P+F Mux
P+F Mux
P+F Mux
MANUAL
TEMPERATURE MULTI
INPUT DEVICE
TM-I
TEMPERATUR MULIT INPUT DEVICE
With regard to the supply of products, the current issue of the following document is appli-
cable: The General Terms of Delivery for Products and Services of the Electrical Industry,
published by the Central Association of the Electrical Industry (Zentralverband Elektrotech-
nik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary
clause: "Expanded reservation of proprietorship"
Temperature Multi Input Device
3 Introduction .............................................................................................. 4
5 Installation .............................................................................................. 18
5.1 Electrical Connection ........................................................................................... 18
5.1.1 Sensors .................................................................................................................. 18
5.1.2 Fieldbus and Shield Connection ............................................................................. 18
5.2 DIP Switches ......................................................................................................... 18
6 Configuration .......................................................................................... 19
6.1 Introduction ........................................................................................................... 19
6.2 Block Interaction and Channel Mapping ............................................................ 19
6.3 Identification, Device ID, PD Tag ......................................................................... 20
6.4 Getting Started ...................................................................................................... 20
6.5 Sensor Block Configuration ................................................................................ 21
6.5.1 Measurement Data Flow ......................................................................................... 21
6.5.2 Sensor Type ........................................................................................................... 22
6.5.3 Sensor Wiring and Wire Resistance ....................................................................... 22
6.5.4 Measurement Unit .................................................................................................. 22
6.5.5 Filtering ................................................................................................................... 22
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 1
Temperature Multi Input Device
7 Operation ................................................................................................ 26
7.1 Primary Value Status ............................................................................................ 26
7.2 Body Temperature Status .................................................................................... 26
7.3 Device Self-diagnosis ........................................................................................... 26
7.4 Alarms .................................................................................................................... 26
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
2 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
ISO9001
2 Symbols used
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 3
Temperature Multi Input Device
3 Introduction
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
4 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
4 Instruction Manual
These instructions apply in conjunction with the respective data sheets and EC-type-
examination certificate. You can access the documents at www.pepperl-fuchs.com.
The 8 channel TM-I Device transfers signals from resistance temperature measuring
sensors (RTD’s), thermocouples, resistance and millivolt signals via FOUNDATION
Fieldbus. Each channel could be configured independently.
The TM-I Device can be used for FOUNDATION Fieldbus H1 bus that use the phys-
ical layout in accordance with IEC 61158-2/ISA-S50.02-1992.
The TM-I Device may be installed in category 2G (Zone 1) or category 3G (Zone 2)
of a hazardous area.
For category 2G (Zone 1) applications the type of protection is "Intrinsic Safety". The
associated field devices could operate in a category 1G (Zone 0) or category 1D
(Zone 20) location.
For category 3G (Zone 2) applications the type of protection is EEx nA. The TM-I De-
vice could be connected to non-intrinsically safe H1 segment. Independent of the type
of protection of the H1 bus the inputs remains intrinsically safe.
The EC-Type Examination certificate and the data sheet are considered as an integral
part of this instruction manual. The data sheet contains the electrical data of the EC-
Type Examination certificate.
TM-I Devices that are operated in general electrical systems must not
thereafter be operated in electrical systems that are connected in haz-
ardous areas.
Laws and/or regulations governing the use or intended usage goal must be observed.
TM-I Devices are only approved for proper professional usage in accordance with the
intended purposes. Improper handling will void any claim made under the warranty
and any manufacturer's liability.
Protection of operating personnel and the system is not ensured if the
module is not used in accordance with its intended purpose.
The device can only be operated by trained professionals in accordance with the
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 5
Temperature Multi Input Device
4.2 Marking
For the ambient temperature range, please refer to the respective data sheet.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
6 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 7
Temperature Multi Input Device
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
8 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 9
Temperature Multi Input Device
If a F2D0-TI-Ex8.FF.*:* with external connectors for the H1 bus mounted at the hous-
ing is in use, these connectors are allowed to be connected or disconnected only if
the H1 bus segment is not powered.
Only intrinsically safe analogue input circuits must be carried in Zone 1 or Zone 2 de-
pending on the ignition protection class.
Sensors mounted in a category 1D (Zone 20) or 2D (Zone 21) location
When using intrinsically safe analogue input circuits in the Dust Ex Area 'D' only ap-
propriate certificated field devices must be connected.
4.5.3 Use as Intrinsically Safe Apparatus
The current supply circuit in category 2G (Zone 1) must be intrinsically safe ia or ib.
The current supply circuit in category 3G (Zone 2) must be intrinsically safe ia, ib or ic.
Only intrinsically safe analogue input current circuits must be carried in Zone 0 or
Zone 1 depending on ignition protection class.
When using intrinsically safe analogue input circuits in the Dust Ex Area 'D' only ap-
propriate certificated field devices must be connected.
For interconnection of intrinsically safe field devices with the TM-I device take into ac-
count the respective maximum values in the sense of explosion protection (proof of
intrinsically safety).
4.5.4 Use as Associated Apparatus
Only intrinsically safe analogue input current circuits must be carried in Zone 0, Zone
1 or Zone 2 depending on ignition protection class.
When using intrinsically safe analogue input circuits in the Dust Ex Area 'D' only ap-
propriate certificated field devices must be connected.
For interconnection of intrinsically safe field devices with the TM-I device take into ac-
count the respective maximum values in the sense of explosion protection (proof of
intrinsically safety).
4.5.5 Use as non-arcing Apparatus "nA"
Only devices which are suitable for use in hazardous areas, category 3G (Zone 2) and
for the conditions at the place of installation must be installed in category 3G (Zone 2;
see declaration of conformity or statement of conformity)
Only intrinsically safe analogue input current circuits must be carried in Zone 0, Zone
1 or Zone 2 depending on ignition protection class.
When using intrinsically safe analogue input circuits in the Dust Ex Area 'D' only ap-
propriate certificated field devices must be connected.
11/2008 132328
For interconnection of intrinsically safe field devices with the TM-I device take into ac-
count the respective maximum values in the sense of explosion protection (proof of
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
10 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
intrinsically safety).
In Zone 2 the connection and disconnection of the internal terminal connectors as well
as the closing of circuits while the power is on is only permissible for reasons of in-
stallation, maintenance or repair.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 11
Temperature Multi Input Device
CH5
CH7
CH1
Bus
CH2
CH4
CH6
CH8
100
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
12 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Only permanently laid cables and lines must be inserted into the cable glands. For the
permissible cable diameters, please refer to the respective data sheet. The operator
must provide an appropriate strain-relief clamp (for example with a suitable cable
clamp). The mounting notes in chapter 4.4.1 must be observed.
258
228
84
9.5
240
for fixing
with screws
(57)
CH3
CH5
CH7
CH1
Bus
M6
CH2
CH4
CH6
CH8
114
X
Earthing point
For examples of stop plugs and screw plugs, please refer to the respective data
sheets.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 13
Temperature Multi Input Device
this purpose. The connection must be designed to prevent lossening and must be pro-
tected against corrosion. Protection against corrosion can also be achieved by using
tinned cable plates, for example
Before closing the cover, a visual inspection must be performed to ensure that there
are no visible signs of damage on the cover seal. In the event of damage, the seal
must be replaced by an original seal.
The screws on the cover should be tightened with a torque of 2.5 Nm.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
14 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Step 3
11/2008 132328
Step 4
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 15
Temperature Multi Input Device
3 to 4 mm
Step 4
Step 5
11/2008 132328
Step 6
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
16 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
• in case of using the R version connected internally to the DIN rail. The DIN rail
should be connected to the cabinet and the cabinet should be connected to the po-
tential equalization.
Depending on this the shield is automatically connected to the potential equalization.
The transmission behavior of the TM-I Device is stable even over long periods of time.
There is thus no need for regular adjustments or similar tasks. Maintenance is there-
fore not required.
TM-I Devices that are operated in connection with hazardous areas must not be mod-
ified. If there is a defect, the TM-I Device must always be replaced.
Defective housing parts (for example cover seals) must be replaced only by original
parts. For detailed information please refer to the respective data sheet.
Tasks for eliminating malfunctions must only be performed by specialists who are
specially trained and authorized for the task.
4.10 Disposal
Disposal of the packaging and TM-I Device must only take place in accordance with
the requirements of the country in which the TM-I Device is installed.
The TM-I Device does not contain any batteries that must be disposed of separately
from the TM-I Device.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 17
Temperature Multi Input Device
5 Installation
5.1.1 Sensors
Five types of sensors can be connected to each channel according to the following
scheme:
+ -
H L
RTD, 2-wire mV Millivolt
technology
+ L -
RTD, 3-wire
H L
technology Thermocouple
+ H L -
RTD, 4-wire
technology
The device has eight DIP switches. Only DIP switch 1 and 2 are in use:
DIP Switches
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
18 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
6 Configuration
6.1 Introduction
The Pepperl+Fuchs Temperature Multi Input Device contains a resource block (like
any FOUNDATION Fieldbus Device), 9 transducer blocks (8 sensor and one concen-
trator block) and 9 standard FOUNDATION Fieldbus function blocks (8 AI and one
MAI block).
The sensor transducer blocks provide connection to the sensor hardware and the
possibility to configure the eight temperature sensors that can be connected to the de-
vice.
The concentrator transducer block provides convenient access to the most impor-
tant configuration options of all sensors as well as Device Description (DD) methods
for easy configuration of the device. This will increase the productivity at configuration
time. Additionally, it provides the device's body temperature and EMC filter settings.
It allows to view the values and diagnostics information of all channels at the same
time.
The Analog Input (AI) blocks are conform to the FOUNDATION Fieldbus specifica-
tion and can be used to build a FOUNDATION Fieldbus application and provides tem-
perature/voltage/resistance value depends on the configuration.
The Multiple Analog Input (MAI) block is conform to the FOUNDATION Fieldbus
specification and provides all eight sensor values in one block. Limits handling and
alarms are not implemented in this block. Also, the block consumes only one execu-
tion time so the FOUNDATION Fieldbus schedule time can be reduced. This block is
convenient if e.g. the device is used for monitoring purposes because it is very easy
to project and do not require configuration. Additionally, there is only one block to con-
figure instead of 8.
Transducer blocks provide a measurement value to AI and MAI blocks. The connec-
tion between the blocks is configured via the „Channel“ parameter of the AI block
which chooses the sensor block to get the process data from.
10 Body temperature AI
Table 6.1: Channel Mapping
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 19
Temperature Multi Input Device
AI
MAI block
block
1-8
Each FOUNDATION Fieldbus device has a unique device ID. The Pepperl+Fuchs
TM-I Device device ID is structured as follows:
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
20 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 21
Temperature Multi Input Device
RTD_2_WIRE_OFFSET
CJC_SELECT
CONSTANT_CJC
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
22 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
happened:
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 23
Temperature Multi Input Device
The concentrator block provides a summary view for the most important sensor con-
figuration parameters of each sensor block. These parameters are simply mapped to
their corresponding counterparts in the sensor blocks. The write protection of the pa-
rameters depends on the sensor block's target block mode.
6.6.1 Body Temperature
The device's body temperature can be read from the "Body Temperature" parameter.
It is possible to configure the temperature unit via the "Body Temperature Unit" pa-
rameter.
11/2008 132328
Please note that it is possible to map body temperature to an AI block (see chapter
6.2).
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
24 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
The AI and MAI blocks are standard FOUNDATION Fieldbus block types. Please re-
fer to the FOUNDATION Fieldbus standard for configuration information. The channel
map can be found in chapter 6.2.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 25
Temperature Multi Input Device
7 Operation
The primary value of the sensor blocks can have the following status:
• Good (NC)-Non specific
• Good (NC)-Active Block Alarm
• Good (NC)-Unacknowledged Block Alarm
• Bad-Sensor Failure: The sensor value exceeds the values defined by Primary Val-
ue. A sensor range or sensor error (wiring error, lead breakage) is detected for the
sensor inputs. The substatus "Hi-limited" or "Low-limited" define in which direction
the sensor's range has been exceeded. The substatus "Not limited" indicates a
sensor error.
• Bad-Device Error: The internal diagnosis of the device detected a hardware fault.
• Bad-OOS: The actual mode of the block is OOS
The body temperature status in the Concentrator block is BAD if the block is in OOS
mode. In AUTO mode, the value is always GOOD as long as there is no self-diagnosis
error detected.
The Pepperl+Fuchs TM-I Device continuously monitors its internal hardware and
body temperature. If an error occurs, the status of all Primary Values switches over to
BAD and the "Device needs maintenance now" bit in the "BLOCK_ERR" error param-
eter of the resource block is set which will generate an alarm.
7.4 Alarms
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
26 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
If the control system does not support alarms, the option "Reports" in
the "FEATURES_SEL" parameter of the resource block should be
deactivated.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 27
Temperature Multi Input Device
The Temperature Multiplexer provides 8 sensor input specific red LEDs to indicate the
status of the related sensor input channels. The status of the bus power is provided
by a green LED, the communication status by a red LED. The LEDs are located on
the upper side of the device.
LED COM ERR
Sensor specific LEDs LED PWR
transducer block
Table 8.1: LED indications
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
28 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Problem Remedy
Parameter Message Cause Procedure
BLOCK_ERR Lost Static Data The parameterization Repeat parameteri-
data stored in the zation. If this error
device were faulty and occurs repeatedly,
replaced by default send the device to
settings Pepperl+Fuchs for
repair
Device needs Hardware error Send device to
Maintenance Pepperl+Fuchs for
now repair
Simulate active Simulation allowed by Check whether
setting the switch 1 simulation shall be
allowed
OOS The target mode of Set block to "Auto"
the block is OOS mode
RS_STATE Online No error -
Stand-by The target mode of Set block into
the block is OOS "Auto" mode
Table 8.2: Resource Block Errors
Problem Remedy
Parameter Message Cause Procedure
BLOCK_ERR Block Confi- • "Sensor Type" is set to Correct parameteriza-
guration Error "Undefined" tion
• "Sensor Range.Unit" is
set to a value not sup-
ported by sensor (e.g.
"mV" for a resistance
based sensor)
• User calibration is
turned on at "Calibration
Mode", but "Calibration
State" shows no valid
user calibration exists
Input failure Several see Table 8.4: Com-
mon Sensor Block
Problems below
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 29
Temperature Multi Input Device
Problem Remedy
Transducer Configuration See above at See above at
Error Error "BLOCK_ERR" "BLOCK_ERR"
(XD_ERROR) I/O failure The sensor value exceeds see Table 8.4: Com-
the HI or LO sensor limits mon Sensor Block
Problems below
Lead Brea- Sensor wiring fault see Table 8.4: Com-
kage / Sen- mon Sensor Block
sor Problems below
connection
error
Sensor Status Sensor con- See "Transducer Error See "Transducer
nection error Error"
Overrange Sensor high measurement see Table 8.4: Com-
limit exceeded mon Sensor Block
Problems below
Underrange Sensor low measurement see Table 8.4: Com-
limit exceeded mon Sensor Block
Problems below
Table 8.3: Sensor Block Errors
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
30 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Problem Remedy
Cause Procedure
Block does not leave A configuration error is Clear configuration error
OOS mode reported cause. See above
Resource block is in OOS Set Resource block to
mode AUTO mode
Sensor failure Sensor error (Overrange, • Check wiring
underrange, leadbreakage) • Use sensor with a greater
input range
Wrong sensor type selected Configure correct sensor
type
RTD3 / RTD4 wires mixed Check cabling, see chapter
up 5.1.1
Wrong measurement Thermocouple polarity Check thermocouple pola-
values reversed rity
Unable to write to Write protection is enabled Set write protection DIP
parameters switch to OFF. see chapter
5.2
Block is in AUTO mode Set "MODE_BLK.Target" to
"OOS"
Table 8.4: Common Sensor Block Problems
Problem Remedy
Parameter Message Cause Procedure
BLOCK_ERR Body tempera- Devices' body • Choose another mount-
ture out of range temperature is too ing location
high / too low • Adjust mounting loca-
tions' ambient tempera-
ture
OOS The target mode Set block to "Auto" mode
of the block is
OOS
Transducer Body tempera- See See "BLOCK_ERR"
error ture out of range "BLOCK_ERR
(XD_ERROR
)
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 31
Temperature Multi Input Device
Problem Remedy
Cause Procedure
Block does not Resource block is in OOS Set Resource block to AUTO
leave OOS mode mode mode
Unable to write to Write protection is enabled Set write protection DIP
parameters switch to OFF (see chapter
5.2)
Corresponding sensor block Set sensor block to OOS
is in AUTO mode mode
Block is in AUTO mode Set "MODE_BLK.Target" to
"OOS"
Table 8.6: Common Concentrator Problems
Problem Remedy
Parameter Message Cause Procedure
The channel parameter Set valid value (see
contains an invalid chapter 6.2).
value.
Block Configu- The function block does Include block into appli-
ration Error not have a schedule cation and download
downloaded schedule to device
"L_TYPE" parameter is Set "L_TYPE" to cor-
set to an incorrect value rect value
BLOCK_ERR
Transducer block Check transducer block
Input failure reports BAD "Primary diagnostics (see Table
Value.Status" 8.3)
Simulation for block is Check simulation acti-
Simulate active
activated vation
Actual block mode is Choose suitable target
Out-of-service OOS mode·Check block con-
figuration
Table 8.7: AI Function Block Errors
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
32 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Problem Remedy
Cause Procedure
Function block does not A "BLOCK_ERR" is repor- Clear block error cause
leave OOS mode ted
The function block does Include block into applica-
not have a schedule down- tion and download sche-
loaded dule to device
Resource block is in OOS Set Resource block to
mode AUTO mode
Simulation does not acti- Simulation DIP switch set Set simulation DIP switch
vate to OFF to ON (see chapter 5.2).
Unable to write to para- Write protection is enabled Set write protection DIP
meters switch to OFF (see chapter
5.2).
Block is in AUTO mode Set "MODE_BLK.Target" to
"OOS"
Table 8.8: Common AI Block Problems
Problem Remedy
Parameter Message Cause Procedure
BLOCK_ERR Block Configu- The channel parame- Set valid value (see
rationError ter contains an invalid chapter 6.2)
value.
The function block Include block into appli-
does not have a sched- cation and download to
ule downloaded device
Table 8.9: MAI Function Block Errors
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 33
Temperature Multi Input Device
Problem Remedy
Cause Procedure
A "BLOCK_ERR" is repor- Clear block error cause. See above
ted
Function block Resource block is in OOS Set Resource block to AUTO mode
does not leave mode
OOS mode The function block does Include block into application and
not have a schedule download schedule to device
downloaded
Write protection is Set write protection DIP switch to
Unable to write to
enabled OFF (see chapter 5.2).
parameters
Block is in AUTO mode Set "MODE_BLK.Target" to "OOS"
Table 8.10: Common MAI Problems
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
34 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
The following chapter shows a summary of the diagnostic features the TM-I Device
will provide and the way they are reported.
Diagnostic Alarm Description Alarm indication
Communication H1 segment communication is not LED
Failure established
The device configuration data RB Alarm, RB
EEPROM Failure
base is corrupted BLOCK_ERR
Program Storage The devices firmware is corrupted LED
Failure
The memory inside the device is LED
Memory Failure
defective
Body Temperature The body temperature of the RB Alarm, Concentrator
too high/low device exceeds it's specification BLOCK_ERR
Resource Block is in The actual mode of the RB is OOS RB Alarm, RB
Out of Service Mode BLOCK_ERR
The actual mode of the block is Block Alarm,
Block is in Out of OOS. BLOCK_ERR
Service Mode This is the same for all function
and transducer blocks
One or more parameters of the Block Alarm,
Block Configuration block contain invalid or conflicting BLOCK_ERR
Error values. This is the same for all
function and transducer blocks.
Sensor error (wiring, A cable of the sensor is broken, Block Alarm,
lead break) incorrect sensor wiring. BLOCK_ERR of all TBs
Sensor Over / Measured sensor value exceeds Block Alarm,
Under Range its high or low range limit. BLOCK_ERR of all TBs
The Simulation is enabled for a Block Alarm,
Simulation active
function block. BLOCK_ERR of all FBs
The device detected an internal Block Alarm,
Device HW Failure
HW failure at the measurement BLOCK_ERR of RB,
(ADC, CJC mea-
unit. status of affected val-
surement etc.)
ues, LED
Table 8.11: Device diagnostic summary
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 35
Temperature Multi Input Device
9 Block Descriptions
Rel.
Parameter Description
Index
01 ST_REV The revision level of the static data associated with the resource block.
The revision value will be incremented each time a static parameter value
in the block is changed.
02 TAG_DESC The user description of the intended application of the block.
03 STRATEGY The strategy field can be used to identify grouping of blocks. This data is
not checked or processed by the block.
04 ALERT_KEY The identification number of the plant unit. This information may be used
in the host for sorting alarms, etc.
05 MODE_BLK The actual, target, permitted, and normal modes of the block:·
• Target: The mode to "go to"
• Actual: The mode the "block is currently in"
• Permitted: Allowed modes that target may take on
• Normal: Most common mode for actual
06 BLOCK_ERR This parameter reflects the error status associated with the hardware or
software components associated with a block. It is a bit string so that mul-
tiple errors may be shown.
Supported values:·
• Simulate Active: Hardware switch is set to simulation possible
• Lost Static Data: The database used for storing the NV parameters
within the device is corrupt
• Device Needs Maintenance Now: The hardware of the device failed in
some way (e.g. body temperature too high)
• Out Of Service: The RB is in Mode OOS
07 RS_STATE State of the resource block application state machine.
08 TEST_RW Read/Write test parameter. Used only for conformance testing.
09 DD_RESOURCE String identifying the tag of the resource that contains the device descrip-
tion for this resource.
10 MANUFAC_ID Manufacturer identification number - used by an interface device to locate
the DD file for the resource.
Pepperl+Fuchs ID is 0x502B46.
11 DEV_TYPE Manufacturer's model number associated with the resource - used by
interface devices to locate the DD file for the resource. The P+F TI Mux is
device type 3.
12 DEV_REV Manufacturer revision number associated with the resource - used by an
interface device to locate the DD file for the resource.
13 DD_REV Revision of the DD associated with the resource - used by an interface
device to locate the DD file for the resource.
14 GRANT_DENY Options for controlling access of host computers and local control panels
to operating, tuning, and alarm parameters of the block.
15 HARD_TYPES The types of hardware available as channel numbers. Only scalar types
are supported.
16 RESART Allows a manual restart to be initiated. Several degrees of restart are pos-
sible:
1. Run - nominal state when not restarting
2. Restart resource - not used
3. Restart with defaults - set parameters to default values
4. Restart processor - does a warm restart of CPU
17 FEATURES Used to show supported resource block options.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
36 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Rel.
Parameter Description
Index
18 FEATURES_SEL Used to select resource block options.
Supported values:
• Unicode: Tells host to use Unicode for string values
• Reports: Enables alarms, must be set for alarming to work
• Hardware Lock: Hardware write locking enabled but not active.
WRITE_LOCK follows the status of the security switch
19 CYCLE_TYPE Identifies the block execution methods available for this resource.
Supported values:
• Schedule
• Completion of Block execution
20 CYCLE_SEL Used to select the block execution method for this resource.
Supported values:
• Scheduled: Blocks are only executed based on the schedule in
FB_START_LIST.
• Block Execution: A block may be executed by linking to another blocks
completion.
21 MIN_CYCLE_T Time duration of the shortest cycle interval of which the resource is capa-
ble.The Pepperl+Fuchs TM-I Device supports 100 ms.
22 MEMORY_SIZE Available configuration memory in the empty resource.
23 NV_CYCLE_T Interval between writing copies of NV parameters to non-volatile memory.
Zero means none.
24 FREE_SPACE Percent of memory available for further configuration. Not supported by
Pepperl+Fuchs TM-I Device.
25 FREE_TIME Percent of the block processing time that is free to process additional
blocks. Not supported by
Pepperl+Fuchs TM-I Device.
26 SHED_RCAS Time duration at which to give up on computer writes to function block
RCas locations.
27 SHED_ROUT Time duration at which to give up on computer writes to function block
ROut locations.
28 FAULT_STATE ondition set by loss of communication to an output block, failure promoted
to an output block or a physical contact. When a fault state condition is
set, the output function blocks will perform their FSTATE actions. The P+F
TI Mux does not support output blocks.
29 SET_FSTATE Allows the fault state condition to be manually initialed by selecting Set.
The P+F TI Mux does not support this function.
30 CLR_FSTATE Writing a Clear to this parameter will clear the device fault state if any field
condition has cleared. The P+F TI Mux does not support this function.
31 MAX_NOTIFY Maximum number of unconfirmed alert notifications messages possible.
This number cannot be changed. The P+F TI Mux supports a maximum of
42.
32 LIM_NOTUIFY Maximum number of unconfirmed alert notification messages allowed.
P+F TI Mux supports a maximum of 42.
33 CONTIRM_TIME The minimum time between retries of alert reports. Retries shall not hap-
pen when parameter is set to 0.
34 WRITE_LOCK If set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
35 UPDATE_EVT This alert is generated by any change to the static data.
36 BLOCL_ALM The block alarm is used for all configuration, hardware, connection failure
or system problems in the block. The cause of the alert is entered in the
subcode field. The first alert to become active will set the Active status in
the ALARM_STATE subcode.
37 ALARM_SUM The current alert status, unacknowledged states, unreported states, and
disabled states of the alarms associated with the function block.
38 ACK_OPTION Selection of whether alarms associated with the function block will be
11/2008 132328
automatically acknowledged.
39 WRITE_PRI Priority of the alarm generated by clearing the write lock.
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 37
Temperature Multi Input Device
Rel.
Parameter Description
Index
40 WRITE_ALM This alert is generated if the write lock parameter is cleared.
41 ITK_VER Major revision number of the Interoperability Test Case used to register
the device with the Fieldbus FOUNDATION.
42 SERIAL_NUM Unit specific serial number to identify production and release information.
Set by manufacturer.
43 SW_REV The software revision of the firmware within the device.
Table 9.1: Resource Block parameter list
Rel.
Parameter Units Description
Index
01 ST_REV The revision level of the static data associated with
the function block. The revision value will be incre-
mented each time a static parameter value in the
block is changed.
02 TAG_DESC The user description of the intended application of
the block.
03 STRATEGY The strategy field can be used to identify a group-
ing of blocks. This data is not checked or pro-
cessed by the block.
04 ALERT_KEY The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
05 MODE_BLK The actual, target, permitted, and normal modes of
the block.
• Actual: The mode the "block is currently in"
• Target: The mode to "go to"
• Permitted: Allowed modes that target may take
on
• Normal: Most common mode for target
06 BLOCK_ERR This parameter reflects the error status associated
with the hardware or software components associ-
ated with a block. It is a bit string, so that multiple
errors may be shown.
07 PV EU of XD_SCALE The primary analog process variable used in block
execution.
08 OUT EU of The primary analog block output value and status.
OUT_SCALE or
XD_SCALE if in
direct L_TYPE
09 SIMULATE A data structure that contains the current trans-
ducer output value and status, the simulated trans-
ducer value and status, and the enable/disable bit.
10 XD_SCALE A data structure that contains the high and low
scale values, engineering units code, and number
of digits to the right of the decimal point associated
with the channel input value.
11 OUT_SCALE A data structure that contains the high and low
scale values, engineering units code, and number
of digits to the right of the decimal point displaying
the OUT parameter.
12 GRANT_DENY Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block. Not used by device.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
38 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Rel.
Parameter Units Description
Index
14 STATUS_OPTS Allows selecting options for status handling and
processing.
The following options are supported in the AI block:
• Propagate fault forward
• Uncertain if limited
• Bad if limited
• Uncertain if manual mode
15 CHANNEL The CHANNEL value is the number of the physical
input (transducer output) that is used as input for
the function block.
Supported values:
• 1-8: physical input from Channel 1 to Channel 8
• 10: physical input from Concentrator block which
is the internal device temperature
16 L_TYPE Determines whether the field value is used directly
(Direct), is converted linearly (Indirect), or is con-
verted with the square root (Indirect Square Root).
17 LOW_CUT % If percentage value of transducer input fails below
this value, then PV is set to 0
18 PV_FTIME Seconds Time constant of the first-order filter for the PV. It is
the time required for a 63% change in the PV or
OUT value. Used for filtering the response time.
19 FIELD_VAL % The value (in percent of the PV range) and status
from the transducer block or from the simulated
input before signal characterization.
20 UPDATE_EVT This alert is generated by any change to the static
data.
21 BLOCK_ALM The block alarm is used for all configuration, hard-
ware, connection failure or system problems in the
block. The cause of the alert is entered in the sub-
code field. The first alert to become active will set
the Active status in the Status parameter. As soon
as the Unreported status is cleared by the alert
reporting task, another block alert may be reported
without clearing the Active status, if the subcode
has changed.
22 ALARM_SUM The current alert status, unacknowledged states,
and disabled states of the alarm associated with
the function block.
23 ACK_OPTION Used to set auto acknowledgment of alarms.
24 ALARM_HYS % Span, expressed in percent of the PV span, in
which a PV must return before an alarm condition
is cleared.
25 HI_HI_PRI The priority of the HI-HI alarm.
26 HI_HI_LIM EU of PV_SCALE The setting for the alarm limit used to detect the HI-
HI alarm condition.
27 HI_PRI The priority of the HI alarm.
28 HI_LIM EU of PV_SCALE The setting for the alarm limit used to detect the HI
alarm condition.
29 LO_PRI The priority of the LO alarm.
30 LO_LIM EU of PV_SCALE The setting for the alarm limit used to detect the LO
alarm condition.
31 LO_LO_PRI The priority of the LO-LO alarm.
32 LO_LO_LIM LO_LO_PRI The setting for the alarm limit used to detect the
LO-LO alarm condition.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 39
Temperature Multi Input Device
Rel.
Parameter Units Description
Index
34 HI_ALM The HI alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of
the alarm.
35 LO_ALM The LO alarm data, which includes a value of the
alarm, a timestamp of occurrence and the state of
the alarm.
36 LO_LO_ALM The LO-LO alarm data, which includes a value of
the alarm, a timestamp of occurrence and the state
of the alarm.
Table 9.2: Analog Input Function Block (AI) Parameter List
Rel.
Parameter Units Description
Index
1 ST_REV The revision level of the static data associated with the input selector
block. The revision value will be incremented each time a static param-
eter value in the block is changed.
2 TAG_DESC The user description of the intended application of the block.
3 STRATEGY The strategy field can be used to identify grouping of blocks. This data
is not checked or processed by the block.
4 ALERT_KEY The identification number of the plant unit. This information may be
used in the host for sorting alarms, etc.
5 MODE_BLK The actual, target, permitted, and normal modes of the block.
• Actual: The mode the "block is currently in"
• Target: The mode to "go to"
• Permitted: Allowed modes that target may take on
• Normal: Most common mode for target
6 BLOCK_ER This parameter reflects the error status associated with the hardware
R or software components associated with a block. It is a bit string, so
that multiple errors may be shown.
7 CHANNEL Allows for custom channel setting.
Valid values:
• 0: Uninitialized
• 9: Physical channels 1 to 8 will be set to the corresponding sensors
8 -15 OUT_(1-8) EU of The block output value and status.
OUT_SCALE
16 UPDATE_E This alert is generated by any change to the static data.
VT
17 BLOCK_AL he block alarm is used for all configuration, hardware connection fea-
M ture, or system problems in the block. The cause of the alert is entered
in the subcode field. The first alert to become active will set the Active
status in the Status parameter. As soon as the Unreported status is
cleared by the alert reporting task, another block may be reported with-
out clearing the Active status, if the subcode has changed.
Table 9.3: MAI Parameter List
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
40 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 41
Temperature Multi Input Device
Rel.
Parameter Properties Description
Index
13 Sensor Type S, OOS Type of the attached sensor. For a list of supported sen-
sors, see datasheet.If "Sensor Type" is written some other
parameters will be set automatically for convenience:
• If voltage mode or a TC is selected,
"SENSOR_CONNECTION" is set to 2-wire
• If voltage mode is selected, Primary Value unit is set to
mV
• If resistance input is selected the Primary Value unit is
set to Ohm
• If a TC or RTD sensor is selected and the Primary Value
Unit is mV or Ohm it is set to °C
14 Sensor Range S, OOS Defines the absolute maximum ends of the sensor range,
the units of those limits and the number of digits to the right
of the decimal point to be used to display these values.
Supported units: mV, Ohm, °C, °F, K, °R
15 Sensor Connection S, OOS Number of wires used to connect the sensor. This parame-
ter is only honored if a resistance-based sensor is config-
ured.
Supported values:
• Two wires
• Three wires
• Four wires
16 Sensor Diagnostics S, W Enables sensor diagnosis.
17 Sensor Status Shows failures of the attached sensor, it is a bit string so
multiple errors can be shown.
Supported values:
• Sensor connection error
• Over range: The measured value is too high for current
sensor
• Under range: The measured value is too low for current
sensor
18 Sensor Serial No. S, W, NF The serial number of the attached sensor.
19 Sensor Calibration S, W, NF Last calibration method used for the attached sensor:
Method • Factory trim standard calibration
• User trim standard calibration
• Factory trim special calibration
• User trim special calibration
• Other
20 Sensor Calibration S, W, NF Shows location of the last calibration for the attached sen-
Location sor.
21 Sensor Calibration S, W, NF Shows date of the last calibration for the attached sensor.
Data
22 Sensor Calibration Who S, W, NF Shows name of person responsible for the last calibration
for the attached sensor.
23 RTD 2 Wire Resistance S, OOS Specifies an offset subtracted from the measured resis-
tance if a two-wire RTD or Ohm sensor is attached. The
value is specified as a positive floating point number.
24 CJC Select S, OOS Selects the method used to do a CJC:
• Internal: use the internally measured value
• Constant: use the value of parameter "Constant CJC"
25 CJC Constant S, OOS Value used for CJ compensation if "CJC select" is set to
Constant. Uses the Unit of "Sensor Range.Units Index".
The value is converted automatically if "Sensor
Range.Units Index" is changed.
26 Calibration Highest S, SP Upper value for calibration of the input. Writeable only dur-
Point ing calibration.
27 Calibration Lowest S, SP Lower value for calibration of the input. Writeable only dur-
Point ing calibration.
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
42 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
Rel.
Parameter Properties Description
Index
29 Calibration Lowest Lowest value allowed to calibrate the input.
Point Limit
30 Calibration Minimum Minimum allowed difference between "Calibration Highest
Span Point" and "Calibration Lowest Point".
31 Calibration Units Unit used to calibrate the input. It is set automatically if a
calibration starts. Valid values: mV and Ohm
32 Calibration Mode S, OOS Stipulates the validity of user calibration and turns the cali-
bration mode on for the input
• User calibration off
• User calibration on: A calibration error ("Calibration
State" reads "Failure") will be reported as a block config-
uration error so the block will not switch to AUTO mode.
• Execute user calibration
33 Calibration State Shows the state of the user calibration for the input.
Supported values:
• Not initialized: No user calibration was carry out yet. It's
not possible to turn on the user calibration
• Executing: A user calibration is being started
• OK: A valid user calibration was executed
• Failure: A failure happened during the last user calibra-
tion. The values are invalid. It's not possible to turn on
the user-calibrated measurement. The block will report
a configuration error if "Calibration Mode" is set to "User
calibration on".
• Wait first: Device is waiting for write on "Calibration
Highest Point" or "Calibration Lowest Point" as first cali-
bration point
• Wait second HI: Device is waiting for write on " Calibra-
tion Highest Point " as second calibration point
• Wait second LO: Device is waiting for write on " Calibra-
tion Lowest Point " as second calibration point
• Sampling HI: Device is measuring HI calibration value.
• Sampling LO: Device is measuring LO calibration value
34 Calibration Location S, W, NF Shows location of the last calibration for the input.
35 Calibration Date S, W, NF Shows date of the last calibration for the input.
36 Calibration Who S, W, NF Shows name of person responsible for the last calibration
for the input.
Table 9.4: TI_SENS Block Parameter List
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 43
Temperature Multi Input Device
Rel.
Parameter Properties Description
Index
03 STRATEGY S, W, NF The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the block.
04 ALERT_KEY S, W, NF The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
05 MODE_BLK S, W The actual, target, permitted, and normal modes of the
block.
• Actual: The mode the "block is currently in"
• Target: The mode to "go to"
• Permitted: Allowed modes that target may take on
• Normal: Most common mode for target
06 BLOCK_ERR This parameter reflects the error status associated with the
hardware or software components associated with a block.
It is a bit string, so that multiple errors may be shown.
Supported values:
• 15: Out-of-Service = Actual Mode of the Block is OOS
• 129: Body temperature too high or too low
07 UPDATE_EVT This alert is generated by any change to the static data.
08 BLOCK_ALM The block alarm is used for all configuration, hardware
connection feature, or system problems in the block. The
cause of the alert is entered in the subcode field. The first
alert to become active will set the Active status in the Sta-
tus parameter. As soon as the Unreported status is cleared
by the alert reporting task, another block may be reported
without clearing the Active status, if the subcode has
changed.
09 Transducer Error Stores the actual transducer block error wit the highest pri-
(XD_ERROR) ority.Supported values:
• 129: Body temperature too high or too low
10 Block Mode Channel 1 S, W Mode block of sensor input 1.
11 Primary Value The value and status of sensor input 1.
12 Primary Value Filter- S, SP The damping value for sensor input 1. Parameter is write-
time Channel 1 able if corresponding sensor block is in OOS mode.
13 Sensor Unit Channel 1 S, SP The unit used for sensor input 1. Parameter is writeable if
corresponding sensor block is in OOS mode.
14 Sensor Type Channel 1 S, SP The type of sensor input 1. Parameter is writeable if corre-
sponding sensor block is in OOS mode.
15 Sensor Connection S, SP The connection type of sensor input 1. Parameter is write-
Channel 1 able if corresponding sensor block is in OOS mode.
16 Sensor Diagnostics S, W Allows to enable/disable the sensor diagnosis for sensor 1.
Channel 1
18 - 73 The sensor specific values above are repeated for the sensor inputs 2 - 8
• 18 - 24 channel 2
• 25 - 31 channel 3
• 32 - 38 channel 3
• 39 - 45 channel 4
• 46 - 52 channel 5
• 53 - 59 channel 6
• 60 - 66 channel 7
• 67 - 73 channel 8
74 Body Temperature Value and status of the body temperature.
75 Body Temperature Unit S, OOS The unit used to display body temperature.
Valid units: °C, °F, °R, K
76 ASIC Rejection S, W Used to set the electrical noise filter depending on the
power line frequency of the installation. Valid values are
50Hz and 60Hz.
77 Status Summary Overview of the sensor status of all sensors. The parame-
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
44 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
Temperature Multi Input Device
10 List of Tables
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 45
Temperature Multi Input Device
11 List of Figures
11/2008 132328
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
46 Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com
PROCESS AUTOMATION –
PROTECTING YOUR PROCESS
Worldwide Headquarters
Pepperl+Fuchs GmbH
68307 Mannheim · Germany
Tel. +49 621 776-0
E-mail: info@de.pepperl-fuchs.com
www.pepperl-fuchs.com
132328 / TDOCT0193DENG
Subject to modifications
11/2008
Copyright PEPPERL+FUCHS • Printed in Germany