Handing over notes of Sri.T. VEERA CHAITANYA,Ex. AEE/Maintenance/Borampalli.

The
Maintenance Section of 132 KV Ankampally LIS Sub-Stations Comprises the following:

1. General: The Asst.Executive Engineer /Maintenance/220 KV SS Borampalli is incharge of


maintenance section of 132/11 KV SS (LIS) Ankampalli. The 132/11 KV SS (LIS)Ankampalli is
purely meant Lift Irrigation System

The 132/11 KV SS (LIS)Ankampalli is having 4 No. 132 KV feeder , 3 No’s 10/16 MVA, 132/11KV
Power Transformer, 4 No’s 11 KV Breakers (KIOSK) in which 2 No’s LV Breakers and 4 No’s 11 KV
feeder breakers.

2. 132 KV Feeder: There are 4 No’s 132KV feeders at Ankampalli (LIS) SS. Namely 132 KV Anantapur-
Ankampalli feeder emanating from 220KVSS Anantapur, 132 KV Kalyandurg- Ankampalli feeder
emanating from 220KVSS Kalyandurg and 2 Nos. Duddekunta wind generating feeders namely 132
KV Duddekunta Wind generating Circuit –I and 132 KV Duddekunta Wind generating Circuit-II were
commissioned on 11-03-2015.

3. Power Transformer: There are 3 Nos.10/16 MVA, 132KV/11KV Power Transformer Bays (make-
ECE) available at 132KV SS (LIS) Ankampalli.

4. 11KV Feeders: There are 5 No’s 11 KV Feeders emanating from 132/11 KV SS (LIS) Ankampalli, out
of which 3 No. feeders are (Over Head Lines) which are connected to the Jeedipalli Pump House and in
which 1 No 11 KV Kiosk of 11 KV Jeedipalli-3 feeder was transferred to 220 KV SS Ragulapadu on
emergency as per instructions of Higher Officials and 2 No. feeders are meant for Ankampalli Pump
House.

5. D.C Supply : The 220V D.C Supply provided to all 132 KV feeders, 11 KV feeders ,power Transformer
relay & control panels breakers panels from 220V, 100AH Battery charger make – AMARA RAJA
available in control room in normal conditions. In case failure of A.C Supply to the charger the D.C
Supply provided by 104 No’s VRLA Station batteries (make – AMARA RAJA) rating of 2V, 100AH each
(Maintenance free).
6. L.T.A.C Supply: The L.T 3 Phase, 415 VAC., Supply is provided by 11/433 KV, 100 KVA, VVE. A.C
Supply to all panels, control room, Yard lighting distributed from L.T.A.C panel in the control room. The
alternate L.T 3 phase, 415V A.C Supply is available to substation from 15KVA GENERATOR
AVAILABLE in Substation

7. Yard & Control Room Lighting: The Control room lighting is provided by 12 No’s 40W, flour cent
lights and 7 Nos. fans are provided in the control room. The yard lighting is provided by 28No’s 250W
MV lamps.

8. Water Supply: Water to the substation is provided by the 3 HP submersible Motor pump inside the
substation and drinking water is supplied by outside because water available at SS is not suitable for
drinking

9. Communication: There is a mobile phone bearing no, 9491067607 and there is an express channel of
PLCC phone having No.0439-31,32.

10. Meters: There are 9 No’s secure meters provided in which 2No. Meters are fixed to 132 KV feeder
panels and 3 No’s meters connected to HV side of PTR’s. MRI readings were down loaded from PTR’s
HV meters on1st of every month and sent them to SLDC Vijayawada. 2 No.s meters are connected to 132
KV Duddekunta line –I & II, 2 Nos Meters are connected to 11 KV Jeedipalli-1 & 11 KV Ankampalli-1
feeders.

11. Staff Position: O&M Staff


Department O & M Staff – Nil
11 No’s contract persons engaged for carrying out operation & maintenance work in which 4 No’s
highly skilled persons, 4 No’s skilled persons and 3 No’s UN- skilled persons for watch & ward on
contract basis at 132KV SS (LIS) Ankampalli.

Handed over Taken over


LIST OF REGISTERS

1. Equipment maintenance Register (quarterly & yearly)


2. PTR(I,II &III) Maintenance Register
3. PTR’s History Books
4. T & P Register
5. Consumable Register
6. Batter Reading Register
7. Tandelta test Register
8. Megger Value Register
9. Agreements / Estimates Register
10. Earth Resistance Register
11. Daily feeder wise Consumption Register
12. Monthly Maximum M.D’s & Interruption Register
13. Daily Lines Loss Register
14. MRT field book & MRT Complaint Register
15. Daily M.D & Voltage Register
16. Message Book
17. Interruption Register
18. L.C Register
19. Monthly Consumption Register
20. Attendance Register
21. Diesel Generator register
22. Log Book
23. LA Counter Reading Register
24. Energy meter Register
25. Failure Equipment Register
26. Inward/ Outward Register

LIST OF FILES

1. Monthly Returns
2. Hot Lines
3. T. Note
4. O & M Contractor labor bills
5. Agreements
6. Monthly energy consumption & lines loss
7. Transformer oil testing
8. Training students file

MANUALS & DIAGRAMS

1. 10 / 16 MVA PTR ECE make connection diagram.


2. 11 KV KIOSK manuals & connection diagram.

CONSUMABLES

1. Cotton wastage 10 Kgs


2. Hand Gloves 1 Set
3. Helmets 7 No.s
4. Gum boots 4 No.s
5. Rain Coats 4 No.s
6. Earth Rods 3 Sets
7. Safety Belts 1 No.
8. Fire Extinguishers 32 Kg’s 6 No’s
9. Fire Extinguishers 6.8 Kg’s 10 No’s
10. Log Sheets 100 No’s
12. Empty Oil Drum 10 No’s

TOOLS & PLANTS

1. Junior Executive Table 2 No’s


2. Steel Table 2 No
3. S.Type Chairs with Arms 3 No’s
4. S.Type Chairs without Arms 4 No’s ( 1 No Un-Servicable)
5. Steel Almarah 1 No.
6. Steel Rack 2 Nos
7. Steel File Trays 1 No
8. Steel Stools 5 Nos
9. Steel Waste Paper Baskets 2 Nos
10. Short Bench 4 Nos (3 Nos Un-Servicable)
11. Steel Cupboard consisting of 8Nos ducts’
Provision with locking arrangement 1 No
12. Key Board 1 No
13. Multi meter 1 No’s
14. Sealing fans 7 No’s ( 1 No Un-Servicable)
15. Wall clock 1 No
16. Screw Driver Big 12” 1 No
17. Screw Driver Small 6” 1 No
18. Adjustable Spanner 1 No
19. Pipe Wretch Big 18” & 24” 2 No’s
20. Computer Chair 1 No
21. Tube Lights 12 Set (6 Set Un-Servicable)
22. Wire Pullar 1 No
23. Round File 10” 1 No
24. Insulated Rubber Mats 7 No’s
25. Ring Spanners 9 No’s
26. D- Spanners 19 No’s
28. Hammer 1 ½ lbs 1 No
29. Hammer 1 lbs 1 No
30. 33 KV Isolator whole Set 1 No
31. MFT’s 3 No’s
32. PLCC AC’s 3 No’s ( 3 Nos Un-Servicable)
33. Cutting Player 2 No’s
34. 1No. SIM Card No.9491067607 1 No
35. 2 Liters Oil Containers with pipe & plunge 3 Nos
36. Samsung shift Mobile 1 No
37. Lenovo Tab 1 No

AMENITIES

1. Water Filter with 4Nos Candles (34 ltr) 1 No


2. Stand for Water Filter 1 No
3. Opela make Cup & Saucer set (6nos each) & Tray Set
4. Steel Glasses of 250ml Capacity 3 Nos
5. Air Coolers 1 No
6. Water Cooler of 80 liters capacity (Blue star make) 1 No ( Un-Servicable)

Pending Works:

1. 3 Nos 11 KV Kiosk, 2 Nos 132 KV CT’s and 1 No 132 KV LA were Failed and all the equipment
Survey Report yet to be proposed.
2. 17 Nos Failed 2 V Battery Cells are present and all the cells yet to be proposed.

HANDED OVER TAKEN OVER


HANDING OVER NOTES OF

ASSISTANT EXECUITVE ENGINEER


(MAINTENANCE)
132KV SUB STATION, ANKAMPALLI

FROM : Sri T. VEERA CHAITANYA


ASSISTANT EXECUTIVE ENGINEER
(In charge) : 132KV SUB-STATION
ANKAMPALLI

TO : Sri V. HANUMANTHA RAO


ASSISTANT ENGINEER
MAINTENANCE : 220KV SUB-STATION
BORAMPALLI