HEIGHT OF INDOOR HOOD

The bottom of the hood should be 30” (76.2 cm) min. to 36” (91.4 cm) max. above the countertop. This would
typically result in the bottom of the hood being 66” (167.6 cm) to 72” (182.9 cm) above the floor. The bottom of the
hood should never be more than 72” (182.9 cm) above the floor or more than 36” (91.4 cm) above the countertop.
These dimensions provide for safe and efficient operation of the hood.

WALL INSTALLATION ISLAND INSTALLATION

18” (45.7 cm)


18” (45.7 cm)

30”
24” or 27” (76.2 cm)
(61.0 cm or 68.6 cm)

30” (76.2 cm) Min.


30” (76.2 cm) Min. 36” (91.4 cm) Max.
36” (91.4 cm) Max.

66” - 72” Countertop Countertop


(167.6 cm - 66” - 72”
182.9 cm) (167.6 cm -
182.9 cm)
36”
(91.4 cm) 36”
(91.4 cm)

3
INSTALLING HOOD CANOPY
Wall Hoods
(Custom Ventilator Kits Only)
A
A* 30” W. 27 7/16” (69.7 cm)
36” W. 33 7/16” (84.9 cm)
42” W. 39 7/16” (100.2 cm)
48” W. 45 7/16” (115.4 cm)
54” W. 51 7/16” (130.7 cm)
21 7/16” 60” W. 57 7/16” (145.9 cm)
(54.5 cm)* 66” W. 63 7/16” (161.1 cm)

Bottom Cutout Dimensions


Make sure the back wall of the
*For best results, center the unit custom hood canopy is flush with the
over the burners of the cooking cutout so the ventilator system may
product (front to back; right to left). be mounted as shown below.

Custom Hood Canopy

1) Position ventilator system


inside of the custom hood
canopy and center it front to Built-in Ventilator System
back and left to right.

2) Bottom mounting holes fasten


ventilator system to bottom of
custom hood canopy with the
screws provided

3) OPTIONAL
Rear mounting holes fasten
ventilator system to rear of
custom hood canopy

6
Transition
BUILT-IN CUSTOM VENTILATOR SYSTEM DIMENSIONS VIV1200 Only

9” (22.9 cm)
1 1/2” 1” (2.54 cm)
(3.81 cm) 1 1/2”
(3.81 cm) 7/8”
(2.22 cm)

11 1/2”
(29.2 cm)

17 1/4”
(43.8 cm)
5/8” (1.6 cm)
6”
21 7/8” (55.8 cm) (15.2 cm) 5/8” (1.6 cm)
21 7/8” (55.8 cm)

FOR 900 or 1200 CFM EXTERIOR


VENTILATOR INSTALLATION FOR 300 or 600 CFM INTERIOR
VENTILATOR INSTALLATION

D
5 1/2” (14.0 cm) 4 5/8” D
8 1/4” (11.7 cm) 9 3/8”
(20.9 cm) (23.8 cm)
6”
(15.2 cm)
9 1/4”
(23.5 cm)

3” 9 5/8”
(7.6 cm) (24.4 cm)
2 1/2” (6.4 cm) 18 3/4” (47.6 cm)

5/8” (1.6 cm) 5/8” (1.6 cm)


C C
Cutout for 10” 7” (17.8 cm)
(25.4 cm) duct. dia. duct
location

30” W./36” W./42” W. 30” W./36” W./42” W. -


900 CFM EXTERIOR VENTILATOR INSTALLATION 300 or 600 CFM INTERIOR VENTILATOR INSTALLATION

C D
30” W. Models 28 1/4” (71.8 cm) 14 1/8” (35.9 cm)
36” W. Models 34 1/4” (87.0 cm) 17 1/8” (43.5 cm)
42” W. Models 40 1/4” (102.2 cm) 20 1/8” (51.1 cm)

*Note: “Dotted Line” (........) represents cutout


17
D
D 18 1/2”
5 1/2” (14.0 cm) 5 1/2”
(50.0 cm)
8 1/4” 9 3/8”
(14.0 cm)
(20.9 cm) (23.8 cm)
6”
(15.2 cm) 8 3/8”
(21.3 cm)

3”
9 1/4” 9 1/2”
(7.6 cm) (23.5 cm) (24.4 cm)
2 1/2” (6.4 cm)

5/8” (1.6 cm) 5/8” (1.6 cm)


C C
10” (25.4 cm)
Cutout for 10”
dia. duct
(25.4 cm) duct.
location
48” W./54” W./60” W./66” W. 48” W./54” W./60” W./66” W.
1200 or 1500 CFM EXTERIOR VENTILATOR 1200 CFM INTERIOR VENTILATOR INSTALLATION
INSTALLATION

*Note: “Dotted Line” (........) represents cutout

C D
48” W. Models 46 1/4” (117.5 cm) 23 1/8” (58.7 cm)
54” W. Models 52 1/4” (132.7 cm) 26 1/8” (66.4 cm)
60” W. Models 58 1/4” (148.0 cm) 29 1/8” (74.0 cm)
66” W. Models 64 1/4” (163.2 cm) 32 1/8” (81.6 cm)

18
BASIC SPECIFICATIONS - INTERIOR AND EXTERIOR POWER HOODS
18” H. Indoor Wall Hoods
RECOM. NUMBER OF 250 WATT 120VAC/60Hz
DESCRIPTION CFM1 HALOGEN HEAT LAMPS FILTERS SPACERS MAX. AMPS3
LIGHTS (bulb sold
(Int.-Interior; Ext.-Exterior) separately) (Interior/Exterior)
24”W. 300 int./600 int./900 ext./1200 ext. 2 1 2 1 5.0/6.2/8.7/6.1
30” W. 300 int./600 int./1200 int./900 ext./1200 ext 2 1 2 1 5.0/6.2/8.7/8.7/6.1
36”W.* 300 int./600 int./1200 int./900 ext./1200 ext. 2 1 2 2 5.0/6.2/8.7/8.7/6.1
42”W.* 600 int./1200 int./900 ext./1200 ext. 2 1 2 2 6.2/8.7/8.7/6.1
48”W., 54”W.* 1200 int./1200 ext./1500 ext. 3 2 3 2 11.1/8.4/9.1
60”W.* 1200 int./1200 ext./1500 ext. 4 2 4 1 11.5/8.8/9.5
66”W.* 1200 int./1200 ext./1500 ext. 4 2 4 2 11.5/8.8/9.5

18” H. Indoor Island Hoods


RECOM. NUMBER OF 120VAC/60Hz
DESCRIPTION CFM1 HALOGEN FILTERS SPACERS MAX. AMPS3
LIGHTS
(Int.-Interior; Ext.-Exterior) (Interior/Exterior)
36”W.* 600 int./1200 int./900 ext./1200 ext. 4 4 2 4.9/7.4/7.4/4.7
42”W.* 600 int./900 ext./1200 ext./1500 ext. 4 4 4 4.9/7.4/4.8/5.4
54”W.* 1200 int./1200 ext./1500 ext. 6 6 4 8.2/5.6/6.2
66”W.* 1200 int./1200 ext./1500 ext. 8 8 4 9.0/6.3/7.1

18” H. Outdoor Wall Hoods*


RECOM. NUMBER OF 120VAC/60Hz
DESCRIPTION CFM1 HALOGEN FILTERS SPACERS MAX. AMPS3
LIGHTS
(Int.-Interior; Ext.-Exterior) (Interior/Exterior)
36”W. 1200 int./1200 ext./1500 ext. 2 2 2 8.7/6.1/6.8
48”W. 1200 int./1200 ext./1500 ext. 3 3 2 11.5/8.8/9.5
60”W. 1200 int./1200 ext./1500 ext. 4 4 1 11.5/8.8/9.5

*1200 CFM interior or exterior or 1500 CFM exterior (if applicable) ventilator should be used with all outdoor approved
models and when indoor models are installed over ranges/rangetops with gas grill.

RECOMMENDED MAX. DUCT


MODEL NUMBER CFM1 DUCT SIZE RUN2 (ft.)
For Use with hoods:
VIV300 (interior) 300 7” round 50
VIV600 (interior) 600 7” round 50
VIV1200 (interior) 1200 10” round 50
VEV900 (exterior) 900 10” round 50
VEV1200 (exterior) 1200 10” round 50
VEV1500 (exterior) 1500 10” round 75

PROPER INSTALLATION/DUCTING IS EXTREMELY IMPORTANT TO ENSURE MAXIMUM PERFORMANCE FROM ANY


VENTILATION PRODUCT
1. •All CFMs stated are based on tests at .1 static pressure: without applying static pressure, CFM would be greatly overstated.
2. •Duct run length is for general reference only; for longer duct runs, increase duct size and contact a qualified and trained
installer.
•Straight runs and gradual turns are best; for example, each 90o elbow is equivalent to 5-10 feet (1.52 - 3.05 cm) of straight run.
•Never use flexible duct; it creates back pressure/air turbulence and greatly reduces performance.
•Proper performance is dependent upon proper ducting; make sure that a qualified and trained installer is used.
•Check with a qualified and trained installer or local codes for makeup air requirement, if any.
3. •Max. amp rating for hoods includes recommended ventilator kit rating; all products must be hard wired direct with 2-wire with
ground.