Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

1.b. Fire Pump Motor

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

FIRE PUMP

MOTORS

BUILT TO SERVE

Open Drip Proof


FIRE PUMP MOTORS
National Motors' NMCM series consists of motors designed With Open Drip Proof enclosures, they provide best
for fire pump applications as specified in NFPA 20 possible ventilation suitable for environments having
(Standard for the Installation of Stationary Pumps for Fire minimal airborne contaminants and better cooling that
Protection). They are certified by UL as per the requirement contribute to the most efficient performance available from
of UL 1004-5 'Standard for Fire Pump Motors'. These these motors. These certified motors are fully complaint
three phase horizontal low-voltage squirrel-cage medium with the motor efficiency requirements as given in the
induction motors are constructed and manufactured as EISA (Energy Independence and Security Act of 2007 - US
per the requirements of NEMA MG 1 standard Design B. federal act).

Features:
15 to 350 horse power rating
400 – 415 voltage rating at 50 hertz
NEMA Energy efficient design
1.15 Service Factor
Class F insulation
50 °C Ambient Temperature rating*
Regreasable Ball Bearing
Cast Iron construction frame
Frame size from 254T to 449TS
UL File No. EX26863
Stainless Steel name plate
RAL 3000 Standard red painted
IP23 Degree of Protection
Altitude rating of 1000 meters above sea level*
F1 foot mounting
2 Pole, 2920 - 2945 rpm speed**
Temperature Rise below Class B (80 K)
Suitable for various standard starters such as across the line, wye-delta, soft starter etc.

Note:
* Derating may be required for higher values.
** Rated speed of the motor varies depending on motor size and it is mentioned on the next page.

2 National Motors
PERFORMANCE DATA
Rated Output Frequency Rated Voltage Full Load Service Number of Speed
Model No. Frame Size
(hp) (Hz) (v) Current (A) Factor Poles (rpm)
NMCM50152PO 15 254T 50 400-415 19.7 1.15 2 2920
NMCM50202PO 20 256T 50 400-415 25.9 1.15 2 2920
NMCM50252PO 25 284TS 50 400-415 31.9 1.15 2 2930
NMCM50302PO 30 286TS 50 400-415 38.8 1.15 2 2930
NMCM50402PO 40 286TS 50 400-415 50.5 1.15 2 2925
40 324TS 50 400-415 50.6 1.15 2 2930
NMCM50502PO 50 324TS 50 400-415 61.3 1.15 2 2930
50 326TS 50 400-415 63 1.15 2 2930
NMCM50602PO 60 364TS 50 400-415 75.4 1.15 2 2930
60 326TS 50 400-415 75.8 1.15 2 2935
NMCM50752PO 75 364TS 50 400-415 92.2 1.15 2 2940
75 365TS 50 400-415 93.6 1.15 2 2940
NMCM501002PO 100 365TS 50 400-415 119.8 1.15 2 2940
100 405TS 50 400-415 124.5 1.15 2 2940
NMCM501252PO 125 404TS 50 400-415 143.5 1.15 2 2940
125 444TS 50 400-415 155.3 1.15 2 2940
NMCM501502PO 150 405TS 50 400-415 178.6 1.15 2 2940
150 445TS 50 400-415 182.9 1.15 2 2940
NMCM502002PO 200 447TS 50 400-415 243 1.15 2 2940
200 444TS 50 400-415 258.2 1.15 2 2945
NMCM502502PO 250 449TS 50 400-415 302 1.15 2 2940
NMCM503002PO 300 447TS 50 400-415 355 1.15 2 2945
300 449TS 50 400-415 355 1.15 2 2945
NMCM503502PO 350 447TS 50 400-415 451.5 1.15 2 2945
350 449TS 50 400-415 451.5 1.15 2 2945

Locked Rotor Insulation Rated Ambient Power Temperature


Model No. Phases Duty Enclosure
Current (A) Class Temperature (°C) Factor Rise (K)
NMCM50152PO 141 3 F 50 Continuous 0.91 55 ODP
NMCM50202PO 177 3 F 50 Continuous 0.91 78 ODP
NMCM50252PO 222 3 F 50 Continuous 0.91 70 ODP
NMCM50302PO 264 3 F 50 Continuous 0.91 70 ODP
NMCM50402PO 354 3 F 50 Continuous 0.91 70 ODP
354 3 F 50 Continuous 0.91 65 ODP
NMCM50502PO 441 3 F 50 Continuous 0.91 76 ODP
441 3 F 50 Continuous 0.91 75 ODP
NMCM50602PO 529 3 F 50 Continuous 0.91 63 ODP
529 3 F 50 Continuous 0.91 75 ODP
NMCM50752PO 661 3 F 50 Continuous 0.92 78 ODP
661 3 F 50 Continuous 0.92 75 ODP
NMCM501002PO 883 3 F 50 Continuous 0.92 80 ODP
883 3 F 50 Continuous 0.92 78 ODP
NMCM501252PO 1105 3 F 50 Continuous 0.92 80 ODP
1105 3 F 50 Continuous 0.92 78 ODP
NMCM501502PO 1319 3 F 50 Continuous 0.93 80 ODP
1319 3 F 50 Continuous 0.93 80 ODP
NMCM502002PO 1764 3 F 50 Continuous 0.93 80 ODP
1764 3 F 50 Continuous 0.93 80 ODP
NMCM502502PO 2320 3 F 50 Continuous 0.93 80 ODP
NMCM503002PO 2770 3 F 50 Continuous 0.93 80 ODP
2770 3 F 50 Continuous 0.93 80 ODP
NMCM503502PO 3243 3 F 50 Continuous 0.93 80 ODP
3243 3 F 50 Continuous 0.93 80 ODP