvred grille
• Then insert the enclosed standard filtermat
• Here again, ensure that the open side (without Logo) faces towards the louvred grille
(see figure)
• Now push the louvred grille back onto the enclosure until it snaps audibly into
position
• Loosen the four captive screws on the IPC’s cover and remove it.
Removed cover
Use of a different type of battery than that specified here may present a risk of fire
or explosion!
Battery may explode if mistreated. Do not recharge, disassemble, heat above 100°C
or incinerate!
• Install the new battery in the retaining clip with the positive (+) side up.
• Replace the front panel on the IPC and tighten the four screws to secure it.
• Check for oil leaks. Clean and seal if necessary. Attention: See the
documentation of the sensor used for proper handling and installation.
• Check for water or dust accumulation within the system. Clean and repair if
necessary.
• The visual inspection includes the following parts / sensors of the system:
• Monitoring Server
• Monitoring module
• Oil temperature
• Ambient temperature
• Load current
• Voltage
• Oil level in the case of the transformer and of the tap changer