Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Lago 0321

Download as pdf or txt
Download as pdf or txt
You are on page 1of 52

Operating and installation instructions Liability

We will not be held liable for damages resulting from non-observance


Heating Controller Lago 0321 of the instructions and non-compliant use.

Safety instructions
Information that is relevant for safety is indicated in the instructions
as follows:
DANGER
Indicates potentially fatal situations.

WARNING
Indicates possible danger to life and limb.

CAUTION
Indicates possible material damage.
All work and settings in the chapters “Expert” may only be carried
out by a qualified technician. Electrical interventions may only be
carried out by a qualified electrician. The heating system must be
disconnected from the power supply before any electrical work is
carried out on the unit.
Safety Conversion
Please read and keep in a safe place All technical changes are prohibited.

Please read through these instructions carefully before Transport


installing or operating. Following the installation, pass the instruc- On receipt of the product, check that the delivery is complete. Report
tions on to the operator. any transport damage immediately.
These instructions can also be found at www.docuthek.com.
Storage
Explanation of symbols Store the product in a dry place. Ambient temperature: see Techni-
• ,  ,  ,  ... = Action cal data.
▷ = Instruction
Table of contents

Table of contents
Heating Controller Lago 0321 . . . . . . . . . . . . . . . . . . . . . . . . . 1 User – Set parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
List of parameters P01 to P19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Explanation of the parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table of contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 P01 – P07 Heating program 2 (Monday to Sunday) . . . . . . . . . . . . . . . 14
P08 Operating mode direct heating circuit (HC1)/
Verify type of application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 P13 Operating mode mixer circuit (HC2) . . . . . . . . . . . . . . . . . . . . . . 14
Type designation codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 P09 Heat slope direct heating circuit/
P14 Heat slope mixer circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Part designations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 P10 Room sensor influence direct heating circuit/
Selector switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 P15 Room sensor influence mixer circuit . . . . . . . . . . . . . . . . . . . . . . 15
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 P11 Room sensor correction direct heating circuit/
P16 Room sensor correction mixer circuit . . . . . . . . . . . . . . . . . . . . . 15
User – Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
P18 Hot water according to program . . . . . . . . . . . . . . . . . . . . . . . . . 15
Set time and day of the week . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 P19 Indication of heating program at the lower margin of the display . 16
Set the desired temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Desired room temperature Day . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 User – Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Setback temperature (desired room temperature Night) . . . . . . . . . . . . 8 How do I switch to summer/winter time? . . . . . . . . . . . . . . . . . 16
Desired hot water temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 How do I set the heating controller so that it gets warm
Display actual temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 sooner in the morning? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Set operating mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 My heater does not get warm enough. What can I do? . . . . . . . 16
Standby/OFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 How do I set the heating system for holidays? . . . . . . . . . . . . . 17
1 Automatic mode 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 How can I switch the heating system off during the summer? . . 17
2 Automatic mode 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Day mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Is it possible to let the heating system run longer in the
Night mode (reduced night mode) . . . . . . . . . . . . . . . . . . . . . . . . . . 10
evening for special occasions such as a party? . . . . . . . . . . . . . 17
Summer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 How do I set the heating controller to save energy? . . . . . . . . . 17
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Which room is allocated to which heating circuit? . . . . . . . . . . . 17
HO Holiday . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 My heating system is not running . . . . . . . . . . . . . . . . . . . . . . . 17
Set heating program 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Set heating program 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Load factory settings (Reset) . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

2
Table of contents
Expert - Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 P32 Warm-Up Temp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
P33 Minimum limit heat source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Expert - Electrical connections . . . . . . . . . . . . . . . . . . . . . . . 18 P34 Dynamic switching hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Define application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 P35 Hysteresis time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Connection diagram controller without socket . . . . . . . . . . . . . . 21 P36 Burner starts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
P37 Burner operating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Connection diagram controller with socket . . . . . . . . . . . . . . . . 22
P38 Address heating module (only for cascade operation) . . . . . . . . 35
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 P50 DHW Relief (charging pump lock) . . . . . . . . . . . . . . . . . . . . . . . . 35
Maximum limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 P51 Parallel pump operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Examples of installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 P52 Antilegion function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Heating system controller for heat source, mixed heating circuit and P53 Temperature increase during hot water preparation . . . . . . . . . . 36
hot water preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 P60 Maximum flow temperature direct heating circuit . . . . . . . . . . . . 36
Heating system controller for mixed heating circuit and hot water P61 Minimum flow temperature direct heating circuit . . . . . . . . . . . . 36
preparation from a buffer storage tank . . . . . . . . . . . . . . . . . . . . . . . . 25 P69 Additional mixer functions (P77 – 79) . . . . . . . . . . . . . . . . . . . . . . 36
Heating system controller for direct heating circuit, mixed heating P70 Maximum flow temperature mixer circuit . . . . . . . . . . . . . . . . . . 36
circuit and hot water preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
P71 Minimum flow temperature mixer circuit . . . . . . . . . . . . . . . . . . . 36
Controller for a mixed heating circuit as expansion for a heating
system controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 P72 Mixer Dynamic OPEN (when opening)/
P73 Mixer Dynamic CLOSED (when closing) . . . . . . . . . . . . . . . . . . . 36
Controller for a heat source in a cascade: Heating module . . . . . . . . 28
74 T-Flow Cooling (flow temperature Cooling) . . . . . . . . . . . . . . . . . . 37
Internal hot water preparation of the first heat source in the cascade
(hydraulic separation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 P75 T-Room Cooling (desired room temperature) . . . . . . . . . . . . . . . 37
P76 Min TO Cooling (Minimum outside temperature for cooling) . . . . 37
Expert – Set DIP switches . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 P77 Mixer scan time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Direct heating circuit or multifunction relay . . . . . . . . . . . . . . . . . . . . . 31 P78 Mixer operating time limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Assigning a remote control FBR2 to the direct heating circuit or P79 Mixer start seconds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
mixer circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 P80 MF Relay function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Set sensor resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 P81 Switching temperature of the multifunction relay . . . . . . . . . . . . 40
P82 Multifunction relay hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Expert – Set parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 P97 PC enable (0000 = disabled) . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
List of parameters P20 to P99 . . . . . . . . . . . . . . . . . . . . . . . . . . 33 P98 Relay Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Explanation of the parameters . . . . . . . . . . . . . . . . . . . . . . . . . . 34 P99 Software version and index (63.XX) . . . . . . . . . . . . . . . . . . . . . . 40
P20 Code no. input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
P21 code no. change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Expert – Checklist for commissioning . . . . . . . . . . . . . . . . . 41
P22 Outside temperature frost protection . . . . . . . . . . . . . . . . . . . . . 34
P23 CAN bus ID mixer circuit (heating circuit address) . . . . . . . . . . . . 34
P30 Maximum heat source temperature . . . . . . . . . . . . . . . . . . . . . . 34
P31 Heat source minimum temperature . . . . . . . . . . . . . . . . . . . . . . 34

3
Table of contents
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Help with faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
STL Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Operating module Merlin BM, BM 8, or remote control Lago Flow and return flow temperature . . . . . . . . . . . . . . . . . . . . . . . 50
FB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Merlin BM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Desired and actual temperature . . . . . . . . . . . . . . . . . . . . . . . . 50
Lago FB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Setback temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
PC Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Heat source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
CoCo PC active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Circulation pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
CoCo PC mobile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Direct heating circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Remote control and room sensor FBR2 . . . . . . . . . . . . . . . . 44
Mixed heating circuit / Mixer circuit . . . . . . . . . . . . . . . . . . . . . . 50
Room sensor RFB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Heating time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Outside sensor AF/AFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Boiler sensor KF/KFS Header pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Storage sensor SPF/SPFS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Feed pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Flow sensor VF/VFAS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Legionella . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Sensor values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

4
Table of contents
Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Eurasian Customs Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Heating circuit allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
For the installation expert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

5
Verify type of application

Verify type of application Part designations


Heating controller to be used as a 5
– heating system controller,
– mixer extension or Tim e
Mode
1
– as a controller for a heat source in a cascade,
o–Su °C
OK⇒M
So
Fr Sa
Th
Tu We

for further explanation see page 18 (Expert - Electrical connections).


Mo °C

/ 1
Mo–Fr
1
Sa–S
u
°C 4
1

The heating controller regulates two independent heating circuits:


1

one indirect heating circuit and one mixer circuit. 2


The function is only guaranteed within the specified limits, see page 4
49 (Technical data).
OK
>1s

Any other use will be deemed improper use.


3

Type designation codes 1 Selector switch


Code Description 2 Rotary knob
Lago Heating controller for changing the set values and displaying the temperatures
0 On//Off boiler control 3 OK button
for displaying the desired temperature of the heat source, for
3 Mixer circuit and hot water preparation confirming settings, and the for testing the Safety Temperature
Limiter
2 Temperature-controlled multifunction relay 4 Assembly holder of the controller
1 CAN bus communication 5 Cable feed-throughs

Selector switch
Standard
Mode Operating mode selection
°C Desired room temperature Day (for both heating
circuits)
°C Setback temperature (for both heating circuits)
°C Desired hot water temperature
Sa – Su Heating program 1 from Saturday to Sunday
Mo – Fr Heating program 1 from Monday to Friday
Parameter setting for User and Expert
Time Setting the time and the day of the week

6
Verify type of application
Display 6 Operating modes:
Mo Tu We Th Fr Sa Su
1 Operational readiness/OFF (Heating and hot water
2 preparation OFF, frost protection operation only)
3 1 Automatic mode 1 (Heating according to heating program
4 1, hot water according to parameter 18)
5 2 Automatic mode 2 (Heating according to heating program
1 2 / 1
6 2, hot water according to parameter 18)
7
Day mode (24 hour heating with desired room temperature
1 Days Monday – Sunday underlined Day, hot water according to parameter 18)
2 Communication to devices on the CAN bus (such as Lago FB,  Night mode (24 hour heating with setback temperature, hot
BM8, Merlin BM) water according to parameter 18)
3 Status indications:
Burner, Summer mode (Heating OFF, hot water according to
parameter 18)
Mixer circuit pump,
 Service (Heat source controls to maximum heat source
Hot water enabled, temperature.)
Storage charging pump,
Holiday mode (During holidays the rooms are heated to 15
Mixer open, °C, after the holidays the rooms are automatically heated
Mixer closed, according to heating program again.)
Room temperature, 7 Display of the heating times
/ 1 Multifunction relay /Pump direct heating circuit
4 Heat source temperature (When used as a mixer expansion,
"--" is displayed.)
5 Time

7
User – Settings

User – Settings 4 Press the OK button.


▷▷ The new desired temperature is displayed.
5 Turn selector switch back to .
Set time and day of the week
1 Turn selector switch to Time. Display actual temperatures
2 Press the OK button. 1 Turn selector switch to .
▷▷ Display flashes. 2 Use the rotary knob to set one of the following temperature indi-
3 Set time with rotary knob. cations:
4 Press the OK button.
5 Set day of the week with rotary knob. H1 to H8
Room temperature for up to 8 heating circuits
6 Press the OK button. +
AF Outside temperature
▷▷ The new time and the day of the week is displayed. Heat source and concurrently flow temperature of the
7 Turn selector switch back to . *)
direct heating circuits (1st HC)
▷▷ To cancel the settings without saving, turn the selector switch *) Flow temperature of the mixer circuit (2nd HC)
back to at any time. *) Hot water temperature
FF *) Multifunction sensor temperature
Set the desired temperature
* The desired temperature is displayed when the OK button is pressed.
Desired room temperature Day ▷▷ If a sensor is not connected, the display will show -- --.
▷▷ Active during heating times ▷▷ The display reverts to the standard indication after a few seconds
1 Turn selector switch to °C . without action.

Setback temperature (desired room temperature Night) Set operating mode


▷▷ Active between heating times The operating mode determines how the heating controller works.
1 Turn selector switch to °C . Whether the heating system is to be controlled automatically or manu-
Desired hot water temperature ally, during a party for example. Or how should the heating system
1 Turn selector switch to °C . be controlled during longer periods of absence such as holidays?
▷▷ The heating controller leaves the factory with the setting
All three temperatures Standby/OFF. The operating mode must be changed for normal
2 Press the OK button. operation.
▷▷ Display flashes. 1 Turn selector switch to “Mode”.
3 Set day of the desired temperature with rotary knob. 2 Press the OK button.

8
User – Settings
▷▷ Display flashes. Lago#1 controls the first heating circuit and hot water. Lago #2
3 Set the operating mode using the rotary knob. controls the second heating circuit and Lago #3 the third. If mode
4 Press OK after you have selected your setting. was selected for Lago #1, the entire system will be switched off,
▷▷ The new operating mode is displayed. regardless of the settings for the other controllers.
5 Turn selector switch back to .
▷▷ All operating modes have an effect on the heat source and on You can set the following operating modes
both internal heating circuits of the controller. A different mode
Standby/OFF
can be assigned to each heating circuit individually, see page 12
Heating and hot water preparation are deactivated. Only the frost
(User – Set parameters).
protection function remains active.
▷▷ If the controller is used as a heating system controller, all heating
circuits of the system are deactivated for operating modes and 1 Automatic mode 1
. This only applies to the associated heating circuit when used Heating occurs according to heating program 1: Heating occurs at
as a mixer expansion. identical times for Monday – Friday, as well as Saturday – Sunday. Hot
water according to parameter 18, see page 11 (Set heating program 1).
Example: Installation with three mixed heating circuits and
hot water preparation 2 Automatic mode 2
#1 #2 #3 Heating occurs according to heating program 2: You can set Individual
Lago 0321 Lago 0321 Lago 0321 heating times for each day. Hot water according to parameter 18,
see page 11 (Set heating program 2).
▷▷ Toggling between Automatic mode 1 and 2 can be useful for shift
workers. The times do not need to be entered for each shift - they
only need to be switched over.

Day mode
Heating occurs for 24 hours to desired room temperature Day. Hot
water according to parameter 18, see page 8 (Set the desired tem-
perature).
This setting is required for events such as a party, when the heat-
Lago #1 #2 #3 ing period in automatic mode will not be sufficient. Do not forget to
off off 1 off 1 off
1 on on off 1 on switch back to automatic mode once the party is over.
off on 1 off 1 off

9
User – Settings

Night mode (reduced night mode) Mode 1 Turn selector switch to „Mode“.
Heating is reduced to the setback temperature for 24 hours. Time
Mo–S
u °C
OK⇒
Hot water according to parameter 18, see page 15 (P18 Hot water e Th
Fr Sa
So

Tu W
according to program). Mo °C

Mo–Fr
This setting can be used to save energy; in exceptional cases when / 1 1
Sa–S
u
1
°C
Mode

no-one is going to be home during the day over a longer period of


1
OK⇒
Mo–Su
Time

▷▷ The display shows the current operating mode


°C

time for example. Do not forget to switch back to automatic mode


So
Fr Sa
Mo Tu
e ThWe Th Fr Sa So
Mo
Tu W
(e.g. automatic mode 1) °C

once the party is over. / 1


Mo–Fr
1
u
°C
Sa–S
1
1
1
Summer mode
/ 1

The heating system is switched off to save energy. Parameter OK 18 for


hot water must be set to 1, 2 or 4, see page 12 (User – Set parameters).
>1s 2 Press the OK button.
Mode
Time
OK
▷▷ Display flashes.
Service
Su
OK ⇒Mo– °C
>1s
So
Fr Sa
The heat source heats to the max. temperature set in parameter
Mo
Tu W
e Th
°C

30. As soon as the temperature of 65 °C has been reached, the / 1


Mo–Fr
1 °C
u
Sa–S
consumers regulate to their max. flow temperature for heat removal. 1
1
3 Rotate the rotary knob clockwise until HO 4
Automatic reset after 15 min.
flashes in the display.
HO Holiday ▷▷ HO 4 indicates that 4 absent days have been pro-
During holidays the room temperature is regulated to 15 °C. grammed (in this example Mon, Tue, Wed and
ode
▷▷ If parameter 18 is set to 3, hot water preparation is deactivated, Thu).MTime
Mo–Su °C
OK OK⇒

see page 15 (P18 Hot water according to program). If>1parameter


s
Mo
Mo e Th
Fr Sa
Tu WTu We Th Fr
So
e
ModSa So
Mode
°C
Time
18 is set to 0, 1, 2 or 4, the HO Holiday mode has no effect Time
Mo–S
u So / °C
1
Mo–Su
OK⇒Mo–Fr
1 °C
°C

OK⇒ Fr Sa

on the hot water preparation.


u
e Th Sa–S
So Tu W 1
Fr Sa Mo 1 °C
e Th
Tu W / 1
Mo °C Mo–Fr °C
/ 1 1
u
Sa–S

Example: Setting HO Holiday operating mode / 1


Mo–
1
Fr
1
u
°C
1

Sa–S
You leave on Monday and return Thursday evening. Before leaving
1
1
4 Press the OK button.
on Monday program:
OK
▷▷ The display shows HO 4.
>1s

OK
>1s

OK
>1s

10 Time
Mode

Su
User – Settings

Mode 5 Turn selector switch back to . Example: Indication of the heating times for heating
Time
Mo–S
u °C ▷▷ The holiday function starts immediately and ends program 1
OK⇒

Th
Fr Sa
So
on Thursday at 24:00. On Friday (day 5) heating Heating is to occur from Monday to Friday respectively between 6:00
°C
mode reverts to the original mode. and 8:00 in the morning, from 11:30 to 13:00 at lunchtime and from
/ 1
Mo–Fr
1
Sa–S
u
°C
▷▷ Should you return from your holiday before this 18:00 to 22:00 in the evening.
1

time, you will need to set the original operating Mo Tu We Th Fr Sa So


mode again (e.g. automatic mode 1).

OK Set heating program 1 1 / 1

Heating program 1 is assigned to automatic mode 1. It is used


0 6 12 18 24
to define the heating times for the working week (Mo – Fr) and the
weekend (Sa – Su). You can set three heating times per day. 7 Finally, turn the selector switch back to .
▷▷ During heating times the controller heats to desired temperature, ▷▷ The heating program 1 has been set. In order to apply it, set
between heating times to setback temperature. the operating mode to “ 1 Automatic Mode 1” , see page 8 (Set
1 Rotate selector switch to Mo – Fr 1 or Sa – Su 1. operating mode).
2 Press the OK button. ▷▷ To cancel the process without saving, turn the selector switch
▷▷ The start time of the first heating time flashes. back to at any time.
3 Use the rotary knob to select the start time. ▷▷ Factory setting:
4 Press the OK button. Mo – Fr: 6:00 to 22:00
▷▷ The end of the first heating time flashes. Sa – Su: 7:00 to 23:00
5 Use the rotary knob to select the end time.
6 Press the OK button. Set heating program 2
▷▷ Continue with step 3 to set the second and third heating time. Heating program 2 is assigned to automatic mode 2. It can be
▷▷ The heating times will only be saved once you have entered all used to set the heating times for each individual day. You can set
three heating times or have set the start time to “----”. three heating times per day.
▷▷ If you want to delete an existing heating time, use the rotary knob ▷▷ During heating times the controller heats to desired temperature,
to set the start or end time to “----”. between heating times to desired temperature Night.
1 Turn selector switch to (Parameter setting).
▷▷ The display shows .

11
User – Set parameters
2 Turn the rotary knob one step in clockwise direction. Load factory settings (Reset)
▷▷ The display shows 01 (Monday). ▷▷ All personal settings will be lost.
3 Press the OK button. 1 Take a note of all the settings you have made in these instructions.
▷▷ The start time of the first heating time flashes. 2 Switch off mains.
4 Use the rotary knob to select the start time. 3 When switching the mains back on, keep the OK button pressed
5 Press the OK button. until EE P appears in the display.
▷▷ The end of the first heating time flashes. ▷▷ The factory settings have been loaded.
6 Use the rotary knob to select the end time.
7 Press the OK button.
User – Set parameters
▷▷ Continue with step 3 to set the second and third heating time.
▷▷ The heating times will only be saved once you have entered all As for heating program 2 you can change further parameters to
three heating times or have set the start time to “----”. adapt the heating system to your requirements.
▷▷ If you want to delete an existing heating time, use the rotary knob 1 Turn selector switch to (Parameter setting).
to set the start or end time to “----”. ▷▷ The display shows .
Example: see page 11 (Set heating program 1). 2 Turn the rotary knob clockwise until the parameter you want
8 Turn the rotary knob clockwise to the next day: 02 = Tuesday to to change appears in the left-hand side of the display: 08 to 19
07 = Sunday. (operating mode direct heating circuit until to display heating
▷▷ Continue with step 3. program).
9 Finally, turn the selector switch back to . 3 Press the OK button.
▷▷ The heating program 2 has been set. In order to apply it, set ▷▷ Display flashes.
the operating mode to “ 2 Automatic Mode 2”, see page 8 (Set 4 Use the rotary knob to set the desired value.
operating mode). 5 Press the OK button to confirm.
▷▷ To cancel the process without saving, turn the selector switch 6 After you have made the setting, continue with step 2 if you want
back to at any time. to change further parameters, or turn the selector switch back to
▷▷ Factory setting: .
Mo – Fr: 6:00 to 8:00, 16:00 to 22:00 ▷▷ The table – see page 13 (List of parameters P01 to P19) – shows the
Sa – Su: 7:00 to 23:00 possible settings (including the parameters for heating program 2).
▷▷ The heating controller will only display those parameters for which
there are sensors connected.

12
User – Set parameters
List of parameters P01 to P19
P-No. Parameter Setting range Factory setting Own values
01 Heating program 2 for Monday 00:00 – 24:00
02 Heating program 2 for Tuesday 00:00 – 24:00 06:00 – 08:00
03 Heating program 2 for Wednesday 00:00 – 24:00
04 Heating program 2 for Thursday 00:00 – 24:00 16:00 – 22:00
05 Heating program 2 for Friday 00:00 – 24:00
06 Heating program 2 for Saturday 00:00 – 24:00
07:00 – 23:00
07 Heating program 2 for Sunday 00:00 – 24:00
08 Operating mode direct heating circuit (HC1) ----, , 1, 2, , ----
09 Heat slope direct heating circuit 0.20 – 3.00 1,20
Room sensor influence
10 OFF, 0 – 20 10
direct heating circuit
Room sensor correction
11 -5 to +5 K 0
direct heating circuit
13 Operating mode mixer circuit (HC2) ----, , 1, 2, , ----
14 Heat slope mixer circuit 0.20 – 3.00 1.20
With underfloor heating set parameter 14 < 1, with radiator heating > 1.
Room sensor influence
15 OFF, 0 – 20 10
Mixer circuit
Room sensor correction
16 -5 to +5 K 0
Mixer circuit
0 = Off
1 = Heating program 1
18 Hot water according to program 2 = Heating program 2 1
3 = 1 hour before heating
4 = 24 hours hot water
Indication of heating program at the lower margin of the 0 = for direct heating circuit
19 0
display 1 = for mixed heating circuit

13
User – Set parameters

Explanation of the parameters In order to use different heating times for the mixer circuit, set pa-
rameter 13 to 2 = Automatic mode 2.
P01 – P07 Heating program 2 (Monday to Sunday) Now you can use Heating program 1 to set the heating times for
Heating program 2 is assigned to Automatic mode 2, see page 11 your radiators and Heating program 2 to set different times for the
(Set heating program 2). floor heating, see page 11 (Set heating program 1) and page 11 (Set
heating program 2).
P08 Operating mode direct heating circuit (HC1)/ If the floor heating is meant to be switched off, set parameter 13 to
P13 Operating mode mixer circuit (HC2) = Standby/OFF.
P08 = ----: The direct heating circuit operating mode corresponds
to the value in chapter “Set operating mode”. P09 Heat slope direct heating circuit/
P13 = ----: The mixer circuit operating mode corresponds to the P14 Heat slope mixer circuit
value in chapter “Set operating mode”. Selecting the correct heat slope saves energy because the heat
A separate and different operating mode can be selected for both sources only heat to the point required by the respective outside
circuits individually. temperature.
1 = Standby/OFF The heat slope specifies the number of °C by which the flow tem-
2 = 1 Automatic mode 1 perature changes when the outside temperature rises or drops.
3 = 2 Automatic mode 2 ▷▷ Before you select the heat slope, set the room temperature to the
4 = Day mode desired value, see page 8 (Set the desired temperature).
5 = Night mode (reduced night mode) ▷▷ Ideally, the heat slope is set when the outside temperature is below
Exception: The general operating modes Standby/OFF and 5 °C. Changes to the heat slope setting must be applied in small
Summer mode have a reducing effect on the entire system. All steps and long intervals (at least 5 – 6 hours between steps). The
heating circuits are switched off. system must be allowed to adjust to the new value after each
change to the heat slope.
Example: Heating by means of radiators and underfloor ▷▷ Select the heat slope so that the desired room temperature is
heating achieved with the thermostat valves fully opened, and doors and
In your house you have heaters that supply the direct heating circuit windows closed.
with water, and underfloor heating that heats the mixer circuit. Be- ▷▷ Increase the heat slope if the desired room temperature is not
cause underfloor heating acts slower than a radiator, the underfloor reached in combination with low outside temperatures.
heating is to be switched on and off beforehand. ▷▷ If the desired room temperature is not reached in combination with
Set the general operating mode “ 1 Automatic mode 1”, see page high outside temperatures, increase the desired room temperature.
8 (Set operating mode). • Now change the heat slope.

14
User – Set parameters
▷▷ Typical values: Within the range 0 – 20 the heating circuit pump operates up to the
floor heating: 0.4 to 0.8 next heating time if there is a heating requirement during the period
Radiators: 1.0 to 1.5 of reduced temperature Night (e.g. frost protection of when the
temperature drops below the setback temperature. This prevents
3
100
2,5 the rooms from becoming too cool.
Flow temperature [°C]
2 Example: P10/15 = 5
With this setting the desired temperature of the heat source is in-
80
creased by 5 K when the room temperature drops below the desired
1,5
room temperature by 1 K.
1,2
60
1 P11 Room sensor correction direct heating circuit/
P16 Room sensor correction mixer circuit
0,8 Only active if a room sensor is connected or an FBR2 remote control
40 0,6 with integrated room sensor is used. This setting can be used to cor-
0,4 rect measurement errors of the connected room sensor, e.g. when
0,2 the room sensor is influenced by incorrect positioning.
20
Setting range: P11/16 = -5 to +5 K.
20 16 12 8 4 0 -4 -8 -16 -20
Outside temperature [°C]
Example: Room sensor correction direct heating circuit
Your room sensor measures 20 °C. A reference thermometer, how-
P10 Room sensor influence direct heating circuit/ ever, determines 22 °C. Now set parameter 11 = 2 so that the value
P15 Room sensor influence mixer circuit 2 K is added to the measured value.
Only active if a room sensor is connected or an FBR2 remote control
with integrated room sensor is used. It is possible to adjust the influ- P18 Hot water according to program
ence of the room sensor on the control process. This parameter can be used to define the heating times for hot water.
▷▷ The higher the set value the greater the influence of the room P18 = 0: Off (no hot water preparation)
sensor on the calculated flow temperature. P18 = 1: hot water in line with heating program 1
P10/15 = OFF: purely weather-guided control P18 = 2: hot water in line with heating program 2
P10/15 = 0: purely weather-guided control P18 = 3: 1 hour before the heating times of automatic mode 1 or 2.
P10/15 = 20: pure room temperature control (The desired automatic mode is set via the operating mode.
With activated HO Holiday mode the hot water preparation is
not switched on.)

15
User – Questions
With the mode “Summer mode” parameter 18 must be set to 1, User – Questions
2, or 4.
P18 = 4: 24 hours hot water
How do I switch to summer/winter time?
Example: P18 = 3 To switch from summer to winter time and vice verse you need to
If “Automatic mode 1” was selected as the operating mode, the reset the time, see page 8 (Set time and day of the week).
heating controller will always switch on the hot water one hour before
switching on the heating. If HO Holiday mode is activated, the How do I set the heating controller so that it gets
hot water is not switched on. warm sooner in the morning?
P19 Indication of heating program at the lower margin of There are two heating programs to set the heating times.
the display Heating program 1 for setting the heating times Mo – Fr (working
P19 = 0: The heating program for the direct heating circuit is dis- week) and Sa – Su (weekend) for the week as a whole,
played. Heating program 2 for setting the heating times for each day of the
P19 = 1: The heating program for the mixed heating circuit is dis- week Mo, Tu, We, Th, Fr, Sa and Su.
played. Heating program 1 in operating mode 1 is assigned to automatic
mode 1.
Heating program 2 in operating mode 2 is assigned to automatic
mode 2.
First select automatic mode 1 or 2, see page 8 (Set operating
mode).
Then adjust the associated heating program to suit your needs, see
page 11 (Set heating program 1) or 11 (Set heating program 2).

My heater does not get warm enough. What can


I do?
You have two options.
First increase the desired room temperature Day, see page 8 (Set
the desired temperature).
Wait for a few hours to give the heating system time to respond to
the new setting.

16
User – Questions
Should the room(s) still not get warm enough, you can increase How do I set the heating controller to save
the heat slope for the direct heating circuit or the mixer cir- energy?
cuit, see page 14 (P09 Heat slope direct heating circuit/
▷▷ Set the desired room temperature only as high as absolutely
P14 Heat slope mixer circuit).
necessary. The energy consumption is increased by around 6%
Should this measure not be sufficient, see page 47 (Help with faults)
for every degree, see page 8 (Set the desired temperature).
and contact your heating engineer.
▷▷ Set your heating program so that it switches the heating off at
night or at times when no-one is home.
How do I set the heating system for holidays? ▷▷ Only open you windows briefly to let in fresh air. Avoid tilted win-
If you want to go away for a number of days, you dows over longer periods.
can set the heating controller to the operating mode
“  HO Holiday”. The heating system will revert to automatic mode at Which room is allocated to which heating
the end of the holiday so that it will be warm when you come home,
see page 8 (Set operating mode).
circuit?
Please contact your heating engineer to answer this question. You
How can I switch the heating system off during will find a table on the last page of these instructions where these
allocations can be entered.
the summer?
In summer you should set the heating controller to the operating My heating system is not running
mode “Summer mode”. This mode deactivates heating and the
Check the selector switch position. The selector switch must be
system is only used for hot water, see page 8 (Set operating mode).
set to .
Check the operating mode. The display must indicate 1 for Automatic
Is it possible to let the heating system run longer mode 1, or 2 for Automatic mode 2, see page 8 (Set operating mode).
in the evening for special occasions such as a
party?
For this purpose select the operating mode “ Day mode”, see page
8 (Set operating mode).

17
Expert - Electrical connections

Expert - Installation Expert - Electrical connections

CAUTION WARNING
The minimum distance from surrounding heat sources is to be Possible life-endangering electrical shock! Switch the power off to
chosen so that the permitted ambient temperature will not be electrical cables before working on power-carrying parts!
exceeded during operation, see page 49 (Technical data).
CAUTION
1a 1b 2 For fixed devices, an isolating mechanism must be installed for
shutting off from the network, in accordance with the installation
guidelines and EN 60335, e.g. with a switch.
The insulation for line conductors is to protected against damage
by overheating, e.g. insulating sleeve.
3
Define application
A B
Top
BA The Lago 0321 can be used for three different applications:
as a heating system controller, as a mixer expansion, or as a controller
for a heat source (boiler control) in a cascade.
The application is determined automatically by connecting certain
A A sensors and on setting specific parameters.
B

A 95
B 75

Ø 3,5
57

60

18
Expert - Electrical connections
Heating system controller Controller for a mixed heating circuit as expansion for a
Lago 0321 heating system controller
Lago 0321

VF
SPF
1 2 VF

KF

Connect heat source sensor (KF/KFS), flow sensor (VF/VFAS) and


storage sensor (SPF/SPFS), This application is automatically activated if only one flow sensor
Parameter 38 = “----” (no heating module address) (VF/VFAS) is connected.
The following functions are now active: Set parameter 23 to heating circuit address (2 – 15).
▷▷ control of a single-stage heat source or an alternative heat removal The following functions are now active:
from a buffer storage tank, ▷▷ Control of an additional mixed heating circuit (expansion for a
▷▷ control of a hot water preparation system, heating system controller), e.g. in a multi-family unit.
▷▷ control of a mixed heating circuit, ▷▷ Control of an additional function with multifunction relay, e.g.
▷▷ control of a direct heating circuit or, alternatively, an additional circulation pump or return flow booster. (For this purpose, set
function with multifunction relay, such as a circulation pump, return the DIP switches and parameters 80 – 82.)
flow temperature increase or header pump. (For this purpose, The following functions can not be used:
set the DIP switches and parameters 80 – 82. Additional sensors ▷▷ Header pump
may be required.) ▷▷ Heat source pump

19
Expert - Electrical connections
Controller for a heat source in a cascade: Heating module
CAN-Bus
#1 #2 Merlin
Lago 0321 Lago 0321

KF KF
VF SPF

This application is automatically activated as soon as you connect


a heat source sensor (KF/KFS) and set parameter 38 = 1 – 8 (heat-
ing module address).
The following functions are now active:
▷▷ Control of a heat source in a cascade,
▷▷ Control of an additional function with multifunction relay, e.g. heat
source pump or return flow booster.
▷▷ A cascade manager, such as Merlin 5064, is required for heating
circuit and hot water control.

20
Expert - Electrical connections

Connection diagram controller without socket ▷▷ Use solid lines or flexible lines with wire
end sleeves for connections (230 V).
Sensor ▷▷ Route CAN bus lines and sensor lines
230 V separately from power lines.
11 H
▷▷ Never mix 1 kΩ and 5 kΩ sensors.

CAN-BUS
12 L N 1
▷▷ Only connect sensors required for the
13 – L1 2
14 + L1’ 3 system.
15 1
1/
4
Sensor
▷▷ Connect a bridge between terminal 16

FBR2
2 2 and GND11bus terminal. If the bridge be-
16 5 H

CAN-BUS
17 3 6 tween terminal
12 L16 and GND is omitted, N
18 SPF 2 7 the sensor
13 values
– will not be displayed.
M
19 RF GND 8 ▷▷ Set bridge
14and +reset heating controller.
20 KF T1 9 15 1

FBR2
21 VF 2 T2 10 16 2
22 AF 17 3

ON
18 SPF
= OFF = ON 19 RF GND
123456
20 KF
21 VF 2
SELV, safety extra low voltage ~230 V, switching capacity of the relays 2(2) A, ~250 V 22 AF
11 – 14 CAN-BUS 1 Neutral conductor mains
ON
15 – 17 FBR2, alternatively: 2 Mains voltage heating controller L1 = OFF
15 – 16 Room thermostat 3 Mains voltage for the outputs L1‘ 123456
Pump heating circuit 1 or
16 – 17 Phone switch 4
multifunction relays
18 Storage sensor 5 Pump heating circuit 2
Room sensor or multifunction sen-
19 6 Storage charging pump
sor
20 Boiler sensor 7 Mixer Open
21 Flow sensor 8 Mixer Close
22 Outdoor sensor 9 – 10 Burner electrically isolated
▷▷ Use solid lines of flexible lines with wire end sleeves for connections (230 V).
▷▷ Route bus lines and sensor lines separately from power lines.
▷▷ Never mix 1 kΩ and 5 kΩ sensors.

21
Expert - Electrical connections

Connection diagram controller with socket ▷▷ Use solid lines or flexible lines with wire
end sleeves for connections (230 V).
Sensor ▷▷ Route CAN bus lines and sensor lines
230 V separately from power lines.
N H 11
N ▷▷ Never mix 1 kΩ and 5 kΩ sensors.

CAN-BUS
1 Top L 12 ▷▷ Only connect sensors required for the
2 L1 – 13
system.
3 L1’ + 14
/ 1 ▷▷ Connect a bridge between Sensorterminal 16
4 230 15
1 V and GND bus terminal. If 11 bridge be-
the

FBR2
2 N
5 2 16 N H

CAN-BUS
6 3 17
1 tween
Top terminal 16 and
L GND12 is omitted,
7 2 SPF 18
2 L1 the sensor values will– not be
13 displayed.
M GND
8 RF 19
3 L1’ ▷▷ Set bridge and reset +heating14 controller.
/ 1
9 T1 KF 20
4 1 15

FBR2
2
10 T2 VF 2 215 2 16
AF 22
6 3 17
7 M
2 GND SPF 18
8 RF 19
9 T1 KF 20
~230 V, switching capacity of the relays 2(2) A, ~250 V SELV, safety extra low voltage
10 T2 VF 2 21
1 Neutral conductor mains 11 – 14 CAN-BUS AF 22
2 Mains voltage heating controller L1 15 – 17 FBR2, alternatively:
3 Mains voltage for the outputs L1‘ 15 – 16 Room thermostat
Pump heating circuit 1 or
4 16 – 17 Phone switch
multifunction relays
5 Pump heating circuit 2 18 Storage sensor
6 Storage charging pump 19 Room sensor or multifunction sensor
7 Mixer Open 20 Boiler sensor
8 Mixer Close 21 Flow sensor
9 – 10 Burner electrically isolated 22 Outdoor sensor

22
Expert - Electrical connections

Options
Provided no separate regulations for protecting the relay apply, a
bridge to supply the relay must be connected between terminals
2 and 3.

230 V
N
N
1
230 V2 L1
3 N
1 Top
Maximum limiter 2
3
4 ϑ
2
5
6
7 heating circuit, e.g. in
If a maximum limiter is required for the mixed
8
combination with underfloor heating, the limiter must be connected
9
between terminal 5 and the heating circuit pump.
10

23
Expert - Electrical connections

Examples of installations ▷▷ FBR2 Remote control with room sensor,


▷▷ RFB Room sensor on terminals 15+16,
Heating system controller for heat source, mixed heating ▷▷ Lago FB, BM8 or Merlin BM operating module, connected via a
circuit and hot water preparation CAN-BUS (Terminals 11 – 14).

Requirements Set parameters


In the condition as supplied to the customer the heating controller can P14, P18, P19 and P70
be used for this system, provided the required sensors are connected. The factory settings apply for all other parameters, see page 32
(Expert – Set parameters).
AF
Lago 01
22 Set DIP switches
ON = OFF
T1 T2 1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON
20 9 10 78 5 21 6 18
ON
2

SPF 1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ)


VF

See page 31 (Expert – Set DIP switches) for explanation.

KF
2

Sensors, see page 43 (Accessories)


▷▷ AF/AFS external sensor: only with atmospheric control
▷▷ KF/KFS boiler sensor: in combination with heat source control
▷▷ VF/VFAS flow sensor: only with mixed heating circuit
▷▷ SPF/SPFS storage sensor.

Room control
The room temperature can be detected and controlled as follows:

24
Expert - Electrical connections
Heating system controller for mixed heating circuit and hot ▷▷ If no heat source sensor (KF/KFS) is installed, the heating controller
water preparation from a buffer storage tank will show “--” for nothing to display.
▷▷ VF/VFAS flow sensor: only with mixed heating circuit
Requirements ▷▷ SPF/SPFS storage sensor
In the condition as supplied to the customer the controller can be
used for this system, provided the required sensors are connected. Room control
The room temperature can be detected and controlled as follows:
AF
22
Lago 01 ▷▷ FBR2 Remote control with room sensor,

Set parameters
P14, P18, P19, P32, P50, P52, P53 and P70
20 78 5 21 6 18
The factory settings apply for all other parameters, see page 32 (Expert
2
– Set parameters) for explanations.

SPF
VF
Set DIP switches
2 ON = OFF
KF 1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON
2 ON

1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ)

See page 31 (Expert – Set DIP switches) for explanation.

Additional functions with multifunction relay


Sensors, see page 43 (Accessories) The multifunction relay (terminal 4) can be used for additional functions.
▷▷ AF/AFS external sensor: only with atmospheric control ▷▷ DIP switch 4 = “OFF” (Multifunction relay activated)
▷▷ KF/KFS boiler sensor: If the KF/KFS sensor is connected, the
heating circuit pump and the storage charging pump will only
be switched on when the Warm Up Temperature is exceeded at
this sensor. The storage charging pump is only activated when
the heat source temperature (KF/KFS) is also higher than the hot
water temperature (SPF/SPFS).

25
Expert - Electrical connections

Circulation pump, Pump heat source Return flow Heating system controller for direct heating circuit, mixed
parameters 80 1, P80 = 05 booster, P80 = 24 heating circuit and hot water preparation
= 02
Requirements
KF KF
▷▷ DIP switch 4 = “ON” (direct heating circuit)
▷▷ Set parameter 23 = Address 2 – 15 for the mixed heating circuit.
SPF
AF Lago 01
22
20

Set P81 and P82 T1 T2


according to boiler 9 10 4 7 8 5 21 6 18
manufacturer’s

2
specifications

SPF
VF
KF 1 2

Sensors, see page 43 (Accessories)


▷▷ AF/AFS external sensor: only with atmospheric control
▷▷ KF/KFS boiler sensor: in combination with heat source control
▷▷ VF/VFAS flow sensor: only with mixed heating circuit
▷▷ SPF/SPFS storage sensor

Room control
The room temperature can be detected and controlled as follows:
▷▷ FBR2 remote control with room sensor, Assign the desired heating
circuit using DIP switch 5.

26
Expert - Electrical connections
▷▷ If a second room sensor is connected to terminal 19, it automati- Controller for a mixed heating circuit as expansion for a
cally affects the other heating circuit. heating system controller

Set parameters Requirements


P9, P14, P18, P19, P30, P31, P32, P50, P51, P52, P60 and P70 ▷▷ This application is automatically activated if only one flow sensor
The factory settings apply for all other parameters, see page 32 (VF/VFAS) is connected.
(Expert – Set parameters) for explanations. ▷▷ Set parameter 23 = Address 2 – 15 for the mixer circuit to be
controlled. This address must not be assigned to another heat-
Set DIP switches ing circuit.
ON = OFF
1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON Lago 01
ON

1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ)

If a remote control is connected, set DIP switch 5: 7 8 5 21


▷▷ DIP switch 5 = “ON”: Remote control with room sensor FBR2 for

2
direct heating circuit,

VF
▷▷ DIP switch 5 = “OFF”: Remote control with room sensor FBR2
for mixer circuit.
See page 31 (Expert – Set DIP switches) for explanation. 2

Sensor
▷▷ VF/VFAS flow sensor: for the mixer circuit.

Set parameters
P14, P19 and P70
The factory settings apply for all other parameters, see page 32 (Expert
– Set parameters) for explanations.

27
Expert - Electrical connections
Set DIP switches Controller for a heat source in a cascade: Heating module
ON = OFF
Requirements
1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON
This application is automatically activated when
ON
▷▷ a heat source sensor (KF/KFS) is connected and
1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ) ▷▷ parameter 38 is assigned an address 1 to 88 (address heating
See page 31 (Expert – Set DIP switches) for explanation. module).
The heating controller controls “his” heat source according to the
Additional functions with multifunction relay requests from the cascade controller.
The multifunction relay (terminal 4) can be used for additional functions. The internal mixer circuit can be used should the mixer circuits con-
▷▷ DIP switch 4 = “OFF” (Multifunction relay activated) trolled by the cascade controller (e.g. Merlin) be insufficient. In this
Circulation pump, Feed pump 1, Return flow case, parameter 23 for the internal mixer circuit must be set to an
parameters 80 P80 = 03 booster, P80 = 24 address 1 – 15.
= 02
Sensors, see page 43 (Accessories)
KF
▷▷ KF/KFS boiler sensor
▷▷ VF/VFAS Flow sensor (only with use of the internal mixer circuit)
SPF

Set P81 and P82


according to boiler
manufacturer's
specifications

28
Expert - Electrical connections
The multifunction relay controls the heat source pump. The multifunction relay controls the return flow booster.
CAN-Bus CAN-Bus
#1 #2 #1 #2
AF Lago Lago AF
Lago Lago Merlin 0321 0321 Merlin
0321 0321
T2 10 T2 10
T2 10 T2 10
T1 9 T1 9
T1 9 T1 9
19 19
4 20 4 20 4 20 4 20

KF KF KF KF
VF SPF VF SPF

Set parameters Set parameters


P30, P31, P32, P38, P80 = 5 P30, P31, P32, P38, P80 = 24, P81 and P82
The factory settings apply for all other parameters, see page 32 (Expert The factory settings apply for all other parameters, see page 32 (Expert
– Set parameters) for explanations. – Set parameters) for explanations.

Set DIP switches Set DIP switches


ON = OFF ON = OFF
1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON 1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON
ON ON

1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ) 1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ)

See page 31 (Expert – Set DIP switches) for explanation. See page 31 (Expert – Set DIP switches) for explanation.

29
Expert - Electrical connections
Internal hot water preparation of the first heat source in the The factory settings apply for all other parameters, see page 32
cascade (hydraulic separation) (Expert – Set parameters) for explanations.

Requirements Set DIP switches


This mode of operation is automatically activated when ON = OFF
▷▷ a heat source sensor (KF/KFS) is connected and 1 2 3 4 5 6 KF, SPF, VF, AF… (5 kΩ) = ON
▷▷ parameter 38 is assigned an address 1 to 88 (address heating ON
module).
1 2 3 4 5 6 KFS, SPFS, VFAS, AFS… (1 kΩ)
In this application the relay for the hot water charging pump is used
for controlling the three-way valve for switching the heat source to See page 31 (Expert – Set DIP switches) for explanation.
the hot water storage tank. The multifunction relay controls the heat
source pump.
CAN-Bus
#1 #2
AF
Lago Lago Merlin
0321 0321
T2 10 T2 10
T1 9 T1 9
4 20 4 20

KF KF
SPF VF

Set parameters
P30, P31, P32, P38, P80 = 05

30
Expert – Set DIP switches

Expert – Set DIP switches Set sensor resistance


The heating controller can be operated with 5 kΩ or 1 kΩ sensors.
= OFF = ON
• Use DIP switch 6.
▷▷ The DIP switches 1 – 3 are now without function. The heating
1 kΩ PTC
circuit address of the mixer circuit is set via parameter 23, see
5 kΩ NTC
page 34 (P23 CAN bus ID mixer circuit (heating circuit address)). 123456

Direct heating circuit or multifunction relay ▷▷ Only sensor of one type may be used.
The output on terminal 4 can be switched over between “Pump direct
heating circuit” and “Multifunction relay”.
• Use DIP switch 4.
Direct heating circuit
Multifunction relay MF
123456
▷▷ If terminal 4 is to be used for the direct heating circuit pump, set
the heating circuit address 2 or higher for the mixer circuit because
the direct heating circuit occupies address 1.

Assigning a remote control FBR2 to the direct heating


circuit or mixer circuit
A connected remote control FBR2, a connected room sensor or
room thermostat can be assigned to the direct heating circuit or
the mixer circuit if the system is operated with two heating circuits.
• Use DIP switch 5.
Direct heating circuit
Mixer circuit
123456

31
Expert – Set parameters

Expert – Set parameters


▷▷ Parameters P1 to P19 for User, see page 12 (User – Set parameters)
WARNING
Incorrect settings can cause malfunctions and damage the heating
installation! Only a qualified expert may change the parameters
from no. 21. 
▷▷ A code number must be entered via parameter P20 to change
parameters P21 and higher.
1 Turn selector switch to (Parameter setting).
▷▷The display shows .
2 Turn the rotary knob until the parameter you want to change or
retrieve appears on the left in the display: 21 to 99.
3 Press the OK button.
▷▷ The indicator jumps to 20 0000. The first digit flashes.
4 Enter code no. (factory setting is 0000).
▷▷ Set each digit with the rotary knob and press the OK button.
▷▷The display jumps back to the parameter to be changed.
▷▷ Display flashes if the correct code no. was entered. (The display
does not flash if the code no. was not entered correctly. Continue
with step 3.)
5 Use the rotary knob to set the desired value.
▷▷ A number of parameters can only be displayed.
6 Press the OK button to confirm.
7 After you have made your settings, continue with step 2 if you
want to change further parameters (you do not need to enter the
code no. again), or turn the selector switch back to .
▷▷ The table on page 33 (List of parameters P20 to P99) shows the
possible settings.
▷▷ Our heating controller will only display those parameters for which
there are sensors connected.

32
Expert – Set parameters

List of parameters P20 to P99 P.


Parameter Setting range
Factory Own
P. Factory Own no. setting values
Parameter Setting range With active mixer circuit
no. setting values
20 Code no. input 0000 – 9999 0000 Additional mixer functions
69 0, 1 0
21 Code no. 0000 – 9999 0000 (P77 – 79)
Outside temperature ----, Maximum flow tempera-
22 0.0 °C 70 20.0 – 110.0 °C 80.0 °C
Frost protection -15.0 to +5.0 °C ture mixer circuit
1 – 15 (2 – 15 with With underfloor heating, set parameter 70 according to manufac-
23 CAN bus ID mixer circuit 2 turer‘s specifications.
direct heating circuit)
Minimum flow temperature
71 10.0 – 110.0 °C 10.0 °C
With active heat source (HS) (boiler module/heating module) mixer circuit
30 Maximum temperature HS 30.0 – 110.0 °C 85.0 °C 5.0 – 25.0 16.0
72 Mixer Dynamic OPEN
31 Minimum temperature HS 10.0 – 80.0 °C 40.0 °C (P69=1: 5.0 – 200.0) (P69=1: 50)
32 Warm Up Temp 10.0 – 80.0 °C 35.0 °C 5.0 – 25.0 12.0
73 Mixer Dynamic CLOSED
33 Minimum limiter HS 0, 1, 2 1 (P69=1: 5.0 – 200.0) (P69=1: 20)
34 Dyn. switching hysteresis 5.0 – 20.0 K 10.0 K
35 Hysteresis time 0 – 30 min 0 min In combination with heating system controllers with active cooling
36 Burner starts Display only function
37 Burner running time Display only 74 T-Flow Cooling 0, 1, 15.0 – 25.0 °C 15.0 °C
Address heating module 75 T-Room Cooling ----, 20.0 – 40.0 °C 25.0 °C
38 (only for cascade ----, 1 – 8 ---- 76 Min TO Cooling ----, 0.0 – 40.0 °C 27.0 °C
operation)
P77 – 79 can only be adjusted if P69 = 1
With active hot water function 77 Mixer scan time 10 – 200 s 100 s
50 DHW Relief 0, 1 1 78 Mixer operating time limit ----, 0 – 30 min ----
51 Parallel pump operation 0, 1 0 79 Mixer start seconds 0 – 30 s 0s
52 Antilegion function 0, 1 1
Temperature increase With multifunction relay (MF Relay)
53 during hot water 0.0 – 50.0 K 20.0 K 80 MF Relay function 0 – 34 0
preparation MF Relay switching
81 30.0  – 90.0 °C 30.0 °C
temperature
With active direct heating circuit 82 Hysteresis of the MF Relay 2.0 – 10.0 K 5.0 K
Maximum flow tempera-
60 20.0 – 110.0 °C 80.0 °C Service
ture direct heating circuit
Minimum flow temperature PC enable (0000 =
61 10.0 – 110.0 °C 10.0 °C 97 0000 – 9999 0000
direct heating circuit disabled)
98 Relay Test 0, 1 – 6 0
Software version and
99 index (63.XX) 63.00 – 63.99 Display only

33
Expert – Set parameters

Explanation of the parameters With active heat source (boiler module/heating module)

P20 Code no. input P30 Maximum heat source temperature


Here the code number defined via P21 is entered for adjustment of P30 = 30.0 – 110.0 °C: The heat source is heated to the maximum
the Expert parameters. of P30.
▷▷ The factory setting for the heating controller is 0000. ▷▷ Protects the heat source from overheating and prevents triggering
the Safety-Temperature-Limiter (LIMITER).
P21 code no. change ▷▷ Limiting the maximum temperature saves energy.
Here you can specify your own code no. Remember this code well! ▷▷ Also has an effect on the hot water preparation.
The parameters 21 – 99 can not be changed without this code no. ▷▷ Settings according to boiler manufacturer’s specifications.
Should you forget the code no., the factory settings must be re-
loaded, and this means that all your settings will be lost, see page P31 Heat source minimum temperature
12 (Load factory settings (Reset)). P31 = 10.0 – 80.0 °C: Set the parameter so that the formation of
• Change every digit of the four-digit code no. and confirm by condensation is prevented in the heat source when there is a low
pressing the OK button. heating requirement. The heat source does not switch off before P31
+ Switching hysteresis (P34) has been reached when heating up.
P22 Outside temperature frost protection ▷▷ Settings according to boiler manufacturer’s specifications.
P22 = ----: Frost protection is deactivated.
P22 = -15.0 to +5.0 °C: When the outside temperature drops be- P32 Warm-Up Temp
low the set value, the heating circuit controller switches the heating P32 = 10.0 – 80.0 °C: The heating controller switches the heating
circuit pumps on. circuit pumps off and closes the mixer until the heat source has
reached the temperature P32 when heating up.
P23 CAN bus ID mixer circuit (heating circuit address) ▷▷ This reduces operation within the condensation range.
P23 = 1 – 15: It is possible to assign an address from 1 to 15 to the ▷▷ Settings according to boiler manufacturer’s specifications.
mixer circuit. If the direct heating circuit is activated via DIP switch 4,
you must set an address of 2 – 15 for the mixer circuit because the P33 Minimum limit heat source
direct heating circuit automatically receives the address 1. Reduces the formation of condensation in the heat source when there
▷▷ Do not assign a heating circuit address more than once. is a low heating requirement. The heating controller does not switch
▷▷ When replacing a controller, always set the same address as the off before the minimum temperature (P31) + Switching hysteresis
original controller. (P34) has been reached.
P33 = 0: The minimum limit is switched off.
P33 = 1: The heat source maintains at least the set minimum tem-
perature (P31) + Switching hysteresis (P34) during any heating time.

34
Expert – Set parameters
P33 = 2: The heat source maintains at least the set minimum tem- The initial switching hysteresis is reduced from 15 K to 5 K after 10
perature (P31) + Switching hysteresis (P34) for 24 hours (including minutes.
setback mode times).
P36 Burner starts
P34 Dynamic switching hysteresis P36 shows the number of burner starts (no setting possible).
P34 = 5.0 – 20.0 K: The switching hysteresis is added to the Mini-
mum Temperature (P31) of the heat source to calculate the actual P37 Burner operating time
switch-off value. P37 shows the entire burner operating time in hours (no setting
possible).
P35 Hysteresis time
This function optimises heat source operation when subjected to P38 Address heating module (only for cascade operation)
varying loads. P38 = ----: individual heat source (no cascade)
P35 = 0: The switching hysteresis (P34) is not reduced. P38 = 1 – 8: In a cascade the heating controller is addressed under
P35 = 1 – 30 min: The switching hysteresis (P34) is reduced to a hyster- the address specified.
esis of 5 K after the heat source is switched on and P35 has elapsed.
▷▷ When there is little removal of heat, set a long period for P35. This
With active hot water function
prevents frequent pulsing of the heat source.
▷▷ Set a short period for P35 when there is a high removal of heat. P50 DHW Relief (charging pump lock)
This avoids heating up the heat source to unnecessarily high P50 = 0: The charging pump lock is switched off.
temperatures. The energy consumption of the heating system P50 = 1: The heating controller only switches the storage charging
is optimised. pump on when the heat source temperature exceeds the storage
temperature by 5 K. The controller switches the pump off as soon as
Example: Hysteresis time
the heat source temperature drops below the storage temperature.
P34 = 15, P35 = 10
▷▷ This prevents the storage from being cooled by the heat source
20
at the beginning of hot water preparation.
P34 [K]

15
P51 Parallel pump operation
10
P51 = 0: Hot water priority mode; During hot water preparation the
5 heating circuit pumps switch off the mixer valves close.
P51 = 1: Parallel pump operation; During hot water preparation the
2 4 6 8 10 12 14 16 heating controller only disables the direct heating circuit. The mixer
P35 [Min.]
circuit continues to be heated.

35
Expert – Set parameters
▷▷ This function extends hot water preparation. With active mixer circuit

P52 Antilegion function P69 Additional mixer functions (P77 – 79)


P52 = 0: Protective function switched off. P69 = 0: The additional mixer functions (P77 – 79) are deactivated.
P52 = 1: As a protective measure against thermoresistant bacte- Instead, the mixer is operated with default settings. This means
ria, the hot water storage tank is heated to 65 °C with every 20th that the heating controller computes a correction value for the mixer
heating-up process or at least once per week on Saturday at 01:00. position every 10s (scan time).
▷▷ Settings when motor-driven roller wheel mixers are used.
P53 Temperature increase during hot water preparation P69 = 1: P77 – 79 can be set.
P53 = 0.0 – 50.0 K: The heat source is operated at increased tem- ▷▷ Settings when motor-driven lifting valves are used.
perature during hot water preparation to ensure that the hot water
temperature is reached quickly via the heat exchanger. P70 Maximum flow temperature mixer circuit
▷▷ The heat source desired temperature during hot water preparation P70 = 20.0 – 110.0 °C: The heating controller limits the calculated
= Desired hot water temperature + P53. desired flow temperature of the mixed heating circuit to P70 to
protect the consumer from overheating, e.g. when an underfloor
heating system is installed.
With active direct heating circuit
P71 Minimum flow temperature mixer circuit
P60 Maximum flow temperature direct heating circuit P71 = 10.0 – 110,0 °C: The heating controller increases the calculated
P60 = 20.0 – 110.0 °C: The heating controller limits the calculated desired flow temperature of the mixed heating circuit to P71, e.g.
desired flow temperature of the direct heating circuit to P60 to protect when air heating is installed.
the consumer from overheating.
▷▷ Only when the temperature of the heat source exceeds P60 by P72 Mixer Dynamic OPEN (when opening)/
8 K does the heating controller switch off the heating circuit pump P73 Mixer Dynamic CLOSED (when closing)
of the direct heating circuit. The controller will switch the heating P72/73 = 5.0 – 25.0 (when P69 = 1; 5.0 – 200.0):
circuit pump back on as soon as the heat source temperature The Mixer Dynamic determines the ratio between switch-on and
drops below P60 + 5 K. switch-off times of the mixer when opening or closing the mixer.
Depending on the deviation between desired and actual flow tem-
P61 Minimum flow temperature direct heating circuit perature, the mixer is actuated for a longer or a shorter period. The
P61 = 10.0 – 110.0 °C: The heating controller increases the calculated ratio is based on a scan rate of 10s.
desired flow temperature of the direct heating circuit to P61, when ▷▷ Lower values cause fast mixer movement and can result in vi-
air heating is installed for example. bration.

36
Expert – Set parameters
Example: Mixer Dynamic OPEN CAN-Bus
P72 = 8
Merlin Lago 0321
5 8 10 12
10

On-period [s]
9 14
8 16
7 18 7 8 5 21
6 20
22

2
5 24
4

VF
3
2
1
OFF ON
1 2 3 4 5 6 7 8 9 10 11 12 2
Control deviation [°K] 2
In the case of a controller deviation of 6 K the mixer is actuated for
7s and remains switched off for 3s.

In combination with heating system controllers with active


The mixer in the heating circuit functions as a valve. The mixer
cooling function
opens (ON). The heating circuit pump is switched on.
As a requirement for cooling mode, the central controller (e.g. Merlin)
P74 = 10.0 – 25.0 °C: The mixer controls to the set flow temperature
must activate the “Cooling” operating mode.
P74 of the heating circuit, see page 38 (Example: Cooling Operation).
74 T-Flow Cooling (flow temperature Cooling)
P75 T-Room Cooling (desired room temperature)
P74 = 0: The heating circuit is not cooled. The mixer in the heating
Room temperature guided cooling
circuit remains closed, the heating circuit pump is switched off.
P75 = ----: The heating controller does not control according to
P74 = 1:
desired room temperature.
P75 = 20.0 – 40.0 °C: The heating controller starts cooling mode
of operation as soon as the temperature exceeds the set desired
room temperature P75. Cooling mode ends when the temperature
drops below P75 by 2 K.

P76 Min TO Cooling (Minimum outside temperature for cooling)


Weather-guided cooling

37
Expert – Set parameters
P76 = ----: The heating controller does not control guided by the hot water preparation and the direct heating circuit. The Lago 0321
weather. controls the bypass valve and the mixed heating circuit.
P76 = 0.0 – 40.0 °C: The heating controller starts cooling mode P80 = 34, P74 = 20 °C
of operation as soon as the temperature exceeds the set outside As soon as the central controller activates “Cooling” mode, the mul-
temperature P76. Cooling mode ends when the temperature drops tifunction relay in the Lago 0321 responds and opens the bypass
below P76 by 1 K. valve (ON) so that the cooling circuit is separated from the heat source.
If values have been defined for P75 as well as P76, both conditions The mixer 2 controls to the set flow temperature P74.
must be met for cooling mode to start.
P77 – 79 can only be adjusted if P69 = 1
Example: Cooling Operation The parameters P77 – 79 are required when a motor-driven elevating
mixer is used.
CAN-Bus

Merlin Lago 0321 P77 Mixer scan time


P77 = 10 – 200 s: The flow temperature is measured in cycles after
P77 has elapsed respectively.
▷▷ The longer the pipes the higher the value for P77 should be set.
4 7 8 5 21

P78 Mixer operating time limit


2

P78 = ----: Limit in the direction CLOSED = 10 min, limit in the


VF

direction OPEN = none


2 P78 = 0: No limit in either direction
P78 = 1 – 30 min: The value specifies the maximum length of time
2 that the mixer is operated in one direction (OPEN or CLOSED).
OFF ▷▷ This is important when the mixer is not equipped with a safety-
ON friction clutch or limit switches.
▷▷ After the mixer has moved in one direction for the specified period,
the mixer will not be controlled in the same direction until there
has been a control process in the opposite direction.
▷▷ Settings according to mixer manufacturer’s specifications.

The central controller activates the “Cooling” operating mode via the
CAN bus and controls the heat source, the refrigerating machine, the

38
Expert – Set parameters
P79 Mixer start seconds ▷▷ The circulation pump is switched on when T-CIRCL < P81, i.e.
P79 = 0 – 30 s: The first stroke of a closed mixer does not immediately when the return flow temperature is lower than the switching
effect a change in the flow temperature. P79 is the time that elapses temperature of the multifunction relay (set via P81).
until a change in flow temperature can be measured. ▷▷The pump is switched off when T-CIRCL  > P81 + P82, i.e. when
▷▷ Increase this value if the flow temperature changes too slowly the return flow temperature is higher than the switching tempera-
during the initial stage. ture of the multifunction relay (set via P81) plus hysteresis (P82).
▷▷ The pump can only be switched on during the switch-on times
With multifunction relay (MF Relay) of the hot water program (P18).
The multifunction relay (terminal 4) is active with the setting DIP P80 = 21: Circulation pump via pulse
switch 4 = “OFF”. The sensor on terminal 19 is assigned to the relays. ▷▷ The circulation pump is switched on for 5 minutes when there is
a short-circuit between terminal 19 and GND.
P80 MF Relay function
▷▷ The pump can only be switched on during the switch-on times
P80 = 0: without function
of the hot water program (P18).
P80 = 1: Header pump (only when the Lago 0321 is used as a
P80 = 24: Return flow booster, heat source
heating system controller)
T-RETURN= Return flow temperature of the system (measured by
▷▷ The header pump is switched on when a consumer requests heat.
the multifunction sensor)
▷▷ When there is no heat request, the pump is switched off. The pump
▷▷ The pump for the return flow boost is switched on when T-RETURN
runs on for 5 minutes after the heat source has been switched off.
< P81, i.e. when the return flow temperature is lower than the
P80 = 2: The circulation pump is switched on simultaneously with
switching temperature of the multifunction relay (set via P81).
the hot water program.
▷▷ The pump is switched off when T-RETURN  > P81 + P82, i.e. when
▷▷ A storage sensor must be installed in the system.
the return flow temperature is higher than the switching tempera-
P80 = 3: Feed pump
ture of the multifunction relay (set via P81) plus hysteresis (P82).
▷▷ The feed pump is switched on when an internal consumer re-
quests heat.
▷▷ When there is no heat request, the pump is switched off. The pump
runs on for 5 minutes after the heat source has been switched off.
P80 = 5: Heat source pump
▷▷ The multifunction relay switches in combination with the burner
relay (T1 – T2), run-on = 5 min
P80 = 20: Temperature-controlled circulation pump
T-CIRCL = Return flow temperature of the circulation line (measured
by the multifunction sensor)

39
Expert – Set parameters
P80 = 34: Bypass valve in cooling mode P98 = 3: Storage charging pump (terminal 6)
▷▷ The multifunction relay witches as soon as a central controller, e.g. P98 = 4: Mixer Open (terminal 7)
Merlin, activates the operating mode “Cooling”. P98 = 5: Mixer Closed (terminal 8)
▷▷ During cooling mode hot water preparation is possible by means P98 = 6: Burner electrically isolated (terminals 9 – 10)
of conventional heat sources.
▷▷ Example see page 37 (P76 Min TO Cooling (Minimum outside Perform relay test
temperature for cooling)). ▷▷ Turn the selector switch back to to cancel.
1 Turn selector switch to (parameter setting).
P81 Switching temperature of the multifunction relay ▷▷The display shows PL.
P81 = 30.0  – 90.0 °C: Switching requirements: see page 39 (P80 MF 2 Turn rotary knob until 98 0 appears in the display.
Relay function). 3 Press the OK button.
▷▷ Display jumps to 20 0000. The first digit flashes.
P82 Multifunction relay hysteresis 4 Enter code no. (factory setting 0000). To do this, set each digit
P82 = 2.0 – 10.0 K: The multifunction relay is switched off when the using the rotary and press the OK button.
measured temperature is greater than P81 + P82. ▷▷ Display jumps back to 98 and the 0 flashes. (If an incorrect code
number was entered, the display jumps back to 20 0000. Con-
Service
tinue with step 4.)
P97 PC enable (0000 = disabled) 5 Use rotary knob to select the desired relay output (1, 2, 3, 4, 5
P97 = 0000 – 9999: Unlock code that can be used to retrieve data or 6) to control.
from the mixed heating circuit by means of the PC software “Com- ▷▷The controlled relay output flashes in the display.
fortSoft”. 6 Check the device connected to the relay output for active running.
• Change every digit of the four-digit code no. and confirm by ▷▷ Continue with step 5 if further relay outputs need to be checked.
pressing the OK button. ▷▷ After no more than 10 minutes control of the connected device
is terminated and the display of the relay to control jumps to “0”.
P98 Relay Test 7 Press the OK button to terminate the relay test.
The relay test is used to check the electrical connection. ▷▷ Display jumps to 98 0.
Each relay output is actuated one after the other by changing the 8 Turn selector switch back to .
parameter values. The corresponding output is shown in the display.
P98 = 0: No relay is controlled P99 Software version and index (63.XX)
P98 = 1: Heating circuit pump Direct heating circuit / multifunction P99 = 63.00 - 63.99
relay (terminal 4) ▷▷ If you have questions about your heating controller, always specify
P98 = 2: Heating circuit pump Mixed circuit (terminal 5) the software version.

40
Expert – Checklist for commissioning

Expert – Checklist for commissioning


❑❑ Heating controller properly wired? Particularly the bridges between
L and L1 and between GND and terminal 16, see page 21 (Con-
nection diagram controller without socket) and page 22 (Connection
diagram controller with socket).
❑❑ Are the sensors required for the application connected?
❑❑ Sensors that are not required are not connected.
❑❑ DIP switch set correctly? See page 31 (Expert – Set DIP switches).
❑❑ User parameters configured? Set at least time and day of the
week, see page 8 (Set time and day of the week).
❑❑ Expert parameters configured? See page 32 (Expert – Set pa-
rameters).
❑❑ Sensors tested for plausible values? See page 8 (Display actual
temperatures).
❑❑ Relay outputs tested? See page 40 (P98 Relay Test).
❑❑ Operating mode set? See page 8 (Set operating mode).
❑❑ Selector switch turned to ?

41
Service

Service ▷▷ If the STL does not trigger, replace STL.


▷▷ Once the OK button is released, the heating circuit pumps switch
1 Remember the current operating mode. on to remove heat.
2 Turn selector switch to “Mode”.
3 Press the OK button.
▷▷ Display flashes.
4 Rotate the rotary knob clockwise up to .
5 Press the OK button.
6 Perform service.
▷▷The heat source heats to the max. temperature set via parameter
30. As soon as the temperature of 65 °C has been reached,
the consumers regulate to their max. flow temperature for heat
removal.
7 Press OK after you have completed the service procedure.
8 Use the rotary knob to set the mode back to the original operating
mode.
9 Turn selector switch back to .
▷▷ The heating controller resets the “Service” operating mode auto-
matically after 15 minutes.

STL Test
▷▷ You will find information on the trigger temperature of the STL in
the heat source manual.
▷▷ It is not necessary to disconnect the heating circuit pumps or the
mixer for the STL test.
▷▷The boiler sensor must be connected.
1 Turn selector switch to “Mode”.
2 Press and hold the OK button.
▷▷ Display flashes and shows the actual temperature of the heat
source. The temperature rises for as long as the OK button re-
mains pressed, up to the point that STL triggers.
3 Unlock the STL manually.

42
Accessories

Accessories Plain text in language of the country and symbols in the display, op-
eration with three buttons, easy setting of desired room temperature
with rotary knob, party button and mode selection.
Operating module Merlin BM, BM 8, or remote
control Lago FB
The controller supports the option to connect an operating module
via the CAN bus. With the operating module it becomes possible
to move various operating functions and the monitoring of system
values into the living space itself.
This makes operation very convenient. The technical information for Instructions in German: Order no. 99 678 736
the operating module describe the full range of functions in detail. With instructions in language of your choice: Order no. 99 678 738
▷▷ Display of the Expert parameters Installation and operation, see enclosed instructions.
▷▷ Input of User parameters
Lago FB
▷▷ Room temperature control
Operation as for heating controller Lago 0321.
▷▷ Automatic adaptation of the heat slope (not for Lago FB)

Merlin BM
With plain text display in the language of the country; illuminated,
4-digit display; a button is allocated to every row, very convenient
to operate.
Order no. D/D 99-678-868
Installation and operation, see enclosed instructions.

PC Adapter
For the communication between heating controller with bus and a PC.
The ComfortSoft program can be used to set and retrieve all system
parameters. In the PC the parameters can be saved, graphically dis-
Instructions in German: Order no. 99 778 201
played and evaluated within a specified time periods. The software
With instructions in language of your choice: Order no. 99 778 202
is available for download at www.docuthek.com. For a connection
Installation and operation, see enclosed instructions.
to the PC the CoCo PC active is required, which, in combination
BM 8
with a modem, also supports sending error messages via SMS

43
Accessories
and the remote retrieval of controller data. The CoCo PC mobile is Remote control and room sensor FBR2
an alternative without remote retrieval or error messages via SMS. Remote control for selecting the operating mode and setting the
desired room temperature
CoCo PC active
Order no. 99 678 288

Scope of supply
CoCo PC active, instructions.
The connecting cable for the RS232 interface must be ordered sepa-
rately: Order no.: 99 676 894. Order no. 99 679 161
Installation and operation, see enclosed instructions.
CoCo PC mobile
Order no. 99 677 961
Room sensor RFB
Scope of supply
CoCo PC mobile, instructions, connecting cable to USB mini-B for
CAN bus or eBus.
Order no. 99 676 857
On installation and operation, see enclosed instructions.
Scope of supply
Room sensor

Position of installation
▷▷ In the main living room of the heating circuit on an inside wall
▷▷ Not in the vicinity of radiators or other devices that give off heat
▷▷ Not covered by curtains
▷▷ Not influenced by draught
▷▷ The radiator valves in the room must be fully opened.

Installation
1 Remove upper part from base at the underside.
2 Screw base to the wall.

44
Accessories
3 Connect electrically, see page 18 (Expert - Electrical connec- Order no. KF/SPF, 5 kΩ, 3 m, ø 6.0x50:
tions). 99 676 769
4 Press upper part back on. Order no. KFS/SPFS, 1 kΩ, 3 m, ø 6.0x50:
5 Set parameter 10 or 15 on the heating controller. 99 676 682
Sensor Position of installation
In the immersion pipe of the hot water storage tank (usually on the
Outside sensor AF/AFS front side of the storage tank

Installation
1 Dry immersion pipe.
2 Insert the sensor as far as possible into the immersion pipe.
Order no. AF, 5 kΩ: 99 679 030 3 Connect electrically, see page 18 (Expert - Electrical connections).
Order no. AFS, 1 kΩ: 99 679 001
Flow sensor VF/VFAS
Scope of supply
Outside sensor, screw and dowel

Position of installation
▷▷ Ideally on a wall facing north or north-east Order no. VF, 5 kΩ, 3 m, ø 6.0x50: 99 679 073
▷▷ Approx. 2.5 m above the ground Order no. VFAS, 1 kΩ, 3 m, ø 6.0x50: 99 679 051
▷▷ Not above windows or air shafts Scope of supply
Flow sensor, thermal compound, retaining strap, instructions
Installation
1 Pull cover off sensor. Position of installation
2 Fasten sensor with enclosed screw. ▷▷ In the case of heating system control instead of boiler sensor KF,
3 Connect electrically, see page 18 (Expert - Electrical connections). as close as possible at the back of the boiler on the heater flow
▷▷ In the case of mixer operation approx. 0.5 m behind the heating
Boiler sensor KF/KFS
circuit pump
Storage sensor SPF/SPFS
Installation
1 Thoroughly clean flow pipe.
2 Apply thermal compound to sensor.
3 Fasten sensor to the flow pipe with the retaining strap.

45
Accessories
▷▷ Set the sensor type with DIP switch 6, see page 31 (Expert –
Set DIP switches).
▷▷ The sensor value of a remote control unit with room sensor FBR
or a room sensor RFB is detected automatically.

4 Connect electrically, see page 18 (Expert - Electrical connections).

Sensor values
Temp. 5 kΩ NTC: 1 kΩ PTC: AFS, KFS,
AF, KF, SPF, VF SPFS, VFAS
[°C] [Ω] [Ω]
-60 698961 470
-50 333908 520
-40 167835 573
-30 88340 630
-20 48487 690
-10 27648 755
0 16325 823
10 9952 895
20 6247 971
25 5000 1010
30 4028 1050
40 2662 1134
50 1801 1221
60 1244 1312
70 876 1406
80 628 1505
90 458 1607
100 339 1713
110 255 1823
120 194 1936
▷▷ Only sensor of one type may be used.

46
Help with faults

Help with faults ? The display shows error no. E 91.


! The set CAN bus address is already used by a different device.
? Fault • Set parameter 23 to a different address that is not yet in use.
! Cause
• Remedy ? All radiators and the hot water storage tank are cold. But the
heating controller display shows high temperatures.
When a fault occurs, the associated error number is indicated in ? All radiators and the hot water storage tank are warm. But the
the display. heating controller display shows low temperatures.
Defective sensor (break / ! DIP switch 6 set to wrong sensor type.
Fault Error no.
short-circuit) • Set DIP switch 6 correctly:
The mixer does not Flow sensor mixer circuit
E 69 OFF = 5 kΩ sensor (KF, SPF, VF, AF…),
start. VF/VFAS
The heating circuit ON = 1 kΩ sensor (KFS, SPFS, VFAS, AFS…)
pumps do not switch E 75
Outside sensor ▷▷ Never mix 1 kΩ and 5 kΩ sensors.
AF/AFS
off.
No more hot water ? When displaying the actual values on the heating controller you
E 76 SPF/SPFS storage sensor realise that the indicated value does not match the real one. For
available.
The flat does not get example, the actual hot water temperature is 20 °C, but the display
Boiler sensor
warm. No more hot E 77 shows 65 °C (or vice versa).
KF/KFS
water available. ! 1 kΩ and 5 kΩ sensors have been mixed.
The multifunction Sensor for the multifunction • Only use sensors with identical resistance values.
E 79
pump is off. relay
The flat gets too warm. E 80 Room sensor
• Check electrical connection. Replace sensor, if necessary.

? The display shows error no. E 81.


! EEPROM error. An invalid parameter has been replaced by the
default value.
• Check parameter values.
• Switch mains power off and on again to reset the error no.

47
Help with faults
? No actual values are indicated on the heating controller.
! No bridge between terminal 16 and GND.
• Check electrical connection, set bridge and load factory settings
on the heating controller (Reset).

? Although pumps and mixer are indicated on the display they are
not actuated.
! No bridge between terminals 2 and 3 or terminal 1 and neutral
block.
• Check electrical connection.

? The flat does not get warm.


! The heating circuits do not respond to the mode setting.
• Set parameters 08 and 13 = “----”.
! The heating times at the bottom of the display to not match the
desired heating program.
• Set parameter 19: P19 = 00 for direct heating circuit, P19 = 01
for mixed heating circuit.
• Set parameters 08 and 13 = “----”.
! Pump for direct heating circuit is not running.
• Set DIP switch 4 to “Pump direct heating circuit”.

? The hot water stays cold during summer mode.


! Parameter 18 = 03 set (hot water 1 h before heating)
• Set P18 = 01 or 02.

Should the actions described above fail to help, please


contact your heating engineer.
▷▷ Please have ready the software version (parameter P99).

48
Technical data

Technical data
Mains voltage according to DIN IEC 60 038: ~230 V, ±10%
Power consumption: max. 5 VA
Switching capacity of the relays: ~250 V, 2(2) A
Max. current via terminal L1’: 6.3 A
Protection class according to DIN EN 60529: IP 40
Protection class according to DIN EN 60730: I
Reserve power of clock: >10 h.
Permissible ambient temperature during operation: 0 to 50 °C
Permissible ambient temperature during storage: -20 to 60 °C
Permissible relative humidity, not condensing: 95 % r. H.
Sensor resistances: NTC 5 kΩ (AF, KF/SPF, VF),
Tolerance in ohms: ±1 % at 25 °C,
Temperature tolerance: ±0.2 K at 25 °C
Sensor resistances:
PTC 1010 Ω, (AFS, KFS, SPFS, VFAS)
Tolerance in ohms: ±1 % at 25 °C,
Temperature tolerance: ±1.3 K at 25 °C
Controller
Efficiency gain* In combination with
class
Room temperature control
3,5% VII Outside temperature control
Staged boiler temperature control
* In accordance with Directive 2009/125/EC Communication 2014/C_207/02/

49
Glossary

Glossary Return flow booster


The return flow booster prevents the temperature difference at the heat
source between flow an return becoming too great. A mixing valve is
Flow and return flow temperature here used to add a portion of the hot flow water to the return flow to
The flow temperature is the temperature to which the heat source prevent condensation of the steam from the heating gas against the
heats the water that transfers the heat to the consumer (e.g. radiator). cold heat carrier inside the heating boiler. The minimum temperature
The return flow temperature is the temperature of the water that flows required for this process inside the heating boiler depends on the
back from the consumer to the heat source. type of fuel (oil 47 °C, gas 55 °C). The risk of corrosion inside the
heating boiler is thereby reduced significantly.
Desired and actual temperature
The desired temperature (or setpoint temperature) describes the Direct heating circuit
desired temperature for a room or for hot water. In the direct heating circuit the flow temperature is identical to the
The actual temperature denotes the actual temperature that prevails. heat source temperature, i.e. the direct heating circuit is operated
The heating controller has the task to adjust the actual temperature with the maximum temperature.
to the desired temperature.
Mixed heating circuit / Mixer circuit
Setback temperature In the mixed heating circuit a three-way valve is used to add cooled
The setback temperature is the desired temperature to which the water from the return flow to the hot flow water. The flow temperature
heating system heats outside heating times (e.g. at night). It should is thus reduced. This is important for underfloor heating systems,
be set so that the rooms do not cool down too much while saving for example, because they must only be operated with low flow
energy. temperatures.

Heat source Heating time


Heat source is generally the designation for the heating boiler. It may In the heating programs you can define up to three heating times per
also be a buffer storage tank however. day, one for the morning, one for lunchtime, and one for the evening
for example. During a heating time, the temperature is controlled to
Circulation pump the desired room temperature. Between heating times the tempera-
The circulation pump ensures that there is constant hot water avail- ture is controlled to the setback temperature.
able. The hot water is held in the storage tank. The circulation pump
circulates it via the fresh water pipes in accordance with the heating
program.

50
Certification

Header pump Standards:


A header pump is used to pump the hot water in a system with one – EN 60730-1
or several heat sources. It is switched on as soon as a consumer in – EN 60730-2-9
the system requests heat. – EN 60335-1
– EN 60335-2-102
Feed pump The manufacture is subject to the quality management system in
A feed pump functions like a header pump. It is switched on as soon accordance with DIN EN ISO 9001.
as an internal consumer in the system requests heat. Elster GmbH

Legionella Scan of the declaration of conformity (D, GB) – see


www.docuthek.com
Legionella are bacteria that live in water. The hot water storage tank
is heated to 65 °C every 20th heating period or at least once a week
Eurasian Customs Union
as protection against these bacteria.

Certification The product Lago 0321 meets the technical specifications of the
Eurasian Customs Union.
Declaration of conformity

We the manufacturer declare the product Lago 0321 is in conformity


with the fundamental requirements of the following directives and
standards.
Directives:
– 2014/35/EU
– 2014/30/EU
– 94/62/EG
– 2009/125/EG
– 1907/2006

51
Contact

Heating circuit allocation

For the installation expert


Please enter which rooms the heating circuits are assigned to here.
Direct heating circuit Mixed heating circuit

Kurt-Schumacher-Allee 2 · 28329 Bremen


https://www.brummerhoop.com
support@brummerhoop.com

52

You might also like