Photovoltaic II
Photovoltaic II
Photovoltaic II
Photovoltaic II
Photovoltaic 1
FROM CELLS TO MODULES TO ARRAYS
Photovoltaic 2
Multiple modules, in turn, can be wired in series to increase voltage and
in parallel to increase current
Such combinations of modules are referred to as an array
Photovoltaic 3
For cells wired in series, their voltages at any given current add.
A typical module will have 36 cells.
Photovoltaic 4
Voltage and Current from a PV Module.
a. Find the voltage, current, and power delivered when the junction
voltage of each cell is 0.50 V
Photovoltaic 5
Using Vd = 0.50 V
Photovoltaic 6
Photovoltaic 7
For a cell to have losses of less than 1% due to its parallel resistance, RP
should be greater than about
For a large cell, ISC might be around 7 A and VOC might be about 0.6 V, which
says its parallel resistance should be greater than about 9 Ω .
For a cell to have less than 1% losses due to the series resistance, RS
will need to be less than about
which, for a large cell with ISC = 7 A and VOC = 0.6 V, would be less than
0.0009 Ω
Photovoltaic 8
From Modules to Arrays
Modules can be wired in series to increase voltage, and in parallel to increase
current. Arrays are made up of some combination of series and parallel
modules to increase power
Photovoltaic 9
Photovoltaic 10
Parallel – series connection
Two ways to wire an array with three modules in series and two modules in
parallel. Although the I –V curves for arrays are the same, two strings of three
modules each (a) is preferred. The total I –V curve of the array is shown in (c).
Photovoltaic 11
There is a reason, however, to prefer the wiring of strings in parallel (Fig.a). If an
entire string is removed from service for some reason, the array can still deliver
whatever voltage is needed by the load, though the current is diminished, which
is not the case when a parallel group of modules is removed.
Photovoltaic 12
THE PV I–V CURVE UNDER STANDARD TEST
CONDITIONS (STC)
Consider, for the moment, a single PV module that you want to connect to
some sort of a load. The load might be a dc motor driving a pump or it might be
a battery, for example. Before the load is connected, the module sitting in the
sun will produce an open-circuit voltage VOC, but no current will flow. If the
terminals of the module are shorted together (which doesn’t hurt the module
at all, by the way), the short-circuit current ISC will flow, but the output voltage
will be zero. In both cases, since power is the product of current and voltage,
no power is delivered by the module and no power is received by the load.
When the load is actually connected, some combination of current and voltage
will result and power will be delivered
Photovoltaic 13
To figure out how much power, we have to consider the I –V characteristic
curve of the module as well as the I –V characteristic curve of the load.
Photovoltaic 14
The I –V curve and power output for a PV module. At the maximum power
point (MPP) the module delivers the most power that it can under the
conditions of sunlight and temperature for which the I –V curve has been
drawn.
Photovoltaic 15
Photovoltaic 16
Since PV I –V curves shift all around as the amount of insolation changes
and as the temperature of the cells varies, standard test conditions (STC)
have been established to enable fair comparisons of one module to another.
The standard cell temperature for testing purposes is 25◦C (it is important to
note that 25◦ is cell temperature, not ambient temperature).
Photovoltaic 17
Photovoltaic 18
Question: how to adjust rated power to account for temperature effects and
how to adjust it to give us an estimate of the actual ac power that the module
and inverter combination will deliver?
Photovoltaic 19
For crystalline silicon cells, VOC drops by about 0.37% for each degree Celsius
increase in temperature and ISC increases by approximately 0.05%. The net
result when cells heat up is the MPP slides slightly upward and toward the left
with a decrease in maximum power available of about 0.5%/◦C.
Photovoltaic 20
NOCT - nominal operating cell
temperature
The NOCT is cell temperature in a module when ambient is 20◦C, solar
irradiation is 0.8 kW/m2, and windspeed is 1 m/s. To account for other
ambient conditions, the following expression may be used:
Photovoltaic 21
Impact of Cell Temperature on Power for a PV Module.
From Table, for this module at the standard temperature of 25◦C, VOC = 42.8 V.
Since VOC drops by 0.37%/◦C, the new VOC will be about
Photovoltaic 22
With maximum power expected to drop about 0.5%/◦C, this 150-W module
at its maximum power point will deliver
Photovoltaic 23
When the NOCT is not given, another approach to estimating cell temperature is
based on the following:
Photovoltaic 24
SHADING IMPACTS ON I –V CURVES
Photovoltaic 25
Photovoltaic 26
Impacts of Shading on a PV Module.
Solution
Photovoltaic 27
The new output voltage will be 19.41 − 14.66 = 4.75 V.
Power delivered by the module with one cell shaded would be
b. All of that 2.14 A of current goes through the parallel plus series resistance
(0.005 ) of the shaded cell, so the drop across the shaded cell will be
normally a cell in the sun will add about 0.5 V to the module; this shaded
cell subtracts over 14 V from the module.
Photovoltaic 28
The power dissipated in the shaded cell is voltage drop times current, which is
All of that power dissipated in the shaded cell is converted to heat, which
can cause a local hot spot that may permanently damage the plastic
laminates enclosing the cell
Photovoltaic 29
Effects of shading on the I –V curves for a PV module. The dashed line shows a
typical voltage that the module would operate at when charging a 12-V battery;
the impact on charging current is obviously severe
Photovoltaic 30
Bypass Diodes for Shade Mitigation
In full sun a cell may contribute around 0.5 V to the module output; but
when a cell is shaded, it can have a large voltage drop across it.
Photovoltaic 31
Mitigating the shade problem with a bypass diode. In the sun (a), the bypass
diode is cut off and all the normal current goes through the solar cell. In shade
(b), the bypass diode conducts current around the shaded cell, allowing just
the diode drop of about 0.6 V to occur.
Photovoltaic 32
Impact of bypass diodes. Drawn for five modules in series delivering 65 V to a
battery bank. With one module having two shaded cells, charging current drops
by almost one-third when there are no bypass diodes. With the module bypass
diodes there is very little drop.
Photovoltaic 33