Manual AVR 4.20 Eng
Manual AVR 4.20 Eng
Manual AVR 4.20 Eng
6 TROUBLESHOOTING ....................................................................................................... 70
2|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
List of figures
FIGURE 1 – VOLTAGE REGULATOR RELAY – AVR ........................................................................................................................... 12
FIGURE 2 – DEPLOYMENT DIAGRAM FOR VOLTAGE REGULATOR RELAY - AVR ..................................................................................... 13
FIGURE 3 – APPLICATION OF AVR VOLTAGE REGULATOR RELAY WITH PARALLELISM CONTROL BY CIRCULATING CURRENT ........................... 14
FIGURE 4 – COMPOSITION OF THE VOLTAGE REGULATION SYSTEM .................................................................................................... 16
FIGURE 5 - DIMENSIONS OF THE VOLTAGE REGULATOR RELAY AVR .................................................................................................. 17
FIGURE 6 – INPUT AND OUTPUT TERMINALS OF THE AVR. ............................................................................................................... 18
FIGURE 7 – CONNECTION AND GROUNDING OF SHIELDING FOR RS485 SERIAL COMMUNICATION IN DATA ACQUISITION .............................. 20
FIGURE 8 - CONNECTION AND GROUNDING OF SHIELDING FOR RS485 SERIAL COMMUNICATION PORT USED IN PARALLELISM CONTROL
(OPTIONAL).................................................................................................................................................................... 20
FIGURE 9 - SINGLE PHASE PT CONNECTION DIAGRAM, 0° PHASE DIFFERENCE ANGLE ............................................................................. 21
FIGURE 10 - PHASE/NEUTRAL PT CONNECTION DIAGRAM, 0° PHASE DIFFERENCE ANGLE ....................................................................... 22
FIGURE 11 - PHASE/PHASE PT CONNECTION DIAGRAMS, 0° PHASE DIFFERENCE ANGLE.......................................................................... 22
FIGURE 12 - PHASE/PHASE PT CONNECTION DIAGRAM, 150° PHASE DIFFERENCE ANGLE ....................................................................... 22
FIGURE 13 - PHASE/PHASE PT CONNECTION DIAGRAM, 210° PHASE DIFFERENCE ANGLE ....................................................................... 23
FIGURE 14 - PHASE/PHASE PT CONNECTION DIAGRAM, 270° PHASE DIFFERENCE ANGLE ....................................................................... 23
FIGURE 15 – CONNECTION OF SHIELDING ON TAP POSITION READING CABLES ...................................................................................... 25
FIGURE 16 – CONFIGURATION OF RESISTORS IN THE POTENTIOMETRIC SENSOR IN INTERMEDIATE POSITIONS OF THE OLTC .......................... 26
FIGURE 17 - AVR WITH TAP POSITION READING............................................................................................................................. 29
FIGURE 18 – AVR WIRING DIAGRAM WITH EXTERNAL SWITCHES ....................................................................................................... 30
FIGURE 19 – FRONT DISPLAY OF THE AVR .................................................................................................................................... 31
FIGURE 20 – ADJUSTING DISPLAY BRIGHTNESS............................................................................................................................... 32
FIGURE 21 – READINGS SCREENS: VARIABLES SHOWN ON THE DISPLAY OF THE AVR.............................................................................. 33
FIGURE 23 – PROCEDURE FOR MANUAL RAISE/LOWER TAP POSITION COMMAND ................................................................................ 38
FIGURE 24 – ACCESS TO PARAMETER DEFINITION SUBMENUS ........................................................................................................... 39
FIGURE 25 – SUBMENU ACCESS FRAMEWORK. .............................................................................................................................. 41
FIGURE 26 - DISPLAY SHOWING SELF-DIAGNOSTIC MESSAGE............................................................................................................. 70
FIGURE 26 – SELF-DIAGNOSTIC MEMORY AND FIRMWARE VERSION SCREEN....................................................................................... 75
3|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
List of tables
TABLE 1 – OPERATING CONDITIONS .............................................................................................................................................. 6
TABLE 2 - INPUT TERMINALS ...................................................................................................................................................... 18
TABLE 3 - SELECTION OF VOLTAGE REGULATION PARAMETER SET OR PARALLELISM GROUP BY EXTERNAL CONTACT INPUTS ............................ 24
TABLE 4 - MAXIMUM LENGTH FOR EACH LEAD GAUGE USED IN TAP POSITION READ OUT CABLES .............................................................. 25
TABLE 5 - RESISTANCE OF THE POTENTIOMETRIC TAP POSITION SENSOR. ............................................................................................. 25
TABLE 6 - OUTPUT TERMINALS ................................................................................................................................................... 27
TABLE 7 - MAXIMUM LOAD OF CURRENT LOOP OUTPUT .................................................................................................................. 27
TABLE 8 - AUXILIARY PARAMETER DEFINITION TABLE – REGULATION MENU ........................................................................................ 76
TABLE 9 - AUXILIARY PARAMETER DEFINITION TABLE – CONFIGURATION MENU ................................................................................... 76
TABLE 10 - AUXILIARY PARAMETER DEFINITION TABLE – ALARMS AND RELAY MENU ............................................................................. 78
TABLE 11 - AUXILIARY PARAMETER SETTING TABLE – MENU OPTIONAL ITEM ON LOAD TAP CHANGER ..................................................... 79
TABLE 12 - AUXILIARY PARAMETER SETTING TABLE – MENUS TRANSFORMER AND CIRCULATING CURRENT................................................ 79
TABLE 13 - POSSIBLE OPTIONAL ITEM COMBINATIONS ..................................................................................................................... 81
4|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
1 Foreword
1.1 Legal Information
The information contained in this document is subject to changes without prior notice.
This document belongs to Treetech Sistemas Digitais Ltda. and may neither be copied, transferred to third
parties nor used without express authorization, in terms of law 9.610/98.
Disclaimer:
Treetech Sistemas Digitais reserves the right to make changes without prior notice in all products, circuits and
functionalities described herein with the aim of improving their reliability, function or design. Treetech
Sistemas Digitais does not assume any liability resulting from application or use of any product or circuit
described herein, and does not transmit any licenses or patents under its rights, not even third party rights.
Treetech Sistemas Digitais Ltda. may own patent or other types of registrations and intellectual property rights
described in the content of this document. Possession of this document by any person or entity does not give
such person or entity any right over these patents or registrations.
1.2 Presentation
This manual presents all the recommendations and instructions for installation, operation and maintenance
of the Voltage Regulator Relay -AVR.
Bold: Symbols, terms and words that are in bold have greater contextual importance. Therefore, pay attention
to these terms.
Italics: Terms in foreign language, alternative or with their use outside the formal situation are written in italics.
Safety Symbols
This manual uses three types of risk classification, as shown below:
Caution
The Caution symbol is used to alert the user of a potentially hazardous operating or maintenance
procedure that demands greater caution in its conduction. There may be minor or moderate injuries, as
well as damages to the equipment.
Warning
The Warning symbol is used to alert the user of a potentially hazardous operating or maintenance
procedure in which extreme caution must be taken. There may be serious injuries or death. Possible
damages to the equipment are irreparable.
5|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Electric Shock Hazard
The Electric Shock Hazard symbol is used to alert the user of an operating or maintenance procedure
that may result in electric shock if not strictly observed. There may be minor, moderate, serious injuries
or death.
General Symbols
This manual uses the following general symbols:
Important
The Important symbol is used to highlight relevant information.
Tip:
The Tip symbol represents instructions that facilitate use and access of functions in the TM1/TM2.
For use of this manual, an authorized and trained person has knowledge of the inherent risks – both electrical
and environmental – involved in handling the AVR.
Only authorized and trained personnel – operators and maintainers – should handle this equipment.
a) The operator or maintainer must be trained and authorized to operate, ground, turn on and
turn off the AVR, following maintenance procedures according to the safety practices established,
under the sole responsibility of the AVR operator and maintainer;
b) Be trained in the use of IPEs, CPEs and first-aid;
c) Trained in the working principles of the AVR, as well as its configuration.
d) Follow regulatory recommendations regarding interventions in any type of equipment
included in an Electric Power System.
Condition Interval/Description
Equipment for sheltered use in substations,
Application
industrial environments and similar.
Internal/External Use Internal Use
Degree of Protection (IEC 60529) IP 20
6|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Altitude* (IEC EN 61010-1) Up to 2000 m
Temperature (IEC EN 61010-1)
Operation -40 °C to +85 °C
Storage -50 °C to +95 °C
Relative Humidity (IEC EN 61010-1)
Operation 5% to 95% – Uncondensed
Storage 3% to 98% – Uncondensed
MAINS Supply Voltage Fluctuation (IEC EN 61010- Up to ±10% of the Rated voltage
1)
Overvoltage (IEC EN 61010-1) Category II
Level of Pollution (IEC EN 61010-1) Level 2
Atmospheric Pressure** (IEC EN 61010-1) 80 kPa to 110 kPa
To guarantee user safety, equipment protection and correct operation, the following minimum cares must be
followed during the AVR installation and maintenance:
1. Read this manual carefully before installation, operation and maintenance of the AVR. Errors
in installation, maintenance or adjustments of the AVR can cause undue operations of the tap
changer in load, unsatisfactory voltage regulation, undue alarms or pertinent alarms may also fail
to be emitted.
2. The installation, adjustments and operation of the AVR must be done by personnel trained
and acquainted with the electric motors, power transformers, tap changers on load or voltage
regulators, control devices and control circuits of substation equipment.
3. Special attention must be paid to installation of the AVR, including the type and size of the
cables and terminal strips used, as well as the procedures for commissioning, including correct
parameterization of the equipment.
The AVR must be installed in a sheltered environment (a panel without doors in a control room or in a
closed panel, in cases of outdoor installation) where the temperature and humidity specified for the
equipment are not exceeded.
Do not install the AVR near sources of heat like heat resistors, incandescent lamps and devices with high
power or with heat dissipaters. Its installation near ventilation orifices or where it can be affected by forced
air flow, like outlet or inlet of cooling fans or forced ventilation ducts, is not recommended.
On conducting dielectric strength tests on the wiring (applied voltage), the ground cables connected to
terminal 17 of the AVR must be disconnected in order to prevent destruction of the protections against
overvoltage existing inside the device due to application of high voltages for a long period (e.g.: 2 kV for
1 minute).
7|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Cleaning and decontamination instructions
Take care when cleaning the TM1/TM2. Use ONLY a cloth wet with soap or detergent diluted in water to clean
the cabinet, front plate or any other part of the equipment. Do not use abrasive materials, polishers or
aggressive chemical solvents (like alcohol or acetone) on any of its surfaces.
Turn off and unplug the equipment before cleaning any of its parts.
Do not open the equipment. In it, there are no parts reparable by the user. This should be done by the
Treetech technical assistance, or by technicians accredited by it.
This equipment is completely maintenance-free, being that visual and operational inspections, periodical
or not, may be conducted by the user. These inspections are not mandatory.
Opening of the TM1/TM2 at any time will imply in loss of the product warranty. In cases of undue opening
of the equipment, Treetech will also not be able to warrant its correct functioning, regardless of the
warranty period having expired or not.
All parts of this equipment must be supplied by Treetech, or by one of its accredited suppliers, according
to its specifications. If the user wishes to purchase it otherwise, he must strictly follow Treetech’s
recommendations for this. This way, the performance and safety for the user and the equipment will not
be compromised. If these specifications are not followed, the user and the equipment may be exposed
to unforeseen and unnecessary risks.
8|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
1.6 Warranty term
The Temperature Monitor is guaranteed by Treetech for the term of 2 (two) years, counted from the date of
purchase, exclusively against eventual manufacture defects or quality vices that render the equipment unfit
for use.
The warranty will not cover damages sustained by the product, as a consequence of accidents, improper
handling, incorrect installation and use, inadequate tests or in case the warranty seal has been breached.
The eventual need for technical assistance must be informed to TREETECH, or to a technical assistance service
appointed by the same, with the equipment being delivered together with the purchase invoice.
Treetech does not supply, nor is liable to, any other warranty, express or understood, in addition to the ones
mentioned above. Treetech does not supply any guarantee of suitability of the TM1/TM2 to any specific
application.
The dealer is not liable to any claims for damage to property, nor any other form of losses that might occur, in
connection to or stemming from the acquisition of the equipment, of the performance of the equipment or of
any other service possibly supplied together with the TM1/TM2.
Under no circumstances will the dealer be made responsible for any losses incurred, included but not limited
to: loss of profit or revenue, impossibility in using the TM1/TM2 or any other associated item of equipment,
costs of capital, costs of energy acquired, costs of replacement equipment, facilities or services, costs of
outages, complaints from clients or employees of the buyer, regardless of whether said damages, complaints
or losses are based on contracts, warranties, negligence, felony or any other reason.
Under no circumstances can the dealer be made liable for any personal damage of any sort.
9|Page
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
1.7 Revision Control
Review Date Description By
0 11/19/2004 Original issue Fco.
Revised firmware version number from 1.0.3 to 1.0.4 (Modbus
1.00 11/26/2004 M. Alves
information).
Manual in new format. Insertion of optional functions Parallelism
by Circulating Current and OLTC Maintenance. Up-date of Modbus Tchiarles/
2.00 07/07/2008 and DNP 3.0. tables. Insertion of parameter definition tables. Rafael/
Note: This review of the Manual is applicable only to devices with Marcos
firmware version V2.00 and later.
João V.
3.00 24/07/2015 New design. International representatives updated
Miranda
João V.
3.10 15/10/2015 Insertion of “Reversion Flow” in subchapter 6.1
Miranda
João V.
3.20 02/12/2015 Optional functions updated
Miranda
João V.
3.30 08/06/2016 Technical Data Review
Miranda
Inclusion of optional function 4: OLTC checking, and subchapter
3.4; Updating: indication to the self-diagnosis memory; self-
diagnosis table and the 2nd delay time and Local Address
parameters. Inclusion of “Screensaver” Parameter (replacing
“Screen Scrolling”) and new layout. Technical Assistance data João V.
4.20 03-01-2018
update. Inclusion of the power flow reversal alarm, error 0200 and Miranda
the fourth digit. The manual version now corresponds to the
Portuguese and Spanish versions.
Note: This manual review applies only to devices with firmware
version v2.19 and later.
10 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Introduction
In an increasingly more demanding market in terms of Quality of Electric Energy, and with increasingly stricter
rules for parameter definition and acceptable supply limits, there is a pressing need for tools capable of
adapting to this reality and afford adequate voltage regulation.
Within this context, Treetech’s Voltage Regulator Relay AVR offers a solution that goes beyond the traditional
and well-known relays “90”, equipped with unprecedented resources to afford better control of load voltage
limits, allowing addressing of the most exacting regulations in this sector.
11 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Universal power input, from 38 to 265Vdc/Vac 50/60 Hz;
Communication via optic fiber cables, deploying external electric-optical converter;
User password protected programming menus;
Parameter definition preserved even in case of long periods without power feed, by way of non-volatile
memory without the need for internal batteries;
Device connection by way of ring-type terminals for CT and PT signals, and detachable connectors for the
other circuits;
Reduced dimensions (96X96X161mm), allowing easy installation in new or existing panels, assembled on
transformers or in control rooms.
Limitation of OLTC excursion range (minimum and maximum tap positions allowed) and memorizing
maximum and minimum positions reached since last reset;
Protection against undue tap operations: blockage of switch in case of operations not initiated by AVR.
12 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Optional item 4 – OLTC Checking:
It works by algorithms that identify voltage levels corresponding to the sensitivity of the circuit, identifying
activity or not of the switching, signaling the fault (Alarm). It does not require potentiometric transmitter
information.
To this end, the AVR performs voltage readings at transformer output and load current. By using these two
readings and the line drop parameters programmed, the voltage on the load is calculated, which is the voltage
that must effectively be maintained within the limits desired as shown in Figure 2.
ILOAD
For more detailed information on the way the AVR acts when regulating voltage. In addition to the basic
voltage regulation function, the AVR also acts as protection for the OLTC, blocking its operation in adverse
conditions, such as a line short-circuit (over-current/under-voltage) and load protection (over-voltage).
13 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
1.11 Control of Parallel Operation using the Circulating Current Method
One of the main concerns when operating power transformers in parallel is avoiding the appearance of
currents circulating between windings in parallel. Once transformers operating in parallel feature the same
vector groups, voltage, power and impedance levels and that the primary windings are powered from the
same source, the main requirement in preventing circulation of current is that transformation ratios be equal.
In transformers with On Load Tap Changers (OLTC), which modify their ratios during operation, this condition
can be achieved through a number of different methods. When transformers have the same number of shunt
positions, with equal transformation ratios in every position, it is enough for them to always operate from the
same tap position, which can be accomplished by applying the “Master-Slave” control philosophy. This is the
philosophy adopted in Treetech’s SPS Parallelism Supervisor, which can be deployed together with the AVR
Voltage Regulator Relay.
However, it is also possible for transformers to be electrically compatible for operation in parallel, but have
different numbers of taps, so that applying the “Master-Slave” philosophy would, in these cases, require a
more complex logic. For these cases, an alternative is the use of the Minimum Circulation Current parallelism
method, which can be applied using AVR Voltage Regulator Relays equipped with optional function no. 6.
Implementing digitally parallelism by Circulating Current on AVR avoids the inconvenience and complexity
faced in the past when applying this method through analog circuits, which required the use of auxiliary CTs
and a high number of connection cables. AVRs are installed as usual, adding only the connection between the
relays with just one shielded, twisted-pair cable, as shown in Figure 3.
Figure 3 – Application of AVR Voltage Regulator Relay with Parallelism Control by Circulating Current
In the parallelism method by Circulating Current, AVRs control tap changers focusing, not on the tap position,
but rather in reducing reactive circulation current between the windings simultaneous to the normal voltage
regulation. To do this, relays calculate the circulating current between transformers through data exchange
via RS485 serial communication network.
Through a Gain factor, user adjusted between 0 and 100%, a Voltage Correction proportional to the value of
the Circulating Current is accomplished, where a gain of 100% corresponds to Correction Voltage equal to
reference voltage for a circulating current corresponding to the transformer’s rated power. In transformers
acting as generators of circulating current, it will be displayed with a positive sign, as will the correction
voltage, and for transformers receiving circulating current, the current will be shown with a negative sign, as
will the correction the voltage.
14 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
The Correction Voltage obtained in this way is added to the reading at the PT input, used by the relay for
regulation, causing a feedback effect that will lead the AVR to a trend to reduce voltage in the transformer
generating circulating current (positive Correction Voltage) and/or raise voltage in the receptor (negative
Correction Voltage).
The choice between the options informed above – reduce voltage in the transformer generating circulation
current or raise it in the transformer receiving – will, in general, be determined by the system voltage level. If
the voltage reading is below the reference value, the trend will be for receiving transformers to change tap in
order to raise voltage. In the opposite situation, if load voltage is above the reference value, the trend will be
for the generating transformer to change tap to reduce voltage.
The Gain adjusted by the user has the purpose of regulating intensity of feedback to reduce circulating current,
avoiding excessively weak correction, thus not allowing high circulation currents, or excessively high, causing
system instability.
In case of failure in actuation of one or more OLTC, the AVR features protection against excessive circulating
current that signals the event through an alarm and blocks the OLTC associated. For correct operation of
parallelism, an essential condition is that relays have identical voltage regulation parameter settings, which is
automatically checked by AVRs, with alarm issued and blockage of the system if any divergences are found.
This way, control of parallelism by Circulating Current afford a simple way of achieving transformer parallelism
in transformers with different numbers of taps, by automatically seeking the tap positions that afford the best
voltage regulation and the lowest circulation current.
15 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
2 Design and Installation
2.1 System Topology
Basically, the AVR - Voltage Regulation system is comprised of:
Tap Position
PT CT Measurement (optional)
Data Parallelism
Acquisition Voltage Regulator Relay - AVR Communication (optional)
System
The AVR is suited for built in type assemblies, and can be fixed, for instance, on doors or front plates of panels.
Fixation clips are supplied with the AVR. Figure 5 shows the main dimensions of the equipment, as well as the
dimensions of the cut out required on the plate in order to fit the equipment. Special attention must be given
to the thickness of the paint coats of the plate at the site of the cut out, because in some cases, high thickness
paint may be used and the resulting reduction in the area of the cut out may even keep the equipment from
fitting. Connection terminals are installed on the rear part of the AVR, with fixed terminals for the PT and CT
connections and 2 detachable connectors for the other connections, in order to facilitate connections. In the
detachable terminals, cables between 0.5 and 2.5mm² may be used, bare or with “pin” type connectors (or
“needle”) for the detachable connectors, and for the PT and CT terminals, eyelet-type terminals should be
used for cables up to 6 mm².
16 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Figure 5 - Dimensions of the Voltage Regulator Relay AVR
A circuit breaker should be used immediately before the power input (Universal Power Supply - 38 ~ 265 Vdc / Vdc,
<8 W, 50/60 Hz), which corresponds to the pins, 18 and 19 of the AVR. This circuit breaker must have the number
of poles corresponding to the number of phases used in the power supply - the poles must interrupt only the phases
and never the neutral or earth - and provide thermal and electrical protection to the conductors that feed the
equipment.
The circuit breaker must be close to the equipment and easily operable by the operator. Additionally, it must have
an indelible identification showing that it is the AVR's electrical disconnect device.
The following circuit breaker specification is recommended when used exclusively for the AVR:
17 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
The minimum insulation for the circuits connected to the AVR is 300 Vrms for equipment and auxiliary
transducers such as Pt-100 and for equipment with own power up to 50 Vrms.
The minimum insulation is 1.7 kVrms for equipment powered up to 300 Vrms, in accordance with IEC EN
61010-1.
These values are related to the intrinsic isolation of devices connected to the AVR. Cases where this
value does not apply to equipment or devices connected to the AVR will be explicitly reported in this
manual.
The AVR Voltage Regulator Relay offers the following inputs and outputs:
Input Terminals
Table 2 - Input Terminals
INPUT TERMINALS
1) Auxiliary power input and ground: 17 – ground
Input for universal power input (38-265 Vdc/Vac, 8W, 50/60Hz). 18 – cc/ca
19 – cc/ca
2) RS485 Port - Scada: 22 – ( + )
Connection with the data acquisition system, protocol MODBUS-RTU, DNP 3.0 optional, 23 – ( - )
via shielded, twisted pair cable...
3) RS485 Port – AVR connections (Optional item no. 6): 20 – ( + )
Connection for communication with other AVR Voltage Regulator Relays, used only 21 – ( - )
when optional function for Parallelism by Circulating Current is available.
18 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
6) Input for CT: 35 – (polarity)
Input for measuring current of the CT secondary. Measuring range 0 to 10A. 36 –
It is advisable to power the AVR using the substation’s auxiliary services, in particular when the device is
integrated in a serial communication network for the purpose of data capture for supervision or monitoring
systems.
The connection between the AVR and the data capture system must be made by way of shielded, twisted pair
cable, with the shielding having to be maintained unbroken along the entire length of the cable. If intermediate
connection terminals are necessary for connection of the serial network, pass the cable shielding on the
terminal as well, thus keeping it free of interruptions/breaks. The stretch of cable without shielding because
of the patch must be kept as short as possible. It is advisable to ground the cable shielding only at one of the
ends. A maximum distance of 1300 meters must be maintained between the ends of the communication
network.
A 120 ohm termination resistor must be installed at each end of the serial communication net, as well as pull-
up and pull-down resistors in just one point along the net, as shown in Figure 7. 5V direct voltage for powering
pull-up and pull-down resistors can be provided internally to the data acquisition system; note that some
communication systems may already have these resistors installed internally, eliminating the need for external
resistors.
19 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
560W 120 W
560W
120 W
Figure 7 – Connection and grounding of shielding for RS485 serial communication in Data Acquisition
All AVRs participating or that may come to participate in parallelism control must be linked together by simply
connecting in parallel their RS485 connection ports using a shielded, twisted pair cable, keeping shield
uninterrupted during the whole cable length. If intermediate connection terminals are necessary for
connection of the serial network, pass the cable shielding on the terminal as well, thus keeping it unbroken.
The stretch of cable without shielding because of the patch must be kept as short as possible. It is advisable
to ground the cable shielding only at one of the ends, and that a 120-ohm termination resistor be installed at
each extreme of the serial communication, as shown in Figure 8. The RS485 connection ports are already
provided with internal pull-up and pull-down resistors, doing away with the need for external resistors. A
maximum distance of 1300 meters must be maintained between the ends of the communication network.
...
120 W 120 W
...
...
Figure 8 - Connection and grounding of shielding for RS485 serial communication port used in Parallelism
control (optional)
20 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
4) RS232 Port
The RS232 port available on the rear of the AVR can be used as an alternative to the RS485 port described
above. RS485 and RS232 ports cannot be used simultaneously, the port to be used is the port selected in
programming the equipment. The RS 232 port uses the same communication protocols as the ones defined
above for the RS 485 port – supervision system. Consult Erro! Fonte de referência não encontrada. for
ommunication protocol details.
The limitations of the RS232 communication standard in relation to electro-magnetic interference must be
observed, maximum distance 50 feet (15 meters) and point to point communication (only 2 devices can be
connected to each other).
Due care must be taken in connecting the CT input, in order to make sure it does not remain open with the
transformer in operation. If interventions are made to this circuit with the transformer energized, make sure
the CT is short-circuited and grounded at the panel terminal boxes. The short-circuit should only be removed
after making sure the AVR’s CT input is correctly connected.
There are several possible combinations for the connection of the PT and CT, and each combination generates
an angle difference between the signals for voltage and current. In programming the AVR, the phase difference
angle is adjusted for the signals between 0° and 330° in 30° steps, which must be compensated for the correct
calculation of the power factor.
Below a few examples of possible combinations are shown for connecting the PT and CT. Other combinations
are also possible, and the phase difference angle can be easily determined by drawing a phase vector diagram,
as shown in the examples.
21 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Figure 10 - Phase/Neutral PT connection diagram, 0° phase difference angle
22 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Figure 13 - Phase/phase PT connection diagram, 210° phase difference angle
Selection of voltage regulation parameters among the six sets available in the device , or
Selection of parallelism group to which the AVR belongs, only when the optional item Parallelism by
Circulating Current is available.
Table 1 shows the way the AVR interprets contacts connected to this input for both of the deployment options
given above.
Contacts connected to these inputs must be free of any external potential, and are energized by way of the
AVR’s own internal potential, by way of a point common to all contacts (terminal 24).
23 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Table 3 - Selection of voltage regulation parameter set or parallelism group by external contact inputs
If the connection is established using more than one length of cable, due to, for example, an intermediate
terminal connection, shielding continuity must be ensured by connecting the ends of the shielding of the
different cables, as shown in Figure 15. The length of cable without shielding must be as short as possible.
24 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Figure 15 – Connection of shielding on tap position reading cables
The AVR compensates automatically for the resistance of the connection cables from the potentiometric
sensor to the AVR, and to this end, the three leads must be the same length and gauge, with maximum
admissible resistance for each cable being 8W. As a function of this maximum resistance and of the gauge of
the cables used, the maximum length for the leads can be calculated. Considering leads with typical resistances
of 13.3Wkm, 7.98Wkm and 4.95Wkm for the 1.5mm2, 2.5mm2 and 4mm2 gauge cables, respectively (cables
not tinned, cabling class 4), we will obtain the maximum lengths shown in the table below.
Table 4 - Maximum length for each lead gauge used in tap position read out cables
In case of tap changers with “intermediate” positions, i.e., transition positions having the same voltage as
other adjacent positions, as shown in the following table, resistors of the potentiometer sensor related to
these positions must be removed and/or short-circuited, as shown in the example of Figure 16. Every
intermediate position (in example, 6A, 6 and 6B) will be shown as tap “6”, since they have the same effective
voltage.
25 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
1 12420 3220.6 0
2 12696 3150.6 10
3 12972 3083.6 20
4 13248 3019.3 30
5 13524 2957.7 40
6A 50
6 13800 2898.6 50
6B 50
7 14076 2841.7 60
8 14352 2787.1 70
9 14628 2734.5 80
10 14904 2683.8 90
11 15180 2635.0 100
Figure 16 – Configuration of resistors in the potentiometric sensor in intermediate positions of the OLTC
The AVR admits that the resistance for each step of the potentiometric sensor falls in the range of 4.7 to 20W,
and the total resistance of the sensor between 9.4 and 1000W. The value for each individual resistor is shown
in Figure 16. The moving contact (cursor) of the potentiometric sensor can be of either “closes before opens”
or “opens before closes” types, which is indifferent. The resistances of the potentiometric sensor must be of
the precision type, i.e., with error tolerances of 1% maximum.
Current Tap position of the OLTC associated can be informed in simple numeric, bilateral numeric or
alphabetical-numeric formats (for example, 1...17, -8...0...8, or 8L...N...8R respectively).
26 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Output Terminals
Table 6 - Output Terminals
4...20 mA 500 W - -
If the output is selected to read voltage, beginning and end of scale are, respectively, 0 and 150V, respectively,
for current reading, 0 and 10A, respectively, and for tap position reading, minimum and maximum tap,
respectively.
Shielded, twisted pair cables, grounded at one end should be used in order to minimize interference.
27 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
2) and 3) Raise/Lower Voltage Output Contacts
The AVR’s output contacts for Raising or Lowering Tap and/or voltage can be connected directly to the
command circuit for the OLTC, acting directly on the coils of Raise/Lower contactors, or may be connected to
the corresponding dry contact inputs of the Treetech’s PI Position Indicator or SPS Parallelism Supervisor.
These contacts are instant activated, so that for every tap change command issued by the AVR, they will close
for approximate time of 0.5 second.
The Raise/Lower voltage output contacts are able to commute loads up to 250Vdc or 250Vac, with maximum
power of 70W or 250VA, respectively (for resistive loads). Their continuous conduction capacity (thermal
current) is 5A.
Attention must be paid to the fact that output contacts 1-2 always have the function of raising voltage, and
output contacts 3-4 always have the function of lowering voltage, and that in some cases raising voltage can
mean lowering the tap position and reducing voltage can mean raising the tap.
4) Self-Diagnostic Relay
Potential free NC contact, signals failures in auxiliary power supply or any other internal failure detected by
self-diagnostic. On energizing the AVR, this contact changes state (open), and returns to the rest position
(closed) in the event of internal failure or power outage.
The self-diagnostic contacts are able to commute loads up to 250Vdc or 250Vac, with maximum power of 70W
or 250VA (for resistive loads). Their continuous conduction capacity (thermal current capacity) is 5A.
The operation logic for the contacts is selected by the user in the options NO or NC (that is, close when the
alarm event occurs or open when it occurs). It is also possible to program more than one relay to signal the
same event (multiplication of contacts).
As mentioned above, one or more of the AVR’s contacts can be programmed for the function of blocking the
OLTC. The conditions that will activate the blockage of the OLTC (following an OR logic) are selected by users
among the events of: under-voltage, over-current or over-voltage.
Each programmable output contact is able to commute loads up to 250Vdc or 250Vac, with maximum power
of 70W or 250VA (for resistive loads), respectively. Their continuous conduction capacity (thermal current
capacity) is 5A.
Please notice that in both applications, the output contact 5-6 (relay 3) must be programmed for the OLTC
blockage function and with normal open (NO) operation mode (0 . In these examples, this relay acts on the
coil of an auxiliary contactor that removes power from the command of the OLTC and interrupts commuting
in case of over-current or under-voltage, for example. This contact could also act interrupting the power supply
to the motor of the OLTC, acting on the coil of a power contactor, whose contacts are connected directly to
the power lead for the motor. Another possibility is using this contact to break directly the power supply to
28 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
the command of the OLTC, without an auxiliary contactor. In this case the relay should be programmed with
operation mode normal closed.
29 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Figure 18 – AVR wiring diagram with external switches
If the optional function for Parallelism by Circulating Current is used, serial communication RS485 ports in
terminals 20 and 21 of all AVRs must be connected in parallel, as shown in figure 6(b).
30 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
3 Operation
All reading consultations and programming operations for the Voltage Regulator Relay AVR are performed
using the display and keyboard on the front panel. Any eventual alarms are also displayed through the front
panel display.
Down Key: navigation between menus and parameters and decrement values programmed.
AVR
Enter Key: Select menus and parameters for display, saves values programmed.
21/07/04 Monday
10:37:51
LTC
I> U< U> Overshoot IC>
31 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
3.2 Contrast Adjustment:
The AVR allows 7 levels of brightness on the display to be adjusted using the keyboard on the front panel.
01/27/04 Monday
On the initial readings screen, press the key: the contrast
10:37:51 adjustment screen will be displayed.
2) Sequential format, where the reading screens are shown in sequence, at intervals of approximately
15 seconds;
When the default or static display screen options are used, the AVR will intermittently invert (text in negative)
and normalize display pixels lighting with a view to avoiding the early wear of the display screen by displaying
the same message for long periods.
Regardless of the mode programmed, readings screens can be queried manually using the and keys.
Optional function screens are only displayed when the function is available. See Appendix C for possible
simultaneous optional item combinations.
32 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
PT secondary voltage 115.5V 1.65 A CT secondary current
Active regulation parameter set Reg: 2 Oper Hour Regulation parameter set selector
(hour, external contacts or standard)
Group of parallel operation (1, 2, 3 Group:1 Ic: 0015A Transformer circulating current (at CT primary)
or Individual) - Optional 6
Uc: 000.1V Correction voltage for reduction of Ic
In case of any abnormal condition occurring, the corresponding self-diagnostic code will be shown on the
display (Chapter 5.1 – Self-diagnostic Messages – Probable Causes and Possible Solutions).
33 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
3.4 Alert screens
The AVR can display alert texts on the display for the purpose of informing users on the occurrence of certain
pre-programmed events, such as maintenance notices for the changer, alarms or parameter definition errors.
Alert texts and procedures to be adopted are shown below.
OLTC Maintenance Notice in xxx Days due to Number of Operations LTC Mainten. No.
Oper in 999 days
Informs that, based on the daily average operations of the OLTC, the number
of operations required for maintenance will be reached in the number of days
shown, which is smaller than the figure programmed in parameter
“Maintenance Warning (days in advance)”.
OLTC Maintenance Notice in xxx Days due to Sum of Ipu2 LTC Mainten. Sum
Ipu 2 in 999 days
Informs that, based on the daily average of the increase in Sum of Current
Switched Squared, the sum of switched current for maintenance will be
reached in the number of days shown, which is smaller than the figure
programmed in parameter “Maintenance Warning (days in advance)”.
34 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
“No” as standard. In order to confirm that maintenance was effectively
performed and deactivate the notice, select “Yes” and press the enter key.
ATTENTION: This operation must not be carried out unless the maintenance
has been effectively performed, since all counters for “Operations since Last
Maintenance” and “Sum of I2 after Last Maintenance” will automatically be
reset to zero.
35 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
3.5 Command of On Load Tap Changer (Optional items No. 3 & 6)
The AVR can be equipped with optional resources for Tap Position Reading and control of OLTC (optional item
no. 3) and control of Transformer Parallelism by Circulating Current (optional item no. 6).
The optional feature Tap Position Reading allows the OLTC to be commanded in the automatic mode,
according to the regulation parameters programmed; or manually, using the keys located in the device’s front
panel.
The optional feature of Parallelism by Circulating Current allows transformers in parallel to be programmed,
split into up to 3 independent groups.
With one of the optional items enabled, momentarily pressing the key will access the OLTC operation
command menu. Press the or keys to navigate between the command parameters OOLTC Operation,
Parallelism, Operation Mode, Reset Minimum Tap and Reset Maximum Tap.
Local: the AVR will be enabled to receive raise / lower tap commands
and Automatic/Manual and Parallelism Group commands using the
keyboard, ignoring commands arriving via RS485 serial
communication or external contacts.
36 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Mode of Operation (optional item no. 3)
Allows selection of OLTC command mode between Automatic and Manual.
Manual: user can issue raise or lower tap commands, using the device
panel keyboard or serial communication. In this case automatic
command is locked out.
Observation: When the AVR is selected for operating within any of the
Parallelism by Circulating Current groups, it is not possible to select the
Manual Operation Mode. Selection of the Operation Mode is automatically
defined to Automatic.
Manual commands will not be executed if the AVR operation mode selected is Automatic. The AVR will not
issue the raise or lower tap command if the changer is already at the programmed maximum or minimum
allowed tap position, respectively.
If AVR operation mode selected is Remote, a notice screen will be displayed with the message “OLTC Operation
on Remote” when an attempt is made to access the manual command screen. Following which, the
Local/Remote selection screen will be automatically displayed.
37 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
169,50kV 115 A OLTC TAP Command
60,00Hz FP: 0.999 Raise ↑ ? ↓ Lower
38 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
3.6 Parameter Definition Menus
In order to ensure the correct operation of the system, ideal operation of the OLTC and its protection, the
different parameters of the AVR must be adjusted to supply the equipment with the necessary operating
information. Adjustments may be performed by way of the front keyboard, using the display, or by deploying
parameter programming software, using the RS232 or RS485 serial communication ports, available for the
user on the device’s rear panel.
The programmable parameters are organized in different submenus, inserted into a main password-protected
programming menu. Within each submenu, users will have access to a set of programmable parameters that
must be adjusted in accordance with each application’s needs and the transformer/regulator’s characteristics.
Follow the procedure outlined below for access to the parameter definition menu of the AVR:
3 – Using the and keys, set the access password for the main menu. Factory set
default value is 0 and the password can then be changed by user (Configuration Menu).
39 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
There are eight standard submenus and two optional ones, which will only be displayed when the feature is
available:
Regulation, Alarms,
Configuration, Relays,
Set Clock, OLTC (optional),
Transformer, Factory Only,
Circulating Current (optional), Download.
The Factory Only submenu is used only by technical assistance services and access is blocked by exclusive
manufacturer password. The Download submenu is used for up-dating the AVR’s firmware, and is also
protected by access password to avoid accidental access. Consult Treetech in case of need to update your
AVR’s firmware.
40 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Screensaver
41 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
To Access a Submenu or Parameter
- Within the main menu, use the and/or keys to navigate among the submenus available;
Optional menus are only displayed when the respective function is enabled.
- Within a submenu, use the and key to navigate among its parameters;
- Use the or keys to set the value desired for the parameter;
- Use to exit parameter and return to the menu, without saving any changes made to the parameter.
Regulation Submenu
Allows access to all parameters related to voltage regulation.
Regulation
With the display showing Regulation menu in highlight, press .
Select the desired set using the or keys and press the key.
After selected, the Regulation Set number (1, 2, 3, 4, 5 or 6) will remain
fixed at the beginning of display’s second line in every parameter of this
Submenu.
The AVR offers 6 sets of parameter for voltage regulation. The sets are numbered from 1 to 6.
This allows pre-programming the AVR’s regulation parameters to meet the different conditions of the power
system. Thus, different levels of regulation can be programmed for load peak and low load periods, for
example.
The parameters in Regulation Set 1 must be programmed, since this set is used as default by the AVR whenever
no other set is selected to operate. Programming the other Regulation Set s (2 to 6) is optional, and if they
have not been programmed, program “OFF” in the “Operating Hours” parameter.
42 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Regulation Sets 2 to 6 can be activated by programming the hour range for each set, informing day of the
week, hour and minute for beginning and end of operation of each Set (see parameter Operating Hours) These
sets can also be activated by way of the external dry contacts. Selection made by dry contacts will always have
priority over programmed Operating Hours activation. When Regulation Sets 2 to 6 are not active, by dry
contact or programming, the device will use Set 1 as default.
Reference Voltage
This is the theoretical voltage that we wish to maintain on the load, referred
to the secondary of the measurement PT, that is:
Example:
Timing Type
The timer resource is used to avoid unnecessary tap changes during
momentary voltage fluctuations, such as for example during the start up of a
large motor.
The timer effectively applied by the AVR in Inverse mode after detection of a
voltage deviation larger than insensitivity will be given by:
43 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Programmed Bandwidth
Effective Time = Programmed Time .
Measured Deviation
Where,
“Programmed Time” will be the value programmed for the parameter “Time
to Raise”, if the deviation measured is negative, or the adjustment set on
“Time to Lower”, if the deviation measured is positive, both in Timer Step 1;
44 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Voltage Drop Ur
This parameter will only be used in regulating voltage if the “LDC Type”
parameter has been set to “RX”. This is the resistive component of the line
voltage drop, in Volts, referred to the secondary of the PT and adjusted for
the rated current of the AVR (5A).
CT Ratio
Ur = 5 . R .
PT Ratio
Where,
“R” is the resistance of the line between the transformer and the load in
ohms;
Voltage Drop Ux
This parameter will only be used in regulating voltage if the “LDC Type”
parameter has been set to “RX”. This is the reactive component of the line
voltage drop as a function of line reactance, referred to the secondary of the
PT and adjusted for the rated current of the AVR (5A).
CT Ratio
Ux = 5 . X .
PT Ratio
Where,
“X” is the reactance of the line between the transformer and the load in
ohms.
Adjustment Range: -25 to + 25V, in 0.1V increments
Z Compensation
This parameter will only be used in regulating voltage if the “LDC Type”
parameter has been set to “Z Compensation”. This is the line drop voltage as
a percentage of the transformer output voltage, adjusted for the rated
current of the AVR (5A). The adjustment of Compensation Z can be obtained
experimentally, by measuring simultaneously the transformer output
voltage, the voltage at the load and the load current, and using this data in
the formula below:
45 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Compensation Limit
When performing line drop compensation, the AVR will cause transformer
output voltage to rise, for the purpose of keeping load voltage within the
bandwidth limits. This rise in voltage will be proportional to the load current,
so that very high load currents might lead to high rises of transformer output
voltage, which could be harmful for those loads close to the transformer. To
keep this from happening, the parameter “Compensation Limit” is
programmed establishing an upper limit for the voltage rise expressed as a
percentage of the Reference Voltage.
Timing Steps
This submenu adjusts the deviation (or Bandwidth) permitted for voltage
regulation, that is, the deviation of voltage at the load, given as a percentage
of Reference Voltage, which when breached triggers count down for the first
operation of the OLTC (time delay to raise or time delay to lower voltage).
The AVR offers up to three different Deviation Steps, each one with its own
adjustments for the Time to Raise and Time to Lower voltage.
On accessing the Timing Step submenu, the Select Step screen will be
displayed, where users choose out of step options 1, 2 or 3. Step
programming must start by programming Step 1. Each of the steps has the
following parameters:
Time to Raise: Time delay set for the first raise voltage command to
the OLTC (see also parameter Timing Type).
Time to lower: Time delay set for the first lower voltage command to
the OLTC (see also parameter Timing Type).
46 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
The adjustment for Deviation in step 1 must not be smaller than half of the
voltage step (voltage difference between two consecutive taps) of the load
tap changer, in order to avoid OLTC instability:
Voltage Step
Deviation 1 > 50% .
Reference Voltage . PT Ratio
Example:
In setting the deviation allowed for the first step, this defines the lower limit
for the adjustment range of the Second Step, which in its turn will define the
beginning of the adjustment range for the third Step. For instance:
Then Deviation Step 2 will be set, with its adjustment range beginning in 3%,
and going to 10%. Let’s suppose this was set at 5%
Once the 3 Steps have been adjusted as shown above, let’s suppose we need
to go back and change the value of the Deviation for Step 2, initially set at
5%. Since the Deviations for Steps 1 and 3 are set to 3% and 8%, respectively,
this time the adjustment range for Step 2 is 3% to 8%. If a value lower than
3% needs to be set, for example 2%, then we must first go to Step 1 and
adjust its step deviation value to a value lower than 2%.
This way different Time Bands are created to activate the OLTC, as a function
of the voltage deviation amplitude. Please remember that the three timer
steps will only be effective if Timer Type is selected for Defined Timing.
Otherwise, if Inverse Timing is selected as the Timing Type option, then only
47 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
the adjustment set for Timer Step 1 will be effectively used in operating the
AVR.
Operation Hours
Actuation of Regulation Sets 2 to 6 can be done by programming a time band
for each set, with hour and minute of beginning (adjustments to the left of
the display), hour and minute of end (adjustments to the right of the display)
and days of the week in which the time band should be actuated for each
set.
OFF: If the regulation parameter set is not being used, this same
parameter should be set to “OFF”.
To select or deselect the days of the week, use the enter key to take the
cursor to the day chosen and then press the UP or DOWN key. The selection
will be confirmed when a horizontal arrow is displayed. Repeat the
operation for the other desired days of the week.
Sets 2 to 6 can also be activated using the external dry contacts, and in this
case, selection made by way of the dry contacts will have priority over
programmed times. When Sets 2 to 6 are not activated by way of the dry
contacts or programming, then Set 1 will be used by default.
Submenu Configuration
Allows access to all parameters related to the AVR’s general operating configurations.
Setting Parameters
Language
Selection of the language used by the device to display information:
Portuguese,
English,
Spanish.
mA Output Range
The analog current loop output can be programmed using this parameter
in the following ranges.
48 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Adjustment 1) 0...1 mA 4) - 5...+5 mA 7) 0...20mA
Range:
2) - 1...+1 mA 5) 0...10mA 8) - 20...+20 mA
3) 0...5 mA 6) - 10...+10 mA 9) 4...20 mA
Analog Variable
The current loop output (configuration defined above) can be configured
for remote display of the following readings taken by the device:
Voltage (0...150 Vac): Voltage measured on the secondary of the PT
Amperes (0...10 A): current measured on the secondary of the CT
Tap Position: OLTC tap position.
Screensaver
It allows the user to parameterize the amount of time for the AVR enter
power-saving mode (minimum contrast) if no key is pressed. Pressing any
key, the device returns to the programmed screen contrast mode.
Adjustment Range: 1 to 15, in increments of 1 minute
Default Screen
Selects screen to be displayed automatically by the AVR equipment is on
Screensaver mode. The options in this case are:
ULoad/Deviation Current/Previous Tap position
Line Voltage/Line Current Min/Max Taps reached
Powers Parallelism Group
PT/CT OLTC Maintenance
Clock
Communication Standard
The AVR has two serial communication ports (RS232 and RS485) available
for users for parameter definition and remote data capture. The two
channels are not active simultaneously and the communication port that
will be used is selected using parameter “Communication Standard”, with
the options being:
RS-232 = use serial RS232 (rear connector DB9)
RS-485 = use serial RS485 (terminals 20 e 21).
Communication Protocol – Optional No. 1
If the optional DNP3.0 communication protocol is available, allows
selection of the protocol used for communication with the data acquisition
or parameter definition systems (otherwise Modbus RTU is the standard
protocol):
MODBUS RTU
DNP 3.0
49 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Communication Address
Defines the address of the AVR in RS232 or RS485 communication ports,
used in communication with data acquisition and parameter definition
systems.
Adjustment Range: 1 to 247, in increments of 1
Baud Rate
Selects transmission speed (baud rate) for serial communication ports
RS232 and RS485, among the options:
9600 bps
19200 bps
38400 bps
Parallelism Address – Optional No. 6
Defines the address of the AVR at the RS485 serial communication port
used to link the several different AVRs deployed in the Parallelism by
Circulating Current function (optional no. 6).
Each AVR in the communication network must have a unique and
sequential address, starting by 3 and rising in increments of 3. For example,
in a 3-transformer parallelism, AVRs will have addresses 3, 6 and 9.
Adjustment Range: 3 to 18, in increments of 3
Number of Nodes – Optional item No. 6
Programmed only in the AVR whose address is 3 in parameter “Parallelism
Address”. Defines total number of AVRs on the RS485 communication net
connecting the different AVRs for the Parallelism by Circulating Current
function (optional no. 6).
Adjustment Range: 2 to 6, in increments of 1
Contact Input – Optional Item No. 6
Defines the functions of external dry contact inputs (terminals 24 to 27,
see Chapter 3.3.1). Programming options:
Regulation – Selection of active set of voltage regulation parameters
Parallelism – Selection of Parallelism by Circulating Current group to
which the AVR belongs.
Mass Memory – Optional Item No. 2
This item is optional and will only be displayed if available. It records the
readings taken, at user-defined interval, for user-defined variables (up to
30 variables), and the recording mode for each variable.
AVRs have 15,429 registers available for storage of the variables selected
by the user. The number of registers used in each recording will be the
number of variables the user wishes to store in the event LOG plus 8:
50 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
No. of registers = n+8
Where,
n is the number of variables selected by user.
For example:
If the number of variables selected for recording on the event log is 20, we
will have:
No. of registers = 20+8 = 28
In this example, the AVR storage capacity will be:
Total Registers Available 15429
Storage Capacity = = = 551 records
No. of Registers 28
The number of records per day may vary due to additional records
triggered by events such as alarms or tap changes. When the maximum
number of registers is reached, the older registers begin to be discarded.
The options available to configure the operation of this optional item are:
Enable Recording: users can determine whether or not data will be
recorded on the data base.
Recording Interval: variables selected will be stored in time intervals
stipulated by the user, which can range between 1 and 120
minutes.
Choose Variable s: the AVR allows storage of up to 30 variables in the
data base. For each variable, one of the 14 magnitudes measured
can be attributed. The same magnitude can be attributed to more
than one variable, thus allowing different values for the same
magnitude to be recorded, according to the recording mode
selected (see next item). The following magnitudes can be
attributed to each variable:
51 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Recording Mode: user can select for each variable the type of
measurement to be recorded don the data base, which can be:
- Instant Value,
- Average Value,
- Minimum Value
- Maximum Value
Reset Log: allows user to erase all data in AVR’s mass memory. The
operation must be confirmed by selecting YES and pressing the
enter key.
New Password
The AVR leaves the factory with the standard menu access password
“000”. This parameter is used to define the new menu access password.
Note: The initial number shown in the access to programming menus can
be used to recover the password, when it is lost (see item 0-
Parameter Definition ). Inform this number to our Technical Assistance
Dept., for decoding your password.
Set Clock
Use the keys and to adjust the value for the field highlighted, then
press to navigate between the fields day, month, year, hour and minute.
Once the adjustments are finished, press to return to the main menu, at
which point the clock will restart with seconds set on 00.
The date format is defined as a function of the language setting selected in
the Submenu Configuration:
Portuguese and Spanish: DD/MM/YY,
English: MM/DD/YY.
The AVR automatically calculates the day of the week.
Submenu Transformer
Allows access to all parameters related to the characteristics of the transformer and PT and CT circuits used in
performing measurements.
52 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
With the display showing the Transformer menu in highlight, press .
53 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
CT Ratio
Adjustment of the CT’s transformation ratio, obtained by dividing the
current on the primary by the current on the secondary winding of the CT.
Example:
Considering the current on the primary winding of the CT 2500A and the
current on its secondary 5A, we obtain the CT’s transformation ratio:
250A
CT Ratio = = 50
5A
The parameters used in the configuration menu Circulating Current are listed below:
Gain
Define the Gain to be used in calculating correction voltage, proportional to
the Circulating Current of transformers in parallel, which is added to the
voltage measured to achieve reduction of circulating current, in a process of
negative feedback.
As the gain is adjusted, the correction voltage for the existing situation is up-
dated in the lower line of the display.
The ideal value for the Gain can be determined experimentally, using the
following procedure:
1) Select manual command mode in the OLTC control cabinet and take
them to tap positions with equivalent voltages (null Circulating Current
between transformers) and for which the load voltage is within the
bandwidth (raise/lower voltage LEDs on AVR are off);
54 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
2) Select in the front panel of AVRs the same parallelism group for all
transformers in parallel;
3) Increase or reduce tap position in one of the tap changers, causing the
appearance of a circulating current;
4) Gradually increase the value of the gain on the AVR for this OLTC,
starting at 0%, until the LED for raise or lower voltage starts flashing. If
in the previous item, the tap change was in the direction of raising
voltage, the lower voltage LED should flash, and vice-versa;
5) Multiply by 1.1 the value of the gain obtained in the previous item and
use the result to adjust the parameter Gain;
6) Carry out 2 tap changes in the OLTC, in the opposite direction to what
was done in item 3, in order to invert the direction of the current
circulation. Check if raise/lower voltage LEDs inverts (if lower LED was
previously flashing, now the raise LED should be flashing, and vice-
versa). If no LED flashes, increment the Gain value until this happens.
Multiply by 1.1 the value of the gain obtained and use the result to
readjust the parameter Gain;
7) Normalize the tap changer’s position (null Circulating Current between
transformers) and repeat procedure above for all other transformers in
parallel.
Adjustment Range: 10 to 99% of Rated Voltage, in 1% increments.
Submenu Alarms
Adjusts alarm trigger values and defines signaling relay operation modes.
The parameters used in configuration of the Alarms menu are listed below:
U< Alarm
The under-voltage alarm signals an excessive voltage drop measured on the
PT. This drop can be caused, for example, by a short-circuit.
This alarm is issued when the voltage measured on the secondary of the PT
presents a value lower or equal to the value set in the parameter Alarm U<,
expressed as a percentage of the adjusted Reference Voltage.
To avoid false alarms during de-energizing of the transformer, the U< alarm
will not be triggered if voltage drops below 10% of Reference Voltage.
In order to prevent the AVR from operating the OLTC to try to increase the
voltage in a short circuit, the U< alarm can be used to block the OLTC in
parameter OLTC Blocking.
Adjustment Range: 10 to 99% of Reference Voltage, in 1% increments.
55 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
U< Relay Alarm
The under-voltage alarm can be signaled remotely using one or more of the
AVR’s output contacts, among the options relay 3, 4, 5, 6 or 7.
In order to change the program set for a relay, use the enter key to take the
cursor to the desired relay and press the Up Key to select it or the Down key
to cancel the selection. Horizontal arrows indicate the relays selected.
The same relay selected for the alarm U< can also be used to signal other
alarm conditions, for example, Alarm I>.
This avoids unnecessary actuation of the alarm due to short duration events
like transients in the power system, for example. Timing is not applied to
blockage of the OLTC for under-voltage, if selected, since this is
instantaneous.
U> Alarm
The over-voltage alarm signals an excessively high voltage measured on the
PT.
This alarm is issued when the voltage measured on the secondary of the PT
presents a value higher or equal to the value set in the parameter Alarm U>,
expressed as a percentage of the adjusted Reference Voltage. This condition
can be harmful to loads connected to the transformer.
In the event of over-voltage, the AVR can operate immediately the OLTC in
an attempt to lower the voltage, ignoring the timer settings. If ignoring this
fast operation is desired, users can select the U> alarm as a condition for
blockage of the tap changer in parameter OLTC Blocking.
Adjustment Range: 101 to 199% of Reference Voltage, in 1% increments.
U> Alarm Relay
The over-voltage alarm can be signaled remotely using one or more of the
AVR’s output contacts, among the options relay 3, 4, 5, 6 or 7.
In order to change the program set for a relay, use the enter key to take the
cursor to the desired relay and press the Up Key to select it or the Down key
to cancel the selection. Horizontal arrows indicate the relays selected.
The same relay selected for the alarm U> can also be used to signal other
alarm conditions, for example, I> Alarm.
56 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
U> Alarm Time Delay
Allows to set a time delay for the Over-Voltage Alarm, which will only be
actuated if the voltage is kept above the value set for the parameter Alarm
U> for a time longer than the time defined.
This avoids unnecessary actuation of the alarm due to short duration events
like transients in the power system, for example. Timing is not applied to
blockage of the OLTC for over-voltage, nor for fast voltage reduction, if
selected, since these are instantaneous.
I> Alarm
The over-current alarm is issued when, due to a short-circuit or overload,
the current measured in the secondary of the CT presents a value higher or
equal to the one set in the parameter for I> Alarm, expressed as a
percentage of the Rated Current for the AVR (5A).
Operating the OLTC under high currents can be harmful to the device’s
contacts. In order to prevent the AVR from actuating the tap changer to try
to raise or lower the voltage during a short-circuit, users can select the I>
Alarm as condition for blockage of the OLTC in parameter OLTC Blocking.
Adjustment Range: 10 to 200% of AVR’s rated current (5A), in 1%
increments.
This avoids unnecessary actuation of the alarm due to short duration events.
Timing is not applied to blockage of the OLTC for over-current, if selected,
since this is instantaneous.
57 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
High Circulating Current Alarm – Optional Item No. 6
Defines the value set for the High Circulating Current alarm between the
transformers in parallel, caused by excessive divergence between the taps
of the transformers.
Adjustment Range: 1 to 1000A, in 1A increments.
High Circulating Current Alarm Time Delay – Optional Item No. 6
Allows setting a timer for actuation of the High Circulating Current Alarm,
which will only be actuated if the circulating current measured is above the
value set for the parameter Alarm High Circulating Current for time longer
than the time defined.
This avoids unnecessary actuation of the alarm due to short duration events.
Timing is not applied to blockage of the OLTC for High Circulating Current, if
selected, since this is instantaneous
58 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Parameter Definition Error Relay – Optional Item No. 6
The alarm Parameter Definition Error between AVRs of transformers in
parallel, caused by programming different regulation parameters on the
devices, can be signaled remotely by way of one or more AVR output
contacts.
In order to change the program set for a relay, use the enter key to take the
cursor to the desired relay and press the Up Key to select it or the Down key
to cancel the selection. Horizontal arrows indicate the relays selected.
The same relay selected for the Parameter Definition Error alarm can also
be used to signal other alarm conditions such as, for example,
Communication Error Alarm or others.
No. of Operations Relay – Optional Item No. 7
The notice issued by the AVR when the number of tap change operations
reaches the value where there is a need to perform maintenance on the tap
changer can be signaled remotely by way of one or more AVR output
contacts. Parameter “Relay No. of Operations” is used to select the output
relays that will be used for this purpose: 3, 4, 5, 6 or 7. The same relay
selected for this notice can also be used to signal other alarm conditions.
Sum of Ipu2 Relay – Optional Item No. 7
The notice issued by the AVR when the sum of current switched squared
(Ipu2) reaches the value where there is a need to perform maintenance on
the tap changer can be signaled remotely by way of one or more AVR
outputs contacts. Parameter “Relay Sum of I2” is used to select the output
relays that will be used for this purpose: 3, 4, 5, 6 or 7. The same relay
selected for this notice can also be used to signal other alarm conditions.
OLTC Blockage
Allows selecting the conditions that should cause blockage of the on load
tap changer among the following options:
59 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
started in the driving mechanism before the operation of the main contacts.
This contact is configured in parameter OLTC Blocking Relay.
Submenu Relays
Selects the work mode for the AVR’s output relays.
The parameters used in the configuring menu Relays are listed below:
60 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Number of Tap Positions
Sets the OLTC number of taps.
Adjustment Range: 1 to 50 taps
Type of Tap Position Indication
This is the type of display for the tap reading adopted by the AVR, and
generally follows the type of reading shown in the On Load Tap Changer.
61 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Raise TAP =
This parameter indicates, for tap changer used, the raise tap command
means raising voltage and the lower command tap means reducing
voltage or if the raise tap command means reducing voltage and the
command lower tap means increase voltage.
Beware of the fact that AVR output contacts 1-2 and 3-4 always have the
function of increasing or reducing voltage respectively.
62 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Total OLTC Operations
Defines total number of tap changer operations since onset of operation.
Allows adjusting current number of tap changer operations, so that the
count of the AVR coincides with the mechanical counter found in most
OLTCs.
The OLTC operation counter is incremented each time the reading for
tap position is changed.
63 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
The sum is incremented by the value of the load current measured,
converted to p.u. (per unit) and squared, in the instant there is a change
in OLTC tap position.
Adjustment Range: 0 to 2000 x 103 pu2 in 0.01 steps (to 99.99), 0.1 (to
999.9) and 1 (starting in 1000).
Adjustment Range: 0 to 2000 x 103 pu2 in 0.01 steps (to 99.99), 0.1 (to
999.9) and 1 (starting in 1000).
64 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Maintenance Notice – Time in advance for issuance
Defines the number of days in advance that the tap changer
maintenance required notice will be first issued.
Submenu Download
Access to the firmware update feature (resident program in the device’s micro-controllers) using the serial
communication ports RS232. Update is carried out using purpose-specific software from Treetech.
65 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
In order to quit this process before beginning transmission of the
firmware, the AVR must be reinitialized (turned off and then on).
66 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
4 Start Up Procedure
Once the equipment has been installed as shown in
67 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Design and Installa part of this manual, the following basic steps must be followed for start-up:
Check that electrical wiring has been correctly done (for instance, by way of continuity testing);
Before energizing the transformer, or before removing the short circuit of the CT secondary, make
sure that the current transformer secondary circuit is correctly connected to the input of the AVR, making
sure the CT secondary is not open;
Disable the commands for OLTC (for example: detach the lower connector of the AVR – terminals 1 to
16 – or select OLTC for Local command in its control cabinet) before energizing the AVR;
If dielectric strength tests are carried out on the wiring (applied voltage), disconnect the leads
connected to the ground terminal of the AVR in order to avoid destroying the protections against over-
voltages inside the device. These protections are connected internally between the input/output and
ground terminals, limiting the voltage at around 300V. Applying high voltages for long periods of time (for
example, 2kV for 1 minute) would destroy these protections.
Reconnect the ground leads to the terminals of the AVR, in case they were disconnected for applied
voltage testing.
Energize the AVR with any voltage in the 38 to 265Vdc/Vac 50/60Hz range.
Carry out parameter definition of AVR, in accordance with the instructions of Chapter 0 –
68 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Parameter Definition , using the front panel keyboard on the device or the parameter programming
software via serial ports. Values used in defining parameters can be written down in the form supplied in
Appendix A;
Remove the short circuit jumper from the secondary of the CT, if this was done previously;
Check that voltage, current and power factor readings of the AVR are correct;
Check that the current loop output features the correct value in relation to the variable associated
(voltage, current or tap position);
Test actuation of dry contact inputs for selection of Voltage Regulation Parameter sets or selection for
the group of Parallelism by Circulating Current;
Normalize commands for OLTC (reinsert lower connector of the AVR or select OLTC for Remote
command);
If possible use variable AC voltage and current sources in order to vary these magnitudes at the AVR’s
input. Check activation of raise and lower voltage contacts, the operation of the different alarms (U<, U>,
I>) and blockage of the OLTC.
The user has the possibility to unlock the OLTC with the active power flow reversal alarm. However,
Treetech does not recommend using this function. Its use and the consequences it generates when
regulating the voltage are the sole responsibility of the user. Unlocking is done via communication
protocol (see "AVR communication protocol").
69 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
5 Troubleshooting
5.1 Self-diagnostic Messages – Probable Causes and Possible Solutions
The software of the Voltage Regulator Relay AVR constantly checks the integrity of its functions by way of its
self-diagnostic circuits and algorithms. Any abnormal condition observed, is signaled by the failure contact and
the messages shown on the display of the AVR, helping in the failure diagnosis process.
Internal Error
Cod: 0040
The self-diagnostic codes shown on the display of the AVR are comprised of four digits. The meaning for each
digit is shown on the following tables. Inform the error code to the Treetech technical assistance service.
0040 Digit 1
Code Description Probable Cause Recommended Actions
Shown
0 No failure - -
1 Micro-controller Internal failure Replace the defective equipment.
communication Contact Treetech technical service.
failure
2 Not used - -
3 Simultaneous See codes 1 and 2 above Proceed as indicated for codes 1 and 2 above.
occurrence of
errors 1 and 2
above
4 Internal EEPROM Internal failure Replace the defective equipment.
memory failure Contact Treetech technical service.
5 Simultaneous See codes 1 and 4 above Proceed as indicated for codes 1 and 4 above
occurrence of
errors 1 and 4
above
6 Simultaneous See codes 2 and 4 above Proceed as indicated for codes 2 and 4 above.
occurrence of
errors 2 and 4
above
7 Simultaneous See codes 1, 2 and 4 Proceed as indicated for codes 1, 2 and 4 above.
occurrence of above
errors 1, 2 and 4
above
8 External EEPROM Internal failure Replace the defective equipment.
memory failure Contact Treetech technical service.
70 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
0040 Digit 2
Code Description Probable Cause Recommended actions
Shown
0 No failure - -
1 Failure in Internal failure Replace the defective equipment.
measuring CT Contact Treetech technical service.
current
2 Failure in Internal failure Replace the defective equipment.
measuring PT Contact Treetech technical service.
3 Simultaneous Simultaneous Proceed as indicated for codes 1 and 2 above.
occurrence of occurrence of errors 1
errors 1 and 2 and 2 above.
above.
71 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
0040 Digit 2
Code shown Description Probable Cause Recommended actions
8 Failure in reading Cables connecting Replace cables connecting potentiometric sensor to
Tap Changer potentiometric sensor to AVR with shielded cables with identical gauges and
Position AVR with different lengths in all 3 wires, according to the instructions in
gauges and/or lengths Item 8) Tap position reading (Optional items no. 3, 7).
for each wire
Error in setting Correct parameter settings “Number of Tap
parameters “Number of Positions” and “Step Resistance” according to
Tap Positions” and/or instructions of Item 0.
“Step Resistance” in AVR
Potentiometric sensor Remove resistors from intermediate tap changer
has step resistors positions, replacing them with wire jumpers,
installed in the transition according to instructions in Chapter 3.3.1, Item
(intermediate) positions Requirements for tap position sensor.
of the tap changer.
Digit 3
0040
Code Shown Description Probable Cause Recommended actions
0 No failure - -
1 Communication Incorrect connection of Check for proper connection of communication
Error between communication cable cables (polarity, eventual short-circuits, open cable,
AVRs shielding grounding) between AVRs (see Chapter
3.3.1).
Incorrect setting of Check for correct setting of the following
communication parameters: “Parallelism Address” and “Number of
parameters between Nodes” (see Chapter 4.6.2).
AVRs.
Distance between ends of If circuit length is in excess of 1300 meters, repeater
the communication modules or optic fiber cabling (with appropriate
network cable longer than media converters) must be used.
1300 meters.
Lack of grounding for the Lack of or incorrect shield grounding may allow
shield of communication induced noise or transients to corrupt data
network cables, transmitted. Carry out checking of cable shields
interruption in cable connections and grounding (see Chapter 3.3.1).
shields continuity, or
shield grounded at both
ends.
72 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
2 OLTC Checking AVR algorithms identified Check the operation of the OLTC command by the
Alarm that the OLTC failed to AVR (the switch motor drive contactors, command
regulate the voltage levels and power voltage, command wiring between the
corresponding to the AVR and the drive panel, local / remote and
sensitivity programmed in automatic / manual OLTC switches, external locks
AVR. and other intermediate points that may prevent
OLTC from working).
73 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
SEVERE ACCIDENTS: do not disconnect cables
connected to terminals 35 and 36 of AVR without before
making sure the secondary of the CT is duly short-
circuited and grounded.
AVR does not measure correctly or displays error message in measuring Tap Position
Probable Causes Possible Solutions
Connection cables between potentiometric Replace connection cables between potentiometric
sensor and AVR are not shielded. sensor and AVR by shielded cables, according to
instructions found in Chapter 3.3.1, item 8) Tap position
reading (Optional items no. 3, 7).
Shielding of connection cables between Ground shielding of connection cables between
potentiometric sensor and AVR grounded in potentiometric sensor and AVR in just one point and
more than one point, not shielded or without maintain continuity of shielding, according to
shielding continuity along the length of the instructions on Item 8) Tap position reading (Optional
cable items no. 3, 7).
Bad contact on cursor of potentiometric Eliminate bad contact on cables cursor of
position sensor or on cables connecting it to the potentiometric position sensor.
AVR
Connection cables between potentiometric Replace connection cables between potentiometric
sensor and AVR with resistance higher than 8 sensor and AVR by cables with suitable gauge,
ohms per wire – gauge too small for the according to instructions on Item 8) Tap position
distance covered reading (Optional items no. 3, 7).
Connection cables between potentiometric Replace connection cables between potentiometric
sensor and AVR with different lengths or sensor and AVR by shielded cables with equal gauges on
gauges in each wire all three wires, according to instructions on Item 8) Tap
position reading (Optional items no. 3, 7).
Error in setting parameters “Number of Tap Correct settings of parameters “Number of Tap
Positions” and/or “Step Resistance” at the AVR Positions” and/or “Step Resistance” at the AVR
according to instructions of Item 0.
Potentiometric sensor has step resistors Remove resistors from transition tap changer positions,
installed in transition (intermediate) tap replacing them with jumpers, according to instructions
changer positions. of Chapter 3.3.1, Item Requirements for tap.
Potentiometric sensor’s step resistors have Replace potentiometric sensor’s step resistors by others
tolerance above 1% of their rated value. with accuracy better than or equal to 1%.
74 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Incorrect programming of serial Check for correct programming of the following
communication parameters. parameters: “Communication Standard”, “Protocol”,
“Address” and “Baud Rate” (see Chapter 4.6.2).
Distance between ends of the communication Where the communication cable exceeds the distance
network cable higher than 1300 meters. of 1300 meters, auxiliary repeater modules or optic
fiber cables (with appropriate media converters) must
be used.
Lack of grounding for the shield of Lack of or incorrect shield grounding may allow induced
communication network cables, interruption in noise or transients to corrupt data transmitted. Carry
cable shields continuity, or shield grounded at out checking of cable shields connections and
both ends. grounding (see Chapter 3.3.1).
75 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
6 Appendix
Appendix A – Parameter Definition Tables
Remark: Tables valid for equipment starting in Firmware version 2.00. Some submenus and parameters will
only be displayed if the respective optional functions are available.
Regulation Set
Parameter
1 2 3 4 5 6
Reference Voltage
Timing Type
2nd Time Delay
Line Drop Compensation Type
Ur Voltage Drop
Ux Voltage Drop
Z Compensation
Compensation Limit
Timing Steps
Deviation (%)
Step 1 Time to Raise (s)
Time to Lower (s)
Deviation (%)
Step 2 Time to Raise (s)
Time to Lower(s)
Deviation (%)
Step 3 Time to Raise (s)
Time to Lower(s)
Operation Hours
Active? (ON/OFF) Yes No Yes No Yes No Yes No Yes No Yes No
Start time (HH:MM)
End time (HH:MM)
Days of the Week Sun Mon Sun Mon Sun Mon Sun Mon Sun Mon Sun Mon
Tue Wed Tue Wed Tue Wed Tue Wed Tue Wed Tue Wed
Thu Fri Thu Fri Thu Fri Thu Fri Thu Fri Thu Fri
Sat Sat Sat Sat Sat Sat
Configuration
Parameter Value Set Parameter Value Set
Language Address
mA Output Range Baud Rate
Analog Variable Parallelism address (op. 6)
Screensaver Number of Nodes (op. 6-Address 3)
Default Screen Contact Input (op. 6)
Communication Standard New Password
Protocol
76 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Mass Memory (Optional item 2)
Parameter Value Set
Enable recording Yes No
Recording Interval
Memory Position Choice of variable to record Recording mode
Variable 1* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 2 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 3 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 4 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 5 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 6 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 7 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 8 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 9 * 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 10* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 11* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 12* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 13* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 14* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 15* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 16* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 17* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 18* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 19* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 20* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 21* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 22* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
77 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Memory Position Choice of variable to record Recording mode
Variable 23* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 24* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 25* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 26* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 27* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 28* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 29* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Variable 30* 1 2 3 4 5 6 7 8 9 Instant Value Average Value
10 11 12 13 14 15 16 17 Minimum Value Maximum Value
Alarms Relays
Parameter Value set Parameter Value set
U< Alarm Operation relay3 NO NC
U< Alarm relay RL3 RL4 RL5 RL6 RL7 Operation relay4 NO NC
Time Delay U< Operation relay5 NO NC
U> Alarm Operation relay6 NO NC
U> Alarm relay RL3 RL4 RL5 RL6 RL7 Operation relay7 NO NC
Time Delay U>
I> Alarm
I> Alarm relay RL3 RL4 RL5 RL6 RL7
Time Delay I>
Alarm High Icirc (op. 6)
Time Delay High Icirc (op. 6)
Relay High Icirc. (op. 6) RL3 RL4 RL5 RL6 RL7
Relay Error Tap Read (op. 3) RL3 RL4 RL5 RL6 RL7
Relay Comm. Error (op. 6) RL3 RL4 RL5 RL6 RL7
Relay Parameter Error (op.6) RL3 RL4 RL5 RL6 RL7
Relay No. Operations (op. 7) RL3 RL4 RL5 RL6 RL7
Relay Sum I2 (op. 7) RL3 RL4 RL5 RL6 RL7
OLTC Blocking I> U> U< OLTC
Icirc
OLTC Blocking Relay RL3 RL4 RL5 RL6 RL7
78 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Table 11 - Auxiliary parameter setting table – Menu optional item On Load Tap Changer
Table 12 - Auxiliary parameter setting table – Menus Transformer and Circulating Current
Transformer
Parameter Value Set Parameter Value Set
CT/PT Phase Shift PT Ratio
Number of Phases CT Ratio
Xfmr. Rated Power Xfmr Impedance
79 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Appendix B – Technical Data
Power Input: 38 to 265 Vdc/Vac 50/60Hz
Maximum Consumption: 8W
Operating Temperature: -40 to +85 oC
Protection degree: IP 20
Connections – except PT and CT inputs: 0.3 to 2.5mm2, 22 to 12 AWG
Connections - PT and CT inputs: one or two 1.5 to 2.5mm2, 16 to 12 AWG - using appropriate
ring type terminals
Fixation: Fixed on panel
Measuring Range
Voltage: 0...160V1
Current: 0...10A
Maximum Errors
Voltage: 0.5% of measurement in 0...160V range
Current: 1% of full scale
Dry contact inputs: 3
Output to relays: 7 NO + 1 NC (self-diagnosis)
Maximum switching power: 70 W(dc) / 220 VA(ac) – resistive load
Maximum switching voltage: 250 Vdc / 250 Vac
Maximum conduction current: 5A
Analog output: 1 in current loop
Variable: Programmable
Output range: Programmable 0...1, -1...1, 0...5, -5...5,
0...10, -10...10, 0...20, -20...20, 4...20mA
Maximum Error: 0.5% of end of scale
Maximum Load 10V
Serial communication ports: 1 RS485/RS232 (for supervisory/laptop)
Optional items:
Tap position reading input: Potentiometric, 3 wires, resistors class 1% or better
Number of Taps on OLTC: 2 to 50
Total resistance of potentiometric sensor: 9.4 to 1000 W
Step Resistance of potentiometric sensor: 4.7 to 20 W accuracy 1% or better
Serial Communication Port: 1 RS485 (for linking AVRs in optional parallelism Functions)
1
The entrance of the TP can be damaged if the voltage values are exceeded
80 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Appendix C – Order Specifications
The Voltage Regulator Relay AVR is universal, with the operating characteristics being selected by way of
program menus. These adjustments can be made directly on its front panel or by way of specific configuration
software, using the RS232 or RS485 serial communication ports. Power input is universal (38 to 265 Vdc/Vac
50/60Hz).
Number of devices;
Optional functions desired. More than one optional item can be specified for the same device, taking
into account the possible combination of optional items shown on table 13 below.
1) DNP3.0 Protocol
2) Mass Memory
3) Position Reading
4) OLTC Checking
7) OLTC Maintenance
SUBTITLE
Allowed
Not Allowed
81 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
Appendix D – Tests performed
Surge Immunity (IEC 61000-4-5):
Phase-neutral surges: 1 kV, 5 per polarity (+/-)
Phase-ground and neutral-ground surges: 2 kV, 5 per polarity (+/-)
82 | P a g e
[ User Manual – AVR | MA–011 | 03-01-2018 | Ver.: 4.20 ]
BRAZIL
Treetech Sistemas Digitais Ltda
Praça Claudino Alves, 141, Centro
CEP 12.940-000 - Atibaia/SP
+ 55 11 2410-1190
comercial@treetech.com.br
www.treetech.com.br