Inverter Documents-OM Textiles 4MW Rev00
Inverter Documents-OM Textiles 4MW Rev00
Inverter Documents-OM Textiles 4MW Rev00
CUSTOMER: OM Textiles
CONSULTANT: ACE Renewtech Engineering Private Limited
PROJECT: 5 MW Solar Power Plant
FIMER REFERNCE NUMBER: F2176029-HAA
SALE ORDER NO: - APPROVED
RAMKUMAR 18-Dec-21, 11:53:02 am
Index Sheet
SL no. Description
1 Inverter Technical Specifications
2 General Arrangement Drawing
3 Free space requirement
4 Single Line Diagram
5 Transformer Specifications
6 Termination and Foundation Detail
7 Bill Of Materials
8 Modification Record
Confidential
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties
without express authority is strictly forbidden. © FIMER India. PROPRIETARY AND SECRET INFORMATION.
INVERTER GENERAL TECHNICAL PARAMETERS
A TOTAL INVERTER QUANTITY 1
B INVERTER DATA
PVS980
58
1 Product Model
5000 kVA
L
2 Inverter Type (Monolithic / Modular) Modular
3 Switching Element and Technology PWM Controlled IGBT based Three Level Inverter
4 Number of IGBT Module (Stack) in Inverter 4 X R35i Module
5 MPPT Tracker - Master slave/ Multi MPPT MPPT single
6 No. of MPPT Trackers/Controller 1
7 Degree of Protection IP55
C INPUT VARIABLES
1 Max. allowed PV field power 10000 kWp
2 Max. DC Power/Max. AC Power ratio 200%
3 DC Voltage range MPP(Udc,mpp) at 25°C 978 - 1350 V
4 DC Voltage range MPP(Udc,mpp) at 35°C 978 - 1250 V
5 DC Voltage range MPP(Udc,mpp) at 50°C 978 - 1100 V
6 Max. Permissible DC voltage(Umax (DC)) 1500 Vdc
7 Max. Permissible DC current (Ipc max) 5300A
8 Number of DC inputs 24H382 - 24 DC Inputs
9 DC Side grounding Negative grounding
10 DC Side Fuses F320 - 500A
11 DC Surge Arresters Type 2 SPD - Standard
D OUTPUT VARIABLES
1 Nominal AC voltage(UN (AC)) 690 Vac(± 10%)
2 Type of Phase Connection 3 Phase, 3 Wire , IT type
3 Nominal AC current (IN (AC)) at 50°C 3700 A
4 Maximum AC current (IMAX (AC))at 25°C 4184 A
5 Output Frequency 50Hz (± 10%)
6 Power factor range (cos phi) 0…1
7 Distribution Network type 3 Phase, IT (floating) networks
8 Harmonic Distortion, Current < 3% at nominal load (under ideal conditions)
9 Nominal Rating at at 50°C 4421 kVA
10 Maximum Rating at at 25°C 5000 kVA
11 Disconnection from Grid +F296 - Fixed Type ACB
12 AC Surge Arrester Type 2 SPD - Standard
13 Connection Method Bus duct
E POWER CONSUMPTION & EFFICIENCY
1 Maximum efficiency* 98.80%
2 Euro efficiency* 98.60%
3 CEC efficiency ** 98.50%
4 Own Power consumption (Operation) < 5000 W
5 Own Power consumption (Standby/Night Time) <460 W
6 Auxiliary Power Supply +G415 - Internal Auxiliary Power
*Without auxiliary power consumption at minimum Udc
** Rounded according CEC rules
Rev-No. Description and Date of Revision Prepared by Dhananjaya H S Doc No.
00 17 December 2021 Approved by Prasanna Kumar L F2176029-HAA
Customer Title Dept. Engg
OM Textiles INVERTER DATASHEET Sheet A4
Project Lang. English
SOLAR
5 MW Solar Power Plant Page 1 of 2
INVERTER GENERAL TECHNICAL PARAMETERS
F CABINET DATA
1 Inverter Dimension (W/H/D) in mm Max. 5055 / 2283 / 1776
2 Total Weight [kg] (Approximately) Max. 5500 kg
G ENVIRONMENT LIMIT
1 Ambient Temperature Range (Nominal Rating) -20 ...+50 DegC
2 Maximum Ambient Temperature (Operational) +60 DegC
3 Relative Humidity 4 ... 100%, Non Condensing
4 Nominal Altitude 1000 meter above Sea Level
5 Maximum Altitude (with power derating) 4000 meter above Sea Level
6 Maximum Noise Level *** < 84 dB(A) at one meter
** *At partial power, typically less than 75 dbA
H USER INTERFACE AND COMMUNICATIONS
1 Local User Interface ABB Control Panel ( LCD Display with Keypad)
2 Fieldbus connectivity +K475, Ethernet Adapter (Modbus TCp/IP, Profinet; 2 - port)
3 Emergency stop switch Yes
4 Display of Alarm and Fault Display is available
5 Display of AC and DC Parameter Display is available
5 Display of Energy Generation Display is available
I TERMINATION DETAILS
1 Cable Entry/Exit Bottom Entry
2 Gland Plate Undrilled
3 AC Termination Busbar Details 160mm X 20mm , Cu ; hole size : 14.5 mm(dia.)
4 DC Termination Busbar Details 40mm X 5mm, Tinned Aluminium; hole size : 13 mm(dia.)
5 Recommended AC Cable Termination Bus duct
6 Recommended DC Cable Termination Calculated based on DC inputs
Note 3
Note 1
Note 2
Note 2
Note 1: Sufficient free space for installation of shroud and AC busbar connections
Note 2: Sufficient free space (min. 2m (80'')) and flat area for power module replacement
Note 3: Sufficient free space (min. 2m (80'')) for working in the control section and emergency exit space
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
express authority is strictly forbidden. © FIMER. PROPRIETARY AND SECRET INFORMATION.
-F71
3
12
-F53
9
-1-4T3
LCL1-4
8
7
11
10
-1-4F3
4
-1-4F2.1-2
-1-4Q3
-1-4Q2
-F1.1-24
18
13
2
1
-Q4
-T10
-F62
-F10
-X62
-Q62
Negative
-A21 grounding
5
17
14
meas.
Insulation
-F12...F21
-F72
resistance -A20
6
AUX.
15
-F70
-X70
16
No. Description No. Description
DC input fuses.
2. As standard, fuses only on positive (+) 12. AC surge arrester, Type 2 as standard
DC poles (negative grounding).
Confidential
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without
express authority is strictly forbidden. © FIMER. PROPRIETARY AND SECRET INFORMATION.
Transformer Specifications
Transformer requirements
These are the transformer requirements for a transformer connected to the AC main
supply of the inverter. This can mean a main transformer that connects the inverter to an MV
network or an external auxiliary power transformer that connects to an AC supply (possible
with option +G430).
The transformer must be/have:
• Suitable for direct bus bar connection.
• Suitable for the network and AC voltage, current and power of the inverter. For
Transformer dimensioning, re fer to inverter hardware manual.
• Suitable for use with IGBT inverters
• A degree of protection, temperature limits and lifetime that are appropriate for the
installation environment
• Galvanically isolated high-voltage and low-voltage windings.
• Equipped with a static grounded screen between the high-voltage and low-voltage
windings.
• A voltage withstand level of the inverter-side winding is at least 2.0 kV against ground. A
typical voltage waveform against ground:
1000
800
600
400
200 10 15 30
U[V] 0
5 20 25
-200
-400
-600
-800
-1000
t[ms]
Confidential
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third
parties without express authority is strictly forbidden. © FIMER. PROPRIETARY AND SECRET INFORMATION.
• If several inverters are connected to the same transformer:
• Each inverter requires separate galvanically isolated LV windings.
• The impedance between the low-voltage windings must be more than 1.5x the
rated short-circuit impedance.
• The voltage rise-time withstand level (du/dt) of the inverter-side winding is at least
1000 V per microsecond against ground.
• The recommended rated short-circuit impedance (Xk) is 7–8%.
• The transformer withstands current DC components of at least 0.5% of the nominal
rated current preferably without using an air gap.
• The transformer withstands the worst case of 3% total harmonic distortion generated
by the inverter. FIMER recommends dimensioning the transformer for at least 5% total
harmonic distortion to withstand possible outside interference from the network.
FIMER recommends that the transformer is equipped with an off-load tap changer for volt-
age regulation on the high-voltage side of the winding with two 2.5% step points to the plus
and minus directions.
The inverter does not require a specific transformer notation. FIMER recommends using
traditional notations, such as Dy11d0, etc.
The AC side of the inverter is designed only for IT (floating) networks. Do not ground the
neutral (star) point of the transformer on the inverter side or connect it to the neutral points
of other windings.
Confidential
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third
parties without express authority is strictly forbidden. © FIMER. PROPRIETARY AND SECRET INFORMATION.
1 2 3 4 5 6 7 8 9 10
PVS980_5MWA_LONG_LAYOUT A.2+ We reserve all rights in this document and in the information contained
therein. Reproduction,
use or disclosure to third parties without express authority is strictly
forbidden. First angle projection. Original drawing made with 3D CAD. Set the correct scale factor when adding
dimensions after DWG/DXF conversion.
MUSTARD_MAIN_ASSY_LONG (ASSEM) A.77 © ABB Oy. PROPRIETARY AND SECRET INFORMATION. CONFIDENTIAL
E
B B
C D
C C
1754
[69]
1430
[56]
1754
[69]
D D
217
[8.5]
C-C
E 569 E
[22]
E
1:10
[2.4]
60
1:10 395 [15.5]
295 [11.6]
L1
236 [9.3]
[2.4]
102
[4]
- 136 [5.3]
60 217
1754
[69]
[8.5]
G 35,5 [1.4] G
14,5 (2 pcs) 0 [.00]
[.6]
1430
[56]
44,5
[1.8]
L3
0 [.000]
32 [1.3]
192 [7.6]
352 [13.9]
512 [20.2]
672 [26.5]
704 [27.7]
C L2
1:10 94
H [3.7] 20 H
[.8]
Based on Prepared R.Jauhonen 14-May-20 Title LAYOUT DRAWING Doc. des. Scale Form
Customer Check. J.Hamari 14-May-20 LAYOUT OF PVS980 5MWA LONG LAYOUT DRAWING 1:20 A2
Appr. E.Roos 14-May-20 Resp.dept. Rev.ind. A (AP) Lang. EN
Cust. Doc. No. Project name Doc. No. Sheet 6
DMS Number 3AXD10001159139 Weight kg 11438.80
3AXD50000631438 Total 6
Please check the
cable entry location of
control &
communication in line
with GA drawing in
Page-5. or
Mention Plus?minus
side like page-15 to
get clarity
BILL OF MATERIAL - PVS980-58-5000kVA-L Title: Bill Of Material
Configuration : PVS980-58-5000kVA-L+K475+F296+24H382+F320+G415+G430+P928 Customer: OM Textiles
Consultant: ACE Renewtech Engineering Pvt, Ltd.
LOCATION
SL NO. ITEM DESIGNATION QTY Description Type Designation Technical Data MAKE
DESIGNATION
1 PS -B10 2 SENSOR, TEMP/HUMIDITY FWL 3/5 24 V;0-100%rh=>4-20mA Galltec - Mela
2 DC -K12-13 2 FILTERING BOARD MEMI-11 EMI FILTER BOARD ABB
3 DC -G42-G43 26 FAN, AXIAL 2218F/17TDH4OR 48 V;103 W;6500 1/min;2,15 A;0,34 m3/s;O EBM-PAPST
4 DC -TE51 5 THERMAL PAD PT100 SENSOR MULLER
5 DC -B1 1 SMOKE DETECTOR APOLLO S65A 55000-327 SUPPLY 9-33V ABB Approved Make
6 DC -B1 1 RELAY BASE APOLLO S65A 45681-255 1 A;9-33 V;30W/50VA ABB Approved Make
7 CS -A20 1 PCB KIT MIRU-01 ABB
8 CS -A21 1 PCB KIT MGND-01 ABB
9 CS -R21 1 RESISTOR CBHK 215 C 50R 1000-1400V;155W;50OHM;11335J DANOTHERM
10 CS -K21 1 CONTACTOR P115CDA 1500 V;50 A;24Vdc coil GIGAVAC
11 CS -F72.1-2 2 FUSE HOLDER LFPXV001 1500V;30A;SPXV;10X85 LITTELFUSE
12 CS -F72.1-2 2 FUSE SPXV010 1500 V;10 A;gPV;10x85 LITTELFUSE
13 CS -Q64 1 LOAD BREAK SWITCH OT80F3 AC21/22 80A 690VAC;AC23 20A 690VAC ABB
14 CS -X70 1 SOCKET OUTLET MODULAR SOCKET OUTLET 125V;15A;4MM2;12AWG;DIN RAIL MOUNTING PHOENIX CONTACT
15 CS -K61 5 CONTACTOR AF09-30-10-11 25A;50/60Hz;690V;AC;DC;220VDC,24-60VDCAC ABB
16 CS -E61 1 LAMP INDICATOR CL2-502L 24 V, AC/DC, BLUE ABB
17 CS -E11 1 LAMP INDICATOR CL2-502G 24 V, AC/DC, GREEN ABB
18 CS -E12 1 LAMP INDICATOR CL-502Y 24 V, AC/DC, YELLOW ABB
19 CS -E13 1 LAMP INDICATOR CL2-502R 24 V, AC/DC, RED ABB
20 CS -T24 1 POWER SUPPLY MCS-B 5-110-240/24 5 A;24 V;110-240 VIN, COATED BOARDS ABB / MURRELEKTRONIK POWER OY
21 CS -C24 1 UPS MB CAP 20/24 BUFFER MODULE 20 A;24 V;DC;BUFFER;0,2s/20A;4s/1A MURRELEKTRONIK POWER OY
22 CS -T48.1-3 3 POWER SUPPLY EP3000AC48INZ 48-58V;3000W;62,5A;90-290 VIN;COATED GE
23 CS -T48.4 1 POWER SUPPLY EMPARRO 2,5-100-240/48 COATED 48V;2,5A;100-240 VIN;COATED MURRELEKTRONIK POWER OY
24 CS -V48 1 DIODE QUINT-DIODE/48DC/2X20/1X40 48V;40A PHOENIX CONTACT
25 CS -C48.1-2 2 UPS EMPARRO CAP 20/48 48 V;DC;BUFFER;20 A;0,1s/20A;2s/1A MURRELEKTRONIK POWER OY
26 CS -G29 13 FAN, AXIAL 4118N/17H6AR 48V;62W;84001/m;1,29A;440M3H EBM-PAPST
27 CS -S20 1 PUSH BUTTON MPET4-10R EMERG.STOP PUSHBUTTO TWIST RELEASE ABB
28 CS -S20 2 PILOT DEVICE ACCESSORIES MCBH-00 FLANGE FOR 3 CONNECTOR ABB
29 CS -S21 1 SELECTOR SWITCH M2SS2-10B BLACK ABB
30 CS -A41 1 CONTROL UNIT BCU-12 7_CH ABB
31 CS -A41 1 MEMORY UNIT KIT ZMU-02 . ABB
32 CS -A49 1 CONTROL PANEL ACS-AP-I MODULE UNIVERSAL ASSISTANT PANEL CPU1 ABB
33 CS -A49 1 ASSEMBLY KIT DPMP-02 PACKED KIT SURFACE MOUNTED PANEL MOUNTING KIT, IP65 ABB
34 CS -A411 1 FENA-21 FENA-21 ETHERNET ABB
35 CS -A412 1 FIELDBUS KIT FSCA-01 SERIAL COMM ABB
36 CS -A415 1 PCB KIT BAMU-12 ABB
37 CS -A500 1 PROGRAMMABLE LOGIC CONTROLLER PM564-RP-ETH /1SAP121000R0071 128kB,6DI/6DO-R/2AI/1AO,24VDC ABB
38 CS -A500 3 CONNECTION UNIT TA565-9 / 1TNE968901R3105 S500,Terminal block, 9 poles ABB
39 CS -A500 5 CONNECTION UNIT TA565-11 / 1TNE968901R3106 S500,Terminal block, 11 poles ABB
40 CS -A510-A511 2 I/O MODULE DI562 S500,DIGITAL INPUT MODULE 16DI ABB
41 CS -A512-A513 2 I/O MODULE DO571 / 1TNE968902R2202 AC500, Digital Out.Mod. 8RO ABB
42 CS -A514 1 I/O MODULE AI523 1SAP250300R0001 S500,Analog Input Module ABB
43 CS -A514 1 MODULE TERMINATION UNIT TU516 / 1SAP212000R0001 S500,I/O Terminal Unit,24VDC ABB
44 PS1-PS4 -1T3-4T3 4 INVERTER MODULE PVS980-104SC-925A-7 690V;925A;1105KW;IP00 ABB
45 PS1 -1F2.1-2 8 FUSE SQB-DC153 1500V;750A;aR;3L EATON/SIBA/MERSEN
46 LCL1 -1C1.1-3 12 FILM CAPACITOR LCL CAPACITOR 690V;40 TDK/EC
LOCATION
SL NO. ITEM DESIGNATION QTY Description Type Designation Technical Data MAKE
DESIGNATION
47 LCL1-LCL4 -1LCONV-4LCONV 4 INDUCTOR LCONV 50mH;690V;875A;1700A;1750A;F CSE/NORATEL
48 LCL1-LCL4 -1LGRID-4LGRID 4 INDUCTOR LGRID 45mH;690V;875A;1500A;F CSE/NORATEL
49 LCL1-LCL4 -1Q2-4Q2 4 CONTACTOR GF1325-20-22-51 1500V;1325A;COIL 24-60V, -40...70C ABB
50 LCL1-LCL4 -1Z1-6 - 4Z1-6 24 CHOKE PS1132AA VACUUMSCHMELZE/HITACHI
51 AC -1-4F3.1-3 12 FUSE 170M6466 1250 A;690 V;SIZE 3;TYPE K EATON/MERSEN
52 AC -1-4Q3 4 CONTACTOR AF1250-30-22-68 1260A(IE); 1000V(UI); 24-60VDC ABB
53 AC -1-4Q19 4 CONTACTOR AF30-30-00-11 690 V;50 A;50/60 Hz;24VDC ABB
54 AC -1-4R1.1 4 CHARGING RESISTOR CBH 335 C H 414 5R0 5OHM;26562J;+-5% DANOTHERM
55 AC -Q4 1 CIRCUIT BREAKER, AIR, LV E6.2H 5000 EKIP DIP LI 3P FHR 690V;5000A;100KA ABB
56 AC -F3.4 1 MOTOR CIRCUIT BREAKER MS132-1.6-HKF1-11 100,00 kA;1,60 A;690,00 V;1NO+1NC ABB
57 AC -K40 2 CONTACTOR AF09Z-30-10-21 25A;50/60Hz;690V;COIL 24-60VDC,9A,400V ABB
58 AC -F11 1 ARRESTER ARRESTER 230 VAC; L+N PHOENIX CONTACT
59 AC -C1-3 9 CAPACITOR FILTER CAPACITOR 2 X 4,7 NF 2x4700 pF, M4/M6 ABB Approved Make
60 AC -F61.1-3 3 FUSE FWP-10A14F 10A 660V(IEC)/700V(UL) AR 14*51MM EATON/SIBA/MERSEN
61 AC -F61.1-3 3 FUSE HOLDER CH141DU 690V;50A;14X51MM;Series -CH14DU EATON/SIBA/MERSEN
62 AC -K15 1 FILTERING BOARD MEMI-01 EMI FILTER BOARD ABB
63 AC -K16 1 FILTERING BOARD MEMI-02 EMI FILTER BOARD ABB
64 AC -TE32, -TE34 2 THERMAL SWITCH THERMIK PROTECTOR V06.115.05.3000/3000 0-250V;-10A THERMIK TECHNOLOGIES SDN BHD
65 CS -F12 1 PROTECTION SWITCH S201-K6 6 kA;6 A;230 V;60VDC ABB
66 CS -F13-F16 4 PROTECTION SWITCH S201-B16 16A; 230/400VAC/60VDC ABB
67 CS -F40, F42 2 PROTECTION SWITCH S201-K13 10 kA;13 A;230VAC;440VAC/60VDC ABB
68 AC -F10.1-2 1 ASSEMBLY KIT BB002EP FUSE BASE KIT ABB/EATON/MERSEN
69 AC -F10.1-2 2 HRC FUSE LINK 35NHC00G-690, OFAA000GG35 ABB/EATON/MERSEN
70 CS -F70 1 SWITCH DS201 M C10 AC30 - RCBO 1V/10A/30MA IM=5-10XIN ICN=6KA ABB
71 CS E65-E68 4 HEATING RESISTOR AR 100 100 W;110 V;100W/220V ADR
72 AC -T10 1 TRANSFORMER 1111-18930 600/630/660/690-115/175/230;6.3KVA CSE/NORATEL
73 CS -Q64 1 LOAD BREAK SWITCH OT80F3 AC21/22 80A 690VAC;AC23 20A 690VAC ABB
74 DC -F1.1-F1.24 24 FUSE PV-500A-3L-B-15 EATON
75 AC -F62.1-3 3 HRC FUSE LINK 63NHG00B-690 EATON/MERSEN
76 AC -F62.1-3 1 ASSEMBLY KIT BB003EPVBLOC FUSE BASE KIT EATON/MERSEN
77 CS -1-2F30-32 6 PROTECTION SWITCH S201-K13 10 kA;13 A;230VAC;440VAC/60VDC ABB
78 CS -F30 - F39 6 PROTECTION SWITCH S201-K13 10 kA;13 A;230VAC;440VAC/60VDC ABB
79 CS -F48 1 PROTECTION SWITCH S201-B16 16A; 230/400VAC/60VDC ABB
80 CS -F29 1 PROTECTION SWITCH S201-K6 6 kA;6 A;230 V;60VDC ABB
81 CS -1,2,4F35 4 PROTECTION SWITCH S201-K6 6 kA;6 A;230 V;60VDC ABB
82 PS1-PS4 1-4E69 4 HEATING RESISTOR AR 100 100 W;110 V;100W/220V ADR
83 CS -Q62 1 LOAD BREAK SWITCH OT80F3 AC21/22 80A 690VAC;AC23 20A 690VAC ABB
Confidential