Combined Overcurrent & Earth-Fault Relay: Type SPAJ 140 C
Combined Overcurrent & Earth-Fault Relay: Type SPAJ 140 C
Combined Overcurrent & Earth-Fault Relay: Type SPAJ 140 C
ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering environmental impact. The ABB Group of companies operates in around 100 countries and employs over 1,05,000 people. In India, ABB serves customers with the complete range of power and automation technologies. The company has a vast installed base, extensive manufacturing facilities and a countrywide marketing and service presence. As a part of its Power Technologies offering, ABB serves electric, gas and water utilities as well as industrial and commercial customers with a wide range of products, systems and services for power generation, transmission and distribution. ABBs system offering ranges from Electrical Balance of Plant (EBOP) for power plants, bulk power transmission, turnkey substations and complete electrification to utility automation and power distribution.
The product offering covers a wide spectrum of technologies across the entire voltage range including indoor and outdoor circuit breakers, air and gas insulated switchgear, disconnectors, capacitor banks, reactive power compensators, power transformers, distribution transformers, instrument transformers, Compact Secondary Substations (CSS) and Ring Main Units (RMU).
Advantage ABB
120 years of technology and innovation Unparalleled domain competence Global experience Complete solution capabilities Large installed base Environment-friendly technologies
ABB
Features
Phase and neutral overcurrent protection relay for distribution feeders Three-phase, high-set and low-set phase over- current protection Sensitive non-directional high-set and low-set earth-fault protection Integrated circuit-breaker failure protection Four standardized inverse definite minimum time (IDMT) time-current curves as per IEC and BS Definite time operation Two special-type inverse-time characteristics called RI and RXIDG Numerical design for stable time-current curves, high accuracy and reliable operation Fault records, event records and diagnostic data can be read remotely via the serial port and locally High immunity to electrical interference and robust aluminum case to class IP54 Improved system reliability supported by a built-in self-supervision system with auto diagnosis Serial communication capability for extensive exchange of data between the protection relay and the substation control level Powerful optional PC tool for reading, setting and recording relay data and parameters
Application
The combined phase and neutral overcurrent relays of the SPAJ 140 series are used for the selective shortcircuit and time overcurrent protection of radial feeders in distribution networks. The relays are also used for feeder earth-fault protection in isolated neutral networks and networks with resistively earthed neutral. Both the overcurrent unit and the earth-fault unit feature two stages: a high-set stage and a low-set stage. Further, the SPAJ 140 series relays include an integrated circuit breaker failure protection function. The relays include a local man-machine interface for setting relay parameters and for interrogating measured and recorded parameters. The relays also include a serial port which connects to the fibre-optic SPA bus and substation control systems. Further, a personal computer with a suitable software can be connected to the serial port, facilitating reading, setting and recording of relay data. The combined overcurrent and earth-fault relays of the SPAJ 140 series are members of the SPACOM product family, which is compatible with PYRAMIDTM, the coordinated protection and control concept of ABB.
ABB
Technical data
SPAJ 140 C
1 A/5 A 4 A/20 A 100 A/500 A 250 A/1250 A <100 m/<20 m 1 A/5 A 4 A/20 A 100 A/500 A 250 A/1250 A <100 m/<20 m 50 Hz or 60 Hz 80...265 V DC/AC 18...80 V DC ~4 W / ~6 W -100C...550C ~3.5 kg
0.50...5.0 x In 0.50...2.5 x In
0.05...300 s Extremely inverse Very inverse Standard inverse Long-time inverse RI-type inverse RXIDG-type inverse 0.05...1.0 0.5...40 x In or 0.04...300 s 20 dB at f = 3 x fn 0.1...0.8 x In
- time multiplier k High-set overcurrent stage I>> Start current Operate time t>> Suppression of harmonics Low-set earth-fault stage Io> Start current
*) Note! The relay allows settings above 2.5 x In, but regards any setting > 2.5 x In as being equal to 2.5 x In
4 ABB
0.05...300 s Extremely inverse Very inverse Normal inverse Long-time inverse RI-type inverse RXIDG-type inverse 0.05...1.0 0.1...10.0 x In or 0.05...300 s 14 dB at f = 3 x fn
-special characteristic according to ABB practice - time multiplier ko High-set earth-fault stage Io>> Start current Operate time to>> Suppression of harmonics
Electrical tests
Insulation test according to IEC 60255-5 Dielectric test 2 kV, 50 Hz, 1 min Impulse test 5 kV, 1.2/50 s, 0.5 J Insulation resistance >100 M at 500 V DC Power supply tests according to IEC 60255-11, IEC 61000-4-11 Interruption of DC voltage 40 ms/80 V, 10ms/18V Interruption of AC voltage 70 ms/80 V Ripple in DC voltage max. 12% of DC value 1 MHz burst disturbance test according to IEC 60255-22-1 class III -common mode 2.5 kV, 1MHz, 400 pulses/sec. 1kV, 1MHz, 400 pulses/sec. Electrostatic discharge test according to IEC 60255-22-2 class III -contact discharge 6kV -air discharge 8kV Radiated, radio frequency, electromagnetic field immunity test according to IEC 60255-22-3, IEC 61000-4-3 10 V/m, f = 80..1000MHz Fast transient disturbance test according to IEC 60255-22-4, IEC 61000-4-4 -differential mode -Power supply ports 4 kV, 5/50 ns, 50 -I/O ports 2 kV, 5/50 ns, 50 Surge immunity test according to IEC 60255-22-5, IEC 61000-4-5 -common mode 2 kV, 1.2/50 s, 12 -differential mode 1 kV, 1.2/50 s, 2 Immunity to conducted disturbances induced by radio frequency fields according to IEC 60255-22-6, IEC 61000-4-6 10 V, f =150kHz...80MHz
Signalling contacts
Terminals
Rated voltage Rated current Make and carry for 0.5 s Make and carry for 3.0 s Breaking capacity for DC, when the signalling circuit time-constant L/R # 40 ms, at 48/110/220 V dc 1 A/0.25 A/0.15 A Contact material AgCdO2
Data transmission
Transmission mode Fibre-optic serial with optional bus connection module ASCII 4800 Bd or 9600 Bd
Conducted and Radiated radio-frequency emission tests according to IEC 60255-25, EN55011-CISPRII -conducted emission (mains) class A -radiated emission class A Power frequency magnetic field immunity test according to IEC 61000-4-8 -continuous 100 A/m -short duration 300 A/m
Environmental tests
Vibration response and endurance test as per IEC 60255-21-1 class 1, 10...150Hz Shock response and endurance test as per IEC 60255-21-2 class 1, 11ms Bump test as per IEC 60255-21-2 20 g,1000 bumps/dir Seismic tests as per ANSI/IEEE C37.98 1987 -Operating basis
Earth-quake 0.50...5.25 g -Safe shut-down earth-quake 0.50...7.5 g Degree of protection by enclosure when panel mounted (front side) according to IEC 60529 Protection IP 54 Dry heat test according to IEC 60068-22-2 Temperature +55o C/+70o C Dry cold test according to IEC 60068-2-1 Temperature -10o C/-25o C Storage temperature test according to IEC 60068-2-48 Temperature -40o C/+70o C Damp heat test, cyclic (12+12 hour cycle) according to IEC 60068-2-30 Condition 96% RH, 6 days Corrosion test Battelle-test
Fig.1- Block schematic diagram and typical connection diagram for the relay SPAJ 140 C. The low-set stages of the overcurrent and the earth-fault units feature definite time or inverse-time characteristic.
ABB
Ordering details
Item No. .... Type Application : : Qty SPAJ 140C Over current and Earth fault protection of feeder, capacitor, transformer etc. Aux Votage : 18 - 80 V DC 80 - 265 V AC/DC CT Secondary : 1A/5A selectable Normal inverse (Selectable at site) : Very inverse Extremely inverse Long time inverse RI characteristic RXIDG ch. Contacts : 2 N/O (Heavy duty)+ 3 N/O (Light duty)+ 1 C/O (for IRF) * Kindly furnish above mentioned details along with your order by ticking ( ) appropriate boxes Type designation explanation SPA...Substation Protection apparatus J...Current Operated 1...100 size case 40...Mechanical Design C...Communicable Case size : Mounting : 100 Flush
ABB
ABB Limited Distribution Automation Maneja, Vadodara 390 013, India. Tel: +91 265 2604384/5/6 +91 265 2604397 Fax: +91 265 2638922 E-mail: aicds@in.abb.com
West
ABB House Dr. S B Path Ballard Estate Mumbai 400 038 Tel: +91 22 56318231 39 Fax: +91 22 56318276/77
South
Embassy Star, 1st Floor No. 8, Palace Road Vasanth Nagar Bangalore 560 052 Tel: +91 80 22949779 Fax: +91 80 22949808 Century Plaza No. 3C, 3D & 3F, 3rd Floor 561 / 562, Anna Salai Teynampet (Mount Road) Chennai 600 018 Tel: +91 44 24340201 Fax: +91 44 24340282
East
4th Floor No. 9 Elgin Road Kolkata 700 020 Tel: +91 33 22832906/8 Fax: +91 33 22832990
Central
Vandana House 1st Floor G E Road, Ramkund Raipur 492 001 Tel: +91 771 5060816-8 Fax: +91 771 5053391
www.abb.co.in