Naffco Jockey Pump
Naffco Jockey Pump
Naffco Jockey Pump
Multistage
sp u mP
91 of 181
AN INTRODUCTION TO NAFFCO
NAFFCO was ounded in Dubai, UAE to become the world’s Our products have been consistently certi ed by UL, FM, BSI,
leading producer and supplier o li e sa ety solutions. By LPCB and Global Mark according to the latest International
recognizing the importance and convenience o having easy Quality Standard or their strict adherence to ISO 9001 quality
access to multiple sa ety services, we became specialized by management system and certi ed or ISO 14001 environmental
o ering complete solutions under one roo or all types o high management systems and BS OHSAS 18001 or occupational
quality re ghting equipment, re protection systems, re alarms, sa ety by UL DQS.
addressable emergency systems, security systems,custom-
made vehicles such as re trucks, ambulances, mobile hospitals Our success is driven by our passion to protect; our vision is to
and airport rescue re ghting vehicles (ARFF). become the world’s number one provider o innovative solutions
in protecting li e, environment and property.
With the most talented and dedicated employees rom around
the world, NAFFCO has over 450 passionate engineers and over
3 million square eet o manu acturing acilities. We are currently
exporting to over 100 countries worldwide.
92 of 181
2 www.nafco.com
PERFORMANCE CURVES
NF-VL 8 50Hz
2900rpm
240
230
220 -200
210
200 -180
190
180
-160
170
160
150 -140
140
130 -120
Head (m)
120
110 -100
100
90 -80
80
70
-60
60
-50
50
-40
40
30 -30
20 -20
10 -10
0
0 1 2 3 4 5 6 7 8 9 10 11
Capacity (m3/h)
0.50
0.40
Power (kW), Stage = 1
0.30
0.20
0.10
0.00
60
50
40
E ciency (%)
30
20
10
2.0
1.6
1.2
NPSHR (m)
0.8
0.4
0.0
0 1 2 3 4 5 6 7 8 9 10 11
Capacity (m /h)
3
8 www.nafco.com
NAFFCO VERTICAL MULTISTAGE PUMPS
NF-VL / NF-VLS is a vertical multistage in-line pump able or using as a pressure maintenance pump (Jockey
series with all wetted parts made o stainless steel. It is Pump) in re ghting applications and it meets NFPA 20
suitable or a variety o di erent applications involving requirements or Jockey Pumps. Each pump set is
various liquids rom potable water to industrial e uent and tested in our actory, prior to dispatch, to con rm that the
cover a wide range o ow and pressure requirements. per ormance is achieved per the speci ed requirements.
NF - Series Name 2
16
VL - Vertical Multistage 3
Note: Letter ‘S’ will be added to ‘VL’ for the models that are designed 6
for 60 Hz operation. 15
7
SL. 8 14
PART NAME MATERIAL STANDARD
NO. 13
9
1 Electric Motor Aluminum Frame 12
NF-VL(S) 8, 16
93 of 181
www.nafco.com 3
SPECIFICATIONS
94 of 181
4 www.nafco.com
Serving Over 100 Countries Worldwide
96 of 181
JOCKEY PUMP CONTROLLER
UL LISTED JOCKEY PUMP CONTROLLER
MODEL NFY-JSD1 REDUCED VOLTAGE/
STAR – DELTA (OPEN TRANSITION)
MODEL NFY-JDO1 DIRECT ON LINE
NAFFCO Jockey Pump Controllers for re pumps are UL recognized components are used in these panels
listed by Underwriters Laboratories (UL le number to guarantee the best possible reliability. Also high
E309408), in accordance with UL508a (Standard for quality UL listed enclosures are used.
Industrial Control Panel), NFPA70 (National Electric
Code) and NEMA. The controller is completely wired, assembled and
tested at the factory before shipment, and ready for
Power ratings vary from 1.5 to 40 horsepower, 380 to immediate installation.
415 volts, 50 or 60 Hz. Only high quality UL listed or
STANDARD FEATURES
• Main disconnected switch with rotary handle, sized for
disconnecting motor horsepower and voltage.
• Motor Starter rated to motor’s horsepower, with
thermal and short circuit protection.
• Rated motor contactors.
• Circuit breaker for protection of control circuit.
• Selector switch for Hand—Off—Automatic operation.
• Star—Delta starting timer. ( in Model NFY-JSD1 )
• Power ON/Healthy indicator/free contact.
• Pump Run indicator/free contact.
• Pump Trip indicator/free contact.
• Adjustable pressure switch.
• UL listed enclosure.
SEQUENCE OF OPERATION
This controller is working under three modes automatic
off and manual mode.
AUTOMATIC START
In this mode, controller will start the Jockey pump
automatically and directly at low pressure detection
by the pressure switch, and will stop the pump
automatically and directly when the pressure goes up
again.
MANUAL START
In this mode, controller will start the Jockey pump
directly, and will not stop until selector switch is
switched off or in Auto mode.
12 www.naffco.com
RATING
RATED SHORT CIRCUIT
POWER RATED VOLTAGE FREQUENCY ENCLOSED SIZE
CONTENT CURRENT
(HP) (VAC) (Hz) (mm)
(A) (kA)
Table (7)
www.naffco.com 13
301
Motor Line Terminal Wire Size Per Phase Output Motor Wire Siz Per Phase Ground Wire
Min Max Min Max Min Max
Power AWG or AWG or AWG or AWG or AWG or AWG or
[HP] MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq. MCM mm Sq.
1.5 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
2 16 1.3 8 8.4 16 1.3 8 8.4 8 8.4 6 13.3
3 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
7.5 14 2.1 8 8.4 14 2.1 8 8.4 8 8.4 6 13.3
10 12 3.3 8 8.4 12 3.3 8 8.4 8 8.4 6 13.3
15 10 5.3 6 13.3 10 5.3 6 13.3 8 8.4 6 13.3
20 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
25 8 8.4 6 13.3 8 8.4 6 13.3 8 8.4 6 13.3
30 6 13.3 6 13.3 6 13.3 6 13.3 6 13.3 1/0 53.5
40 4 21.2 1 42.4 4 21.2 1 42.4 4 21.2 1/0 53.5
AWG OR TIGHTENING
TORQUE USING
CIRCULAR EXTERNAL DRIVE
WRENCH
MILL SIZE LP.In N.m
14 75 8.5
12 75 8.5
10 75 8.5
8 75 8.5
6 110 12.4
4 110 12.4
2 150 16.9
1 150 16.9
1/0 180 20.3
2/0 180 20.3
3/0 250 28.2
4/0 250 28.2
250 325 36.7
350 325 36.7
500 375 42.4
600 375 42.4
700 375 42.4
750 375 42.4
800 500 56.5
1000 500 56.5
Serving Over 100
100
00 Countries
C
Co
Cou
ou
oun
unt
ntr
ntri
ntrie
trie
ries
ies
ess W
Worldwide
Wo
Wor
Worl
orld
rld
rldw
ldw
dw
dwi
dwid
wid
wide
de
e
CAT.NO.NF/MPBFPC/01/15
NAFFCO FZCO
World Headquarters
Dubai, United Arab Emirates
Email: info@naffco.com
www.naffco.com
In line with NAFFCO policy for continuous product development,
NAFFCO has the right to change specifications without prior notice.