FROM A NEW

BC HYDRO
PADMOUNT
MCC #1 TRANSFORMER

3P, 1000A
LSIG BREAKER,
100% RATED

UTILITY
METERING
300 mm

OUTDOOR ENCLOSURE

STANDBY GENSET

3P, 600A CB
3P, 1000A
ATS 600V

PQM
7070

635 1120 510 1120 510 635 635 635 635 635

1200A CU BUS

CIP TANK
IMMERSION
200

SPD HEATER
FEEDER
3P, 3P, 70A CB SERVICE FEEDER TO
3P, 70A MCP 3P, 70A MCP 3P, 70A MCP 3P, 70A MCP 3P, 200A CB 3P, 300A CB 3P, 200A CB
30A ENTRANCE EXISTING
CB PUMP
PQM
STATION

AUTOMATIC UF FEED UF FEED UF FEED UF FEED


LINE LINE LINE LINE 20A CB 25A CB
PULL VERTICAL TRANSFER OSHG OSHG PUMP #1 PUMP #2 PUMP #3 PUMP #4
FILTER FILTER FILTER FILTER
SECTION BUS SWITCH RECT. HW. VFD VFD VFD VFD MCC #2
(40HP) (40HP) (40HP) (40HP) FEEDER
(400A FRAME)
MAIN
ASD ASD ASD ASD CIRCUIT
BREAKER SPACE
MCC #3
FEEDER
(250A FRAME)
LOAD LOAD LOAD LOAD
FILTER FILTER FILTER FILTER
100

MCC #1 ELEVATION
1:20
3P, 100A DS 3P, 100A DS 3P, 100A DS 3P, 100A DS

50kW
40 40 40 40
50

hp hp hp hp

UF FEED UF FEED UF FEED UF FEED CIP TANK EXISTING (TO MCC #2) (TO MCC #3)
PUMP #1 PUMP #2 PUMP #3 PUMP #4 IMMERSION PUMP
HEATER STATION

SINGLE-LINE DIAGRAM
10 mm

(SHEET 1/4)
0

PRELIMINARY
Revision Amendment Approved Revision Date Project

R0 ISSUED FOR REVIEW GV 2014-02-28 DISTRICT OF SICAMOUS


MARA LAKE WTP UPGRADE
210-889 Harbourside Drive
North Vancouver Office North Vancouver BC Sheet
604-990-4800
V7P 3S1, Canada
Drawn Designed Approved Revision Date ELECTRICAL
GV/RB GV GV 2014-02-28 MCC #1 SINGLE LINE DIAGRAM AND LAYOUT
Project No. Scale Drawing No. Sheet. No. Revision
1:1
0 10 20 30 40 50 60 70 80 90 100 mm
@ ANSI D D-94102.00 NTS NV D-94102.00 E3 R0
Original Sheet Size ANSI D [22"x34"] Plot Date 17 Jun 2014 @ 4:35 PM Path G:\D&K CAD Drawings\DKSERVER P Share\Drawings\SICAMOUS\D-94102.00\Current Working Folder\Electrical\WTP\D-94102 E3-E9.dwg E3